0% found this document useful (0 votes)
208 views

Matt Foundation

This document provides information for designing the foundation system for a structure, including pile foundations and a raft foundation. It specifies parameters like the safety factor, allowable bearing capacity, modulus of subgrade reaction, pile dimensions and spacing, raft thickness and reinforcement details. Design checks are performed in SAFE software to ensure the raft foundation has adequate strength based on the calculated loads and material properties.

Uploaded by

Lavender Honey
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
208 views

Matt Foundation

This document provides information for designing the foundation system for a structure, including pile foundations and a raft foundation. It specifies parameters like the safety factor, allowable bearing capacity, modulus of subgrade reaction, pile dimensions and spacing, raft thickness and reinforcement details. Design checks are performed in SAFE software to ensure the raft foundation has adequate strength based on the calculated loads and material properties.

Uploaded by

Lavender Honey
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 9

Metric Unit

Safety Factor, SF = 3 (usually 2 for grandular soil (Sandy) and 3 for cohesive s
Allowable bearing Capacity, (qa) = 150 kN/m2
Modulus of Subgrade Reaction, Ks = 18000 KN/m3 𝐾𝑠=40∗𝑆𝐹∗𝑞𝑎
Modulus of Subgrade Reaction, Ks at edge = 21600 (Assumed 20% increasee at the edges. This should b
according to the recommendation of geotechniacl rep

FPS
𝐾𝑠=12∗𝑆𝐹∗𝑞𝑎
(Sandy) and 3 for cohesive soil (clay))

e at the edges. This should be


ndation of geotechniacl report)

Ref: Foundation Analysis and Design-Bowles (5th-Edition)-Page-526


Diameter of Pile, D = 1.2 m
Length of Pile, L = 70 m
Capacity of Pile = 12000 kN
Total Reaction (DL+LL) = 202133.6433 kN
Number of pile required = 43
fc' = 35 MPa
E = 27805.6 MPa N/mm2
= 27805575.0 kN/m2
Crossional Area of Pile = 1.1 m2
Pile Spring, K= (EA/L) = 449248.063309 kN/m
= 449.248 kN/m

Pile Distance from Edge = 1.25D (Range D-1.25D)


= 1.5 m

Pile Spacing = 2.5D (Range 2.5D-3D)


= 3 m
Raft Foundation Design
Nos Dia ø Spacing
Rebar for Raft at Bottom = 10 16 350.00
Bottom Clear Cover = 75 mm
Rebar for Raft at Top = 10 16 350.00
Top Clear Cover = 75 mm
Raft Thickness 3500 mm
d = 3417 mm
d' = 83 mm
Yield Strength of Steel, fy = 390 N/mm2

Ultimate Moment Resistance by Reinforcement at Bottom in Column Strip


Mr = 2222178671 (Formula- 0.85*Fy*Ast*(d-d')
= 2222.18 kN-m/m

For Top Face,


d 3417 mm
d' 83 mm

Ultimate Moment Resistance by Reinforcement at Top in Middle Strip


Mr = 2222178671 (Formula- 0.85*Fy*Ast*(d-d')
= 2222.18 kN-m/m

SAFE -Envelope-Strength Ultimate -M11,M22 Check !!


At the base of column/wall strip (External Reinforcement needed) Reinforcing Direction 1 (Y)-Bottom R
At the top of middle strip (External Reinforcement needed) Reinforcing Direction 1(Y)-Top Rebar

*Load Combination According to (ACI318-08) - Defult Load Combination (Strength Ultimate).


nforcing Direction 1 (Y)-Bottom Rebar
nforcing Direction 1(Y)-Top Rebar

gth Ultimate).
Thickness of Mat/Raft = 3200 mm

Minimum Reinforcement in Mat/Raft (Temperature & Shrinkage)


Rebar Strength = 390 N/mm2
Minimum Required Steel Ratio = 0.002
Required Asmin = 6400 mm2/m in gross x-sectional area
Distributed Steel at Top = 6400 mm2/m
Distributed Steel at Bottom = 6400 mm2/m

Select Rebar (A) = 16 ø


Required Spacing = 31.42 mm
Provide Spacing = 400 mm

Reinforcement Calculation as per result in SAFE (Direction 1: Bottom)


At Bottom of Col Strip (A+B) = 1456.744 mm
Required Extra Over Minimum Reinf.Provided (B) = 0
Select Rebar (B) = 16 ø
Required Spacing = 0.00 mm
Extra Betwwen (A) at Bottom in Column Strip

Reinforcement Calculation as per result in SAFE (Direction 1: Top)


At Top of Middle Strip (A+C) = 821.108 mm
Required Extra Over Minimum Reinf.Provided (B) = 0
Select Rebar (B) = 16 ø
Required Spacing = 0.00 mm
Extra Betwwen (A) at Bottom in Column Strip
ACI 308-08 Chapter 15-p267

ss x-sectional area

Maximum spacing shall not exceed 450 mm.


eed 450 mm.

You might also like