0% found this document useful (0 votes)
67 views32 pages

FARAKA Fashions LTD

This document provides details from an infrared thermographic inspection of electrical equipment. It includes information about the thermographic camera used, qualifications of the thermographer, equipment inspected, standards used to evaluate thermal images, and a summary of findings. The summary shows 25 minor issues (Category 00) that warrant further investigation within 6 months, and 3 low risk issues (Category 01) that also require attention within 6 months. No urgent high risk or critical issues were found. Thermal images taken during the inspection are provided on pages 6-63 to document conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views32 pages

FARAKA Fashions LTD

This document provides details from an infrared thermographic inspection of electrical equipment. It includes information about the thermographic camera used, qualifications of the thermographer, equipment inspected, standards used to evaluate thermal images, and a summary of findings. The summary shows 25 minor issues (Category 00) that warrant further investigation within 6 months, and 3 low risk issues (Category 01) that also require attention within 6 months. No urgent high risk or critical issues were found. Thermal images taken during the inspection are provided on pages 6-63 to document conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 32

Table of Contents

Serial No Content Page no

01 Instrument Details 02

02 Thermographer details 02

03 Inspection Summary 02

04 Standard for evaluating results 03

05 Summary of findings 04-05


Thermal of analysis
06 06-63
Details of Thermographic camera:

Manufacturer Name Fluke Thermography

Model Number TiS10

Serial Number TiS10-16010562

Thermographar details

Name of Thermographer: Milon Kumar Bishnu

Qualification of Thermographer: Member of NFPA-3086075


BSc in EEE

INSPECTION SUMMARY

For the equipment inspected, we have recorded some Thermographic(s) and/ or daylight photographs document
conditions found during our inspection. These thermograms and/ or photographs appear on the image Pages found at
the end of this report. As a reference, each Image Page contains Evaluation Priority Ratings. Subjective Evaluation
Ratings are based upon the Qualified Assistant’s opinion of the subject item’s importance to the safe and condition
operation of the facility. American National Standards Institute (ANS) has approved a standard for international
Electrical Testing Association (NETA) for performing different testing in the Electrical system named as
“STANDARD FOR ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWER AND
SYSTEMS”. Based on Acceptance Testing Specification (ATS) 2009, we have below table to identify hot spots and
consequent actions for hot spots.
Standard for evaluating results

As per NETA Maintenance Testing Specifications for Electrical Equipment (Tablet: 100.18 )
Delta T between Similar
Delta T Over ambient
Priority Components Under Similar Recommend Action
Air Temperature
Load
00 1 to 3 °C 1 to 10°C Possible Deficiency Warrants
Investigation
01 4 to 15 °C 11 to 20°C Indicates Probable Deficiency Repair as
time Permits
02 --- 21 to 40°C Monitor Until Corrective Measures Can
be Accomplished
03 > 15 °C >40°C Major Disarepancey; Repair Immediately
Summary of findings

Category Rating Priority Frame No Total no Comments

IR_00071.IS2
IR_00072.IS2
IR_00073.IS2
IR_00075.IS2
IR_00077.IS2
IR_00078.IS2
IR_00079.IS2
IR_00080.IS2
IR_00081.IS2
IR_00082.IS2
IR_00084.IS2
IR_00085.IS2
Minor(Category IR_00086.IS2
Category-00 25 6months
00) IR_00087.IS2
IR_00088.IS2
IR_00089.IS2
IR_00090.IS2
IR_00091.IS2
IR_00092.IS2
IR_00093.IS2
IR_00094.IS2
IR_00095.IS2
IR_00096.IS2
IR_00097.IS2
IR_00098.IS2

IR_00074.IS2
Low Risk IR_00076.IS2
Category-01 03 6months
(Category 01) IR_00083.IS2

Category-02 High Risk Nil 3 months

Category-03 Critical Nil Immediate


Inspected By:
Inspection Date: 1/9/2021 10:53:17 AM Location 1ST FLOOR , SEWING
Equipment MDB-1 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 400A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00071.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.5°C
Image Range 29.1°C to 35.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 10:53:17 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 34.3°C
Hot 35.9°C
Cold 29.1°C
Inspected By:
Inspection Date: 1/9/2021 10:55:49 AM Location 1ST FLOOR, SEWING
Equipment DB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00072.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 29.7°C
Image Range 26.8°C to 36.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 10:55:49 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 29.4°C
Hot 36.4°C
Cold 26.8°C
Inspected By:
Inspection Date: 1/9/2021 11:05:52 AM Location GF, FINISHING
Equipment MDB-1 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 400A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00073.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 28.5°C
Image Range 26.8°C to 31.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:05:52 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 28.4°C
Hot 31.2°C
Cold 26.8°C
Inspected By:
Inspection Date: 1/9/2021 11:09:13 AM Location GF, FINISHING
Equipment SDB-1 Equipment Name:
Ambient Air Temp: 30.1°C Wind Speed
Load (%) Adequate Max Rated Load: 10A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk (Category 01)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00074.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 32.6°C
Image Range 28.9°C to 98.1°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:09:13 AM
Calibration Range -20.0°C to 250.0°C

Main Image Markers


Name Temperature
Centerpoint 32.5°C
Cold 28.9°C
P0 45.3°C
Inspected By:
Inspection Date: 1/9/2021 11:13:47 AM Location SUB-STATION
Equipment MDB Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 200A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00075.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 23.4°C
Image Range 22.0°C to 28.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:13:47 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 23.1°C
Hot 28.2°C
Cold 22.0°C
Inspected By:
Inspection Date: 1/9/2021 11:21:14 AM Location SUB-STATION
Equipment MAIN MDB Equipment Name:
Ambient Air Temp: 30.1°C Wind Speed
Load (%) Adequate Max Rated Load: 200A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk (Category 01)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00076.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.0°C
Image Range 29.0°C to 45.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:21:14 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 31.8°C
Hot 45.2°C
Cold 29.0°C
Inspected By:
Inspection Date: 1/9/2021 11:24:45 AM Location GF, SUB-STATION
Equipment Main MDB, RIGHT Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 800A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00077.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.1°C
Image Range 29.8°C to 32.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:24:45 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 31.0°C
Hot 32.9°C
Cold 29.8°C
Inspected By:
Inspection Date: 1/9/2021 11:25:34 AM Location GF, SUB-STATION
Equipment Main MDB, LEFT Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 800A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00078.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.2°C
Image Range 29.8°C to 36.7°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:25:34 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 31.1°C
Hot 36.7°C
Cold 29.8°C
Inspected By:
Inspection Date: 1/9/2021 11:31:58 AM Location SUB-STATION
Equipment PFI, LEFT SIDE Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 630A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00079.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.1°C
Image Range 29.8°C to 33.2°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:31:58 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 30.8°C
Hot 33.2°C
Cold 29.8°C
Inspected By:
Inspection Date: 1/9/2021 11:32:56 AM Location SUB-STATION
Equipment PFI, RIGHT SIDE Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 630A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00080.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.5°C
Image Range 30.0°C to 39.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:32:56 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 30.9°C
Hot 39.9°C
Cold 30.0°C
Inspected By:
Inspection Date: 1/9/2021 11:37:28 AM Location 1ST FLOOR, IPS
Equipment SDB-IPS Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00081.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 31.3°C
Image Range 30.0°C to 39.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:37:28 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 31.5°C
Hot 39.4°C
Cold 30.0°C
Inspected By:
Inspection Date: 1/9/2021 11:45:38 AM Location TRANSFORMER
ROOM
Equipment HT Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 630A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00082.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 29.5°C
Image Range 28.3°C to 31.7°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:45:38 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 29.2°C
Hot 31.7°C
Cold 28.3°C
Inspected By:
Inspection Date: 1/9/2021 11:49:05 AM Location TRANSFORMER
ROOM
Equipment TRANSFORMER Equipment Name:
Ambient Air Temp: 30.1°C Wind Speed
Load (%) Adequate Max Rated Load: 500KVA
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Low Risk (Category 01)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00083.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 32.3°C
Image Range 27.9°C to 39.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:49:05 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 31.0°C
Hot 39.6°C
Cold 27.9°C
Inspected By:
Inspection Date: 1/9/2021 11:51:19 AM Location GENERATOR, ROOM
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 3A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00084.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 28.4°C
Image Range 26.9°C to 32.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:51:19 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 28.0°C
Hot 32.6°C
Cold 26.9°C
Inspected By:
Inspection Date: 1/9/2021 11:55:26 AM Location GF, BOILERS
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 16A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00085.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 36.5°C
Image Range 34.6°C to 40.7°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 11:55:26 AM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 35.7°C
Hot 40.7°C
Cold 34.6°C
Inspected By:
Inspection Date: 1/9/2021 12:00:33 PM Location 1ST FLOOR
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00086.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 29.0°C
Image Range 27.6°C to 31.1°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:00:33 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 29.0°C
Hot 31.1°C
Cold 27.6°C
Inspected By:
Inspection Date: 1/9/2021 12:04:31 PM Location 1ST FLOOR
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 6A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00087.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 30.4°C
Image Range 29.4°C to 32.3°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:04:31 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 30.7°C
Hot 32.3°C
Cold 29.4°C
Inspected By:
Inspection Date: 1/9/2021 12:07:23 PM Location 1ST FLOOR, ADMIN
Equipment SDB-02 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 40A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00088.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 30.0°C
Image Range 28.8°C to 31.8°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:07:23 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 30.2°C
Hot 31.8°C
Cold 28.8°C
Inspected By:
Inspection Date: 1/9/2021 12:11:22 PM Location 1ST FLOOR, BOILER
ROOM
Equipment SDB-03 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 40A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00089.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 29.8°C
Image Range 28.4°C to 36.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:11:22 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 29.7°C
Hot 36.4°C
Cold 28.4°C
Inspected By:
Inspection Date: 1/9/2021 12:15:21 PM Location 2ND FLOOR,
CONFERENCE ROOM
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00090.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 29.8°C
Image Range 28.3°C to 36.0°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:15:21 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 29.0°C
Hot 36.0°C
Cold 28.3°C
Inspected By:
Inspection Date: 1/9/2021 12:23:34 PM Location 3RD FLOOR, OFFICE
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00091.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 30.6°C
Image Range 29.3°C to 32.9°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:23:34 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 30.2°C
Hot 32.9°C
Cold 29.3°C
Inspected By:
Inspection Date: 1/9/2021 12:28:02 PM Location 2ND FLOOR, SAMPLE
Equipment MDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 32A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00092.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 28.4°C
Image Range 26.4°C to 34.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:28:02 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 30.4°C
Hot 34.6°C
Cold 26.4°C
Inspected By:
Inspection Date: 1/9/2021 12:31:46 PM Location 5TH FLOOR
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00093.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 26.2°C
Image Range 24.8°C to 28.3°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:31:46 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 26.2°C
Hot 28.3°C
Cold 24.8°C
Inspected By:
Inspection Date: 1/9/2021 12:34:45 PM Location 4TH FLOOR, BONDED
WARE HOUSE
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00094.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 26.6°C
Image Range 25.5°C to 30.0°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:34:45 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 27.1°C
Hot 30.0°C
Cold 25.5°C
Inspected By:
Inspection Date: 1/9/2021 12:36:37 PM Location 3RD FLOOR, FINISHED
GOODS
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 25A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00095.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 26.5°C
Image Range 22.0°C to 28.6°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:36:37 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 26.2°C
Hot 28.6°C
Cold 22.0°C
Inspected By:
Inspection Date: 1/9/2021 12:38:29 PM Location 2ND FLOOR, SAMPLE
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 16A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00096.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 25.9°C
Image Range 24.7°C to 28.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:38:29 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 26.0°C
Hot 28.4°C
Cold 24.7°C
Inspected By:
Inspection Date: 1/9/2021 12:41:21 PM Location 1ST FLOOR, STORE
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 20A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00097.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 25.8°C
Image Range 24.6°C to 28.1°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:41:21 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 25.7°C
Hot 28.1°C
Cold 24.6°C
Inspected By:
Inspection Date: 1/9/2021 12:43:34 PM Location GF, DINING
Equipment SDB-01 Equipment Name:
Ambient Air Temp: 29.6°C Wind Speed
Load (%) Adequate Max Rated Load: 16A
Exception Temperature: Potential Problem
Recommended Action Possible Deficiency Warrants Repair Priority: Minor(Category 00)
Investigation
Emissivity: 0.87 Reflected Temperature: 22.0 °C
Camera Manufacturer Fluke Thermography Camera: TiS10-16010562

IR_00098.IS2 Visible Light Image

Image Info
Transmission 1.00
Average Temperature 26.6°C
Image Range 25.4°C to 29.4°C
Camera Model TiS10
IR Sensor Size 80 x 60
Image Time 1/9/2021 12:43:34 PM
Calibration Range -20.0°C to 80.0°C

Main Image Markers


Name Temperature
Centerpoint 26.5°C
Hot 29.4°C
Cold 25.4°C

You might also like