Hydraulic Caluculation Report
Hydraulic Caluculation Report
ACUTE CONSTRUCTION
INDIAN OIL CORPORATION LIMITED P-MECH CONSULTANT PVT. LTD
========================================================================================================================
Page
----
Control Information......................................... 1
Fluid System................................................ 1
Design Information.......................................... 2
Pipe Configuration.......................................... 4
Nozzle Configuration........................................ 5
Flow in Pipes............................................... 7
Flow at Inlets.............................................. 9
Important Notice............................................ 13
Comments.................................................... 14
CONTROL INFORMATION
-------------------
Convergence accuracy = 1.00E-03
Maximum no. of iterations = 50
Elevation Check Tolerance = 0.50 metres
Warnings Control Option = 0
****** Diagnostic level = 2
FLUID SYSTEM
------------
DESIGN INFORMATION
------------------
foam System
AVAILABLE PIPE SIZES AND MAXIMUM VELOCITIES USED FOR PIPE SIZING
----------------------------------------------------------------
IS 1239 H
Not lined
PIPE CONFIGURATION
------------------
Pipe Label Input Node Output Node Nom.Bore Length Elevation C Fitt.eq.lnth
(milli.m.) (metres ) (metres ) Factor (metres )
---------------------------------------------------------------------------------------------------------
5 6 5 80.00 15.00 0.000 120.0 13.82
6 5 4 50.00 16.00 7.500 120.0 2.577
7 5 2 50.00 16.00 7.500 120.0 2.577
PIPE FITTINGS
-------------
NOZZLE CONFIGURATION
--------------------
Nozzle Input Nozzle K-Factor Req Flow Min Press Max Press
Label Node Type (lit/min ) (kg/cm2 G) (kg/cm2 G)
---------------------------------------------------------------------------------------------------
1 4 1 118.0000 204.5000 0.30000E+01 0.70000E+01
2 2 1 118.0000 204.5000 0.30000E+01 0.70000E+01
Pipe Input Output Flowrate Pipe Act. Bore Nom. Size Pipe
Label Node Node (lit/min ) Type (milli.m.) (milli.m.) Group
------------------------------------------------------------------------------------------
5 6 5 439.0208 9 78.4000 80.0000 *
6 5 4 219.5104 9 50.7000 50.0000 *
7 5 2 219.5104 9 50.7000 50.0000 *
FLOW IN PIPES
-------------
Pipe Input Output Nom.Bore Inlet Pr. Outlet Pr. Drop in Pr. Frict. Loss Flowrate Velocity
Label Node Node (milli.m.) (kg/cm2 G) (kg/cm2 G) (kg/cm2 ) (kg/cm2 ) (lit/min ) (m/sec )
-----------------------------------------------------------------------------------------------------------------------
5 6 5 80.00 4.500 4.383 0.1166 0.1166 439.0 1.516
6 5 4 50.00 4.383 3.461 0.9229 0.1742 219.5 1.812
7 5 2 50.00 4.383 3.461 0.9229 0.1742 219.5 1.812
TITLE : Hydraulic calculations for Foam system DATE : 02-Aug-2016 PAGE 8 OF 14
-----------------------------------------------------------------------------------------------------------------------
Nozzle Input Inlet Press Req. Flow Flowrate % Deviation Req. FlowDens FlowDens
Label Label (kg/cm2 G) (lit/min ) (lit/min ) ( lit/min /metres **2 )
--------------------------------------------------------------------------------------------------------------
1 4 0.34605E+01 204.5000 219.5099 7.34
2 2 0.34605E+01 204.5000 219.5099 7.34
FLOW AT INLETS
--------------
Materials Take-off
------------------
Pipe lengths
------------
IS 1239 H
Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length Nom. Size Tot. Length
(milli.m.) (metres ) (milli.m.) (metres ) (milli.m.) (metres ) (milli.m.) (metres ) (milli.m.) (metres )
----------------------------------------------------------------------------------------------------------------------
50.0 32.00
80.0 15.00
TITLE : Hydraulic calculations for Foam system DATE : 02-Aug-2016 PAGE 11 OF 14
-----------------------------------------------------------------------------------------------------------------------
Materials Take-off
------------------
Nozzles
-------
Fitting
Nominal
Size Fitting Type
(milli.m.) 1 2 3 4 5 6 7 8 9
-------------------------------------------------------------------------
50.0 0 4 0 0 0 0 0 0 0
80.0 0 4 0 1 1 0 0 0 0
All fittings are as specified by user - no additional fittings have been generated automatically.
The supply demand graph is not available for the network without pump
TITLE : Hydraulic calculations for Foam system DATE : 02-Aug-2016 PAGE 13 OF 14
-----------------------------------------------------------------------------------------------------------------------
IMPORTANT NOTICE
----------------
Your attention is drawn to the need to maintain adequate standards. SUNRISE SYSTEMS Ltd
has itself taken steps to ensure that this program produces valid results when properly
used. Users are reminded of their responsibilities in the application of program results
and, in particular, you should ensure that pertinent output documents are examined and
approved by qualified staff prior to use.
TITLE : Hydraulic calculations for Foam system DATE : 02-Aug-2016 PAGE 14 OF 14
-----------------------------------------------------------------------------------------------------------------------
COMMENTS
--------
========================================================================================================================
========================================================================================================================