Generator Automatic Voltage Regulator Operation Manual
Generator Automatic Voltage Regulator Operation Manual
Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw
SECTION 1 : SUMMARY The AVR is equipped with adjustable under frequency
protection and over voltage protection to prevent
EA06-220V is equipped with 3 separate sensing inputs generator from overloading and over excitation.
(1-2, 3-4, 5-6 terminals R.S.T phase), which can survey
from single up to three phase voltages and check the The 3 LED each represents (Green) normal operation,
average voltage from Y, YY or wiring accordingly to (Red) under frequency and (Yellow) over excitation.
the generator requirement or user preference.
The built in EMS filter helps to prevent possible
interference from the AVR to the generator.
SECTION 2 : SPECIFICATION
Sensing Input (1-2, 3-4, 5-6) Soft Start Ramp Time
Voltage 170 − 280 Vac / 270 − 520 Vac 4 sec.
1 or 3 phase selectable by wiring
Frequency 50 / 60 Hz Unit Power Dissipation
Max.5 watts
Power Input (+, 2)
Voltage 50 − 280 Vac EMI Suppression
Frequency 50 / 60 Hz Internal EMI filtering
5
4 3 2 1 0 B + ATTENTION
6
1. AVR can be mounted directly on the engine,
genset, switchgear, control panel, or any position
that will not affects operation. For dimension
reference, please see Figure 1.
2. All voltage readings are to be taken with an
150.0
122.0
EA06
___________________________________________________________________________________________
4 EA06-220V
S
- Field
+
N T
R
Auxiliary
winding Delta winding
6 5 4 3 2 1 0 B + -
60HZ
VR
S S
-
-
Field
Field
+ +
N T N T
R R
Delta winding Delta winding
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
R R
-
-
Field
Field
S S
T + T +
N N
Auxiliary
winding
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
Figure 6 1 phase 220 Vac Figure 7 1 phase 220 Vac With auxiliary winding
R
-
R
-
Field
Field
S S
T + T +
N N
Auxiliary
winding
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
Figure 8 3 phase 220 Vac Figure 9 3 phase 220 Vac With auxiliary winding
___________________________________________________________________________________________
EA06-220V 5
R R
-
Field
Field
S S
T + T +
N N
Auxiliary
winding
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
Figure 10 3 phase 380 / 480 Vac Figure 11 3 phase 380 / 480 Vac With auxiliary winding
R R
-
-
Field
Field
S S
T + T +
N N
Auxiliary
winding
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
Figure 12 3 phase > 480 Vac Figure 13 3 phase > 480 Vac With auxiliary winding
-
Field
Field
S S
T + T +
N N
Auxiliary
winding
5C 4 5 3A 3 1 SR7 5C 4 5 3A 3 1 SR7
Terminal Terminal
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
Figure 14 1 phase 220 Vac Figure 15 1 phase 220 Vac With auxiliary winding
R R
-
-
Field
Field
S S
T + T +
N N
Auxiliary
winding
5C 4 5 3A 3 1 SR7 5C 4 5 3A 3 1 SR7
Terminal Terminal
6 5 4 3 2 1 0 B + - 6 5 4 3 2 1 0 B + -
60HZ 60HZ
VR VR
Figure 16 1 phase 380 / 480 Vac Figure 17 1 phase 380 / 480 Vac With auxiliary winding
※ Use only original supplied spare protection fuse for fuse replacement.
※ Please accept our sincere apology if any modification in performance, specification or appearance is made
without prior notice.
___________________________________________________________________________________________
6 EA06-220V