Part10 13.8 & 33 KV Metered Ring Main Unit SF6 Room Substations
Part10 13.8 & 33 KV Metered Ring Main Unit SF6 Room Substations
SDCS-02
SEC DISTRIBUTION CONSTRUCTION STANDARD
DATE: November 2016
SDCS-02
CONSTRUCTION STANDARD
FOR
SDCS-02
SEC DISTRIBUTION CONSTRUCTION STANDARD
DATE: November 2016G
PART 10
INSTALLATION
OF
13.8 & 33 KV
Page 2 of 10
Saudi Electricity Company الشركة السعودية للكهرباء
SDCS-02
SEC DISTRIBUTION CONSTRUCTION STANDARD
DATE: November 2016G
TABLE OF CONTENTS
PAGE
Sr. No. DESCRIPTION
NO.
1 INTRODUCTION 4
6 DRAWINGS 6-10
Page 3 of 10
Saudi Electricity Company الشركة السعودية للكهرباء
SDCS-02
SEC DISTRIBUTION CONSTRUCTION STANDARD
DATE: November 2016G
1 Introduction
This construction standard specifies the construction design of 13.8 & 33 KV
Metered Ring Main Unit SF6 Room Sub-station. This standard is intended to assist
the field engineers and technicians to achieve unified standard in construction to
ensure a satisfactory and economical level of service without operation restrictions
so that the operational errors are minimized for safety and reliability of the system.
Page 4 of 10
Saudi Electricity Company الشركة السعودية للكهرباء
SDCS-02
SEC DISTRIBUTION CONSTRUCTION STANDARD
DATE: November 2016G
Shall be operated by Central handle lock by using SEC standard key or pad
lock according to SEC specification SEC-02-02 latest revision.
4.2.5 The door shall be made of steel 2500mm wide and 3498mm high
excluding the door frame.
4.2.6 Ventilation louvers shall be shall be provided as shown in figure 5.
4.2.7 Door shall be bonded to any metal framework by a bolted removable 35
mm2 tinned copper braid.
4.3 For the entry & exit of SEC Cable in to and out of the meter room shall be 4
PVC pipes of 150mm diameter in compliance with latest revision of relevant SEC
Specification shall be provided.
6 Drawings
Fig.1 Meter Room Fig.2 Cable trench & Cover
Fig.3 Front elevation Fig.4 Lighting arrangement
Fig.5 Door Details. Fig.6 Window Details
Fig.7 Foundation Plan Fig.8 Roof Slab Plan
Fig.9 Tie Beam Detail Fig.10 Roof Beams detail
Fig.11 Column and foundation detail.
Page 5 of 10
Saudi Electricity Company
SDCS-02
SEC DISTRIBUTION CONSTRUCTION STANDARD
DATE: November 2016G
B
6200
400
2400x1000mm WINDOW WITH VENTILATION
200
200
450
600 GROUND ROD AT EACH CORNER
1000
COMPRESSION COMPRESSION
CONNECTOR CONNECTOR
81
CABLE SCREEN
R1
600
G M.R.M.U G
81
A R1
A
R1
4000
4400
5200
5200
4000
3500
TRENCH COVER
TRENCH COVER
70mm sq.
Ground Conductor C
HIGH VOLTAGE ROOM
450
200
25
8
Saudi Electricity Company
10
LIFTING HOOK
600
1300
TO EQUAL LENGTH
SEC DISTRIBUTION CONSTRUCTION STANDARD
SECTION C
SDCS-02
400
400
400
400 400
2400 x 1000mm
500
STEEL WINDOW
1000
500 2000 x 3500mm
FULLY LOUVERED DOOR
2mm FLY MESH IN
ALUMINUM FRAME
METER
BOX 2400
3500
3500
3500
3600
3600
3500
2400 x 1000mm
WINDOW WITH STEEL FLY MESH
4000
1500
FINISH FLOOR LEVEL +50
150
500
500
500
500
500
2500 Compacted Backfill
Saudi Electricity Company
ASHPALT LEVEL 0.00 ASHPALT LEVEL 0.00 ASHPALT LEVEL 0.00 ASHPALT LEVEL 0.00 ASHPALT LEVEL 0.00 ASHPALT LEVEL 0.00
2 STEP-UP 2 STEP-UP Compacted Backfill
1300
1300
1300
1300
Compacted Backfill Compacted Backfill
400
1450
1450
1450
1450
100
1200
5000
4000
2500x3500mm DOOR OPENING
SDCS-02
200
2336
2mm GAP 2mm GAP
PLAN
2mm GAP
2500
200
10x10x1 ANGULAR
4-20cm HINGES BAR DOOR FRAME 80
80
2 2400
80
IN ALUMINUM FRAME
50x5mm STEEL SIRIP
2mm FLY MESH
2mm LOUVER ANGULAR BAR
50x50x5mm
2mm THK.
1350
LOUVERS
PLAN
2mm LOUVER
50x5mm STEEL SIRIP
50
3498
3500
1000
646
IN ALUMINUM FRAME
2mm FLY MESH
1000
50
50 2400 50
1300
1200
FRONT VIEW
1000
2mm GAP
2500
SECTION D-D
FRONT VIEW
@150mm C.C. Z1
200
500
1400 1400
450
370
1200
1400
F1 5000 F1 @ 150mm C.C.
Z1 10cm THK. LEAN CONCRETE
C1 C1 200
200 10cm THK. LEAN CONCRETE 5000 200
1200
120
450
1400
1200
TB2 C1 TIE BEAM (TB2) C1
SECTION Z1-Z1
1200
@150mm C.C. Y1
GROUND ROD AT EACH CORNER
PLAN (F1/C1)
(COPPERWELD, 16mm DIA.)
200
500
3500
TB1
TB1 Y1
10cm THK. LEAN CONCRETE
500
3500 450 200
1400 1400 10cm THK. LEAN CONCRETE
450
TIE BEAM (TB1) C1 SECTION Y1-Y1
C1
F1 F1
C1 C1 FIG: 9 TIE BEAMS DETAIL
SCALE: NTS
450
450
1400
1400
1200
1200
as per site
Depth Varies
1200 1200
Saudi Electricity Company
300 300
300
400
10cm THK. LEAN CONCRETE
1200
Z 1400
200
200 5000 200 SECTION X-X (F1/C1)
C1 ROOF BEAM (RB2) C1 SECTION Z-Z
B FIG: 11 COLUMN AND FOOTING DETAIL
400 200 5000 200 400
SCALE: NTS
200 400
200 400
RB2
SEC DISTRIBUTION CONSTRUCTION STANDARD
450
400
/m
RB1
Y 200
RB1
200 1000 200
450 3500 450
C1 ROOF BEAM (RB1) C1
SECTION Y-Y
SPECIAL NOTE:
FIG: 10 ROOF BEAMS DETAIL
SCALE: NTS
4000
4000
REINFORCEMENT COVER WITHIN CONCRETE SHALL BE:
1200 SLABS-20mm FOOTINGS-75mm COLUMNS :-40mm OTHERS-40mm
1000
(TYPICAL)
A A
/m
120
/m 1200 1200
150 20 RB2 RB2
1000
450
RB2
400 200 4000 200 400
400 200
400 200
SECTION B-B
B SCALE: NTS
400 200 200 400
SECTION A-A
SCALE: NTS
DATE: September 2016G