Determining Cable Sizes and Protection in An Off Grid PV System Final. 030719pptx - Compressed
Determining Cable Sizes and Protection in An Off Grid PV System Final. 030719pptx - Compressed
3 4
PV CABLE SIZING
1
5/7/19
10
2
5/7/19
However, if the array consists of three (3) parallel strings and • A formula for determining the maximum number of strings
a fault occurs in one (1) string then the fault current could allowed before fuses are required is:
come from the other two (2) strings.
This current is 17.8A (2 x 8.9A) and is now greater than the Maximum Number of Strings without string protection
reverse current rating of the module. Protection is now = reverse current rating of a module/Isc of the module
required.
(a) be rated for dc use; 1.5 x Isc of module < 𝐼"#$% < 2.4 x Isc of module
(b) have a voltage rating equal to or greater than the PV array and
Fuse Rating < IRC of module
maximum voltage determined in section 5 of the guidelines;
(c) be rated to interrupt fault currents from the PV array; and • Where
• Isc of module= Module short circuit current
(d) be of an overcurrent and short circuit current protective • ITRIP = rated trip current of the fault current protection device.
type suitable for PV complying with IEC 60269-6 (i.e. Type • IRC of module= Module reverse current rating
3
5/7/19
EXAMPLE 1 EXAMPLE 1
An array consists of 3 parallel strings. These connect to a
controller and then to a battery bank. For this exercise, A table showing current carrying capacities of different cable sizes has been
provided to assist you.
assume the main battery protection is not sized to protect Table 1: Current carry capacities of cables
16 63 1000
19 20
SOLUTION
Array Protection
• Must be between 1.25 and 2.4 times the array short circuit
current (from VOLTAGE DROP
• Hence: Minimum fuse size = 1.25 x 3 x 5.4 = 20.25A
Maximum fuse size = 2.4 x 3 x 5.4 = 38.88A
• The fuse chosen is 30A.
Array cable
• The circuit protection can be smaller than the current carrying
capacity of the cable but never larger.
• Thus, the cable chosen from Table 1 is 6mm 2 with a CCC of
34A.
21 22
23 24
4
5/7/19
25
>? Where:
Voltage Drop in percentage = × 100 • LCABLE = route length of cable in metres (multiplying it by two adjusts for total circuit wire
>CABB
length since a complete circuit requires a wire out and another wire back along the route).
• I = current in amperes.
• ρ = resistivity of the wire in W/m/mm2
= 0.351/12 × 100 • ACABLE = cross sectional area (CSA) of cable in mm2.
• VMAX = maximum line voltage in volts
= 2.9%
5
5/7/19
= 0.88/154.4 x 100
= 0.57%
MAXIMUM DISTANCE IN METRES TO PRODUCE MAXIMUM CABLE LENGTHS IN METRES FOR 12V
5% VOLTAGE DROP (12V SYSTEM) SYSTEM 3% VOLTAGE DROP
Current (A) 1mm2 1.5mm2 2.5mm2 4mm2 6mm2 10mm2 16mm2 Current
(A) 1mm2 1.5mm2 2.5mm2 4mm2 6mm2 10mm2 16mm2
1 16.4 24.6 41 65.6 98.4 163.9 262.3
1 9.8 14.8 24.6 39.3 59.0 98.4 157.4
2 8.2 12.3 20.5 32.8 49.2 82 131.1
2 4.9 7.4 12.3 19.7 29.5 49.2 78.7
3 5.5 8.2 13.7 21.9 32.8 54.6 87.4
3 3.3 4.9 8.2 13.1 19.7 32.8 52.5
4 4.1 6.1 10.2 16.4 24.6 41.0 65.6
4 2.5 3.7 6.1 9.8 14.8 24.6 39.3
5 3.3 4.9 8.2 13.1 19.7 32.8 52.5
5 2.0 3.0 4.9 7.9 11.8 19.7 31.5
6 2.7 4.1 6.8 10.9 16.4 27.3 43.7
6 1.6 2.5 4.1 6.6 9.8 16.4 26.2
7 2.3 3.5 5.9 9.4 14.1 23.4 37.5
7 1.4 2.1 3.5 5.6 8.4 14.1 22.5
8 2.0 3.1 5.1 8.2 12.3 20.5 32.8
8 1.2 1.8 3.1 4.9 7.4 12.3 19.7
9 1.8 2.7 4.6 7.3 10.9 18.2 29.1
9 1.1 1.6 2.7 4.4 6.6 10.9 17.5
10 1.6 2.5 4.1 6.6 9.8 16.4 26.2
10 1.0 1.5 2.5 3.9 5.9 9.8 15.7
11 1.5 2.2 3.7 6.0 8.9 14.9 23.8
11 0.9 1.3 2.2 3.6 5.4 8.9 14.3
12 1.4 2.0 3.4 5.5 8.2 13.7 21.9
12 0.8 1.2 2.0 3.3 4.9 8.2 13.1
13 1.9 3.2 5.0 7.6 12.6 20.2
13 1.1 1.9 3.0 4.5 7.6 12.1
14 1.8 2.9 4.7 7.0 11.7 18.7
14 1.1 1.8 2.8 4.2 7.0 11.2
15 1.6 2.7 4.4 6.6 10.9 17.5
15 1.0 1.6 2.6 3.9 6.6 10.5
16 1.5 2.6 4.1 6.1 10.2 16.4
16 0.9 1.5 2.5 3.7 6.1 9.8
17 2.4 3.9 5.8 9.6 15.4
17 1.4 2.3 3.5 5.8 9.3
18 2.3 3.6 5.5 9.1 14.6
18 1.4 2.2 3.3 5.5 8.7
19 2.2 3.5 5.2 8.6 13.8
19 1.3 2.1 3.1 5.2 8.3
20 2.0 3.3 4.9 8.2 13.1
20 1.2 2.0 3.0 4.9 7.9
6
5/7/19
output of the array and the inverter is 33 feet. The short circuit
current of the array is 9.6A.
• The cable is AWG 6 = 9.6 x 2 x 33 x 0.491/1000 V
= 0.311 V
• The battery voltage of the system is 12V . > ?
Voltage Drop (in percentage) = × 100
• From Table 4 (previous slide), the dc Resistance in Ohms > CABB
= 0.311/12 x 100
per 1000 feet =0.491 = 2.6%
> ?
• From Table 4, the dc Resistance in Ohms per
Voltage drop (in percentage) =
> DEF
× 100
1000 feet =1.24
7
5/7/19
EXAMPLE – VOLTAGE DROP METHOD WHEN EXAMPLE - VOLTAGE DROP METHOD WITH
SELECTING CABLE (PWM Controller) SOLUTION MPPT (MPPT Controller)
Minimum cross-sectional area = Cable length = 10m between solar
2 x 12 x 30 x 0.0183 array and MPPT controller
0.03 x 24 Array current = 27.3A
= 18.3 mm2
Vmpp of array= 92.1V
Choose the next size of cable ABOVE this – 25mm
squared. Using copper wire – resistivity = 0.0183
Next, we have to check that the 25mm sq. cable can Maximum allowable voltage loss = 3%
carry 30A. (0.03)
Upon checking CCC tables, it can carry more than
30A, therefore 25 sq. should be ok.
8
5/7/19
49 50
CABLE SIZING BETWEEN MPPT CONTROLLER CABLE SIZING BETWEEN BATTERY AND BATERY
AND BATTERY INVERTER (IF APPLICABLE)
• The current carrying capacity of the cable between the • The current carrying capacity of the cable between the
controller and battery shall be capable of carrying the battery bank and the battery inverter shall be capable
maximum charge current from the MPPT. of carrying the maximum current based on either the 30
• The dc current rating of the associated over-current minute power rating of the inverter (if provided) or the
protection shall not be greater than that of the cable. continuous power rating of the inverter.
• If it is an non-seperated MPPT (all are at moment) the • The dc current rating of the associated over-current
cable needs voltage rating greater than the Voc of the protection shall not be greater than that of the cable
array.
51 52
53 54
9
5/7/19
Notes:
1. A PV array dc switch disconnector is recommended because it helps with maintenance and
troubleshooting. However many standards allow the battery bank switch fuse to meet the isolation
requirement. A switch disconnector will be required to be a protection device (e.g. a non polarised
dc circuit breaker) if the battery bank fuse ratings are greater than the current carrying capability of
the PV array cables and the solar controller allows back feed from the battery bank.
3. Batteries in parallel each require their own isolation and protection devices.
Over-current protection is required for the battery bank cable when the current-
carrying capacity of the battery bank cable is less than the sum of all individual
battery over-current protection devices. A battery bank switch disconnecting
device is recommended because it allows the disconnection of the complete
battery bank via the one switch disconnector.
10
5/7/19
11
5/7/19
• Obtain Time-Current characteristics for the overload protection • Consult the Time-Current characteristic of available
to be used. overload protection devices to determine the device with an
[All manufacturers publish time-current information for their circuit appropriate rating that matches the maximum load and
breaker and HRC fuse ranges]
maximum load surge characteristics.
12
5/7/19
EXAMPLE
74
75 76
The End
13