MTZ Package Ansal
MTZ Package Ansal
(6.2 - 25 TR)
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
Contents
1. Models List…………..……………………………………………….…2
2. External Appearance…………………………………………………..5
3. Model Number Nomenclature………………………………………..6
4. Feature & Benefits……………………………………………………..7
5. List of Functions………………………………………………………..8
6. Specifications…………………………………………………………10
7. Dimensional Drawings……………………….………………………23
8. Wiring Diagrams………………………………………………………27
9. Performance Data…………………………………………………….34
10. Electrical Data……………..…………………………………………48
11. Parameter & Pressure Chart for Air Volume……………………50
12. Refrigerant Cycle Diagram...………………………………………59
13. Operation Limit………………………………………………………61
14. Installation…………..………………………………………………..63
15. Wired Controller…………..…………………………………………68
16. Error Code…………..………………………………………………69
17. Accessories…………………………………………………………69
18. Maintenance and Upkeep…………………………………………70
19. Variable Pitch/Speed Pulleys…………………….………………72
Appendix…………………………………………………………….……77
※ Manufacture reserves the right to discontinue, or change at any time, specifications or designs without
notices and without incurring obligations.
1
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
1. Models List
Table 1:
Nominal Capacity Model Power Supply
Ton Refrigerant Model Name Function V, ph, Hz
6.2 MRBT-062C-D
7.5 MRBT-075C-D
8.5 MRBT-085C-D
10 MRBT-100CW-D
12.5 MRBT-125CW-D Cooling Only
15 MRBT-150CW-D
17.5 MRBT-175CW-D
20 MRBT-200CW-D
25 MRBT-250CW-D
6.2 MRCT-062EW-D
7.5 MRCT-075EW-D
8.5 MRCT-085EW-D
10 MRCT-100EW-D
12.5 MRCT-125EW-D
15 MRCT-150EW-D
17.5 R22 MRCT-175EW-D 220V, 3ph~ 60Hz
20 MRCT-200EW-D
25 MRCT-250EW-D Cooling and Electric heater
6.2 MRDT-062EW-D
7.5 MRDT-075EW-D
8.5 MRDT-085EW-D
10 MRDT-100EW-D
12.5 MRDT-125EW-D
15 MRDT-150EW-D
17.5 MRDT-175EW-D
20 MRDT-200EW-D
7.5 MRBT-075HW-D
10 MRBT-100HW-D
15 MRBT-150HW-D Cooling and Heating
20 MRBT-200HW-D
25 MRBT-250HW-D
2
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
Table 2:
Nominal Capacity Model Power Supply
Ton Refrigerant Model Name Function V, ph, Hz
6.2 MRT-062C-R
7.5 MRT-075C-R
8.5 MRT-085C-R
10 MRT-100C-R
12.5 MRBT-125CW-R Cooling Only
15 MRBT-150CW-R
17.5 MRBT-175CW-R
20 MRBT-200CW-R
25 MRBT-250CW-R
6.2 MRCT-062EW-R
7.5 MRCT-075EW-R
8.5 MRCT-085EW-R
10 MRCT-100EW-R
12.5 MRCT-125EW-R
15 MRCT-150EW-R
17.5 R22 MRCT-175EW-R 380-415V, 3ph~ 50Hz
20 MRCT-200EW-R
25 MRCT-250EW-R Cooling and Electric heater
6.2 MRDT-062EW-R
7.5 MRDT-075EW-R
8.5 MRDT-085EW-R
10 MRDT-100EW-R
12.5 MRDT-125EW-R
15 MRDT-150EW-R
17.5 MRDT-175EW-R
20 MRDT-200EW-R
7.5 MRBT-075HW-R
10 MRBT-100HW-R
15 MRBT-150HW-R Cooling and Heating
20 MRBT-200HW-R
25 MRBT-250HW-R
3
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
Table 3:
Nominal Capacity Model Power Supply
Ton Refrigerant Model Name Function V, ph, Hz
6.2 MRBT-062CW-C
7.5 MRBT-075CW-C
8.5 MRBT-085CW-C
10 MRBT-100CW-C
12.5 MRBT-125CW-C Cooling Only
15 MRBT-150CW-C
17.5 MRBT-175CW-C
20 MRBT-200CW-C
25 MRBT-250CW-C
6.2 MRCT-062EW-C
7.5 MRCT-075EW-C
8.5 MRCT-085EW-C
10 MRCT-100EW-C
R22 380-415V, 3ph~ 60Hz
12.5 MRCT-125EW-C
15 MRCT-150EW-C
17.5 MRCT-175EW-C
20 MRCT-200EW-C
25 MRCT-250EW-C Cooling and Electric heater
6.2 MRDT-062EW-C
7.5 MRDT-075EW-C
8.5 MRDT-085EW-C
10 MRDT-100EW-C
12.5 MRDT-125EW-C
15 MRDT-150EW-C
17.5 MRDT-175EW-C
20 MRDT-200EW-C
4
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
2. External Appearance
6.2~10Ton:
12.5~25Ton:
5
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
M R B T - 125 C W - D
Power Supply
D: 220V~,60HZ,3Ph
R: 380-415V~,50HZ,3Ph
C: 380-415V~,60HZ,3Ph
W: Wired Controller
Function Code
C: Cooling Only
E: Electric Heater and Cooling
H:Cooling and Heating
Product Series
T: T3 Condition
Rooftop Package
6
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
6. Optional supply/return airflow design, from side or bottom, It could be flexibly applied
to multi-position.
7
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
5. List of Functions
5.1 STANDARD SPECIFICATIONS
A. General
Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground. The
packaged unit consists of scroll compressors, cooling coil, condenser coil, control wiring and interconnecting
piping- all factory assembled and mounted on heavy gauge G-90 galvanized steel sheet press formed base,
ready for field connection to utilities and ducts. The packaged unit is of rigid construction with holes provided
in the base rails for overhead rigging. The unit is provided with an integral weather resistant control panel.
These units are rated and tested in accordance with ARI standard 210/ARI 360.
B. Unit Enclosure
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely
weatherized for outdoor installation and properly reinforced and brazed. Panels and access door are
provided for inspection and access for all internal parts. Enclosures are provided with adequately reinforced
points of support for setting in the unit. Steel sheet panels are zinc-coated and galvanized by the hot dip
process of lock forming quality conforming to ASTM A 653 commercial weight G-90, followed by baked on
electrostatic polyester dry powder coat paint, on all external panel.
C. Compressor
Compressors are scroll for all the models. They are provided with all the standard controls and accessories
necessary for safe operation. These are equipped with internal motor protector; factory installed crank case
heater and rubber vibration isolator for quiet and efficient operation.
D. Air-cooled Condensing Section
1. The air-cooled condensing section is enclosed within the unit housing and consists of condenser coil,
fan(s) electric motor(s) and inherently protected compressor(s). Inner grooved copper tubes with wall
thickness of 0.3mm, mechanically bonded to enhanced louvered aluminum fins are standard for all
condenser coils. Return bends have 0.022 inch thickness (0.56mm). As an option, enhanced coated
aluminum fins may be provided. Tube support sheets are galvanized steel, formed to provide structural
strength.
2. Fans are propeller type, direct driven, upward discharge and provided with fan grille mounted on the
casing.
3. Motors are totally enclosed air-over type with class F insulation. Inherent thermal protection is automatic
reset type.
E. Evaporator Coil Section
1. All cooling coils are of enhanced louvered fins and inner grooved copper tubes with wall thickness of
0.3mm, mechanically bonded to aluminum fins. Return bend has 0.022 inch thickness (0.56mm). As option,
enhanced coated aluminum fins may be provided. Tube support sheets are galvanized steel, formed to
provide structural strength.
2. Drain Pan: An insulated drain Pan made of G-90 galvanized steel is provided, for additional corrosion
protection.
3. Insulation: Insulation is supplied in adequate density and thickness for all units to prevent condensation
from forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against
deterioration and erosion from air currents.
F. Evaporator Fan
Evaporator fan is of centrifugal forward-curved blade design capable of handling total required CFM and
static pressure in the low and the medium ranges. Casings are made of galvanized steel. Blower motors are
of open drip proof type (totally enclosed types are optional) and conform to NEMA MG-1 and MG-2. Fan
drive is through adjustable pitch pulleys and belt driven. Blower motor is mounted on adjustable base and
8
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
secured by locking device. Fan wheels shafts and bearing are selected to operate at 25% below first critical
speed. Pillow block bearing are selected for at 200,000 hours average life at design operating conditions.
Shaft is turned, ground and polished from solid steel. Fans and pulleys are keyed to shaft and designed for
continuous operation at maximum motor horse power and fan speed. All rotating components and
assemblies are statically and dynamically balanced and every unit is vibration tested before shipment from
the factory.
G. Electronic Thermostats
General information: A dedicated electronic thermostat is supplied with unit controls as standard. This
thermostat controls one or two stage heating and cooling applications. The thermostat normally displays
room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also
allows you to select continuous fan operation, or have the fan on intermittent operation with the equipment. It
also displays the status of unit, thus providing maximum information for the end user.
9
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
6. Specifications
Nominal ton (Ton) 6.2 7.5 8.5 10
Model MRT-062C-R MRT-075C-R MRT-085C-R MRT-100C-R
Btu/h 73400 94000 107000 127000
Cooling (1)
W 21500 27500 31400 37200
Btu/h 65000 80100 94600 107000
Cooling (2)
Capacity W 19000 23500 27800 31400
Power Input(1) W 7400 9700 10200 12300
Power Input(2) W 8900 11000 12600 14500
Current A 13.5 18 20 22.5
Power supply V-PH-Hz 380~415-3-50 380~415-3-50 380~415-3-50 380~415-3-50
Electrical data(3)
Rated power Input W 10000 14000 14800 17600
Air Circulation (High speed) CFM 2480 3000 3400 4000
Indoor external static pressure Pa 60 60 70 75
Performance
SEER (1) Btu/h W 9.9 9.7 10.5 10.3
SEER (2) Btu/h W 7.3 7.3 7.5 7.4
Number of rows 2 2 3 3
mm 1.5 1.5 1.7 1.7
Fin spacing
Indoor Coil inch 1/16 1/16 1/16 1/16
mm Ф9.5 Ф9.5 Ф9.5 Ф9.5
Tube diameter
inch 3/8 3/8 3/8 3/8
Type Centrifugal Blower Centrifugal Blower Centrifugal Blower Centrifugal Blower
No. used 1 1 1 1
mm Ф282(257) Ф282(257) Ф305(305) Ф305(305)
Diameter(Width)
inch 11(10) 11(10) 12(12) 12(12)
Indoor fan Drive type Belt Belt Belt Belt
No. motors 1 1 1 1
Motor model YFD90L-4 YFD90L-4 YFD90L-4 YFD90L-4
Motor output W 1500 1500 1500 1500
Motor rpm r/min 1020 1020 1020 1020
Type Scroll Scroll Scroll Scroll
Quantity 2 2 2 2
ZR61KC-TFD-522
Model ZR47KC-TFD-522 ZR61KC-TFD-522 ZR72KC-TFD-522
ZR47KC-TFD-522
Compressor Brand Copeland Copeland Copeland Copeland
Capacity Btu/hr 39000(×2) 49700+39000 49700(×2) 59300(×2)
Input W 3480(×2) 4430+3480 4430(×2) 5248(×2)
Rated current(RLA) A 6.3(×2) 8.2+6.3 8.2(×2) 9.2(×2)
Refrigerant oil charge ml 1350(×2) 1700+1350 1700(×2) 1700(×2)
Number of rows 3 3 3 3
mm 1.7 1.7 1.7 1.7
Fin spacing
Outdoor Coil inch 1/16 1/16 1/16 1/16
mm Ф9.5 Ф9.5 Ф9.5 Ф9.5
Tube diameter
inch 3/8 3/8 3/8 3/8
Type Axile Axile Axile Axile
No. used 1 1 1 1
mm Ф650(90) Ф650(90) Ф650(90) Ф650(90)
Diameter
inch 25 5/8(3 1/2) 25 5/8(3 1/2) 25 5/8(3 1/2) 25 5/8(3 1/2)
Outdoor Fan Drive type Direct Direct Direct Direct
No. motors 1 1 1 1
Motor model YS550W-6P YS550W-6P YS600-6P YS600-6P
Motor output W 550 550 600 600
Motor rpm r/min 940 940 930 930
Type R22 R22 R22 R22
Refrigerant Refrigerant volume kg 5.6 5.3 6.4 5.6
Refrigerant Control Capillary tube Capillary tube Capillary tube Capillary tube
mm 2089X900X1235 2089X900X1235 2165X1002X1335 2165X1002X1335
Dimensions(W×H×D)
inch 82×35×49 82×35×49 85×40×53 85×40×53
kg 383 387 441 443
Net Weight
Ibs 844 853 972 977
No. Used 4 4 4 4
Filter
Size mm 529×357×12.5 529×357×12.5 566×404×12.5 566×404×12.5
Note:
The data are based on the following conditions:
Cooling (1)and Power input(1): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 35°C(95°F) DB.
Cooling (2)and Power input(2): Indoor Temperature 26.7°C(80°F) DB / 19.4°C(67°F) WB; - Outdoor Temperature 46.1°C(115°F) DB.
Electrical data(3): Indoor Temperature 32°C(90°F) DB / 23°C(74°F) WB; - Outdoor Temperature 52°C(125°F) DB.
10
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
11
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
12
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
13
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
14
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
15
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
16
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
17
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
18
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
19
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
20
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
21
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
22
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
7. Dimensional Drawings
7.1 6.2 & 7.5 Ton
23
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
24
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
25
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
26
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
8. Wiring Diagrams
8.1 MRT-062C-R MRT-075C-R MRT-085C-R MRT-100C-R
27
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
28
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
29
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
30
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
31
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
32
MCAC-UTSM-2009-05 T3 Condition Rooftop Package
33
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
9. Performance Data
Cooling capacity for 6.2Ton:
Air Flow CFM 2100 2480
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 67.2 69.3 74.2 77.4 69.1 72.3 76.2 79.1
61
SHC 58.4 65.8 70.5 73.5 62.4 68.0 71.6 74.4
MBH 75.7 76.0 76.6 77.7 76.5 77.0 77.8 79.3
85 67
SHC 44.4 55.5 66.2 76.6 46.4 57.8 69.3 78.3
MBH 79.1 80.0 80.8 81.7 79.4 80.3 81.4 82.2
73
SHC 29.2 40.6 49.0 58.2 29.7 42.3 50.1 59.7
MBH 62.2 65.3 70.6 75.1 64.1 68.3 73.6 77.5
61
SHC 56.0 61.5 66.5 70.7 59.8 64.3 69.3 73.0
MBH 72.2 72.5 73.4 75.2 72.9 73.4 76.2 77.8
95 67
SHC 43.1 54.6 66.1 74.2 45.2 57.8 70.1 75.8
MBH 78.1 78.6 79.4 80.1 78.5 79.1 79.9 80.8
Temperature(℉)
73
SHC 28.2 39.6 50.8 59.8 28.7 41.2 51.0 61.6
MBH 57.0 61.0 66.4 71.8 58.8 63.9 69.7 74.6
Entering Wet Bulb(℉)
61
SHC 53.5 56.7 61.8 66.8 57.4 59.4 64.8 69.4
MBH 66.8 67.4 68.5 72.1 68.4 69.0 70.4 74.6
105 67
SHC 40.7 52.2 63.8 69.7 43.0 55.7 68.7 73.5
Ambient
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. MBH=Total Gross Capacity. (Unit: kBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: kBtu/h).
34
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 7.5Ton:
Air Flow CFM 2700 3000
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 82.5 84.2 85.8 87.5 87.3 89.0 90.8 92.6
61
SHC 72.7 80.4 85.3 87.5 77.4 84.3 88.2 91.1
MBH 94.8 96.7 98.6 100.6 95.9 97.8 99.8 101.8
85 67
SHC 55.6 68.8 81.8 94.3 58 72.6 85.4 96.3
MBH 98.6 100.6 102.6 104.6 99.2 101.2 103.2 105.2
73
SHC 36.8 51.0 62.0 72.4 37.3 50.7 62.3 75.1
MBH 78.6 80.2 81.8 83.4 81 82.6 84.3 86.0
61
SHC 69.6 75.6 78.0 81.4 72.3 78.6 81.2 85.3
MBH 85.6 87.3 89.1 90.8 87.1 94.0 96.6 98.0
95 67
SHC 53.9 67.7 81.6 86.2 56.3 71.6 86.5 91.3
MBH 97.8 99.8 101.8 103.8 98.3 100.3 102.3 104.3
Temperature(℉)
73
SHC 35.7 50.2 62.3 74.5 36.2 51.2 64.1 77.3
MBH 72.1 73.5 75.0 76.5 74.4 75.9 77.4 79.0
Entering Wet Bulb(℉)
61
SHC 66.4 68.3 71.3 73.2 71.2 72.4 76.3 78.4
MBH 84.4 86.1 87.8 89.6 86.3 88.0 89.8 91.6
105 67
SHC 51 65.0 79.2 86.3 53.7 66.2 85.0 90.3
Ambient
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. MBH=Total Gross Capacity. (Unit: kBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: kBtu/h).
35
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Heating capacity for 7.5Ton:
Net Capacities(kW)-3000 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(℃) Peak Net Power(KW) at Indicated Dry Bulb(℃)
Outdoor Temp(℃) 70% RH
15 21 24 27 15 21 24 27
-15 14.9 14.0 13.7 13.4 6.9 7.6 8.0 8.5
-12 16.0 15.3 15.0 14.9 7.1 7.7 8.1 8.6
-9 17.0 16.5 16.4 16.4 7.1 7.8 8.2 8.8
-6 17.8 17.3 17.1 16.9 7.2 7.9 8.3 8.9
-3 18.8 18.5 18.4 18.1 7.3 8.0 8.5 9.1
0 20.3 20.0 19.7 19.4 7.4 8.1 8.6 9.2
3 23.3 23.1 22.7 22.4 7.5 8.3 8.8 9.3
6 26.9 26.5 26.2 26.0 7.8 8.4 9.1 9.6
9 30.5 30.2 29.9 29.6 8.1 9.0 9.5 10.1
12 32.4 33.5 33.4 33.1 8.4 9.4 9.9 10.5
15 35.0 34.4 34.2 33.8 8.6 9.6 10.1 10.7
18 37.1 36.4 36.0 35.7 8.9 9.8 10.4 11.0
21 39.8 38.9 38.4 37.9 9.0 10.0 10.5 11.0
24 42.0 40.9 40.2 39.8 9.2 10.1 10.9 11.3
36
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 8.5Ton:
Air Flow CFM 2700 3000 3400
Ent DB (℉) 75 80 85 90 75 80 85 90 75 80 85 90
MBH 91.6 95.5 99.3 102.4 96.5 100.7 104.5 107.8 98.6 102.8 106.7 110.2
61
SHC 71.4 82.1 90.1 94.9 76.8 88.1 96.6 101.7 80.8 92.8 101.7 107.1
MBH 101.4 103.2 104.7 105.6 106.7 108.6 110.2 111.4 109 110.9 112.5 113.7
85 67
SHC 54.1 67.9 81.7 90.6 58.1 72.8 87.7 97.3 61.2 76.6 92.3 102.6
MBH 103.2 104.8 106.4 107.7 108.6 109.5 111.2 113.5 112.4 114.1 115.8 117.1
73
SHC 23.9 44.5 61.6 74.9 25.8 48.3 67.9 86.1 27.2 56.3 74.6 97.8
MBH 88.5 92.3 95.8 99.0 93.1 97.1 100.8 104.2 95.1 99.2 102.9 106.3
61
SHC 72.6 83.2 91.7 96.3 78.2 89.8 98.6 103.7 82.4 94.6 98.1 102.1
MBH 97.8 99.6 101.0 102.3 102.7 104.8 106.3 107.4 105.1 107.0 108.5 109.7
95 67
SHC 55.2 68.7 83.4 92.4 59.2 74.3 89.4 99.8 62.4 78.1 94.1 104.5
MBH 105.1 106.3 107.5 109.1 110.7 111.8 112.9 114.1 113.2 114.6 116.3 118.7
Temperature(℉)
73
SHC 26.4 55.2 67.8 88.9 26.1 48.9 69.8 82.3 30.8 67.2 94.3 106.7
MBH 83.7 87.5 90.8 93.8 88.1 91.9 95.4 98.5 90.1 93.8 97.4 100.6
Entering Wet Bulb(℉)
61
SHC 69.7 80.0 87.7 92.3 74.7 85.8 94.1 98.5 78.7 90.4 93.5 96.5
MBH 92.6 94.2 95.8 97.1 97.4 99.1 100.5 101.7 99.5 101.2 102.7 103.8
105 67
SHC 52.8 66.1 79.5 88.4 56.6 70.8 86.1 98.3 59.6 74.7 89.9 99.8
Ambient
MBH 94.5 96.1 97.8 99.4 104.1 105.6 107.2 108.6 106.9 108.3 109.7 111.2
73
SHC 23.3 44.7 59.8 72.6 82.3 87.1 90.6 99.8 31.2 67.4 98.6 106.8
MBH 78.3 81.6 84.7 87.6 82.3 86.1 89.6 92.3 84.1 87.7 92.1 94.0
61
SHC 67.2 77.1 83.5 86.6 72 82.7 89.1 92.0 75.8 87.1 91.0 92.7
MBH 86.5 88.1 89.3 90.6 91 92.6 94.0 95.4 92.9 94.6 96.0 97.1
115 67
SHC 50.9 63.7 76.7 85.2 54.5 68.7 82.3 94.6 57.4 71.9 86.6 96.2
MBH 95.1 96.4 97.8 99.8 97.8 99.3 101.4 103.6 99.9 101.3 103.4 105.2
73
SHC 22.5 41.8 57.7 70.5 28.3 53.2 89.1 101.6 32.1 68.4 98.9 103.6
MBH 71.2 74.2 77.0 79.6 74.8 78.3 81.5 83.9 76.5 79.7 83.7 85.5
61
SHC 61.1 70.1 76.8 78.5 65.5 75.2 81.0 83.6 68.9 79.2 82.7 84.3
MBH 78.6 80.1 81.2 82.4 82.7 84.2 85.5 86.7 84.5 86.0 87.3 88.3
125 67
SHC 46.3 57.9 69.7 77.5 49.5 62.5 74.8 86.0 52.2 65.4 78.7 87.5
MBH 86.5 87.6 88.9 90.7 88.9 90.3 92.2 94.2 90.8 92.1 94.0 95.6
73
SHC 20.5 38.0 52.5 64.1 25.7 48.4 81.0 92.4 29.2 62.2 89.9 94.2
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. MBH=Total Gross Capacity. (Unit: kBtu/h).
3. SHC=Sensible Heat Capacity. (Unit: kBtu/h).
37
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 10Ton:
73
SHC 46.3 65.4 81.5 97.8 47.2 66.7 84.3 101.9
MBH 94.5 96.4 98.3 100.3 97.8 99.8 101.8 103.8
Entering Wet Bulb(℉)
61
SHC 88.6 90.4 92.2 94.0 95.2 97.1 99.0 101.0
MBH 110.3 112.5 114.8 117.1 112.9 115.2 117.5 119.8
105 67
SHC 67.6 86.4 105.9 115.6 71.3 92.1 113.7 117.9
Ambient
Notes: 1. All capacities are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat.
2. MBH=Total Gross Capacity.(Unit: kBtu/h).
3. SHC=Sensible Heat Capacity.(Unit: kBtu/h).
38
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Heating capacity for 10Ton:
Net Capacities(kW)-4000 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(℃) Peak Net Power(KW) at Indicated Dry Bulb(℃)
Outdoor Temp(℃) 70% RH
15 21 24 27 15 21 24 27
-15 19.8 18.6 18.2 17.9 9.2 10.1 10.7 11.3
-12 21.3 20.4 20 19.8 9.4 10.3 10.8 11.5
-9 22.6 22 21.8 21.8 9.5 10.4 10.9 11.7
-6 23.7 23 22.8 22.5 9.6 10.5 11.1 11.9
-3 25.1 24.7 24.5 24.1 9.7 10.6 11.3 12.1
0 27 26.6 26.2 25.9 9.8 10.8 11.5 12.2
3 31.1 30.8 30.3 29.9 10 11 11.7 12.4
6 35.8 35.3 34.9 34.7 10.4 11.2 12.1 12.8
9 40.7 40.2 39.8 39.4 10.8 12 12.7 13.5
12 43.2 44.7 44.5 44.1 11.2 12.5 13.2 14
15 46.6 45.9 45.6 45.1 11.5 12.8 13.5 14.3
18 49.4 48.5 48 47.6 11.8 13.1 13.9 14.6
21 53 51.9 51.2 50.5 12 13.3 14 14.7
24 56 54.5 53.6 53 12.3 13.5 14.5 15
39
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 12.5Ton:
Air Flow CFM 4500 5000
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 133.0 134.6 140.6 148.5 136.6 139.5 145.5 153.4
61
SHC 106.9 126.7 135.0 142.6 112.8 134.6 141.1 148.8
MBH 149.0 150.8 152.5 154.6 153.4 154.5 155.4 156.4
85 67
SHC 85.1 103.9 121.8 140.6 88.9 107.9 127.7 146.5
MBH 157.4 160.4 162.4 164.4 159.2 161.4 164.4 166.3
73
SHC 58.7 78.7 95.1 110.9 59.8 80.5 97.2 112.7
MBH 124.7 127.7 133.7 142.6 126.3 131.7 139.6 147.5
61
SHC 101.9 121.8 124.7 131.6 107.9 126.4 134.0 141.6
MBH 139.6 141.6 143.6 146.5 145.5 150.0 151.5 152.5
95 67
SHC 81.2 100.0 118.8 137.6 84.6 104.9 124.8 145.5
MBH 153.5 155.4 157.3 159.4 154.6 156.3 158.7 161.4
Temperature(℉)
73
SHC 56.1 75.7 93.3 109.9 57.3 78.3 95.8 113.9
MBH 116 119.0 125.0 135.0 120 123.0 133.0 139.0
Entering Wet Bulb(℉)
61
SHC 97.2 104.0 113.0 125.0 104 111.0 122.0 129.0
MBH 133 135.0 138.0 139.0 134 137.0 141.0 143.0
105 67
SHC 76.9 96.0 114.9 134.7 88.6 101.0 121.8 143.0
Ambient
40
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 15Ton:
Air Flow CFM 5500 6000
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 163.6 165.6 172.9 182.7 168.0 171.6 179.0 188.7
61
SHC 131.5 155.8 166.0 175.3 138.7 165.6 173.6 183.0
MBH 183.3 185.5 187.6 190.2 188.7 190.0 191.1 192.4
85 67
SHC 104.7 127.8 149.8 172.9 109.3 132.7 157.1 180.2
MBH 193.6 197.3 199.8 202.2 195.8 198.5 202.2 204.5
73
SHC 72.2 96.8 117.0 136.4 73.6 99.0 119.6 138.6
MBH 153.4 157.1 164.5 175.4 155.3 162.0 171.7 181.4
61
SHC 125.3 149.8 159.5 170.1 132.7 157.1 166.6 176.0
MBH 171.7 174.2 176.6 180.2 179.0 180.0 182.7 183.9
95 67
SHC 99.9 123.0 146.1 169.2 104.1 129.0 153.5 179.0
MBH 188.8 191.1 193.5 196.1 190.2 192.2 195.2 198.5
Temperature(℉)
73
SHC 69.0 93.1 114.8 135.2 70.5 96.3 117.8 140.1
MBH 142.7 146.4 153.8 166.1 147.6 151.3 163.6 171.0
Entering Wet Bulb(℉)
61
SHC 119.6 140.5 147.6 159.4 127.9 145.2 157.0 164.1
MBH 163.6 166.1 169.7 171.0 164.8 168.5 173.4 175.9
105 67
SHC 94.6 118.1 141.3 165.7 109.0 124.2 149.8 170.6
Ambient
41
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Heating capacity for 15Ton:
Net Capacities(kW)-6000 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(℃) Peak Net Power(KW) at Indicated Dry Bulb(℃)
Outdoor Temp(℃) 70% RH
15 21 24 27 15 21 24 27
-15 29.7 27.9 27.3 26.9 13.8 15.2 16.1 17.0
-12 32.0 30.6 30.0 29.7 14.1 15.5 16.2 17.3
-9 33.9 33.0 32.7 32.7 14.3 15.6 16.4 17.6
-6 35.6 34.5 34.2 33.8 14.4 15.8 16.7 17.9
-3 37.7 37.1 36.8 36.2 14.6 15.9 17.0 18.2
0 40.5 39.9 39.3 38.9 14.7 16.2 17.3 18.3
3 46.7 46.2 45.5 44.9 15.0 16.5 17.6 18.6
6 53.7 53.0 52.4 52.1 15.6 16.8 18.2 19.2
9 61.1 60.3 59.7 59.1 16.2 18.0 19.1 20.3
12 64.8 67.1 66.8 66.2 16.8 18.8 19.8 21.0
15 69.9 68.9 68.4 67.7 17.3 19.2 20.3 21.5
18 74.1 72.8 72.0 71.4 17.7 19.7 20.9 21.9
21 79.5 77.9 76.8 75.8 18.0 20.0 21.0 22.1
24 84.0 81.8 80.4 79.5 18.5 20.3 21.8 22.5
42
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 17.5Ton:
Air Flow CFM 6500 7000
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 191.4 193.7 202.3 213.7 196.6 200.7 209.4 220.7
61
SHC 153.8 182.3 196.3 207.3 162.3 193.7 203.1 214.1
MBH 214.4 217.0 219.4 222.5 220.7 222.3 223.6 225.1
85 67
SHC 122.5 149.5 175.3 202.3 127.9 155.3 183.8 210.8
MBH 226.5 230.8 233.7 236.6 229.1 232.3 236.6 239.3
73
SHC 84.5 113.2 136.8 159.6 86.1 115.8 139.9 162.2
MBH 179.4 183.8 192.4 205.2 181.7 189.5 200.9 212.3
61
SHC 146.6 175.3 186.6 199.0 155.3 183.8 194.9 205.9
MBH 200.9 203.8 206.6 208.0 207.0 210.0 213.7 215.1
95 67
SHC 116.8 143.9 171.0 198.0 121.7 151.0 179.6 209.4
MBH 220.9 223.6 226.4 229.4 222.5 224.9 228.4 232.3
Temperature(℉)
73
SHC 80.7 108.9 134.3 158.1 82.5 112.7 137.9 163.9
MBH 166.9 171.2 179.9 194.3 172.7 177.0 191.4 200.0
Entering Wet Bulb(℉)
61
SHC 139.9 166.1 174.5 188.4 149.7 171.7 185.6 194.0
MBH 191.4 194.3 198.6 200.0 192.8 197.1 202.9 205.8
105 67
SHC 110.7 138.1 165.3 193.8 127.5 145.3 175.3 199.6
Ambient
43
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 20Ton:
Air Flow CFM 7500 8000
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 216.1 218.7 228.5 241.3 222.0 226.7 236.4 249.3
61
SHC 173.7 205.9 221.6 234.1 183.3 218.7 229.3 241.8
MBH 242.1 245.1 247.8 251.2 249.3 251.1 252.5 254.2
85 67
SHC 138.3 168.8 197.9 228.5 144.5 175.3 207.5 238.1
MBH 255.8 260.7 263.9 267.2 258.7 262.3 267.2 270.2
73
SHC 95.4 127.9 154.5 180.2 97.2 130.8 158.0 183.1
MBH 202.6 207.5 217.3 231.7 205.2 214.0 226.9 239.7
61
SHC 165.6 197.9 210.7 224.8 175.3 205.5 217.8 230.1
MBH 226.9 230.1 233.4 238.1 236.4 240.0 241.3 242.9
95 67
SHC 132.0 162.5 193.1 223.6 137.5 170.5 202.8 236.4
MBH 249.4 252.5 255.6 259.0 251.2 254.0 257.9 262.3
Temperature(℉)
73
SHC 91.2 123.0 151.6 178.6 93.1 127.2 155.7 185.1
Entering Wet Bulb (℉)
44
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Peak Net Heating(kW) at Indicated Dry Bulb(℃) Peak Net Power(KW) at Indicated Dry Bulb(℃)
Outdoor Temp(℃) 70% RH
15 21 24 27 15 21 24 27
-15 39.6 37.2 36.4 35.8 18.4 20.2 21.4 22.6
-12 42.6 40.8 40.0 39.6 18.8 20.6 21.6 23.0
-9 45.2 44.0 43.6 43.6 19.0 20.8 21.8 23.4
-6 47.4 46.0 45.6 45.0 19.2 21.0 22.2 23.8
-3 50.2 49.4 49.0 48.2 19.4 21.2 22.6 24.2
0 54.0 53.2 52.4 51.8 19.6 21.6 23.0 24.4
3 62.2 61.6 60.6 59.8 20.0 22.0 23.4 24.8
6 71.6 70.6 69.8 69.4 20.8 22.4 24.2 25.6
9 81.4 80.4 79.6 78.8 21.6 24.0 25.4 27.0
12 86.4 89.4 89.0 88.2 22.4 25.0 26.4 28.0
15 93.2 91.8 91.2 90.2 23.0 25.6 27.0 28.6
18 98.8 97.0 96.0 95.2 23.6 26.2 27.8 29.2
21 106.0 103.8 102.4 101.0 24.0 26.6 28.0 29.4
24 112.0 109.0 107.2 106.0 24.6 27.0 29.0 30.0
45
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Cooling capacity for 25Ton:
Air Flow CFM 9500 10000
Ent DB (℉) 75 80 85 90 75 80 85 90
MBH 277 283 288 294 285 290 296 302
61
SHC 242 247 252 257 258 263 268 274
MBH 309 315 321 327 312 318 324 331
85 67
SHC 183 230 276 312 189 241 295 321
MBH 320 326 333 339 321 327 334 340
73
SHC 119 172 209 248 121 175 216 267
MBH 257 262 267 273 265 270 275 281
61
SHC 232 236 241 246 248 253 258 263
MBH 284 290 296 302 289 300 306 312
95 67
SHC 177 225 269 309 186 237 285 295
MBH 317 323 330 336 318 324 331 337
Temperature(℉)
73
SHC 116 164 204 245 118 167 211 262
Entering Wet Bulb (℉)
46
MCAC-UTSM-2009-05
T3 Condition Rooftop Package Rooftop Package
Heating capacity for 25Ton:
Net Capacities(kW)-10000 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(℃) Peak Net Power(KW) at Indicated Dry Bulb(℃)
Outdoor Temp(℃) 70% RH
15 21 24 27 15 21 24 27
-15 49.5 46.5 45.5 44.8 23.0 25.3 26.8 28.3
-12 53.3 51.0 50.0 49.5 23.5 25.8 27.0 28.8
-9 56.5 55.0 54.5 54.5 23.8 26.0 27.3 29.3
-6 59.3 57.5 57.0 56.3 24.0 26.3 27.8 29.8
-3 62.8 61.8 61.3 60.3 24.3 26.5 28.3 30.3
0 67.5 66.5 65.5 64.8 24.5 27.0 28.8 30.5
3 77.8 77.0 75.8 74.8 25.0 27.5 29.3 31.0
6 89.5 88.3 87.3 86.8 26.0 28.0 30.3 32.0
9 101.8 100.5 99.5 98.5 27.0 30.0 31.8 33.8
12 108.0 111.8 111.3 110.3 28.0 31.3 33.0 35.0
15 116.5 114.8 114.0 112.8 28.8 32.0 33.8 35.8
18 123.5 121.3 120.0 119.0 29.5 32.8 34.8 36.5
21 132.5 129.8 128.0 126.3 30.0 33.3 35.0 36.8
24 140.0 136.3 134.0 132.5 30.8 33.8 36.3 37.5
47
MCAC-UTSM-2009-05 Rooftop Package
48
MCAC-UTSM-2009-05 Rooftop Package
Unit main power Applicable Compressor motor Evaporator fan Condenser fan Auxiliary
Model
VOL Hz Ph Max. l Min. STC RNC IPT RNC IPT RNC IPT h IPTi
MRBT-075CW-C 380-415 60 3 418 342 63 16.2 9.5 3 1.9 2.2 0.8 --
MRBT-085CW-C 380-415 60 3 418 342 63 17.5 10.2 5.3 2.8 2.2 0.8 --
MRBT-100CW-C 380-415 60 3 418 342 63 18.8 11 5.3 2.8 2.2 0.8 --
MRBT-125CW-C 380-415 60 3 418 342 160 28.7 14 8.5 5.5 3.4 1.5 --
MRBT-150CW-C 380-415 60 3 418 342 160 30.3 15.5 8.5 5.5 5.2 1.7 --
MRBT-175CW-C 380-415 60 3 418 342 160 38.6 18.5 8.5 5.5 5.2 1.7 --
MRBT-200CW-C 380-415 60 3 418 342 160 42.8 20 8.5 5.5 5.2 1.7 --
MRCT-062EW-C 380-415 60 3 418 342 38 13.1 7.92 2.8 1.8 2 0.7 14
MRCT-075EW-C 380-415 60 3 418 342 63 16.2 9.5 3 1.9 2.2 0.8 14
MRCT-085EW-C 380-415 60 3 418 342 63 17.5 10.2 5.3 2.8 2.2 0.8 21
MRCT-100EW-C 380-415 60 3 418 342 63 18.8 11 5.3 2.8 2.2 0.8 21
MRCT-125EW-C 380-415 60 3 418 342 160 28.7 14 8.5 5.5 3.4 1.5 30
MRCT-150EW-C 380-415 60 3 418 342 160 30.3 15.5 8.5 5.5 5.2 1.7 30
MRCT-175EW-C 380-415 60 3 418 342 160 38.4 18.5 8.5 5.5 5.2 1.7 39
MRCT-200EW-C 380-415 60 3 418 342 160 42.8 20 8.5 5.5 5.2 1.7 39
MRDT-062EW-C 380-415 60 3 418 342 38 13.1 7.92 2.8 1.8 2 0.7 14
MRDT-075EW-C 380-415 60 3 418 342 63 16.2 9.5 3 1.9 2.2 0.8 14
MRDT-085EW-C 380-415 60 3 418 342 63 17.5 10.2 5.3 2.8 2.2 0.8 21
MRDT-100EW-C 380-415 60 3 418 342 63 18.8 11 5.3 2.8 2.2 0.8 21
MRDT-125EW-C 380-415 60 3 418 342 160 28.7 14 8.5 5.5 3.4 1.5 30
MRDT-150EW-C 380-415 60 3 418 342 160 30.3 15.5 8.5 5.5 5.2 1.7 30
MRDT-175EW-C 380-415 60 3 418 342 160 38.4 18.5 8.5 5.5 5.2 1.7 39
MRDT-200EW-C 380-415 60 3 418 342 160 42.8 20 8.5 5.5 5.2 1.7 39
VOL: Unit Power Supply Rated (plated) Voltage (V)
Hz: Frequency (Hz)
STC: Starting Current (A)
RNC: Running Current (A)
IPT: Input (kW)
Note:
1. These data are based on the following conditions:
Evaporator Air Input Temperature 85 F DB, 66 F WB.
Condenser Air Input Temperature 115 F DB.
2. The starting current is indicated for each compressor motor.
3. The maximum currents of the compressor can be estimated as follows.
One compressor unit Two compressor unit
Max. current RNC×Max. IPT×/IPT RNC×Max. IPT×/IPT
Max. instantaneous current STC STC+RNC×0.5×Max. IPT×/IPT
Max. IPT×: Compressor power input from the performance table at the expected maximum condition
STC, IPT, RNC: Compressor data from the above table
4. The data in the compressor motor column shall indicate the respective values of the refrigeration cycle.
49
MCAC-UTSM-2009-05 Rooftop Package
250
225
200
175
150
125
100
75
50
25
0
1765 2060 2355 2650 2945 3240 3535 3830
Air volume(CFM)
50
MCAC-UTSM-2009-05 Rooftop Package
250
225
200
175
150
125
100
75
50
25
0
2060 2355 2650 2945 3240 3535 3830 4125
Air volume(CFM)
51
MCAC-UTSM-2009-05 Rooftop Package
250
225
200
175
150
125
100
75
50
25
0
2600 2800 3000 3200 3400 3600 3800 4000
Air volume(CFM)
52
MCAC-UTSM-2009-05 Rooftop Package
300
270
240
210
180
150
120
90
60
30
0
2900 3200 3500 3800 4100 4400 4700 5000
Air volume(CFM)
53
MCAC-UTSM-2009-05 Rooftop Package
300
270
240
210
180
150
120
90
60
30
0
4250 4500 4750 5000 5250 5500 5750 6000 6250
Air volume(CFM)
Parameter table for outdoor unit air volume:
Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)
0 10000 0.78×2 935
12.5Ton 10 9800 0.79×2 926
20 9600 0.80×2 918
54
MCAC-UTSM-2009-05 Rooftop Package
300
270
240
210
180
150
120
90
60
30
0
4750 5000 5250 5500 5750 6000 6250 6500 6750 7000 7250
Air volume(CFM)
Parameter table for outdoor unit air volume:
Static pressure Air flow Brake power Fan speed
Model
(Pa) (CFM) (kW) (rpm)
0 11000 0.78×2 935
15Ton 10 9800 0.79×2 926
20 9600 0.80×2 918
55
MCAC-UTSM-2009-05 Rooftop Package
300
270
240
210
180
150
120
90
60
30
0
5200 5500 5800 6100 6400 6700 7000 7300 7600 7900 8200
Air volume(CFM)
56
MCAC-UTSM-2009-05 Rooftop Package
300
270
240
210
180
150
120
90
60
30
0
7000 7150 7300 7450 7600 7750 7900 8050 8200 8350 8500
Air volume(CFM)
57
MCAC-UTSM-2009-05 Rooftop Package
300
270
240
210
180
150
120
90
60
30
0
8950 9300 9650 10000 10350 10700 11050 11400 11750 12100 12450
Air volume(CFM)
58
MCAC-UTSM-2009-05 Rooftop Package
TP
TP
Capillary
Capillary
Comp A Comp B
T2
Evaporator
T3
T3
Condersor
Four-way valve Four-way valve
expansion valve for
Capillary (Thermal
High-pressure High-pressure
switch switch
TP TP
optional)
Low-pressure
Low-pressure switch
switch
Comp B
Comp A
Evaporator
T2
T2
59
MCAC-UTSM-2009-05 Rooftop Package
60
MCAC-UTSM-2009-05 Rooftop Package
Standard
operation
Temperature
Outdoor temperature Indoor temperature
Model
Without auxiliary electric heater models 18℃~52℃ 17℃~30℃
With auxiliary electric heater models -- 17℃~30℃
13.1 Cooling and heating
Cooling mode
Outdoor temperature(℃ DB)
Standard
operation
61
MCAC-UTSM-2009-05 Rooftop Package
Temperature
Outdoor temperature Indoor temperature
Model
Cooling model 18℃~52℃ 17℃~30℃
Heating model
Standard
operation
Temperature
Outdoor temperature Indoor temperature
Model
Heating model -15℃~24℃ 17℃~30℃
62
MCAC-UTSM-2009-05 Rooftop Package
14. Installations
14.1 Service Space
1. The recommended clearances for single-unit installations are illustrated in following Fig.
These minimum requirements are not only an important consideration when determining unit placement, but
they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation
or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be
reviewed with a local engineer.
63
MCAC-UTSM-2009-05 Rooftop Package
64
MCAC-UTSM-2009-05 Rooftop Package
65
MCAC-UTSM-2009-05 Rooftop Package
14.5 Ductwork
1. Attaching horizontal ductwork to unit
1) All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a
minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be weatherproofed
between the unit and the building.
66
MCAC-UTSM-2009-05 Rooftop Package
2) When attaching ductwork to a horizontal unit, provide a flexible watertight connection to prevent noise
transmission from the unit to the ducts. The flexible connection must be indoors and made out of heavy
canvas.
Note:
Do not draw the canvas taut between the solid ducts.
67
MCAC-UTSM-2009-05 Rooftop Package
KJR-23B
Thermostats choose non-programmed electrical thermostat series of Honeywell such as:
Honeywell TH5220D Honeywell T8000C Honeywell T8400C
Honeywell TH5220D
68
MCAC-UTSM-2009-05 Rooftop Package
17. Accessories
Name Quantity Shape
Manual 1
Drain outlet 1
Snap ring 1
Drain pipe 1
69
MCAC-UTSM-2009-05 Rooftop Package
Model A Model A
6.2 Ton 8.5 Ton
328mm 395mm
7.5 Ton 10 Ton
12.5 Ton 17.5 Ton
555mm 525mm
15 Ton 20 Ton
Regulating belt of rate of tension, inner fan Refer to the following Fig. fixed bolt of electric motor’s supporting
slide was loosened, following electric motor was droved, belt of rate of tension will begin change.
70
MCAC-UTSM-2009-05 Rooftop Package
NOTE
The belt which is too tight or too loose may generate noise and be harmful to the unit.
71
MCAC-UTSM-2009-05 Rooftop Package
72
MCAC-UTSM-2009-05 Rooftop Package
Variable belt:
Turn Air flow (CFM) Fan speed(RPM) Static pressure (pa)
73
MCAC-UTSM-2009-05 Rooftop Package
7.5Ton:
Fixed belt:
Air flow (CFM) 3254 3192 3122 3066 3010 2943 2888 2819 2755 2683 2615
Static pressure (pa) 0 15 30 45 60 75 90 105 120 135 150
Variable belt:
74
MCAC-UTSM-2009-05 Rooftop Package
8.5Ton:
Fixed belt:
Air flow (CFM) 3906 3814 3717 3640 3555 3459 3361 3270 3181 3097 3005
Static pressure (pa) 0 15 30 45 60 75 90 105 120 135 150
Variable belt:
3750 1050 75
3500 1062 120
0 3250 1077 170
3000 1084 210
2750 1090 256
3750 1094 102
3500 1104 150
1 3250 1111 199
3000 1120 244
2750 1126 286
3750 1122 125
3500 1138 175
2 3250 1140 220
3000 1149 270
2750 1158 310
3750 1145 150
3500 1155 200
3 3250 1163 242
3000 1180 287
2750 1182 326
3750 1169 165
3500 1188 226
4 3250 1205 282
3000 1217 334
2750 1225 365
3750 1195 185
5
3500 1203 233
75
MCAC-UTSM-2009-05 Rooftop Package
10 Ton:
Fixed belt:
Air flow (CFM) 4453 4126 3982 3783 3696 3498 3433 3349 3279 3212 3143
Static pressure (pa) 0 20 40 60 80 100 120 140 160 180 200
Variable belt:
Turn Air flow (CFM) Fan speed(RPM) Static pressure (pa)
4500 1100 25
4250 1122 75
0 4000 1130 120
3750 1138 170
3500 1150 220
4500 1140 45
4250 1145 100
1 4000 1152 140
3750 1158 185
3500 1166 250
4500 1148 75
4250 1156 135
2 4000 1162 180
3750 1168 240
3500 1174 290
4500 1156 105
4250 1165 200
3 4000 1173 242
3750 1180 287
3500 1184 326
4500 1169 125
4250 1188 226
4 4000 1205 280
3750 1217 315
3500 1225 335
4500 1195 165
5
4250 1203 260
76
MCAC-UTSM-2009-05 Rooftop Package
Appendix 1: Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (℃--K)
77