4 The Digital Controller For Large Chillers: 4.1 What Is in This Chapter?
4 The Digital Controller For Large Chillers: 4.1 What Is in This Chapter?
Part 2
1
4 The Digital Controller For Large chillers
2
4.1 What Is in This Chapter?
Introduction In this chapter the practical use of the pCO² controller for large chillers will be explained.
2–113
4
4.5–Menu Overview 2–114
2
The digital controller consists of:
• • An alphanumeric LCD display.
• • 6 keys (4 of them are colored when activated).
Front panel The illustration below shows the front panel of the controller.
Keys The table below contains an overview of the keys and their functions.
h lower a setting.
How to switch
between Screens
Each menu contains a number of screens. You can switch between the screens using the h g or
keys. In the upper-left corner of the screen you will find a screen indicator, indicating whether there is 1
a previous or next screen.
Screen detail Each screen contains 4 lines which give information about a setting (a description and an entry field). 3
The entry fields can be adjusted using the h and the g keys.
The cursor is marked by the sign "_". The cursor can be moved between the screen indicator and the
entry fields using the q key.
The cursor can be moved directly to the screen indicator by pressing the f key. 4
Cursor Screen indicator
_ / l
l
i
i
n
n
e
e
1
2
: T I
v a
T
l
L E
u e 1 : 1 0 5
l i n e 3 v a l u e 2 : 2 0
l i n e 4 v a l u e 3 : 3 0
Remark: Make sure that the cursor is at the screen indicator position when scrolling through the
screens.
2 Remote start/stop The procedure to start or stop the unit depends on the settings of the remote start/stop.
How to cool or heat To change from cooling to heating (or visa versa) you have to enter the Cooling/Heating menu through
the main menu.
5 Emergency stop In case of an emergency: switch off the unit by pushing the emergency button.
Temperature To adjust the inlet or outlet water temperature, go to the Set Points menu through the main menu.
setting
Remark To prevent the unit from stopping at 100% the unit will always load-down to 12% and operate at this
capacity for a couple of seconds before shutting down.
For a full list of all possible safeties reffer to overview of fault indications and safeties on page 3-9.
Overview safeties
2
Safety possible
Unit safety Description
if unit is off?
Safety possible
Dual pump safety Description
if unit is off?
2
Initial Test Main menu Readout menu
3
Service menu
4 Timers menu
History menu
Info menu
5
Input/Output menu
Cooling/heating menu
Network menu
Safety menu
Begin (*)
2
Press the f key.
No
Do you want to adjust a parameter setting?
Yes 5
Select the parameter by using the q key.
No
Do you want to save the modifications?
Yes
Yes
Do you want to adjust another parameter in the same screen?
No
Yes
Do you want to adjust a parameter in another screen?
No
2 Screen 1 This screen shows information about the operation mode, the setpoints and the temperatures:
Line 1f and 3a only visible if the unit is an ERAP.
Line 4a is only visible if the unit is a "HP".
Line 4b is only visible if the unit is a "HR".
5
1f SETPOINT1(2) The unit works on thermostat control (ERAP units).
Screen 2 This screen shows information about the evaporator outlet water temperature:
4a
C2
UNITCAPACITY
Actual status of compressor 2
OFF-CAN STARTUP The compressor is ready to start up when extra cooling is requested.
OFF-TIMER BUSY One of the software timers is counting. Compressor cannot start up.
ON – 12% STAR
ON – 12% DELTA
Compressor works on 12% in star (this mode is used to start up).
OFF–0% LIMIT Compressor is disabled, to limit the unit capacity. This can be acti-
vated with a schedule timer, a remote digital input or with a fixed Lim-
ON – YY% (LIMIT)
itation.
ON – 12% SHEAT REC Compressor works on 12% in star (this mode is used to start up) and
heat recovery is activated.
ON – 12% DHEAT REC Compressor works on 12% in delta (this mode is used to start up)
and heat recovery is activated.
ON – ZZ% HEAT REC Compressor works on ZZ% and heat recovery is activated.
Remark: Possible values for xx, yy and zz are between 12% and 100%.
2 3
4
LP1: b =
HP SETPOINT C1: b
°C Actual low pressure and corresponding temperature
4 4 HP SETPOINT C: b This line is only for units with inverter fan control. It
shows the target high pressure set point.
Screen 6 This screen shows information about the compressor running hours:
Screen 6a This screen shows extra information about the compressor running hours for heat pump units:
1
Line n° Display Description
2.2
3.1
H:
C2C: h
h Total running hours of compressor 1 in heating mode.
Screen 7 and 8 These screens show information about the EEV and will therefore only be visible if electronic
expansion valves are present. 3
Line n° Display Description
2
Line n° Display Description
Remark: The units leave the factory with the user password set to "1234". This user password can be
modified in the user password menu.
3
Screen 2: This menu allows you to set the inlet/ outlet water temperature of the evaporator/condenser of circuit
1 and 2. These set points will not be active in the Manual Control Mode.
Upper
Line n° Display Description Default value Lower limit
limit
4 1 INLSETP1 E Inlet water temp. set 12.0 °C MOW+3°C 23°C
point 1 evaporator
Not all lines are visible. The type of unit and the operating mode determine which lines are visible:
• • Line 1, 2, 3, 4: Water and air-cooled units: Cooling mode(Inlet/Outlet/Manual).
• • Line 1a, 2a: only for water-cooled units: Heating mode(Inlet/Manual).
• • Line 1, 2, 1a, 2a: only for water-cooled units: Double thermostat (Inlet/manual).
• • Line 3a, 4a: only for ER units (Thermostat setpoint).
Remark: You can select setpoint 1 or 2 with a digital input from a switch. In the service menu you can
select which digital input you want to use for this.
Remark:
• • The limit values mentioned in the table above are valid for the standard MOW (Minimum Outlet
Water) setting of 4°C.
1
• • For glycol units the lower limit of the cooling temperature set point depends on the MOW setting.
The possible MOW settings depend on the percentage of glycol in the water.
2
Screen 3: This menu allows you to set the EEV set points.
This screen is only visible if electronic expansion valves are present.
1 EEV SETPOINTS
Screen 4 This menu allows you to set the EEV set points.
This screen is only visible if electronic expansion valves are present.
Between the min and the max operation pressures the unit will regulate on superheat setpoint.
5
The details of this function are explained in the chapter about superheat control.
Screen 1: password You need the user password to enter this menu.
Remark: The units leave the factory with the user password set to "1234". This user password can be
3 modified in the user password menu.
4 1
2
CONTROL SETTINGS
MODE:
screen title
For more info about this function refer to the corresponding chapter.
Screen 3 This screen allows you to modify the thermostat loadup - down parameters.
Default
1
Lower Upper
Line n° Display Description (Depending on
limit limit
control mode)
Lower Upper
Line n° Display Description Default
limit limit
If equal startup is set to "NO" then one compressor will go to 100% capacity before the second
compressor is started.
* If the lead-lag mode is not set to auto, the possible settings are:
C1>C2 C2>C1
For more info about this function refer to the corresponding chapter.
1 Screen 5 This screen allows you to choose whether the capacity limitation settings of the circuits are selected
by: a digital input (remote switch or timer), via the schedule timer, not active or set to lim1.
2
REMOTE DIG INP.
to select the capacity limitation SCHEDULE TIMER
2 MODE:
mode NOT ACTIVE
LIM1
3 Remark: Only one mode is active at the time. When one mode is selected the other ones can't be
used.
For more info about this function refer to the corresponding chapter.
4 Screen 6
Line n° Display Description Possible settings
For more info about this function refer to the corresponding chapter.
Screen 7 This screens allows to set the pump lead and lag times. It is also in this screen that the "pump daily
on" function can be activated. 1
Lower Upper
Line n° Display Description Default
limit limit
2 PUMPLEAD-
TIME
Time to run the water pump
before starting up the chiller
020 sec 020 sec 180 sec
2
3 PUMPLAGTIME Time to keep the pump on, after 000 sec 000 sec 180 sec
stopping the chiller
Remark: The default value for the PUMPLAGTIME is 0 sec, but it is recommend setting the lag time
to 120s. This is to prevent the evaporator from freezing up when there is no flow. 4
For more info about this function refer to the corresponding chapter.
Screen 8 This screen allows you to enable or disable the schedule timer and the holiday period timer.
This screen is only visible if the unit is operating as a standalone unit or if the unit is the master in a
DICN setup.
5
Possible
Line n° Display Description
settings
Remark: New screens will be available if one or both timer possibilities are set to Yes.
For more info and all the sceens about these schedule and holiday timers refer to the
schedule timer managment chapter on page 2–56.
1 Screen 9 This screen will only be visible if in service menu "Dual Evap. Pump" is selected as digital output
2
PUMP2 > PUMP1
PUMP1 > PUMP 2
For more info about this function refer to the corresponding chapter.
4 2
SETPOINT
Screen 10a When you choose ambient mode the following settings will appear.
1
Lower Upper
Line n° Display Description Default
limit limit
4.1 ZERO: Here the setpoint value will be 20°C 20°C 43°C
equal to 0.
2 PRESS ENTER TO
5
3 CHANGE LANGUAGE
When in this screen just press enters to change language, this is a loop function which means when
you reached the last selectable language you are sent back to the first. If only one language is
available the screen will not change when enter is pressed.
Depending on the memory size of the pCO2 controller 2 or 5 language are stored in the memory.
1 Screen 13 This screen will only be visible if in the service menu free cooling is selected as digital output.
Free cooling is only selectable on units with an ambient sensor (air-cooled cooling only or
condenserless).
2
2 MODE: Choose mode to regulate the free cool- NOT ACTIVE
ing on INLET-AMBIENT
AMBIENT
3 For more info about this function refer to the corresponding chapter.
Screen 13a When you choose (Inlet -)ambient mode the following settings will appear.
Lower Upper
Line n° Display Description Default
limit limit
4 1 FREE COOLING screen title
2 MODE Selected mode
3.1 SP Define setpoint of free cooling 5°C -30°C 25°C
3.2 DI Setting of the free cooling differ- 1.0°C 1.0°C 5.0°C
ence
Line 4 will only be visible if Ambient is selected. Inlet-Ambient is chosen the pump will remain "ON"
Lower Upper
Line n° Display Description Default
limit limit
For more info about this function refer to the corresponding chapter.
Remark: When used in DICN option, the Schedule Timer (screens 8…) will only be available on the
master unit
Screen 15a
3
Line n° Display Description Possible settings
1 MASTER SETTING screen title
2 MODE Normal: the unit works normally. NORMAL
Standby: if the unit is in standby it will only
start-up in case the other DICN units don’t
DISCONN.
ON/OFF 4
have enough capacity or error on other
STANDBY
unit, ...
Disconnected: the unit is disconnected of
the DICN setup and will operate as a
standalone.
3 OFFSET After the adjusted hours the units will
change the sequence of start-up.
0h till 9000h 5
4 PUMP ON IF: Select when the pump must start UNIT ON
COMPR ON
Possible
Line n° Display Description
settings
1 SLAVE “X” screen title SLAVE 1 / 2 / 3
SETTINGS
2 MODE Normal: the unit works normally. NORMAL
Standby: if the unit is in standby it will only DISCONN.
start-up in case the other DICN units don’t ON/OFF
have enough capacity or error on other
STANDBY
unit, ...
Disconnected: the unit is disconnected of
the DICN setup and will operate as a stan-
dalone.
3 OFFSET After the adjusted hours the units will 0h till 9000h
change the sequence of start-up.
4 PUMP ON IF: Select when the pump must start. UNIT ON
This selection is for the unit only COMPR ON
1 Screen 16 This screen allows you to protect the access of the setpoint menu with a password.
Possible
Line n° Display Description
settings
2
2 PASSWORD NEEDED TO Depending on the setting the system No
may require the user password to enter
3 CHANGE SETPOINTS: Yes
the setpoint menu.
Service menu
1
Operational The service menu is accessible through the last screen of the user settings menu, to enter the service
information menu you need the service password. Please contact your distributor for this password.
It is only possible to access the service menu when the unit is "OFF".
Remark: when the unit is operating it is not possible to enter the service menu. 3
Screen 2 This screen allows you to modify the minimum outlet water, the BMS communication interval and the
master-slave option.
Line 4 is not visible for ER units.
The minimum outlet water temperature is restricted depending on the percentage of glycol in the
water.
Screen 3 This screen allows you to modify the low pressure bypass timer, the low pressure setpoint and delay
network error.
Line 4 is only visible if MS Option setting = Yes or if PCOE is present.
1 Screen 4 This screen allows modifying the compressor running hours and number of start-ups (e.g. after
replacing a compressor).
2
2 RUN.HRS-COMPR Screen title
STARTS
4 Screen 5 This screen allows modifying the extra data about the compressor running hours in heating or cooling
(e.g. after replacing a compressor).
5
2 RUN.HRS Screen title
COOL-HEAT
Screen 6 This screen allows you to set the changeable digital inputs.
When you want to program on of these inputs, check the field wiring to see if this input is installed
correctly.
Each setting can only be assigned to one input, if you try to select it a second time it will not be
4
accepted.
For more info about this function refer to the corresponding chapter.
1 Screen 7 This screen allows you to set the changeable digital in- and output.
Line 3 not visible in case of CO, HR or ERAP unit.
2
STATUS
DUAL SETPOINT
REMOTE ON/OFF
REMOTE COOL/HEAT
2 DI4: To set the digital input 4 CAP. LIMIT 1
CAP. LIMIT 2
CAP. LIMIT 3
3 CAP. LIMIT 4
LOW NOISE
HEAT RECOVERY
NONE (open)
1 (closed)
3 DO1: REV. VALVE(C/H)
5 HR COND PUMP
When you want to program on of these inputs, check the field wiring to see if this input is installed
correctly.
Each setting can only be assigned to one input or output, if you try to select it a second time it will not
be accepted.
For more info about this function refer to the corresponding chapter.
2
2 AI1 • • To set a floating NONE
setpoint with an
MS OUTL WATER E
electrical signal.
SETP.SIGN.0/1V
• • To select if AI1 is SETP.SIGN.0/10V
used for HR inlet SETP.SIGN.0/20mA
water C SETP. SIGN.4/20mA
HR INLET WATER C
• • To select if AI1
is used for MS
outlet water E 3
3 MAX SETP.DIF: Maximum difference Between -50°C and 50°C
between set-points.
When you want to program this input, check the field wiring to see if this input is installed correctly.
For more info about this function refer to the corresponding chapter.
Remark:
4
• • If AI1 is programmed as HR inlet water C then Heat recovery mode is enabled, and the heat
recovery setpoint screen will appear in the user menu.
• • If AI1 is programmed as MS outlet water E, the controller will take the temperature reading from
AI1 as the DICN common outlet water temperature. If this AI1 is not programmed when DICN is
used, the controller will automatically take the AI1 input as DICN sensor. If the slave 1 setpoint
signal is used, the master must be programmed manually to MS outlet water C. 5
Screen 9 This screen allows you to adjust the offset of the probe.
Line 2/3 not visible in case of 'ERAP' unit type.
Lower Upper
Line n° Display Description Default
limit limit
2
2 SER. BOARD: To select the communication NONE NONE
protocol between the BMS and RS485
the gateway RS232 (not used)
RS422 (not used)
LON FFT (not used)
LON RS485
(not used)
4 BAUD RATE: To select the baud rate for 19200 bps 1200
communication between the 2400
BMS card and the gateway 4800
4 9600
19200
For more info about this function refer to the corresponding chapter.
Remark: Refer to the BMS manual (Service Manual BMS option for Daikin water chillers) for more
5
detailed information.
Screen 11 This screen allows you to activate the PC control mode and to modify the BMS settings.
Possible
Line n° Display Description Default
settings
For more info about this function refer to the corresponding chapter.
Remark: Refer to the BMS manual (Service Manual BMS option for Daikin water chillers) for more
detailed information.
Screen 12 This screen allows you to customize the flow indication after start up.
Remark: In this menu you can turn 1 or 2 pumps on manually. The pump(s) will operate until they are
switched off or until you exit the service menu.
4
Screen 13 This screen allows you to customize the freeze up safety.
Possible
Line n° Display Description Default
settings
5
1 SERVICE MENU Screen title
2 FREEZE UP: To select one of the freeze up DIS&SAFETY DIS&SAFET
settings. Y/DIS. ONLY
3.1 SAFETY: Number of allowed freeze ups 2 0 to 5
during a specified time before
the circuit would stop.
3.2 IN To select the time in which the 60 min 5 till 180min
specified number of freeze ups
is allowed.
4 INL CHECK To select if the unit should N Y/N
AFTER RESET: check the inlet water tempera-
ture before reset.
Remark:
DISABLE ONLY:
• • The circuit will shut off after every freeze up protection (activated from MOW-1.5K) and will reset
automatically if evaporator outlet temperature > MOW. There will be no fault indication on the
controller.
For more info about this function refer to the corresponding chapter.
Lower Upper
Line n° Display Description Default
limit limit
1 SERVICE Screen title
2 2.1
MENU
FAN UP: Delay timer for switching on 10s 0s 180s
the fans one step up after Fan
HP is reached
2.2 DOWN : Delay timer for switching off the 180s 0s 180s
fans after Fan LP is reached
3 3.1 FAN LP :
Fan lower Limit, when pressure
is reached the fan down timer
6.0 bar
(R134a)
5.5 bar 8.7 bar
5
(R407C)
For more info about this function refer to the corresponding chapter.
For more info abaut these functions refer to the corresponding chapter. 4
The following screens are additional screens that appear in case of inverter driven fans.
Lower Upper
Line n° Display Description Default
limit limit
1
2.1
SERVICE MENU
DO FAN OFF: %
Screen title
Digital output to switch 45% 0% 50%
5
the on/off fans, depend-
2.2 ON: % 55% 50% 99%
ing on the output signal
of the inverter.
3.1 INVMIN1: °C Parameters to define 0 -99 99
the minimum fan speed
3.2 - Hz 5 0 50
of the inverter driven
4.1 INVMIN2: °C fans in function of the 25 -99 99
outdoor ambient tem-
4.2 - Hz perature. 15 0 50
Lower Upper
Line n° Display Description Default
limit limit
For more info about these functions refer to the corresponding chapter.
Lower Upper
Line n° Display Description Default
limit limit
2
2.1 C12%: Set the timer to run in 12% 20s 20s 180s
mode to start up
3
3.1 STOP: Timer to set to 12% before 8s 0s 99s
stop.
3.2 HP SETBACK: Function used to prevent the 16.5 bar 14 bar 18.0 bar
unit from going into high pres- (R134a)
sure safety
24.5 bar 23.5 bar 26.0 bar
(R407C)
For more info about this function refer to the corresponding chapter.
Remark: Stop: This timer allows you to set the time of the 12% capacity step before stopping the
compressor. When a time is entered:
• • Time /2 is used to run in 12% capacity step.
• • Time /2 is used to still activate the 12% coil even if the compressor is switched off.
Screen 16 This screen allows you to choose whether a password is needed to reset safeties.
2
3 RESET SAFETIES:
4 Indication of the password NONE
needed to reset safeties. USER PASSWORD
(DEFAULT)
SERVICE PASSWORD
For more info about this function refer to the corresponding chapter.
3
Screen 17 This screen allows you to adjust the EEV settings
Only visible if EEV1 or EEV2 is present
For more info about this function refer to the corresponding chapter. 5
Screen 18a This screen allows you to adjust the EEV settings
Only visible if EEV1 or EEV2 is present
Screen 18b This screen allows you to see and reset the warning
Only visible if EEV1 or EEV2 is present
Remark: After setting GO AHEAD on Y you will be able to reset the Valve Open error on the Error
menu
1 Screen 18c This screen allows you to see if the battery is charged
Only visible if EEV1 or EEV2 is present
2
3 BATTERY CHARGED Indicates if battery is charged
4 Status N–Y
Screen 19
For more info about this function refer to the corresponding chapter.
5
Screen 20 This screen allows you to modify the stepless differential thermostat settings
Lower Upper
Line n° Display Description Default
Limit Limit
For more info about this function refer to the corresponding chapter.
When a unit is on outlet control, then the inlet water temperature is stored in the memory at the moment
the last compressor is stopped by thermostat (not when stopped by safety, change mode...). The unit
will only restart if the thermostat ON is requested and if the inlet evapovator water temperature > stored
value + inldiff.
Screen 1 This screen shows the actual value of the general timers:
2a.1 LOADUP: Delay timer for loading up; during countdown, the unit is unable
to load up
2a.2 -DWN: Delay timer for loading down; during countdown, the unit is una-
ble to load down 3
3a PUMPLEAD: The time the pump has to run before the chiller can start up.
3b PUMPLAG: The time the pump still has to keep running after the chiller has
stopped.
(appears when PUMPLEAD TIME =0)
3c PUMPDAILY: Countdown timer, counts if the daily pump start is activated and 4
if the start time is reached.
4 FLOWSTOP: Delay timer that starts counting when the water flow through the
evaporator stops during normal operation; if the water flow has
not restarted during the countdown, the unit will shut down
(default: 5s)
For more info about this function refer to the corresponding chapter.
5
Screen 2 This screen shows the actual value of the startup difference timer:
For more info about this function refer to the corresponding chapter.
1 Screen 3 This screen shows the actual value of the compressor timers:
2 GRD1: s AREC1: s Guard timer & Anti recycling timer for compressor 1
2 3 GRD2: s AREC2: s Guard timer & Anti recycling timer for compressor 2
Remark: Guard timer: delay timer to prevent compressor from restarting after a shutdown
(default 60s). Only if AREC timer is already on 0s.
Anti recycling timer: AREC timer is used to limit the starts per hour, means counting after
starting the compressor. For a screw compressor the default value is 600sec (max. 6
3 starts/hour).
Screen 4 This screen shows the actual value of the compressor timers:
4 1 COMPRESSOR
TIMERS
Screen title
2.1 START1: Delay timer that shows the remaining time that the unit has
to run in its first capacity step at start up.
2.2 STOP: Delay timer that shows the remaining time that the unit has
to run at 12% capacity before shutting down.
5 3.1 START2: Delay timer that shows the remaining time that the unit has
to run in its first capacity step at start up.
3.2 STOP Delay timer that shows the remaining time that the unit has
to run at 12% capacity before shutting down.
Additionally the number of safeties that already occurred on each circuit can be consulted on the first
line of the history screens.
2
Screen 1
1 UNIT HISTORY:XXX
CIRC 1 HISTORY:XXX
Indicates the safety. 3
XXX is the number of the alarm.
CIRC 2 HISTORY:XXX
NET HISTORY:XXX
U WARN HISTORY:XXX
C1WARN HISTORY:XXX
4
C2WARN HISTORY:XXX
When in this main history screen it is possible to go to sub screens for more detailed information. To
access these sub screen press the q key as many times as needed to reach the desired sub screen.
Remark: The sub-screens automatically disappear after 5 seconds.
1 Sub screen 1.1 Push the q key to enter the first sub-screen.
Line n° Display Description
2 NET HISTORY:XXX
U WARN HISTORY:XXX
C1WARN HISTORY:XXX
C2WARN HISTORY:XXX
3 3.2 INL.C:
the moment of shutdown.
5
1 UNIT HISTORY:XXX Indicates if it was a unit, circ1, circ2 or network
CIRC 1 HISTORY:XXX safety.
CIRC 2 HISTORY:XXX XXX is the number of the alarm.
NET HISTORY:XXX
U WARN HISTORY:XXX
C1WARN HISTORY:XXX
C2WARN HISTORY:XXX
Screen 1.3 Push the q key once more to enter the third sub-screen.
1
Line n° Display Description
4 C2:
moment of shutdown.
Screen 1.4 Push the q key once more to enter the fourth sub-screen.
Line n° Display Description
4
1 UNIT HISTORY:XXX Indicates if it was a unit, circ 1, circ2, or network
CIRC 1 HISTORY:XXX safety.
CIRC 2 HISTORY:XXX XXX is the number of the alarm.
NET HISTORY:XXX
U WARN HISTORY:XXX
C1WARN HISTORY:XXX 5
C2WARN HISTORY:XXX
1 Screen 1.5 Push the qkey once more to enter the fifth sub-screen.
Line n° Display Description
2 NET HISTORY:XXX
U WARN HISTORY:XXX
C1WARN HISTORY:XXX
C2WARN HISTORY:XXX
3 4 LP2: = °C
moment of shutdown.
Screen 1.6 Push the q key once more to enter the sixth sub-screen.
4 Line n° Display Description
5 U WARN HISTORY:XXX
C1WARN HISTORY:XXX
C2WARN HISTORY:XXX
For more info about how to set these parameters refer to the corresponding chapters. 3
Screen 2 This screen shows the unit type.
1 Screen 3 This screen shows additional information about the unit, especially about the software and the EEV
drivers if present on the unit.
Line 4 only visible if EEV1 = Yes or EEV2 = Yes
4 EEV1: -2: XXXXXX The hardware (first 3 digits) and software version
(last 3 digits ) of the EEV driver
4
2 BOOT: Indicates boot version and date.
For more info about how to set these parameters refer to the corresponding chapters.
5
2
• • Screen 6 and 14 provides the status of the changeable digital inputs and outputs.
• • Screen 15 provides the status of the EEV inputs and outputs.
Screen 1 This screen shows the status of the emergency stop and the flow switch.
3 C1 REV.PH.PROT.:
circuit 1
1 Screen 4 This screen shows you the status of digital inputs of circuit 2.
2
circuit 2
3 Screen 5 This screen shows you the status of digital inputs of circuit 2.
4
2 C2 DISCH. TH. PR. Status of discharge thermal pro- OK/NOK
tection switch of circuit 2
CHANG.
1 DIG. Screen title
INPUTS
Screen 7 This screen shows the status of the compressor relays of circuit 1.
1
Line n° Display Description Possible settings
Screen 8 This screen shows the status of the compressor relays of circuit 2.
1 Screen 9 This screen shows the status of the relay outputs of compressor 1.
2 4 C1 Feedback:
up or loading down
Gives the feedback from the compres- ± 30 : = 0% cap
sor control motor
± 120 : =
100% cap
3
Screen 10 This screen shows the status of the relay outputs of compressor 2.
5
Screen 11 This screen shows the status of the relay outputs of the fans from circuit 1.
Screen 12 This screen shows the status of the relay outputs of the fans from circuit 2.
Only for air-cooled units with 3 step fans 1
Line n° Display Description Possible settings
2
2 C2 FANSTEP 1 Indicates the status of the fan contac- Open/closed
tor of circuit 2
Screen 13 This screen shows the status of the general alarm and the pump contacts.
1 Screen 14 This screen shows the status of the changeable digital input and the digital outputs.
CHANG.
1 Screen title
INP/OUTPUTS
2
2 DI4 XXXX:XXXX Changeable digital NONE
input 4 + status of input DUAL SETPOINT
SETP.1/SETP.2
REMOTE ON/OFF
ON/OFF
REMOTE
COOL/HEAT
COOL/HEAT
NO LIM/LIMIT
CAP. LIMIT 1
NO LIM/LIMIT
CAP. LIMIT 2
NO LIM/LIMIT
CAP. LIMIT 3
3
NO LIM/LIMIT
CAP. LIMIT 4
N/Y
LOW NOISE
OPEN/CLOSED
STATUS
NO REQ/REQ
HEAT REC:
4
2ND EVAP PUMP
4 DO2 XXXXXXX Changeable digital out- CONDENSER
put 1 + status of output PUMP
O/C
100% CAPACITY
(Open/Closed)
FREE COOLING
GEN.OPERATION
REV.VALVE(C/H)
EVAPHEATERT.:
5 HR COND PUMP:
Screen 15 This screen shows the status of the In/Outputs of the EEV
Only if 1 or 2 electronic expansion valves are present on the unit.
2
• • the user password menu
The units leave the factory with user password "1234". The service password overrides the user
password (in case you don't know or forgot the user password).
Screen 1 In this screen the user password must be entered to access the user password menu.
Use the h and g keys to select the password.
3
Line n° Display Description Possible settings
3
ENTER PASSWORD
PASSWORD: 0000
Screen title
2 NEW PASSWORD: To set the new password From 0000 till 9999
1 NETWORK
3
setpoint if selected )
INLETSP1(2) C
SP1(2) E: C:
Line 4 is only visible if in user settings menu the control setting mode is "outlet water setpoint".
An extra temperature sensor must be installed to measure the mixed outlet water temperature.
5
Screen 2
Line n° Display Description Possible settings
The safeties menu is linked to the history screen. By pushing the q key when in the safety menu
2 you jump to the history menu where, along with the basic information, more detailed data screens can
be consulted, by pressing the q key again.
Remark: In the service menu it is possible to choose the password that will be requested to be able
to reset the safeties. This can be either the service either the user password. When one of these
passwords is selected in the service menu, it will be requested to enter that password before the safety
can be reset. Default the user password (1234) is needed to reset the errors.
3
Screen 1a
Line n° Display Description
4 UNIT SAFETY
CIRCUIT SAFETY
NETWORK SAFETY
safety or warning (Not possible to reset, safety is
still present)
CIRCUIT WARNING
5 Screen 1b When the error is solved the p key starts blinking and it is possible to reset the safety by pressing
the p key.
1b RESET UNIT WARNING After solving the problem, the alarm key starts
RESET UNIT SAFETY blinking and the display indicates that resetting is
RESET CIRCUIT SAFETY possible.(possible to reset)
RESET NETW SAFETY
RESET CIRC WARNING