Introduction:
Prok dv’s make Microcontroller Based Motor Protection Relay PD-MMPR-303 uses the state-of-the-art
Microcontroller based measurement techniques for providing protection for Motors up-to 75HP. The
comprehensive protection features of the relay make it ideal for Motor protection. The heart of the relay
is microcontroller based reliable hardware with special algorithms to calculate the tripping time. The
relay continuously monitors the Three Phase Currents to build the thermal replica of the Motor. This
thermal replica is used to protect the Motor against Thermal over Loads.
The Microcontroller Based Motor Protection Relay does not require external Current Transformer (CT)
for its operation for within the bandwidth of Im ranges. The three phase R, Y and B cables are made to
pass through the CT hole which is in the relay. The built in CT’s takes care of stepping down of the
Currents to the required level. The stepped down three phase Currents are continuously monitored by
the relay to detect any abnormal behavior of the Motor and to make tripping decision.
The following protections offered by Prokdv’s make Microcontroller Based Motor Protection Relay PD-
MMPR-303:
Thermal Over Load Protection
Single Phasing /Phase Fail Protection
Phase Reversal Protection
Unbalance Protection
Earth Fault Protection
Locked Rotor Protection
Under Current Protection
Instantaneous Short Circuit protection during Run mode
FEATURES
Accurate and Real Time TRUE RMS measurements.
Motor Rated Current (Im) Selection by means of Pot meter with markings.
Earth Fault Setting provided by means of Pot meter with markings.
Selectable Thermal Trip Time characteristics Class - 10A, 10, 20 & 30.
I > Thermal over load above105 % of Im - provided through visual led indication
Provided the Thermal replica for motor overload condition.
Continuous monitoring of Motor IDLE/Stop, COLD, WARM, HOT, I> & Various Fault status through
visual LED indication.
Motor protections – UB (Unbalance), UC (Under current), LR (Locked rotor), EF (Earth fault) can be
enabled or disabled using Dip switch setting.
Motor Trip class – Class 10A, Class 10, Class 20, Class 30 can be configured using dipswitch
If none of the trip class selected, Default: CLASS 20 Selected internally
Potential free Relay changeover output contacts C& NC and C& NO provided for all Fault TRIP
Instantaneous short circuit protection > 10 times of Im, during Run mode
Front end Communication through Mod bus protocol with RS-485 Port for Fixed slave I.D-
(optional).
Various Models with Current ratings.
Compact and Reliable.
Manual TEST / RESET Facility.
1
Applications: Protection of LV Motors up-to 75HP in Motor Control Center
Specifications:
1) Thermal over Load Protection:
Over Load Current Setting Range 1.0Amps – 96.0Amps in 4 ranges as explained in SL.13
Trip Time Characteristics Class -10A, 10, 20 &30 as per IEC 947-4-1(Default: Trip class 20) if none
of the trip class selected by means of Dip switch.
Thermal overload pick up above 105 % of Im indication through blinking of TOL led
Provided the Thermal Replica for Motor over load
Thermal overload pick up status I> indicated through visual LED indication
2) Instantaneous Short circuit Protection > 10 (Im) During Run mode
If Short circuit Current above 10 times the Motor Rated Current (Im) during Run mode or Status
Instantaneous trip initiated irrespective of Trip class indicated through by switching on all the Fault
LED’S Permanently
3) Earth Fault Protection
Earth Fault Current Setting Range - 10% to 50% of Im, in steps of 10%
Fixed Trip Time Delay - 0.5Sec
Enable / Disable Option using Dip switch
4) Unbalance Protection
Fixed Unbalance current setting - 40% of Iavg
Fixed Trip Time Delay - 5.0Sec
Enable / Disable Option using Dip switch
5) Locked Rotor Protection
Locked Rotor Current -Greater than 3 times of Im
Fixed Trip Time Delay –0.5S
Enable / Disable Option using Dip switch
6) Under Current Protection
Fixed Under Current Setting - 15% of Im
Fixed Trip Time Delay – 1 Sec
Enable / Disable Option using Dip switch
7) Loss of Phase / Single Phasing
Applicable when one or two line currents falls below the 50% of motor rated current
Fixed Trip Time 3.0 Sec
8) Phase Reversal Monitoring
When Power sequence reversed
Fixed Trip Time Delay 0.1 Sec
9) Contacts: C & NC and C & NO 240V@5A AC, 30V@5A DC Potential-Free Output Contacts for trip
circuits for all Seven faults
10) Auxiliary Power Supply: 85-275V AC / DC
11) Trip Accuracy: As per IEC 947-4-1, for Trip Class 10A, 10, 20, & 30
12) Pick-Up Accuracy: +/- 12.5%
13) Reset: Manual
14) Models: PD-MMPR-303-1(1.0A-10.0Amps)
PD-MMPR-303-2 (10.0Amps-32.0Amps)
PD-MMPR-303-3 (20.0Amps-64.0Amps)
PD-MMPR-303-4 (30.0Amps-96.0Amps)
15) Front end Communication is through RS-485 MODBUS Protocol (HALF DUPLEX), fixed Baud
rate: 9600 bps & For fixed device i.d- 10, Data: 8Bit, stop bit:1, (optional)
16) Mounting: DIN Rail
17) Dimensions in mm: 70X55X108 (WXHXD) ±1mm
18) Operating Temp: 0⁰c to +55⁰c
2
Protections Offered By PD-MMPR-303 Series
Prok dv’s make Microcontroller Based Motor Protection Relay PD-MMPR-303 Series is designed to
offer the following protections to Low Voltage (LV) 3-Phase induction motors rated up to 75HP.
Whenever a Relay detects any of the following faults,
Prok dv’s make Microcontroller Based Motor Protection Relay having two set of potential free output
changeover contact (C &NC) and (C& NO) for TRIP circuit
Thermal Over Load Protection:
Prok dv’s make Microcontroller Based Motor Protection Relay continuously monitoring Real Time
Motor Current of all the Three Phases. When the Motor Current exceeds the set value Im, the relay
issues a trip command after the calculated time elapse (Based on selection of trip Class). The relay
visually indicating the fault trip status by means of LED’s
Two Set of potential free output changeover contact is provided in the relay C& NC and C& NO for trip
circuit .The relay continuously monitors the Currents and using this data it builds Thermal replica of the
Motor and monitoring the Thermal status of the Motor. This information is used to protect the Motor
against Thermal over Loading.
Instantaneous short circuit Protection- (Run Mode)
Prok dv’s make Microcontroller Based Motor Protection Relay continuously monitoring Real Time
Motor Current of all the Three Phases during Run mode, When the Motor Current exceeds the 10
times the set value Im, the relay issues a instantaneous trip command, irrespective of selection of trip
Class The relay visually indicating the short circuit fault trip status by means of glowing all fault LED’s
Earth Fault Protection:
Prok dv’s make Microcontroller Based Motor Protection Relay senses the Zero sequence components
of the TRUE RMS Currents are measured simultaneously and detecting the Earth Faults. The moment
the Earth Fault crosses the Threshold Set value, a trip command is given by the relay to the trip circuit
with a time elapse. The Earth Fault phenomenon is predominant in the Motor and Motor Control
Centers, Hence protection against Earth Fault is necessary. Microcontroller Based Motor Protection
Relay uses the proven Holmgren technique for detection of Earth Fault in the Motor.
Unbalance Protection:
Prok dv’s make Microcontroller Based Motor Protection Relay measures and monitors all the Three
Phase Currents and extracts the Unbalance Currents presents in the Three Phase Motor circuit. The
moment an Unbalance Current is detected and if it crosses the Set value, the relay is activated in
tripping the circuit.
3
Setting Procedure for PDMMPR303
Step1: Connect the suitable Auxiliary supply in the range from 85-275vac/dc to the terminal 1 & 2 of
Relay by Referring to the PDMMPR-303-1/2/3/4 wiring diagram
Step2: Select the required motor rated current Im using the Trim pot with steps markings
For PDMMPR303-1, Im Ranges from (1A-10A) in steps 1A -10 markings
PDMMPR303-2, Im Ranges from (10A-32A) in steps 2A -12 markings
PDMMPR303-3, Im Ranges from (20A-64A) in steps 4A -12 markings
PDMMPR303-4, Im Ranges from (30A-96A) in steps 6A -12 markings
Rated current
Step3: After selecting the Motor rated current Im in Amps Select the % EF setting in the ranges
from 10% to 50% in steps of 10%- 5 markings using Trim pot
Earth Fault%
Note : Earth Fault Protection is user selectable by means of DIP SWITCH selection
Set the EF switch to ON position to enable the Earth Fault Protection
Set the EF switch to OFF position to disable the Earth Fault Protection
Earth Fault trip time is y default fixed 0.5Sec
Type of protection
5
Note: Potential free Relay changeover output contacts C& NC and C& NO provided for all seven
Faults TRIP
Note: 1) For Motor Rated Current (In) within the range of the Relay (Im), Set Im =In
2) For Motor Rated Current (In) below the range of the Relay (Im), Set Im= In * number of turns
3) For Motor Rated Current (In) above the range of the Relay (Im), Use three ----/5A CT’S
CT primary
6
FRONT FASCIA
7
Mod bus address Format
Function code: 04,
Device address-10, Fixed Baud rate: 9600 bps, Data bits: 8, Parity: none, Stop bit: 1
8
Dip Switch configuration Format
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5