SIPROTEC Processbus - Profile
SIPROTEC Processbus - Profile
www.siemens.com/processbus
Description
Protection functions require the measurement of voltages
and currents. The analog values are measured via instru-
ment transformer, then provided to the protection device
and processed by the protection algorithm.
Conventional solution
The conventional instrument transformers are directly con-
nected to the protection devices with parallel copper lines.
This solution is proven, but requires a lot of wiring effort,
has physical limits (accuracy, saturation) and bears the risk
of open CT circuits.
Process bus solution
This innovative solution involves positioning a merging SIPROTEC 5 Process bus solution
unit close to the transformer. The merging unit reads the
measured values of the instrument transformers, digital- • Independency - Interoperable design enables multi-
izes them and sends them to one or more protection de- vendor solutions based on IEC 61850 standard
vices via a sampled measured values (SMV) data stream
over fiber optical Ethernet.
• Flexibility and scalability - Easier adaptation to future
requirements and integration of wider range of data
The protection relays no longer work with direct con-
sources (independent signal routing)
nected analog values but uses the digital values from the
sampled measured values data stream. • Operational safety – Danger of open CT circuits
obsolete for LPITs and reduced for conventional instru-
The merging unit is the interoperable interface between ment transformers
primary and secondary equipment for process bus solu-
The use of non-conventional transformers (LPIT) makes
tions conforming to IEC 61869 and IEC 61850-9-2. meas-
the process bus solution even more efficient.
ured values of conventional and non-conventional trans-
formers are converted into standardized, Ethernet-based • Cost saving - Reduced space and 90 % reduced weight
telegrams (SMV). of transducers
Benefits • Cost saving – One LPIT type for protection and meas-
urement in all feeders because of the wide dynamic
• Cost saving - Copper cable reduction, faster installa-
range
tion and commissioning
Efficient and flexible
• Adapts to multiple CT, VT including LPIT sensors • Up to 80 channels for Sampled Measured Values per
SIPROTEC 5 device
• Trip circuit supervision
The SIPROTEC 6MU85 merging unit as well as all modular
• Backup protection functions SIPROTEC 5 protection devices support:
• CB wear monitoring • PRP and HSR* (IEC 62439)
• Scalable number of binary inputs and outputs • Integrated web server
(expandable by a 2nd row)
• Full integration of whole substations in process bus
• Direct “high speed” tripping technology
of circuit breaker < 1ms
Siemens process bus solutions fulfill the international
• Collection of additional data (temperature, pressure, standards and create customer benefits.
tap changer positions, …)
*) in preparation
LPIT = Low Power Instrument Transformer