SIPROTEC4 PROFIBUS DP FAQ en
SIPROTEC4 PROFIBUS DP FAQ en
FAQs
on
PROFIBUS DP
s FAQs on PROFIBUS DP
Table of Contents
Table of Contents
1. References
FAQs about:
2. General PROFIBUS DP and SIPROTEC PROFIBUS DP Modules
3. Electrical (RS485) Interfaces and Networks
4. Fiber-Optical Interfaces and Networks
5. Redundant PROFIBUS DP Networks
6. Time Synchronization of SIPROTEC Devices via PROFIBUS DP
7. Transmission of Indications with Time Stamp
s FAQs on PROFIBUS DP
References
s FAQs on PROFIBUS DP
General PROFIBUS DP and SIPROTEC PROFIBUS DP Modules
Question Answer
Which max. data transfer rates (baud rates) are possible with • 6 MB/s with SIPROTEC RS485 PROFIBUS modules and
PROFIBUS DP and SIPROTEC PROFIBUS DP modules? • 3 MB/s with SIPROTEC fiber-optical PROFIBUS modules.
s FAQs on PROFIBUS DP
Electrical (RS485) Interfaces and Networks
Question Answer
Electrical (RS485) topologies consist of so-called bus segments.
At most 32 devices with a RS485 interface can be connected to
one segment. Repeaters are used to expand the bus with
How many devices can be connected to a RS485 bus?
additional segments (and additional devices).
The max. number of PROFIBUS devices is 126 because of each
device needs its unique address in the range 0…125.
s FAQs on PROFIBUS DP
Fiber-Optical Interfaces and Networks
Question Answer
Depending on the data transmission rate:
How many devices can be connected to a fiber-optical ring? 187.5 kB/s Î 55
500 kB/s and 1.5 MB/s Î 41
s FAQs on PROFIBUS DP
Redundant PROFIBUS DP Networks
Question Answer
SIPROTEC devices have a single (non-redundant) PROFIBUS DP
interface. In order to connect them to a redundant PROFIBUS DP
system with a S7-400 H, so called Y-Links are necessary.
We want to connect SIPROTEC devices to a redundant
These Y-Links are devices from Siemens A&D which are used for
PROFIBUS DP master system (S7-400 H). Is this possible?
connecting non-redundant PROFIBUS DP slave devices to a
redundant S7-400 H PROFIBUS DP master system.
Order no. for Y-Links e.g. 6ES7197-1LA11-0XA0.
s FAQs on PROFIBUS DP
Time Synchronization of SIPROTEC Devices via PROFIBUS DP
Question Answer
Yes, but the master must support this (this is not a standard
function of PROFIBUS DP-V0).
All S7 400 CPU with PROFIBUS DP master and firmware from V3
Can the SIPROTEC devices be time-synchronized via
and all S7 CP443-5 extended PROFIBUS DP modules as well as
PROFIBUS DP?
the CP 5613 PC card support this.
Æ For SIPROTEC devices connected via Y-Link to a redundant
system please observe the next question/answer.
Time synchronization via PROFIBUS DP for devices connected via
Y-Links to a redundant system is only possible with Y-Links
Can the SIPROTEC devices also be time-synchronized via 6ES7197-1LA11-0XA0 using the IM 157-2 High Feature
PROFIBUS DP if they are connected with a Y-Link to a modules (situation in Nov. 2007).
redundant PROFIBUS DP system? Other Y-Links do not relay the time synchronization messages
and therefore time synchronization of SIPROTEC devices then
will not be possible!
Absolute difference of ≤ 10 ms between the devices.
What accuracy can be reached with time synchronization via
PROFIBUS DP? For time synchronization of devices connected to a Y-Link the
absolute difference is ≤ 20 ms between the devices.
s FAQs on PROFIBUS DP
Transmission of Indications with Time Stamp
Question Answer
Yes, with the following preconditions:
• Select a PROFIBUS DP mapping file for the SIPROTEC device
that supports the event list mechanism via PROFIBUS DP
(available for all SIPROTEC devices except 7VK6 and 7SJ602).
• The PROFIBUS DP master (PLC) must be programmed to read
Can time-stamped indications be transferred via PROFIBUS the time stamped information according to the handshake
DP from the SIPROTEC device to the PROFIBUS DP master and mechanism described in our “PROFIBUS DP – Communication
what prerequisites are to observe? profile” user manual!
Æ You find the manual in the communication modules
user manuals directory on www.siprotec.com.
• The SIPROTEC device should be time synchronized (via
PROFIBUS or another method, like e.g. IRIG-B). This is not
necessary but recommended for evaluation of time stamps.
No.
Indications with time stamp can also be transmitted to the
Is the restriction for time synchronization via Y-Link also valid PROFIBUS DP master if the SIPROTEC device is connected to a
for transmission of indication with time stamps? Y-Link which do not support time synchronization via bus.
Use then e.g. IRIG-B or DCF for external time synchronization of
the devices over port A.