Cat A5vr (Y) 1702 PDF
Cat A5vr (Y) 1702 PDF
FLOW (VRF)
Air Conditioner
DC INVERTER variable refrigerant flow
ACSON
Provides The Best Cooling Experience
Since 1984
Customer needs and comforts have been our priorities ever since our inception.
At Acson, we focus on delivering healthier lifestyles and happiest moments to our
customers without causing harm to the environment.
As we move towards vision 2020, the demographic for Malaysia residential is moving
towards building that are much compact than ever before. We, Acson are proud to
present to you our latest Variable Refrigerant Flow (VRF) system. It is suitable for both
residential and commercial with our wide range of capacity.
Inspired Cooling Companion
02 Common Features
08 Unique Features
08 Carefree
12 EcoPlus & EcoPro
13 Control System
16 Indoor Unit Line-up
16 Wall Mounted
18 Ceiling Cassette
Common Features
Acson Carefree, EcoPlus & EcoPro have a lot of unique features but it also share a lot of similarities.
Here are some of them:
2
Inspired Cooling Companion
Anti-corrosion layer
New heat
exchanger fin
Platinum foil
substrate
9.52mm 7.94mm
Ecosystem Friendly
Similar to our Ecocool lineup, our AVR series use R410A refrigerant. Which at the moment the most probable line-up as R22 refrigerant line-up. It
does not deplete the ozone and pose any hazardous threat that most non-ODP refrigerant do. As a responsible corporate, our line-up is also RoHs
compliance.
3
Common Features variable refrigerant flow
4
Inspired Cooling Companion
Exhaust Refrigerant
gas (with
little oil) One-way valve One-way valve
Oil separator
Oil separator
separation
Level 2 oil
Compressor
Compressor
Solenoid
valve
Gas liquid
splitter
Suction
5
Common Features variable refrigerant flow
Smart Room
Be it hotel operators or smart home aspirant, our AVR system is capable to perform such function. With a simple card detector or a sensory device
such as infrared or sound sensor. We can design the air conditioning system to be operating as if it is self-conscious.
Mode 1 Mode 2
When the user enters the room, the air conditioner with the When entering the room, the user inserts the card to directly
inserted card is in the standby status. The user can use power on the air conditioning unit for operation. When
the controller to start the air conditioner; the user unplugs leaving, the user unplugs the room card, and then the air
the card when leaving the room and the air conditioning conditioning unit powers off automatically.
unit is powered off automatically, which avoids unwanted
electricity waste when the user forgets to power off the unit
before leaving.
Mode 3
The smart room card interface can also implement multiple power-on/off functions, e.g., the external module can be used to power on/off the air
conditioner through modes such as sound control or infrared sensing.
ODU
failure
Automatic restart
after power supply
connection
6
Inspired Cooling Companion
System Redundancy
Our AVR system uses a lot of sensors, switches, program logics and so on to provide a reliable system redundancy. This make our unit more resilient,
a single component failure might not cause total failure. This enable user able to operate the system albeit not in full capacity while wait for the
system to be rectified.
Over-high temperature
Compressor/fan overload protection protection of air exhaust/return
Refrigerant leakage
Inverter failure protection protection
Over-high/low ambient
temperature protection
7
CareFree Unique Features variable refrigerant flow
Permanent-
magnet rotor
2 Supercool Stages
Each of the series have 2 supercool stages, the only
difference is Carefree series uses only a simple reservoir
compare to the latter. By doing so, we could maximize the
performance in an economical and efficient way.
320mm
900mm
Compact Design
One of the reason why Carefree series is a preferred choice
when it comes to residential application is the compact
design of it. With the ever stringent rule of high building,
space has become a rare commodities. The compact design 1222mm
of Carefree fit in just right.
8
Inspired Cooling Companion
Optimized Pipeline
The entire pipeline system is optimized to avoid the pipeline vibration and resonance
generated during operation of the air conditioner and decrease the vibration and noises of
pipeline.
9
EcoPlus/EcoPro Unique Features variable refrigerant flow
Acson DC Inverter Variable Refrigerant Central Air Conditioner adopts high pressure chamber compressor with high performance yet low in sound
level. In comparison to conventional low pressure chamber scroll compressor, high chamber scroll compressor uses the asymmetric scroll design.
Our compressor also possess intelligent oil control technology with most oil stay inside the compressor rather than being distributed throughout the
system.
The scroll compressor of high pressure Good sound insulation effect, sturdy and
chamber adopts the asymmetric scroll durable.
design to realize good stability and high
efficiency.
Outputting 180° smooth sine wave to The bearing part has special functions to
ensure stable operation of the compressor support operation of the compressor at
d r i v e r a n d re d u c e t h e c o m p re s s o r high frequency.
vibration and noise effectively.
10
Inspired Cooling Companion
Inhaled gas is
compressed directly
Movable to avoid the defect of
scroll symmetrical line.
2 Supercool Stages
Similar to Carefree Series, there is two supercool stages. However, the equipment used in both EcoPlus and EcoPro is more
sophisticated due to the scale of cooling capacity of the unit.
11
EcoPlus/EcoPro Unique Features variable refrigerant flow
12
Inspired Cooling Companion
Control System
One of the advantages of Acson AVR line-up is it use common control system. Thus, this make the system is more user
friendly especially for future upgrades.
Independent Controller
Acson provides a big variety of independent controllers, including fashionable touch-screen wired controllers and practical and nice-looking
wireless remote controllers. All of them can help you easily control the air conditioning unit and bring you more convenient and comfortable life
with easy operations.
1 Temperature settings 5 Keyboard locking and unlocking 9 Timed power-on/off 13 Real-time clock settings
2 Mode settings 6 Fan speed settings 10 Filter cleaning reminder 14 Setting automatic startup after
3 Sleep mode 7 IDU address display 11 Control function of auxiliary heater power restoration
Touch-screen
wired controller
13
Control System variable refrigerant flow
Centralized
control
converter
A maximum of 192 ODUs
are connected
Computer
USB
password key
he system can perform centralized monitoring on multiple IDUs and ODUs from a remote end. A computer can be connected with a centralized
T
control converter to perform network control on up to 192 ODUs and 3072 IDUs.
●
1
Sets the IDU mode and wind speed, auxiliary settings, temperature and power on/off (multiple units or machines in multiple units can
be selected to perform operations at the same time)
●
2 IDU and ODU group settings; group settings can be customized
●
3 Centralized power-on/off (group control and control of a single IDU can be implemented)
●
4
Local wired controller can be locked
●
5 Week or date settings
●
6 Monitoring data can be connected to the building system directly so that the unit status can be checked
● T
7 he historical operating status and operating parameters of multiple IDUs or ODUs and the unit operating data in the historical time
segment can be queried, and the operating record report can be exported
14
Inspired Cooling Companion
he unit can be connected to the BACnet based building automation system through the BACnet gateway. A maximum of 24 ODUs can be
T
connected to a BACnet gateway and up to 1536 IDUs can be connected at one time.
BACnet gateway
A maximum of 8 ODUs can be connected to each RS485 interface
BACnet gateway
Switch
Building automation
BACnet gateway
15
Wall Mounted variable refrigerant flow
Model:
A5VWM022W~
A5VWM071W
Swing Design
Guide blades can automatically swing up and down to achieve Left pipe
the good air supply status. The peak air supply mode can also be
set by remote control to supply comfortable air everywhere in the
room.
Left rear pipe
16
Inspired Cooling Companion
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. All specifications are subjected to change by the manufacturer without prior notice.
17
Ceiling Cassette variable refrigerant flow
Model:
A5VCK028V~
A5VCK140VP
The standard configuration of the unit provides the long acting dust
filter screen. Meanwhile, the fresh activated-carbon filter assembly
is optional to filter dust particles from the air efficiently and remove Smooth Drainage
the peculiar smell and odor. The filter screen can be removed and The standard unit is configured with the condensate water lifting pump
cleaned conveniently to keep the indoor air clean. with the head being 700 mm to facilitate setting of drain pipes greatly.
Note: The 1200 mm condensate water pump is optional.
18
Inspired Cooling Companion
Cooling BTU/h 21,500 24,200 27,300 30,700 34,100 38,200 42,700 47,800
Capacity kW 6.30 7.10 8.00 9.00 10.00 11.20 12.50 14.00
Nominal Input Power kW 0.102 0.142 0.144 0.155 0.171 0.204
Operating
A 0.47 0.82 0.85 0.91 1.05 1.23
Current
Operation WIRELESS CONTROLLER (WIRED: OPTIONAL)
Control
Air Discharge AUTOMATIC LOUVER (UP AND DOWN)
Power Source V/Ph/Hz 220 ~ 240VV/~/50Hz
Refrigerant Control BUILT - IN ELECTRONIC EXPANSION VALVE
Low m³/h / CFM 810 / 477 880 / 518 920 / 541 1,040 / 612 1,090 / 642 1,230 / 724
Air Flow Rate Medium m³/h / CFM 980 / 577 1,060 / 624 1,160 / 683 1,250 / 736 1,310 / 771 1,480 / 871
High m³/h / CFM 1,200 / 706 1,300 / 765 1,360 / 800 1,530 / 901 1,600 / 942 1,800 / 1,059
Sound Pressure Level dB(A) 40 42 42 43 45 48 50
Height mm(in) 265(10.43) / 340 (13.39) 315(12.4) / 390(15.35)
Unit Dimension
Width mm(in) 893 (35.16), (990 (38.98))
(With Panel)
Depth mm(in) 820 (32.28), (990 (38.98))
Height mm(in) 513 (20.20) 555 (21.85)
Packing
Width mm(in) 948 (37.32)
Dimension
Depth mm(in) 918 (36.14)
Unit Weight kg / lb 31 / 68 35 / 77 36 / 79
Panel Weight kg / lb 4.4 / 9.7
Drainage Pipe Size mm(in) 20.5 (4/5")
Discharge mm(in) 9.52(3/8”)
Piping
Suction mm(in) 15.88(5/8”)
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. All specifications are subjected to change by the manufacturer without prior notice.
19
Ceiling Mounted variable refrigerant flow
Model:
A5VCM056V~
A5VCM125V
Creative Dual Air Outlet Design Anti-Mildew And Washable Filter Screen
The unit supplies air with a wide air supply angle horizontally or The filter screen can be cleaned easily and conveniently to keep
from the bottom, making temperature/air distribution more even. the indoor air clean.
20
Inspired Cooling Companion
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. All specifications are subjected to change by the manufacturer without prior notice.
21
Ceiling Concealed (Standard) variable refrigerant flow
Model:
A5VCC022V~
A5VCC071V
Movable plate
Back air return
22
Inspired Cooling Companion
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. Unit in parentheses is available external static pressure. Please contact us for more details.
4. All specifications are subjected to change by the manufacturer without prior notice.
23
Ceiling Concealed (Compact) variable refrigerant flow
Model:
A5VCC080V~
A5VCC160V
24
Inspired Cooling Companion
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. Unit in parentheses is available external static pressure. Please contact us for more details.
4. All specifications are subjected to change by the manufacturer without prior notice.
25
Ducted Blower variable refrigerant flow
Model:
A5VDB125V~
A5VDB280V
26
Inspired Cooling Companion
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. Unit in parentheses is available external static pressure. Please contact us for more details.
4. All specifications are subjected to change by the manufacturer without prior notice.
27
Ducted Blower (Fresh Air) variable refrigerant flow
28
Inspired Cooling Companion
Besides, the fresh air unit can implement multiple control modes
such as centralized control and building automation. IDU and fresh air unit interlocked and started automatically
VRF system
Centralized control
≤ 64 sets
A5VDBX 140VP
A5VR
Use Conditions
One EcoPlus module can be connected to multiple fresh air units. However, the total capacity of the fresh air unit must be within 50% ~ 100% of the
outdoor unit.
29
DC INVERTER variable refrigerant flow
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. Should the application require one to one or one to many coupling. The fresh air unit need to be A5DBX140/224/280V.
4. Should the system require both fresh air and normal indoor unit (Mixed System). The IDU total cooling capacity must be 50% ~ 100% of the ODU total cooling capacity.
5. The fresh air unit for mixed system cooling capacity must not exceed 30% of the ODU cooling capacity.
6. All specifications are subjected to change by the manufacturer without prior notice.
30
Inspired Cooling Companion
A5VR A5VR A5VR A5VR A5VR A5VR A5VR A5VR A5VR A5VR
Model
030DRM 035DRM 040DRM 050DRM 050DRM(3) 060DRM 060DRM(3) 065DRM 070DRM 080DRM
Cooling kW 8.00 10.00 11.20 14.00 14.00 15.50 16.00 18.00 20.00 22.40
Capacity BTU/H 27,300 34,100 38,200 47,800 47,800 52,900 54,600 61,400 68,200 76,400
Nominal Input Power kW 2.34 3.12 3.20 4.24 3.70 4.69 4.40 5.29 5.40 6.59
Nominal Operating Current A 11.90 15.20 15.30 20.30 7.40 23.00 8.00 27.00 9.60 11.90
Efficiency COP W/W 3.42 3.21 3.50 3.30 3.78 3.30 3.64 3.40 3.70 3.40
Integrated Part Load Value 4.75 4.7 4.45 4.75 4.55 4.75 4.85 4.75 4.8 4.8
380 ~ 415V/ 220 ~ 240V/ 380 ~ 415V/ 220 ~ 240V/
Power Source V/Ph/Hz 220 ~ 240V/~/ 50Hz 380 ~ 415V/ 3 / 50Hz
3 / 50Hz ~/ 50Hz 3 / 50Hz ~/ 50Hz
3,200/ 3,400/ 5,500/
Air Flow Rate m³/h / CFM 6,500 / 3,826 8,200 / 4,826
1,883 2,001 3,237
Noise dB(A) 54 55 55 57 57 59 59 62
Height mm(in) 782 (30.79) 1,222 (48.11) 1,354 (53.31)
Unit Dimension Width mm(in) 900 (35.43)
Depth mm(in) 320 (12.6)
Height mm(in) 942 (37.09) 1,382 (54.41) 1,514 (59.61)
Packing
Width mm(in) 950 (37.40)
Dimension
Depth mm(in) 440 (17.32)
Unit Weight kg / lb 71 / 157 76 / 168 102 / 225 110 / 243 107 / 236 110 / 243 107 / 236 120 / 265 128 / 282
Maximum Indoor Unit pcs 5 6 6 8 9 11 11 13
Type R410A
Refrigerant
Charge kg / lb 3.5 3.9 4.5 4.5 3.5 4.7 3.7 5.9 5.2 5.95
Discharge mm(in) 9.52(3/8”)
Connection Pipe
Suction mm(in) 15.88(5/8”) 19.05(3/4”)
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
Indoor 27°C DB / 19° C WB
Outdoor 35°C DB / 24° C WB
Length 5m
Pipe
Height 0m (On Ground)
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. All specifications are subjected to change by the manufacturer without prior notice.
31
EcoPlus variable refrigerant flow
Model A5VR080DR A5VR100DR A5VR120DR A5VR140DR A5VR160DR A5VR180DR A5VR200DR A5VR220DR A5VR240DR
Cooling kW 24.50 28.00 33.60 40.00 45.00 50.40 56.00 61.60 68.00
Capacity BTU/h 83,600 95,500 114,600 136,500 153,500 172,000 191,100 210,200 232,000
Nominal Input Power kW 6.00 7.36 8.84 10.52 12.50 14.70 15.20 16.62 20.00
Nominal Operating Current A 12.2 14.3 15.4 18.3 21.8 26.4 27.5 30.4 35.2
Efficiency COP W/W 4.08 3.80 3.80 3.80 3.60 3.43 3.68 3.71 3.40
Integrated Part Load Value 7.2 7.0 6.8 6.5 6.3 6.0 6.6 6.3 6.0
Power Source V/Ph/Hz 380 ~ 415V/3N~/50Hz
13,000 /
Air Flow Rate m³/h / CFM 14,500 / 8,534 24,800 / 14,597
7,652
Noise dB(A) 58 59 60 61 62
Height mm(in) 1,515 (59.65) 1,780 (70.78)
Unit Dimension
Width mm(in) 990 (38.98) 1,350 (53.15) 1,990 (78.35)
(Individual)
Depth mm(in) 840 (33.07)
Height mm(in) 1,700 (66.93) 1,970 (77.56)
Packing
Dimension Width mm(in) 1,080 (42.52) 1,440 (56.69) 2,090 (82.28)
(Individual)
Depth mm(in) 890 (35.04)
Unit Weight kg / lb 181 / 399 182 / 401 213 / 470 290 / 639 314 / 692 320 / 705 448 / 988 473 / 1,043 480 / 1,058
Maximum Indoor Unit pcs 13 16 20 20 24 28
Type R410A
Refrigerant
Charge kg / lb 7.3 / 16.09 8.4 / 18.52 9.6 / 21.16 11.4 / 25.13 13.9 / 30.64 14.6 / 32.19 16.5 / 36.38 20.2 / 44.53 23.4 / 51.59
Discharge mm(in) 9.52(3/8”) 12.7 (1/2”) 15.88(5/8”)
Connection Pipe
Suction mm(in) 22.23(7/8”) 28.6(9/8”)
Model A5VR260DR A5VR280DR A5VR300DR A5VR320DR A5VR340DR A5VR360DR A5VR380DR2 A5VR380DR3 A5VR400DR2
A5VR120DR A5VR120DR A5VR140DR A5VR160DR A5VR160DR A5VR180DR A5VR160DR A5VR120DR A5VR160DR
Combination A5VR140DR A5VR160DR A5VR160DR A5VR160DR A5VR180DR A5VR180DR A5VR220DR A5VR120DR A5VR240DR
A5VR140DR
Cooling kW 73.60 78.60 85.00 90.00 95.40 100.80 106.60 107.20 113.00
Capacity BTU/h 251,100 268,200 290,000 307,100 325,500 343,900 363,700 365,800 385,600
Nominal Input Power kW 19.36 21.34 23.02 25.00 27.20 29.40 29.12 28.20 32.50
Nominal Operating Current A 33.7 37.2 40.1 43.6 48.2 52.8 52.2 49.1 57.0
Efficiency COP W/W 3.80 3.68 3.69 3.60 3.51 3.43 3.66 3.80 3.48
6.8 + 6.8
Integrated Part Load Value 6.8 + 6.5 6.8 + 6.3 6.5 + 6.3 6.3 + 6.3 6.3 + 6 6+6 6.3 + 6.3 6.3 + 6
+ 6.5
Power Source V/Ph/Hz 380 ~ 415V/3N~/50Hz
39,300 / 43,500 / 39,300 /
Air Flow Rate m³/h / CFM 29,000 / 17,069
23,131 25,603 23,131
Noise dB(A) 64 64 64 64 65 65 65 65 66
1,780 1,780
Height mm(in) 1,780 (70.78) x 2
(70.78) x 3 (70.78) x 2
32
Inspired Cooling Companion
990 (38.98) +
Unit Dimension 990 (38.98) x 2
Width mm(in) 1,350 (53.15) 1,350 (53.15) x 3
(Individual) + 1,350 (53.15)
x2
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
Indoor 27°C DB / 19° C WB
Outdoor 35°C DB / 24° C WB
Length 5m
Pipe
Height 0m (On Ground)
33
EcoPro variable refrigerant flow
Model A5VRY080ER A5VRY100ER A5VRY120ER A5VRY140ER A5VRY160ER A5VRY180ER A5VRY200ER A5VRY220ER A5VRY240ER
Cooling kW 25.00 28.00 33.60 40.00 45.00 50.50 56.00 61.60 68.00
Capacity BTU/Hr 85,300 95,500 114,600 136,500 153,500 172,300 191,100 210,200 232,000
Nominal Input Power kW 5.66 6.48 8.85 10.25 11.85 14.75 15.28 17.43 19.52
Nominal Operating Current A 10.7 12.8 15.9 18.3 21.8 26.2 27.5 29.3 33.3
Efficiency COP W/W 4.42 4.32 3.8 3.9 3.8 3.42 3.66 3.53 3.48
Integrated Part Load Value 8.75 7.80 7.35 8.15 7.80 7.50 7.90 7.60 7.40
Noise dB(A) 58 59 60 61 62
Unit Weight kg / lb 208 / 459 209 / 461 242 / 534 304 / 670 327 / 721 329 / 725 414 / 913 439 / 968 442 / 974
Type R410A
Refrigerant
Charge kg / lb 8.5 / 18. 74 9.5 / 20.94 10.5 / 23.15 11.5 / 25.35 13.0 / 28.66 14.5 / 31.97 16.5 / 36.38 19.5 / 42.99 22.5 / 49.6
34
Inspired Cooling Companion
Refrigerant 10.5 x 2 + 14.5 10.5 + 11.5 + 10.5 + 13.0 + 10.5 + 14.5 x 2 11.5 + 14.5 x 2 13 + 14.5 x 2 / 14.5 x 2 + 16.5
14.5 x 3 / 31.97
Charge kg / lb / 23.15 x 2 + 14.5 / 23.15 + 14.5 / 23.15 + / 23.15 + 31.97 / 25.35 + 31.97 28.66 + 31.97 / 31.97 x 2 +
x3
31.97 25.35 + 31.97 28.66 + 31.97 x2 x2 x2 36.38
Discharge mm(in) 19.05 (3/4”) 22.23 (7/8”)
Connection Pipe
Suction mm(in) 38.1 (1-1/2") 44.5 (1-3/4”)
Refrigerant 14.5 x 2 + 19.5 14.5 + 16.5 + 14.5 + 19.5 x 2 16.5 + 19.5 x 2 19.5 x 2 + 22.5 19.5 + 22.5
19.5 x 3 / 42.99 22.5 x 3 / 49.6
Charge kg / lb / 31.97 x 2 + 19.5 / 31.97 + / 31.97 + 42.99 / 36.38 + 42.99 / 42.99 x 2 + x 2 / 42.99 +
x3 x3
42.99 36.38 + 42.99 x2 x2 49.6 49.6 x 2
Discharge mm(in) 22.23 (7/8”)
Connection Pipe
Suction mm(in) 44.5 (1-3/4”)
Notes:
1. Nominal cooling capacity are based on the conditions below:
Cooling
Indoor 27°C DB / 19° C WB
Outdoor 35°C DB / 24° C WB
Length 5m
Pipe
Height 0m (On Ground)
2. Sound pressure level is measured in a semi-anechoic chamber. Actual noise level might be higher due to external influence.
3. Multiple module installation will require additional accessory.
4. All specifications are subjected to change by the manufacturer without prior notice.
35
Accessories variable refrigerant flow
Accessories Kit
Indoor Unit
LCD Wired Controller LCD Wireless Controller Condensate Water Lifting Pump
A5VR260DR - A5VR400DR
1 AVR-A-A1E Right angle elbow, variable diameter tube, Y-type triplet
A5VRY260ER - A5VRY360ER
A5VR380/400DR3
2 AVR-A-A2E Right angle elbow, variable diameter tube, Y-type triplet A5VR420DR - A5VR500DR
A5VRY380ER - A5VRY500ER
A5VR520DR - A5VR540DR
3 AVR-A-A3E Right angle elbow, variable diameter tube, Y-type triplet
A5VRY520ER - A5VRY540ER
4 AVR-A-A6E Right angle elbow, variable diameter tube, Y-type triplet A5VRY560ER - A5VRY720ER
Note: In the case of installation of combined modular units, please buy the above corresponding installation accessories.
Controller
1 AC-HMI321AE-(1/10/50)A Wired Controller AC 321A All IDUs and Fresh air IDU
Note: * (1/10/50) indicates the number of controllers accommodated in single package box.
* A/B/C indicates white, blue, and gold respectively.
For details, see the order naming list.
Control mode Centralized wired controller Centralized monitoring system Household-based billing system Building automation
AC-CCS101A
(centralized monitoring software) Does not need to order
AC-CCS102A (software system)
AC-GTW001A ModBus gateway (Built-In)
Ordered parts AC-HMI323A AC-GTW002A (power divider)
(1-channel conversion interface) AC-GTW003A
AC-GTW002B (data backup device)
AC-GTW001 B (BACNET protocol gateway)
(4-channel conversion interface)
36
Inspired Cooling Companion
Model Capacity range (kW) 2.2 2.5 2.8 2.2 3.6 4.0 4.5 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 22.4 28
Ceiling
concealed
(Standard)
A5VCC-V
Ceiling concealed
(compact)
A5VCC-V
Four-direction air
outlet ceiling
cassette
A5VCK-V
High static
IDU ducted blower
A5VDB-V
Ceiling mounted
A5VCM-V
Wall mounted
A5VWM-W
Fresh Air
Ducted Blower 14~58kW (fresh air flow: 1100~6000m3/h)
A5VDBX-V
Note:
1. The lineup is for indicative purposes, actual coupling will still depends on the outdoor unit. Please consult us should you need further assistance.
2. Fresh air ducted blower only available for EcoPro Series.
A5VR DRM
ODU
Carefree Series
37
Summary-Outdoor Unit Line-up variable refrigerant flow
80 A5VR080DR
100 A5VR100DR
120 A5VR120DR
140 A5VR140DR
160 A5VR160DR
180 A5VR180DR
200 A5VR200DR
220 A5VR220DR
240 A5VR240DR
260 A5VR260DR
280 A5VR280DR
300 A5VR300DR
320 A5VR320DR
340 A5VR340DR
360 A5VR360DR
380 A5VR380DR2
380 A5VR380DR3
400 A5VR400DR2
400 A5VR400DR3
420 A5VR420DR
440 A5VR440DR
460 A5VR460DR
480 A5VR480DR
500 A5VR500DR
520 A5VR520DR
540 A5VR540DR
38
Inspired Cooling Companion
13
16
16
20
20
24
24
28
28
32
32
36
36
40
40
44
44
44
48
48
48
52
52
54
54
56
39
Summary-Outdoor Unit Line-up variable refrigerant flow
80 - 180 MBH 200 - 240 MBH 260 - 540 MBH 560 - 580 MBH
80 A5VRY080ER
100 A5VRY100ER
120 A5VRY120ER
140 A5VRY140ER
160 A5VRY160ER
180 A5VRY180ER
200 A5VRY200ER
220 A5VRY220ER
240 A5VRY240ER
260 A5VRY260ER
280 A5VRY280ER
300 A5VRY300ER
320 A5VRY320ER
340 A5VRY340ER
360 A5VRY360ER
380 A5VRY380ER
400 A5VRY400ER
420 A5VRY420ER
440 A5VRY440ER
460 A5VRY460ER
480 A5VRY480ER
500 A5VRY500ER
520 A5VRY520ER
540 A5VRY540ER
560 A5VRY560ER
580 A5VRY580ER
600 A5VRY600ER
640 A5VRY620ER
640 A5VRY640ER
660 A5VRY660ER
680 A5VRY680ER
700 A5VRY700ER
720 A5VRY720ER
40
Inspired Cooling Companion
13
16
16
20
20
24
24
28
28
32
32
36
36
40
40
44
44
48
48
52
52
54
54
56
56
58
58
60
60
60
60
60
60
41
Design Application variable refrigerant flow
ODU Capacity Pipe Cooling Capacity (MBH) Specification diameter (mm) The first branch pipe Other branch pipe models
Note:
1. 1MBH is equivalent to 1,000 BTU/h.
2. X is the cooling capacity of the system.
Bedroom
Bedroom
Bedroom
Bathroom
The total pipe length for the IDU and ODU is 120 m.
The maximum height difference between IDU and ODU
Living room is 20 m.
The maximum equivalent pipe length between the IDU
Max. drop between IDUs
Bathroom
Note: When the maximum pipe length of A5VR050/060DR
model is greater than 50 m,
Bedroom the air pipe used between the ODU and the first branch
connector should be 19.05.
42
Inspired Cooling Companion
A5VR - DR EcoPlus
Selection of pipes and refnet
249.1 Φ 19.05
CX Φ 41.3
X ≤ 19.1 Φ 6.35
Liquid pipe
21.5 ≤ X 47.8 Φ 9.52
Note:
1. 1MBH is equivalent to 1,000 BTU/h.
2. X is the cooling capacity of the system.
Maximum drop between IDUs: 15 m
Maximum drop between IDUs
Piping Overview
and ODUs: 50 m
Note: "※" indicates correspondence. Please consult the technician. Total pipe length of IDUs and ODUs: 1000 m; maximum drop
between IDUs and ODUs: 50 m
43
Design Application variable refrigerant flow
A5VRY - ER EcoPro
A5VRY A5VRY A5VRY A5VRY A5VRY A5VRY A5VRY A5VRY
Model
080ER 100~120ER 140~180ER 200~240ER 260~300ER 320~340ER 360~540ER 560~720ER
532.3 ≤ X Φ 22.23
532.3 ≤ X Φ 44.5
Liquid pipe The indoor unit connected to the piping Conform to the interface of the indoor unit
Gas pipe The indoor unit connected to the piping Conform to the interface of the indoor unit
Note:
1. 1MBH is equivalent to 1,000 BTU/h.
2. X is the cooling capacity of the system.
44
Inspired Cooling Companion
Piping Overview
The ECO PRO series VRF units optimize the supercooling design and refrigerant control technologies and break through limitations in the pipe
connection, which give larger product design and construction space and allow for more flexible deployment of ODUs.
240m
Maximum drop between IDUs: 30 m
Maximum drop between IDUs
1,000m
and ODUs: 90 m
30m
Maximum height difference between IDUs and
ODUs when ODUs are installed above IDUs:
90m
Maximum distance between the first refnet and furthest IDU:
90m*
For items marked with *, consult technicians for details.
45
Inspired Cooling Companion
A5VR(Y)-1702