UPS Failure
UPS Failure
1.0 All HMI supplies from main UPS will not be available but from battery supply will be available
for around 2 hours.
2.0 Scanner panel power supply will trip and immediately scanner will sense no Flame in the Boiler.
3.0 Unit will trip on flame failure protection. Turbine trips on MFT & Generator will trip on Low Forward
Power protection.
4.0 ID fans VFDs air flow relays and its control supply will be Lost and VFD will trip.
5.0 APH Air Motor will take auto start.
6.0 MDBFP scoop will become inoperative from remote.
7.0 All Drives vibration including the Turbine vibration data will not be available.
8.0 O2 analyzer data will not be available.