User's Manual: Easergy Range
User's Manual: Easergy Range
Easergy range
T200S
Automation and control unit for SM6
User's manual
Easergy T200 S Summary
2 NT00243-EN-03
Overview General description
1 General description
1.1 Introduction
Easergy T200 S is a range of autochangeover automation and telecontrol interface
dedicated to SM6 range of switchgears.
Logs
stamped chronological logging of events and measurements.
Time-stamped
This information can be transmitted to the control centre and archived in logs for
consultation and local downloading (in file form), by connection of a microcomputer.
Automatic controls
ATS (Automatic Transfer of Source): Automatic source changeover upon
voltage loss detected on one of the channels.
Note: In an RS232 link, the port is replaced by the RS232 port integral with the
COM card and accessible via the RJ45 connector on the t right of the rack.
In the case of the other transmission options, the modem is connected directly to
the front panel of the COM card.
NT00243-EN-03 3
Overview General description
Calculation formulae
T200S NSM réseau The calculation formulae are a standard
andard feature of the T200.
They can be used in the T200 to create new customized functions or applications
not requiring writing of a program in PLC language.
The functions that can be used in the formulae are:
- Mathematical functions;
- Statistical functions;
- Logical functions;
- Time/date functions;
- etc.
These formulae make it possible, more easily than with a PLC program, to create
logic equations based on combinations of variables. The types of variables that
can be used are the same as for PLC C programs (existing T200 variables or virtual
variables created specifically). This inter--equipment communication is typically
used in applications of the self-healing
healing network type.
1.2 Description
Its main parts are:
a rack gathering all electronic modules,
a grid to support the transmission equipment (radio, external modem…),
a battery providing a backup power supply when the enclosure is no longer
powered by the AC supply,
a “connection” part with:
two 9 pins plugs for connection to the switch,
T200S NSM Groupe two 4 pins plugs for the connection to the toroid sensors,
a lever type fuse holder for the AC power supply,
eventually, a terminal block to connect the emergency generator.
4 NT00243-EN-03
Overview General description
Note:: The various modules are connected via a “rack backplane card” not shown in
this diagram.
NT00243-EN-03 5
Installation Installation and connections
6 NT00243-EN-03
Installation Connecting the CPU card
The type of current input acquisition chosen can be configured for each channel via
jumpers (W2: channel 1 and W3: channel 2):
3 phases CTs : position A = I1, I2, I3
2 phases CTs + residual or 1 residual CT : position B/C = I1, I3, I0.
The Connection card integral with the CPU card permits connection to the switch, to the
digital inputs/outputs, to the current inputs (toroid sensors).
NT00243-EN-03 7
Installation Connecting the switch and CTs
Control polarity
The switches are controlled via a relay contact inside the T200 S enclosure.
Depending on the position of the fuse on the Control module, the switch motorization can
be controlled :
From the T200 internal power supply by a +V or 0V polarity.
polarity
From an external power supply.
Caution: for the T200S, the fuse must be set for a +V internal power supply.
The standard voltage of the internal power supply is 48V.
48
Marking on the 4 pin MATE N LOCK connector coming from the rack
Connector pin Marking Function
1 I1 Courant phase 1
2 I2 ou IH Courant phase 2 ou homopolaire
3 I3 Courant phase 3
4 COM Commun
8 NT00243-EN-03
Installation Other connections
Note 1: in the case of the Genset ATS automatic transfer system, the voltage present on
the genset can also be acquired via the terminal block connected to the genset (see
below). The choice of acquisition is determined by software configuration (see chapter
"Automatic control parameters").
Note 2: the "source changeover" operation also requires an automatic transfer system
(ATS) lock to be wired (see chapter "Automatic
Automatic control parameters").
parameters
Note: voltage presence on a channel controlling the genset can also be detected by a
VD23 voltage relay (see above).
2.6 CT installation
The CTs must be mounted the same side up, the cables being oriented to the bottom :
Tag HAUT/TOP up above, wire outputs down (see below).
IMPORTANT: the MV cable earthing braid must be fitted back through the CT, before
being connected to the earth. The green/yellow wire must be connected to the same
earth as the CT.
NT00243-EN-03 9
Installation Remote transmission equipments
10 NT00243-EN-03
Installation Remote transmission equipments
NT00243-EN-03 11
Installation Remote transmission equipments
Connecting to an analogue radio transceiver Connection of RS232 external modem (PSTN, radio modem,
(accessible on the RJ45 connector on the front of the internal GSM, etc.)
radio modem of the COM card) (accessible on the RJ45 8-pin
pin connector on the right of the rack)
12 NT00243-EN-03
Installation Power supply
To prevent any risk of electric shock or burns, check that the mains supply is
disconnected before carrying out any work on the enclosure.
Switch off the supply circuit by moving the central lever on the safety fuse located in the
centre to the down position. It is not necessary to remove the fuse.
Connect the main power cable “AC supply” (2 x 2.5 mm2 into the appropriate cable
gland and connect it using the shortest possible length of cable of the bottom screw
terminals on the safety fuse (phase on the right, neutral on the left).
Check that the mains connector is correctly connected under the rack.
Battery
The battery is of 12 V - 24 Ah type. It is housed in the lower left part of the enclosure.
It is held in position by a strap with tightening buckle.
Normal use
When the operations described above have been performed, the normal power supply to
the equipment is resumed and the battery can be charged.
NT00243-EN-03 13
Connection to the T200 Initialization of connection
NB: TCP/IP ports 1168, 1169 and 1170 must be accessible on the PC
for trace operation. Contact the network administrator if it is necessary to
alter the PC or network configuration to deactivate the firewall on these ports.
Configuration of the T200 is performed directly from Internet Explorer.
No other additional software is needed to access the T200 testing-
testing
maintenance configuration operations (apart from Java Runtime 1.5).
14 NT00243-EN-03
Connection to the T200 Initialization of connection
NT00243-EN-03 15
Connection to the T200 Initialization of connection
Important note: Unlike the previous USB driver, this driver is installed for all
the USB ports of the PC. This driver needs therefore be installed only once,
irrespective of the USB port used. If a different USB port is used for a future
connection, Windowss will automatically detect and install the Easergy USB
driver for this other USB port.
Note: Step 2 is therefore necessary only for the first connection to equipment
with the PC. For a future connection, go directly to step 4.
16 NT00243-EN-03
Connection to the T200 Initialization of connection
Note: It is not necessary to create this type of connection for the GPRS/3G
GPRS
link.
With Windows XP
Click on the Windows “Start” button.
Click on “Control Panel”.
Click on “Network connections”.
Click on “Create a new connection”.
Select the option “Connect to the network at my workplace”.
workplace
Select the option “Dial-up connection”.
From the list of peripherals displayed, select that corresponding to the
modem to be used for telephone connection to the T200, by checking it.
Give a name to the telephone connection
n created (e.g. “T200 remote
connection”).
Enter the phone number of the T200 to be contacted (this number may
be changed later, at each connection attempt).
Select the option “Do
Do not use my smart card”.
card
Select the option “All users”.
Check the option “Add a shortcut to this connection to my desktop”,
desktop then
on “Terminate”.
When the connection window is displayed on screen, there is no need to
give a user name and login password, and if necessary change the
phone number of the T200 to be contacted.
Click on the option “Dial number”.
The PSTN or GSM remote network connection between the PC and the
T200 is initialized between the two devices, then a modem connection
status icon is inserted in the Windows toolbar.
NT00243-EN-03 17
Connection to the T200 Initialization of connection
Note: contrary to the old USB driver, to stop the USB connection, you just
have to disconnect the USB cable. Windows will stop automatically the
current USB connection.
18 NT00243-EN-03
Connection to the T200 Initialization of connection
Note: there are useful utilities that can change automatically the TCP/IP
address of the PC. We recommend the software "Free IP Switcher" that can
be downloaded as a freeware on internet.
NT00243-EN-03 19
Connection to the T200 Initialization of connection
Note: Generally the default IP address of the T200 cannot be used on the
Ethernet ,3G or GPRS network employed, and it must therefore be replaced,
in the T200's specific IP address configuration page, with an address
acceptable for the network (see section on IP address configuration). In that
case, the only way to access the T200's IP address configuration page is to
use the USB local connection.
20 NT00243-EN-03
Connection to the T200 Initialization of connection
This access operates only when the T200 includes a GSM or PSTN (telephone)
internal modem installed on the COM card.
When an external modem is used, it is possible that this access may operate, but
that depends on the modem used.
NT00243-EN-03 21
Connection to the T200 Overview of the Web server
Home Page:
This page is displayed at connection to the T200. It enables definition of the
language to be used for displaying the pages. It also allows definition of user access
rights by user name and password.
The users and passwords that can be accessed depend on the configuration defined
in the Maintenance page and the Users sub-menu.
menu.
Home Page A wrong user or password automatically opens access in “Monitoring” mode.
A click on the "Remote" option at the top of the page makes it possible to log on to
the
e T200 Web server with a simplified display of information (without images or
logos) so as to optimize data transfer times. This mode is used automatically for slow
remote network connections (PSTN or GSM at 9.6 Kbits/s).
A click on the "Local" button at the top of the page makes it possible to log on to the
T200 Web server with a normal display (all logos and images are transferred and
displayed). This mode is used automatically for high-speed
high local area connections:
USB (115.2 Kbits/s) or Ethernet (100 Mbits/s).
Monitoring Page:
This page can be used to consult the T200 states:
TSS: State of digital inputs, T200 i
nternal faults, voltage presences, current faults, etc.
TSD: open or closed state of switch, automatic control, digital outputs
TM: measurements of currents.
Counters: number of operations.
The page is displayed by class (e.g. State of channels, System, Automatic Control,
etc.).
Monitoring Page Each class covers a category of information so as to facilitate viewing on screen.
The states of the indications or measurements are refreshed every 3 seconds
automatically.
The presentation, quantity of data displayed and content of this page may vary from
one application to another.
Control Page
This page allows local control orders to be sent from the PC to:
The switches (change of position by CO/CF);
The operation and counters (counter initialization);
The automatic controls (switching ON/OFF);
The digital outputs (forced setting open or closed);
The fault detector (fault memory resetting).
The T200 must be in "Remote" mode to be able to send control orders.
The control orders on the TSDs make it possible to go to the state complementing
that displayed by the T200.
The control orders on the counters enable them to be initialized at a value
valu predefined
by the user.
For safety reasons, each control order must be confirmed by the user.
The state of a control order in progress is displayed in orange (default colour).
Control Page
22 NT00243-EN-03
Connection to the T200 Overview of the Web server
Diagnostic Pages:
These pages allow consultation of the logs recorded in real time by the T200. The
event time stamping is 1 ms.
Each log allows consultation of the history of states occurring on the T200 with a
Drop-down list – Diagnostic page description of the states.
All the information present in the logs is time-and
and-date stamped by the T200's
internal clock.
The logs are as follows:
A box associated with each alarm is checked when the control centre has
acknowledged this alarm.
For all the logs, when the storage capacity is reached, the most recent event
occurring erases the oldest
st event on the list.
An "Empty log" button in each log can be used to empty their content, i.e. to erase
all the information saved previously.
NT00243-EN-03 23
Connection to the T200 Overview of the Web server
Maintenance Pages:
Several pages can facilitate maintenance of the T200, by giving information or
allowing configuration of the T200 application:
1. General information: Specific sub-pages
pages provide information concerning the
T200 application, namely:
- Substation page: information concerning the current application (version No.
of the application and fault detector, date and time of last configuration, name
na
of substation, etc.).
- Software page: information concerning the software used by the T200
(version, date and time of compilation, size and CRC32).
The T200 is capable of storing two different software versions in memory. It
is possible to switch from one software version to another simply by selection
(if two versions are available).
Drop-down list – Maintenance page It is also possible to load a new software version from a file available on the
PC or from a floppy disk or CD-ROM.
ATTENTION : The loading process manages only the file format f with .zip
extension. The software must therefore not be unzipped before loading it on
the T200 (file with .mem extension not managed).
Note: When loading a software on the T200, one in fact loads the protocol
used for remote transmission but also all the equipment operating options,
including some that are managed and displayed by the Web server if
configured and/or detected physically on the COM card, namely:
- The Modbus master function
- The function of synchronization by GPS
- The digital input counting function.
- Clock page: Allows the T200 date and time to be configured manually or
automatically from the time on the PC.
A click on the "Update" button causes the manual change of date and time to
be accepted.
A click on the "Synchronization" button allows the PC date and time to be
taken into account automatically for configuration on the T200.
Comment: This configuration is possible only if synchronization by SNTP
server or by GPS module is not installed in the T200.
Substation information – Maintenance page
- IP parameters page: Allows consultation
ltation or where applicable configuration
of the Ethernet and USB interface parameters (IP addresses, sub-network
sub
masks, etc.).
When a GPRS or 3G modem is installed on the COM card, this page also
allows consultation of the IP addresses assigned automatically
automatica by the
GPRS/3G server.
NB: It is dangerous to modify the Ethernet IP parameters, with a risk of no
longer being able to access the T200. Call on competent authorities to
modify these parameters.
- IP server ports page: allows redefinition of the port numbers
num used by the
T200 for COM card access, in the event that the transmission network does
not accept the default numbers (e.g. restriction on certain GPRS operators).
By default, the following port Nos. are configured on the T200:
HTTP server port = 80
Telnet server port = 23
Port 1,2 and TCP/IP trace server port = 1168,
1168 1169 and 1170
TCP/IP port trace server port = 1170
This page is optional depending on the embedded software in the T200 (e.g.
present page for software including GPRS transmission).
NB: If the HTTP port number is changed in this page, to be able to log
on to the T200 Web server again, it is essential to add the port number
Port trace – Maintenance page at the end of the T200's IP address preceded by a colon
(e.g. 10.207.154.239:1500 for a T200 access on port 1500).
1500)
- User page: Allows creation, modification or deletion of users and
management of rights (login, password, access rights).
2. Port 1 & 2 & TCP/IP & Modbus Master traces: The "Port 1, 2 and TCP/IP
traces" pages allow viewing, for each available port, of communication
commun
exchanges between the control centre and the T200.
The "Modbus Master trace" page allows viewing of exchanges between the
T200 and the Modbus slaves of the substation (see additional manual
NT00121-xx).
This trace is displayed on screen in decoded form to facilitate reading of the
frame's content:
Column 1: frame time-and-date date stamping (in
hour:minute:second.thousandth of second format).
Column 2: direction of dialogue, RTU ->
- PC or PC -> RTU, with
associated
iated address Nos of the PC and RTU.
Column 3: hexadecimal frame + brief description of the content of the
frame.
24 NT00243-EN-03
Connection to the T200 Overview of the Web server
3. Configuration:
- Save/Restore page: Allows all the current T200 configuration parameters to
be saved to a file.
It is also possible to load from a file available on your PC or from a floppy disk or CD-
CD
ROM the T200 configuration parameters coming from a preceding backup or coming
This file can be used to configure one or more other substations in the same
Drop-down list – Settings page way without being
ing obliged to reconfigure all the parameters one by one.
Note: During loading from a file, the data integrity is verified automatically so as
to ensure the compatibility of application versions.
Settings Pages
Configuration of the T200 is performed from pages grouped together in several
different categories:
1. Communication: Several pages allow you to configure the specific
communication parameters of the T200:
- Operation Mode page: For each communication port available on the T200,
it is possible to determine:
The protocol available;
The type of transmission medium to be used (Radio, PSTN, GSM, etc.);
The way in which the ports will be managed according to one of the
available modes:
Not used
Normal
Balanced – Normal/Backup
Protocol parameters – Settings page Main – Normal/Backup
Backup – Normal/Backup
Store & forward
- Protocol + TCP/IP Protocol pages: These pages are used to configure the
parameters specific to the protocol used:
Max. number of send operations
Collision avoidance system;
Configuration of link addresses;
Frame size;
etc.
Note: Each type of protocol has its specific configuration page. For more
details, refer to the specific user manual for the protocol installed on the
T200.
2. Control Module No. x: Some parameters of the T200 are managed for each
Control module of the T200.
Two pages allow this configuration:
- Control and Automation page: This page can be used to configure the
parameters related to electrical control of the switch and automation
management:
Type of switch (Standard, PM6, CI2 or other);
Change-of-position
position waiting time;
Type of automatic control;
Etc.
NT00243-EN-03 25
Connection to the T200 Overview of the Web server
26 NT00243-EN-03
Commissioning T200 settings
4 T200 settings
This chapter aims to provide the user with all the information needed to be able to
perform configuration of the T200 data.
Comment area
Configuration of SNTP service
Configuration of Ethernet interfaces
Backup/Restoral of configuration parameters
Configuration of communication with the Supervisor
Configuration of switch controls
Configuration of the various options
Automatic control configuration
Configuration of the fault detection module
T200 variable configuration
Class configuration
NT00243-EN-03 27
Commissioning Comment area
28 NT00243-EN-03
Commissioning SNTP service setting
The T200 incorporates an SNTP client. It allows the time on the internal clock of the T200
to be set automatically from a network synchronization server, when T200 is connected to
this network.
Comment: When the SNTP option tion is configured, it overrides manual synchronization of
the T200 time and date. It is then no longer possible to configure the PC time and date
manually.
Operating principle
The T200 includes the capability for defining 2 different SNTP servers, one main server
and one auxiliary server, each being on different networks.
When the "Polling period"" time delay configured has expired, the T200 sends a request to
the main SNTP server.
If the T200 receives a synchronization from the
he main SNTP server, the time on the latter is
set and the synchronization cycle is completed.
If the T200 obtains no response from the main SNTP server after the end of delay "Max.
"
server response time"" has elapsed, the T200 attempts a new connection again.
agai
If the "Number of reconnection attempts"" is reached, the T200 tries to become
synchronized with the auxiliary SNTP server.
The cycle ends once the T200U has been synchronized with the second server or when it
reaches the "Number of reconnection attempts".
Configuration parameters:
• SNTP server and auxiliary SNTP server: IP address of the main and auxiliary
SNTP servers.
Note:: When the address is set to "0.0.0.0", the synchronization by SNTP function is
deactivated on the server.
• Synchronization period: Allows the time synchronization period to be defined via
the SNTP server. Configurable from 1 to 300 seconds.
• Number of reconnection attempts: Upon failure of synchronization with the server,
max. number of attempts to be made.
• Last SNTP synchronization:: Indication of the time and date of the last SNTP
synchronization performed (consultation exclusively).
• SNTP server gateway and auxiliary SNTP gateway:gateway Address of the gateway for
access to the main and auxiliary SNTP servers.
• Max. server response time: Maximum time waiting for the reply from the SNTP
server before making a further attempt at synchronization.
• Period of validity of the clock: Time after which the T200 must be resynchronized
with the SNTP server.
NT00243-EN-03 29
Commissioning Ethernet interface setting
The three IP addresses use the same network physical interface (single Ethernet port on
GPRS the COM card). For this reason, the two additional IP addresses added to that included as
1 Ethernet interface
10.y.y.y standard in the "Ethernet Interface" part are called virtual Ethernet interfaces 1 and 2.
2 virtual IP address
Supervisor 2 Note : The GPRS or 3G port is not is not affected by these virtual addresses.
addresses
Interface Ethernet :
• MAC address:: Unique identification address for each T200, set in factory.
(Consultation exclusively)
• DHCP:: Defines whether the router of the Ethernet local area network can allocate a
new IP address to the T200 automatically upon a new connection. It is recommended
not to activate this function or else you could no longer be able to log on to the T200
if the modified address is not known.
• IP address:: Base IP address of the T200 (as standard: 172.16.0.5).
• Sub-network mask:: The mask defines the possibility of configuration
configura of the IP
address on the Ethernet network. For each IP address field, (0) means authorization
of 255 values and (255) means fixed value for this field.
(As standard: 255.255.255.0)
• Gateway addresses:: IP address of the server's Ethernet gateway. The gatewayga
centralizes all the network IP accesses (as standard: 172.16.0.1).
• Primary DNS server:: IP address of the primary DNS server (Domain Name Server).
The DNS enables the IP addresses to be associated with the website names (as
standard: 172.16.0.1).
• Secondary DNS server:: IP address of the secondary DNS server (Domain Name
Server). Backup DNS server (as standard: 0.0.0.0).
USB interface:
• Server IP address:: IP address of the T200's embedded Web server for USB access.
Unmodifiable (as standard: 212.1.1.10).
• Client IP address:: IP address assigned to the PC connected via USB to the
embedded Web server. Unmodifiable. (As standard: 212.1.1.11).
21
30 NT00243-EN-03
Commissioning Save/restore configuration
The T200 can save in file form all the configurable parameters of the equipment
(except the parameters of the "IP parameters"" page which remain specific to each
equipment item).
This file can then be used for downloading to other equipment of the same type,
thus enabling the T200 to be configured automatically without needing to redo the
entire configuration manually, which would be rather onerous.
However, the parameters specific to each T200 must then be personalized (e.g.
(e
protocol address, fault detection thresholds, etc.).
The "Maintenance/Backup-Restoral"" page provides access to backup/restoral
resources.
NT00243-EN-03 31
Commissioning Communication configuration
The parameters present in the configuration pages for ports 1 and 2 take into
account
unt the type of medium that has been selected, because each type of medium
has specific configuration parameters.
The configuration page for protocol parameters may take also into account certain
parameters related to the type of medium selected.
Comment: The protocol parameters related to the type of medium will be described
in this chapter. The other parameters related to the protocol will not be described in
detail, however. For more information concerning the latter, refer to the User's
Manual for the protocol.
Objective of this page:: Activate the transmission ports and select the type of modem
to be used and how it will be managed (up to two communication ports available).
The parameters for this page can be consulted and/or modified depending on
the user profile.
Mode: Allows choice (or merely gives an indication depending on the protocol)
of the transmission mode used for dialogue with
th the SCADA system.
Depending on the protocol used, there is a choice between one of the two
modes mentioned below. Some protocols are fixed from the transmission
mode viewpoint and do not allow this choice.
In that case, the T200 proposes merely an indication,
cation, with no possibility of
modification:
32 NT00243-EN-03
Commissioning Communication configuration
Link: Allows definition of the way in which the ports will be managed according
to one of the following modes:
Note: Depending on the protocol, all the operating modes of the ports
mentioned above are not necessarily available.
NT00243-EN-03 33
Commissioning Communication configuration
When the "Normal/Standby" mode is configured as link type on ports 1 and 2, the
"Quality of transmission parameters" section becomes
become accessible in the "Operating
modes" page and the corresponding parameters can be configured.
This mode requires the use of two communication channels (ports 1 and 2) to
Excerpted from the page: "Configuration/Operating operate.
modes"
Two operating modes are possible:
- Balanced mode: No criterion of priority of one channel over the other in this
mode. So long as communication functions on the channel in service, it stays on
that channel. Upon detecting loss of communication on the channel in service, it is
switched over to the other channel. Both channels
nels must be declared as "Balanced".
Diagnostic:
For each port, the T200 gives information concerning the number of valid frames
sent and received and a quality percentage relative to the number of frames
handled.
34 NT00243-EN-03
Commissioning Communication configuration
The Store & Forward function allows a T200 to serve as a radio relay for another
distant T200 which cannot be accessed directly by the Supervisor due to access
problems. The Distant T200 must be within transmission range
ra of the first T200
acting as relay (Repeater T200).
Upon detecting a message which is not addressed to it, the Repeater T200 resends
Excerpted from the page: "Configuration/Operating it over the same channel so as to reroute it toward the T200 for which the message
modes" is destined.
Three types of T200 can be managed in the "Store & Forward" mode:
- Standard T200:: This is a conventional T200. It can communicate directly with the
control centre without going the through Repeater T200. This T200 must be
configured with "Normal" link type.
Repeater T200 - Repeater T200: This will act as relay for other T200s which cannot communicate
directly with the Supervisor. This T200 must be configured with "Store & Forward"
link type.
- Distant T200:: This is a distant T200 which cannot communicate directly with the
Supervisor Distant T200 Supervisor and which
hich will use the Repeater T200 as communication gateway to be
able to communicate with the Supervisor.
Obstacle This T200 must be configured with "Normal" link type.
Specifications
The Repeater T200 uses the same port (and hence the same radio) to
communicate with the Supervisor and with the Distant T200s.
Scada end link address:: This is the address that will have to be defined at the
Supervisor end to access
ess the Distant T200. This address must be configured
identically in the Repeater T200. This address is used only for the Supervisor-
Supervisor
Repeater T200 connection.
Distant T200 end link address:: This is the address that will have to be
configured on the Distant
ant T200 and also identically in the Repeater T200. This
address is used only for the Repeater T200-Distant
Distant T200 connection.
The Repeater T200 has its specific link address so that the latter may be used as
a mere Standard T200 in addition to the Repeater function.
NT00243-EN-03 35
Commissioning Communication configuration
Operation
When the Supervisor wants to communicateicate with one of the Distant T200s, the
latter sends a protocol frame containing the link address of the Distant T200 to be
accessed.
The Repeater T200 receives this frame and sees that the address was not destined
for it but that it corresponds to the address
ddress of one of the Distant T200s defined in its
list of 10 Distant terminals.
Supervisor Repeater T200 Distant T200
Address A Address B The Repeater T200 sends back a frame to the corresponding Distant T200,
replacing the link address with that which has been defined for it in its list for this
Address A Address B Distant T200.
The Distant T200 receives the frame and replies to the request with a frame
containing the link address that is specific to it.
Substitution principe of adresses link :
In blue color : message including address used by the The Repeater T200 receives the reply and sends a frame back to the Supervisor
Supervisor for accessing Distant T200 (e.g. : address A) according to the same principle of replacement of the link address between that
In red color : : message including address used by the used by the Distant T200 and that used by the Supervisor.
Repeater for accessing Distant T200 (e.g. : address A)
Note: When a Master/Master type link is used, the Distant T200 can initiate
communication to send an alarm. The transmission principle remains the same.
2°) The Repeater function of the T200 uses only a s ingle transmission port. Radio
traffic over this channel is therefore fairly substantial due to the numerous
messages to be re-transmitted
transmitted at the Distant T200 end and the Supervisor end.
Message collisions and repetitions must therefore be expected on the radio traffic.
3°) The handling of messages received by the Repeater T200 is treated as a whole.
The Repeater T200 will end retransmission of the message to be handled to the
Supervisor and the Distant T200 before being able to receive and handle other
messages. This constraint may result in repetition phenomena on devices other
than the Repeater T200.
4°) It should be borne in mind that if a Repeater T 200 can no longer transmit for
whatsoever reason, all the Distant T200s will be affected by this non-
non
communication.
5°) The qu ality of the radio link largely depends on the efficiency of the collision
avoidance function. This function gives good results if the information giving the
busy state of the wireless network is reliable. Now, because the Distant T200s can
pick up frames sent by other T200s, the occupancy state of the wireless network
may be not as efficient as normally. The functioning of the Repeater system may be
degraded for this reason.
36 NT00243-EN-03
Commissioning Communication configuration
Refer to the protocol User Manual for details concerning configuration of the
parameters of this page.
Note that certain parameters of this page depend on the type of modems installed
on the ports.
For example, the "Collision Avoidance Parameters"" section (see image below) is
displayed in this page only when a Radio or PSTN modem (internal or external) is
configured on the COM card.
NT00243-EN-03 37
Commissioning Communication configuration
The parameters display for this page depends on the type of modem installed on
the port of the COM card (port 1 or port 2) and on the transmission medium chosen
in the "Settings/Operating Mode" page.
Configuration procedure:
The T200 is factory-delivered
delivered with a default configuration corresponding to the type
of modem installed on the COM card (internal modem) or on the sliding plate of the
enclosure (external modem).
The user should then (if need be) adjust the parameters of this page (in particular
the modem management signals and associated time delays) depending
dependi on what is
required for the modems used or possibly the transmission network.
The following timing diagram shows the management signals involved during
communication between the T200 modem and the interface or the external radio, or
even directly with the control centre.
DSR
CD
Received frame
DTR
or
Send Cd
RTS
CTS
Sent frame
Squelch
CD (Carrier Detect):
This signal, when it exists, is used to confirm receipt of the received frame. It can
also be used to learn the transmission networkork occupancy.
38 NT00243-EN-03
Commissioning Communication configuration
Squelch: This signal is used only in radio mode to indicate to the T200 the occupancy
state of the radio network.
We give below the list of configurable options concerning these modem management
signals. Configuration is performed in the pages for ports 1 and 2 of the T200 Web
W
server:
• Delay before response:: After receiving a message, this is the waiting time before
sending the message (response). This delay serves to avoid any overlapping of
signals between the message received and the message sent.
This delay is often used with a radio medium or with certain modems which
require a time lag to turn around, i.e. a minimum time to go from receive mode to
send mode.
♦ DTR management: If this option is selected, the DTR signal will be managed
during transmission exchanges with the modem.
• DTR - RTS delay (if RTS used):
♦ RTS management: If this option is selected, the RTS signal will be managed
during transmission exchanges with the modem.
♦ CTS management If this option is selected, the CTS signal will be managed
during transmission exchanges with the modem.
♦ RTS - CTS delay (if CTS used): This is the maximum time during which the T200
waits for the CTS after the RTS has been activated. If, after this delay,
delay CTS has
not become active, the T200 discontinues sending the frame.
• RTS (or CTS) delay - Message (if RTS or CTS used): This is the time between
transition to the active state of RTS (or CTS if this signal is used) and the start of
message sending. Typically lly this time lag is used to wait for a stable carrier period
established by the modem.
If necessary, when CTS is not available, the time for installation of the carrier to
solve the problem posed by the non-availability
availability of this signal can be added to this
delay. Likewise, if the DTR and RTS commands are common, the time for rise in
power of the sender can be added.
NT00243-EN-03 39
Commissioning Communication configuration
♦ Message - RTS delay (if RTS used):: This is the minimum time to be waited, after
sending a message, before causing RTS and DTR (or Send command) to fall
again. This delay prevents the end of the message from being truncated by the
premature fall of modem sending.
40 NT00243-EN-03
Commissioning Communication configuration
♦ Dialing type: Choice of the type of dialling to be used for the telephone call
to the Supervisor during an alarm sequence.
There are two possible choices: pulse (decimal) and multifrequency (MF).
Note: Configuration available in PSTN but not in GSM.
♦ Modem Init: The Modem Init sequence is necessary to configure the modem
for operation linked to the T200 application.
The defaultt Init sequence corresponds to the AT commands necessary for
an internal modem (modem installed on the COM card). For an external
modem, the Modem Init sequence is not defined in the configuration
supplied. It is up to the user to define it according to the
th brand and model
used (refer to the modem manual).
Note: Configuration available in PSTN but not in GSM.
NB: The Modem Init sequence is sent to the modem only after initialization of
the T200 COM card (following a reset or power up of the T200). After
changing
anging the Init sequence, you must remember to reinitialize the COM card
for it to be taken into account by the modem.
♦ Called communication delay: Maximum delay dela for connection between the
T200 and the Supervisor following a call by the Supervisor before release of
the PSTN line by the T200.
♦ Host tel number (main): Main phone number that the T200 uses to call the
Supervisor during an alarm sequence.
The T200 will try to call three times on this "normal" number before switching
to the "Backup" number.
Note: A space must be inserted between the "T" or "P" and the call number.
NT00243-EN-03 41
Commissioning Communication configuration
08:48:34.474 MODEM - Power up ♦ PIN Number: Configuration of the SIM card PIN code on four figures.
08:48:35.986 MODEM - Command mode
08:48:36.994 MODEM - Tx : ATE0 NB: After three validations of the page configuration or three modem
08:48:39.518 MODEM - Tx : AT&S0 initializations with an incorrect PIN code, the SIM card is blocked. The only
08:48:42.045 MODEM - Tx : AT solution in this case is to call the operator who will
w be able to unblock it.
08:48:43.071 MODEM - Rx : OK
08:48:44.079 MODEM - Tx : AT+CPIN? The first time that the T200 initializes the GSM modem, the latter asks the
08:48:45.120 MODEM - Rx : +CPIN: SIM PIN modem if it needs the PIN code.
08:48:45.120 MODEM - Tx : AT+CPIN=**** If the modem replies in the negative, the T200 will not manage the PIN code
08:48:47.230 MODEM - Rx : OK and the latter will not need to be entered byy the user.
08:48:47.230 MODEM - Tx : AT+CLCK="SC",0,**** On the other hand, if the modem replies that it needs the PIN code, the T200
08:48:49.770 MODEM - Tx : AT+CREG? will manage this parameter and the PIN code must therefore be configured.
08:48:50.807 MODEM - Rx : +CREG: 0,1 Once the PIN code has been initialized a first time, the T200 asks the
08:48:50.807 MODEM - Tx : AT+CSCA=0689004000 modem to deactivate use of the PIN code.
08:48:54.818 MODEM - Tx : AT+CMCF=1 The latter will therefore no longer be used by either the T200 or the GSM
08:48:57.347 MODEM - Tx : AT+CSAS modem.
08:48:59.875 MODEM - Tx : AT+CMEE=0
08:49:02.403 MODEM - Tx : AT&C1 ♦ SMS service centre tel number: This is the number of the service centre of
08:49:04.929 MODEM - Tx : AT&D2 the GSM operator which centralizes and stores all the SMS messages sent
08:49:07.455 MODEM - Tx : AT+IPR=0 to reroute them to the end user.
08:49:09.983 MODEM - Tx : ATS0=1 Contact the operator to know this number. It is also possible to find out this
08:49:12.509 MODEM - Tx : AT+WIND=0 number from a GSM telephone using the same operator as that used by the
08:49:15.039 MODEM - Tx : AT+CICB=0 SIM card of the T200, because the number can be looked up in the
08:49:17.567 MODEM - Tx : AT+CBST=7,0,1 telephone's configuration parameters.
08:49:20.101 MODEM - Tx : AT&W Finally, it is also possible to find out this number in the port trace following
08:49:20.101 MODEM - Modem GSM initialized connection of the modem to the GSM network. The number is displayed on
the line including the "AT+CSCA" command (see enclosed example:
Example of port trace during an attempt to connect number=0689004000).
to the GSM network (Modem Init)
♦ SMS user tel number: SMS number that the T200 uses in the event of an
alarm sequence to send the text message to the user who is
i on standby
11:38:37.093 SlaveAddr = 03 <<<<< Reading N output words duty.
Addr = 0x34
03 03 00 34 00 03 45 E7
Same comment as for the "Normal" telephone number concerning the codes
11:38:37.113 SlaveAddr = 03 >>>>> Reading N output words to be used for the telephone number.
03 03 06 A9 AA AA A9 55 00
F6 9C
11:38:37.357 SlaveAddr = 04 <<<<< Reading N output words GSM modem connection status:
Addr = 0x0
04 03 00 00 00 01 84 5F To check the connection status of the GSM modem, there are several
11:38:37.593 SlaveAddr = 04 <<<<< Reading N output words possibilities:
Addr = 0xf
04 03 00 0F 00 21 B5 84 By flashing of the e indicator lamp on the front of the GSM modem:
- The indicator lamp is lit steadily:: the modem is not connected to the
Example of exchange frames during connection GSM network.
established with the Supervisor (in Modbus - The indicator lamp flashes slowly (every 2.5 seconds): the modem
protocol) is connected to the network but there is no remote link.
- The indicator lamp flashes rapidly (every second): the modem is
Yellow status connected to the network and a remote link is established.
indicator of
connection to the By consulting the AT commands for modem initialization in the port
GSM network trace corresponding to the GSM modem: To the "AT+CREG"
" command
requested by the T200, the modem should reply "+CREG:
" 0.1" when
the modem is connected to the network or "+CREG:
" 0.2" if it is not (see
example opposite).
Moreover, when the remote link is established between the T200 and
the Supervisor, the port trace also
lso displays protocol frame exchanges
between the T200 and the Supervisor.
Indications on the front panel of the GSM modem
for the COM card
42 NT00243-EN-03
Commissioning Communication configuration
The SMS messages sent contain the following information: Possible values for GSM signal :
• Identification of the substation: - Reception GSM not detectable : level = 99
- equipment type (F200) - Reception GSM not sufficient : level = 0 à 10
- slave address in Modbus, link address in IEC, etc. - Reception GSM correctly detected : level = 11 à 31
- name of substation (configurable)
• Identification of the variable:
- variable name (configurable)
- variable state (configurable text associated with state 0 or
1 for digital, value + unity for analogue)
- change of state time
♦ Line type: Configuration of the type of LL line installed between the T200
and the Supervisor.
There are two possible configurations: two--wire or four-wire.
NT00243-EN-03 43
Commissioning Communication configuration
♦ Polarization: Activates line polarization at the T200 end. The RS485 line
should be polarized at one termination, generally at the Master end.
♦ End-of-line resistance: Activates the load résistance at the T200 end. The
RS485 line should be loaded at both its terminations.
♦ Line type: Choice of type of transmission used: 2-wire
2 or 4-wire.
The
he only way to know the IP address of the T200 in this case is to log on locally
(on site) to the embedded Web server of the T200 via an USB access, which is
hardly possible because that would imply going to the site for each enclosure
each time an IP address is reassigned.
Example: "HTTP server" port N°80 is not open for the operato r
"Orange". A port number greater than 1024 should be configured on the
T200 to have an open port from this operator.
44 NT00243-EN-03
Commissioning Communication configuration
♦ Access Point Name (APN): Access Point Name. Name of the access point for
connection to the GPRS/3G network. This name is generally given by the operator
who provides access to the GPRS/3G network.
(e.g. "internet-entreprise"
entreprise" for the operator Orange).
♦ Specific ping IP address: The ping in theory makes it possible to verify and
measure the quality of the equipment's
pment's connection with another device connected
to the IP network.
This configurable parameter can determine to what IP address will be sent the
packet corresponding to the ping allowing this quality to be measured.
Configure, for example, a known Web server ver IP address or possibly that of the
supervisor, provided that the latter incorporate a known fixed IP address.
The configured address must correspond to a standard IP address format, i.e. be
in the form of four values of at most three digits separated by
b a dot (e.g.
192.168.2.101).
NT00243-EN-03 45
Commissioning Communication configuration
To avoid this drawback, the regular ping test is used to prevent disconnection of
the T200 when the problem is exclusively due to the Supervisor and not to a
network problem. In other words, if the T200 is still connected to the GPRS/3G
network, there is no
o reason to disconnect it because of a non-existent
non IP protocol
flow.
As soon as a ping address has been configured in this field, the T200 will try
every 4 minutes (“Ping time interval”)
”) to send a ping to the specified IP address.
Accordingly, an IP data flow will return to the T200 and the latter will not cut off the
connection to the network.
If the result of the ping test is satisfactory, the T200 will remain connected to the
network, because it knows that it is available. The T200 will then do nothing
nothin in
particular except for the next ping test following the next 4 minutes elapsed.
If the result of the ping test is unsatisfactory, after an extra minute the T200,
seeing no IP data flow for the last 5 min., will disconnect from the network
automaticallyy (modem reset), and then try (after the end of modem initialization) to
reconnect to the network again.
If the network is still not available, the T200 will again request the modem to
reinitialize immediately, and this indefinitely until the next detection
detecti of the network.
This phase of initialization and reconnection to the network requires approximately
1 min. for the GPRS/3G modem (see enclosed diagram).
If the ping address is set to "0.0.0.0" (default value), the regular ping test is
deactivated.
Comment: The regular ping test method is preferable to the "Daily disconnection"
method because, for the regular ping test, network disconnection lasts only 5 min.
at most during a brief failure (case of network disconnection just after the ping
test).
Note: The regular (or manual) ping test sends to the specified IP address the
smallest possible number of data packets (equivalent to 0 byte), to avoid causing
the extra cost of an IP data flow transfer.
Problem on
GPRS network
Yes
GPRS network
T200 power up
availability No
1
GPRS modem
reset 0
T200 Yes TA TA TA TA
TC
connection to
the GPRS No Test Test Test
ok failed ok
1 TB TB TB
Automatic ping
test 0
Supervisor T200 stays
protocol connected
frames
Supervisor
inoperative
♦ Test Ping: Allows manually activation of the ping test. A click on this button starts
a manual ping test. This manual test is generally used to verify T200 connection
to the GPRS/3G network immediately.
The T200 then displays the result of the test in a specific window (see enclosed
windows).
There are two possible results following this test: "Ping
" Ok" or "Ping failed"
46 NT00243-EN-03
Commissioning Communication configuration
08:48:34.474 MODEM - Power up ♦ Ping time interval: Delay between two successive automatic “Test ping”.
08:48:35.986 MODEM - Command mode
08:48:36.994 MODEM - Tx : ATE0
08:48:39.518 MODEM - Tx : AT&S0 ♦ Ping attempts: Number of maximum attempts for the “Test ping” process in
08:48:42.045 MODEM - Tx : AT case of no response from remote IP address.
08:48:43.071 MODEM - Rx : OK
08:48:44.079 MODEM - Tx : AT+CPIN? ♦ Ping time out: Maximum delay to wait for the response during the “Test
08:48:45.120 MODEM - Rx : +CPIN: SIM PIN ping” to define “Ping error”.
08:48:45.120 MODEM - Tx : AT+CPIN=****
08:48:47.230 MODEM - Rx : OK
08:48:47.230 MODEM - Tx : AT+CLCK="SC",0,**** ♦ Authentication: When the GPRS/3G network requires authentication during
08:48:49.770 MODEM - Tx : AT+CREG? the connection phase, it is possible in such cases to activate this function by
08:48:50.807 MODEM - Rx : +CREG: 0,1 checking the corresponding box.
08:48:50.807 MODEM - Tx : AT+CSCA=0689004000 The authorized encryption protocols are:
08:48:54.818 MODEM - Tx : AT+CMCF=1 - PAP, CHAP, MSCHAP, MSCHAP V2
08:48:57.347 MODEM - Tx : AT+CSAS
08:48:59.875 MODEM - Tx : AT+CMEE=0
08:49:02.403 MODEM - Tx : AT&C1 ♦ Login: Configuration of the e login used for authentication. Configure this field
08:49:04.929 MODEM - Tx : AT&D2 only if the "Authentication"" option has been checked.
08:49:07.455 MODEM - Tx : AT+IPR=0
08:49:09.983 MODEM - Tx : ATS0=1 ♦ Password: Configuration of the password used for authentication. Configure
08:49:12.509 MODEM - Tx : AT+WIND=0 this field only if the "Authentication"" option has been checked.
08:49:15.039 MODEM - Tx : AT+CICB=0
08:49:17.567 MODEM - Tx : AT+CBST=7,0,1
Note: To check that the modem is correctly connected to the GPRS/3G
08:49:20.101 MODEM - Tx : AT&W
08:49:32.706 MODEM - Tx : AT+CGCLASS? network, it is possible to consult the trace of the port corresponding to the
08:49:33.720 MODEM - Rx : +CGCLASS: "B" GPRS/3G modem. The modem starts by initializing the GSM connection and
08:49:33.720 MODEM - Tx : AT+CGDCONT=1,"IP","internet-
AT+CGDCONT=1,"IP","internet then the GPRS/3G connection. Accordingly, following
fol the AT commands for
company" connection to the GSM network can be found the commands relating to
08:49:36.248 MODEM - Tx : AT+CGATT=1 GPRS/3G connection. At the end of them, the trace should indicate
08:49:38.769 MODEM - Tx : AT+CGREG? "GPRS/3G modem initialized" with also the indication of the IP addresses of
08:49:39.784 MODEM - Rx : +CGREG: 0,1
08:49:39.784 MODEM - Tx : AT+CGACT=1,1
the T200 assigned by the operator (local=xxx.xxx.xxx.xxx) and the IP address
08:49:42.307 MODEM - Tx : ATD*99***1# of the GPRS/3G gateway provider (dest=xxx.xxx.xxx.xxx) (see example
08:49:43.327 MODEM - Connection opposite).
08:49:44.335 MODEM - PPP link: UP -> > ESTABLISH ()
08:49:44.350 MODEM - PPP link: OPEN -> AUTH ()
08:49:44.363 MODEM - PPP link: PAP: Local successfully
authenticated
Modem connection status:
08:49:44.363 MODEM - PPP link: SUCCESS -> > NETWORK () Same comment as for the GSM modem.
08:49:44.363 MODEM - PPP link: IPCP UP -> > NETWORK ()
08:49:44.400 MODEM - PPP link: IPCP CONFIGURED ->
NETWORK ()
08:49:44.401 MODEM - PPP link: connected, Connection speeds in TCP/IP communication
local=90.95.65.78, dest=212.234.96.90 Depending on the connection type, the T200/Scada link can be implemented at
08:49:44.401 MODEM - GPRS modem initialized different speeds. This is a maximum connection speed. They depend on many
factors such as the network's availability, the received signal level or the location
Example of port trace in the event of a connection of the receiver:
to the GPRS network
• GPRS:
PRS: max. bit rate = 19.2 Kbits/s (in practice)
• EDGE: max. bit rate = 64 Kbits/s (in theory)
• 3G: max. bit rate = 2 Mbits/s (in theory), 115 Kbits/s (in practice)
NT00243-EN-03 47
Commissioning Configuration of switch controls
Remote configuration:
The @ sign alongside each parameter of "Control &automation"
&automation page and
"Measurement and fault indicator" page allows to configure an external address.
This external address can be used by the SCADA, to configure or define remotely a
new value for the parameter associated, via the communication and the protocol. To
set the parameter, an analogue value can be written to this
th address.
► Type of control:
There are four possible options: Standard, PM6, CI2, Other
Active
Filteringprinciple for indication inputs related to remote
controls:
Inactive
The interface between the T200 and the switch includes two electric signals for
Non-complementary switch positions
motorization control (CO: Opening control / CF: closing control) and two signals for
Open position
the current switch position (O: open position / F: closed position).
Active
The T200 systematically performs a consistency check on the positions read: it is in
theory impossible to have the "open" and "closed" signals simultaneously or neither
Inactive
of the two signals at the same time, but this may occur following a system
malfunction. This is complementary of the switch states is verified cyclically for
TSD updating the states of the associated TSD variables.
In the case of non-complementary
complementary values, filtering is applied and the old TSD value
Undefined is kept during a configurable time delay (see No complementary
compl filtered time
parameter). If the non-complementary
complementary persists after the time delay, this is probably
Closed due to a fault relating to the signals delivered by the switch and the "undefined"
state is finally indicated in the TSD associated with the position.
Open
Non-complementarity Non-complementarity
filtering time delay not filtering time delay
elapsed elapsed
48 NT00243-EN-03
Commissioning Configuration of switch controls
Reminder: The "Standard" configuration applies to the main switches used with the
T200 I application such as SM6 or RM6. Not applicable for T200S on which "CI2"
configuration is required.
After the control relay has fallen, the order is considered as completed by the T200
when the switch indicates a position in conformity with the order (the TSD is
updated with the new status). The order is considered in error (e.g. external error) if
the position is not in conformity with the requested order or if undefined after a loss
of position filtering time delay (Return
Return position waiting time).
Closing control
Active
Inactive
TCD Switch state Order sending TCD Switch state Order sending
Opening control CR: order in progress CR: order in progress
Active
Inactive
Closed
Open
NT00243-EN-03 49
Commissioning Configuration of switch controls
With this type of switch, the principle is to apply the motor control signal until the
requested position is obtained. This control will be maintained only during a
configurable limited period (Return
Return position waiting time parameter), and this in
the event that the position indicated by the TSD variable is not that which is
expected by the T200 (case of degraded control).
With this type of switch, the time for execution of the electrical order therefore
depends exclusively on the time taken by the switch to change position.
The Open and Closed switch statuses are read constantly with a consistency check chec
so as to update the associated position TSD variable (see Filtering principle for
indication inputs related to remote controls).
Important remark : In this mode, the open and close control command to the
switchgear are send to the same signal, ie open command signal ("OC").
TCD Switch state Order sending TCD Switch state Order sending
CO/CF control CR: order in progress CR: order in progress
Active
Inactive
Closed
Open
Note : the signal management control of the switch is different from the
mode "PM6". Unlike the mode PM6, the control signal to initiate the switch
is sent on the wire opening control "OC" and the closing control signal is
sent over the wire closure control "CC".
50 NT00243-EN-03
Commissioning Configuration of the various options
Some specific options allow operation of the T200 to be customized for the needs of certain
users.
The T200 is generally delivered without these specific options being activated (factory
settings).
8 bits measurements
s as in T200 series
ser 2:
By default, on the T200 S series 3, the current (or voltage) measurements are coded on
16 bits, whereas on the preceding series they were coded on 8 bits. By selecting this
option, however, it is possible to make the T200 compatible with the old-generation
old
T200s. This option is used especially when a Supervisor already polls T200s of an old
generation with measurements on 8 bits. Now, a given Supervisor can hardly read
measurements in 2 different formats.
Note: Same comment as for the previous option concerning the possibility of using the
"OFF Line Configurator" to generate a configuration file compatible with this option.
Parallel mode
e allowed in automatic mode
Activating this option enables paralleling of the channels by automatic control, during
the phase of automatic return to the priority channel.
NB: The dedicated digital input (DI 5) must also be activated to authorize paralleling.
parallelin
Note: recommended position = not checked
NT00243-EN-03 51
Commissioning Configuration of the
he various options
52 NT00243-EN-03
Commissioning Automation configuration
To activate "ATS" automatic transfer system on a channel, simply set the Type of Automatic
Vn Control variable in the
e specific page of the embedded Web server ("Control
(" and Automation"
page):
0
C Two possible versions for ATS:
RT
SW1 T1 RT - Network ATS version:: Control of two MV network channels. Network ATS version
O needs the use of VD23 relay for voltage presence/absence detection.
C - Genset ATS version:: Control of one network channel and one generating set channel.
SW2 RT T1 RT
O Several operating modes can be selected (Operating
Operating mode parameter), namely:
NT00243-EN-03 53
Commissioning Automation configuration
Configuration parameters :
Parameter Description Config. range
Network ATS and Generator ATS configuration
Automation type Choice of automatic control type. None or ATS[1/2] Network
->
> Choose Network ATS [1/2] or or ATS[1/2] Genset
Generator ATS [1/2]
Permutation waiting Waiting time for stability of voltage 0ms to 120s (in increments
type disappearance on the channel that with 100 ms
(T1) was operational before the start of By defaut : 1000 ms
Example of configuration for Network ATS automatic the changeover cycle
transfer system Time before returning Waiting time for stability of voltage 0s to 1800s (in increments
(Configuration/Control & Automation page) on normal way return on the normal channel before with 5s)
(T2)(*) return to that channel By default : 15 s
Configuration ATS Réseau uniquement
Type Choice of changeover type. (see SW1 -> SW2 or
details of operation above) SW2 -> SW1 or
SW1 <-> SW2 or
Auto-SW1 or
Auto-SW2
Configuration ATS Groupe uniquement
Genset connected to Choice of the channel that is SW1 or SW2
connected to the generator By default : SW2
Mode of operation Choice of changeover type. (see SW -> SWG or
details of operation above) SW <-> SWG or
Auto SW
Genset SW close Choice of mode of changeover to After genset inputs terminal
control the Generator block or After genset start
control order
Example of configuration for Generatior ATS automatic Genset voltage Choice of mode of detection of DI4 of digital inputs terminal
transfer system presence wired on voltage presence on the channel block or MV cubicle
(Configuration/Control & Automation page) managing the Generator connector
(*) : This delay is applied only if MV voltage is present on the back-up channel
Changeover sequence:
Changeover takes place if the following conditions are met:
■ Automatic control enabled.
■ Position of channel 1 and 2 switches complementary: TSD variable
variab SW1 closed position
and SW2 open position (or SW2 closed and SW1 open).
■ No fault current on the two channels (only if locking by fault detection option activated);
■ "Transfer locking" absent;
■ "MV earthing switch" absent on the two channels;
■ MV voltage absent on the enabled channel;
■ MV voltage present on the other channel.
Return to the main channel for the “AUTO” modes occurs if:
■ the priority channel is open;
■ the MV voltage on the priority channel is present during time delay T2.
Note: Voltage presence on a channel managing the Generator can be executed by two
processes. Configure the "Generator power on…" option according to the connection
performed (see table above):
- Either by a dedicated
d "Voltage" digital input (wired internally on DI 4)
- Or by voltage relay VD23 (via pin 8-"MV"
"MV" on the cubicle connection cable).
Specific generator-related
related management:
Upon changeover to Generator, if the latter doesn't start and the T200 is configured to
t wait
for Generator voltage, the automatic transfer system waits for a period of 60s at most before
stopping changeover, then:
- In SW ->> SWG mode: The automatic transfer system is locked and it must be reset (on the
Control panel) to restart the device.
- In SW <-> SWG mode or in Auto mode:: the automatic transfer system remains operational.
If voltage returns to the network channel, the automatic transfer system requests return to the
network channel.
54 NT00243-EN-03
Commissioning Automation configuration
NT00243-EN-03 55
Commissioning Fault detector configuration
Configuration parameters:
Parameter Description Config. range
Network MV network frequency 50 Hz or 60 Hz
frequency (by default 50 Hz)
Voltage input Type of sensors used for measurement Set in factory on PM6
Comment: The grey shaded parameters in the table are set in factory and can be
modified only by the manufacturer.
MV network parameters
The ratio of the toroid should also be entered when toroids having characteristics
different from those provided by the manufacturer are used.
The two values to be configured correspond to the Primary/Secondary ratio of the
toroids,, in other words the transformation ratio of the toroids.
(e.g. "500/1" means a toroid transformation ratio equal to 500).
The default value "500/1" corresponds to the type of toroids supplied for a PM6
switch.
Configuration parameters:
Parameter Description Config. range
Current input Type of sensors used for measurement Set in factory on PM6
Current Value of the toroid primary/secondary Primary: 50 to 2500
transformer ratio used for current measurement Secondary: 1 or 5
ratio (by default: 500/1)
Current Choice of type of toroid setup: I1,I3,I0 or I1,I2, I3
transformer 3 phase toroids or (by default: I1, I3, I0)
configuration 2 phase toroids + 1 zero sequence
Current measurement parameters Comment: The grey shaded parameters in the table are set in factory and can be
modified only by the manufacturer.
56 NT00243-EN-03
Commissioning Fault detector configuration
Configuration parameters:
Parameter Description Config. range
Imax threshold Fault current detection threshold I max 10 to 800 A
(in 1 A
increments)
By default: 500 A
I0 threshold Zero sequence fault current detection 2 to 160 A
threshold (in 1 A
increments)
By default: 20 A
Imax fault I max. fault filtering time. Any fault > Imax 40 to 800 ms
duration threshold and of a duration exceeding this (in 1 ms
time will be considered by the T200 as a increments)
phase fault (if validated by voltage and current By default: 200
loss) ms
I0 fault duration I0 fault filtering time. Any fault > I0 threshold 20 to 800 ms
and of a duration exceeding this time will be (in 1 ms
considered by the T200 as an earth fault (if increments)
validated by voltage and current loss) By default: 200
ms
Imax fault "Rapid" fault filtering time. Any fault > Imax Set in factory at
duration (fast threshold and of a duration exceeding this 50 ms
mode) time and less than the "Time for taking into
account Imax" will be indicated by the T200
as a "rapid" fault
Voltage If selected, the detector uses the image of Set in factory at
absence = enclosure mains voltage present instead of selected
PWR card using the voltage present/absent thresholds
voltage failure delivered by the fault detector to define
network voltage absent
Validation time Mains power-off filtering time e to confirm the Set in factory at 3
presence of a phase or zero sequence current s
fault
Inrush time Inrush function filtering time. Any fault Set in factory at 3
appearing during this time configured s
Current measurement parameters following a network voltage return will be
ignored by the T200 fault detector
Inrush If selected, can filter the faults resulting from Checked or not
closing of the upstream circuit breaker (faults checked
due to transformer magnetization)
Reset on Reset (if selected) or not of the memory of Checked or not
voltage fault detection indication upon network checked
recovery voltage return.
RAZ voltage Time delay for filtering the presence of mains 0 to 70 s
return duration voltage to reset the stored fault (in 1 s
increments)
By default: 3 s
Automatic FPI Maximum time delay for indication of a current 0 to 120 min. (in 5
reset fault. At the end of this delay, the fault is min. increments)
automatically erased. By default: 2 h
Comment: The grey shaded parameters in the table are set in factory and can be
modified only by the manufacturer.
Comment: If the circuit breaker opens 1 second after occurrence of the fault, the
T200 indicates the fault as soon as circuit-breaker
breaker opening is detected and not just
after the 3 seconds' wait. On the other hand, if voltage absent is detected only after
the 3 seconds, the fault is not indicated.
NT00243-EN-03 57
Commissioning Fault detector configuration
Generally, this type of fault does not last very long and weakens rather quickly
(significant duration < 200 ms). They can therefore be filtered easily by using the
"Inrush" function, designed to ignore the presence of any fault during 3 seconds
after closing of the circuit breaker.
The disadvantage of this operating procedure is that if a real fault appears during
these 3 seconds, it will not be taken into account by the T200.
There is no need to use the inrush in the following case (alternative solution if
possibility of configuration):
If there are tripping/resetting cycles (without presence of inrush currents).
If the time delay for the first "Rapid" fault of the circuit-breaker
circuit cycle is fairly
long, exceeding 200 ms (rule also valid for the second "Normal" fault, but
generally the second fault lasts a longer time than the first one).
If the first "Rapid" fault does not need to be detected.
Comment: The "Rapid" fault is not counted by the "Sectionalizer" automatic
control).
Alternative configuration
nfiguration solution without inrush with the T200:
No inrush (standard configuration)
Rapid Imax < 80 ms, Normal Imax > 200 ms
Alarm to SCADA system on the TSS (Imax, rapid)
Example of situation with Inrush not used and fault acknowledgment time set to 200
ms.
58 NT00243-EN-03
Commissioning Fault detector configuration
TSS 18 therefore plays a role of power supply under voltage signal filtering. The
purpose of this filtering is not to send too many successive alarms to the Supervisor
Main power supply failure whenever TSS17 changes state, following regular MV network failures (e.g. during
Active circuit-breaker
breaker reset cycles). It is therefore preferable to use the alarms on the
TSS18 rather than on the TSS17 in some cases.
Inactive
Note: The alarms can be generated only if the remote alarm function is activated on
the equipment.
TSS17: Immediate AC supply OFF Power supply failure time delay parameter:
Active
configurable from 0 to 21600 seconds
Inactive
Time-delayed
delayed undervoltage indication
NT00243-EN-03 59
Commissioning Variable configuration
The T200 Web server provides access to all the variables defined by default on the
T200.
The level of access to a variable (visible in read-only
only mode, accessible in
write mode, not visible) depends on how the variables have been configured.
The parameters
rameters for this page can be consulted and/or modified depending on
the user profile.
With the factory settings, you must be an administrator to be able to change the
level of access to a variable.
In each class, a number of variables of several different types are found ("type"
column).
Variable types:
The variables break down into several types presented in the table below.
In the standard version it is not possible add extra variables to those already
Different types of variable existing on T200P created as standard.
Note: However, when the "local Modbus network" option is present in the
equipment, it is possible to add variables corresponding to this option (see "local
"
Modbus network"" User Manual for more information).
Variable addresses:
All the variables can be configured
red with an external address. This external address
allows the variable to be made accessible in read or write mode from the Supervisor
by means of the protocol used for transmission.
A variable which has no address configured (address = "-")
" will not be accessible
from the Supervisor.
The values of the addresses configured depend on the type of protocol used.
Note:: Refer to the user manual for the protocol installed on the T200 for more
information concerning the addressing tables related to this protocol.
protocol
Example of configuration with or without event and
alarm saving
60 NT00243-EN-03
Commissioning Variable configuration
Saving variables:
T200 included a number of logs allowing archiving of events of various types (event
log, alarm log, measurement log).
The logs can be accessed by the user via the embedded Web server ("Diagnostic"
("
page).
All the variables can be configured separately with or without being
bein saved as a
measurement (if it is a measurement), event or alarm in these logs.
Note:: The system log, for its part, does not take into account variable changes of
state but rather information concerning the internal operation of the equipment.
When a variable
riable is configured to be saved in a log, a specific symbol appears in the
Variable configuration page on the same line as the variable:
= Saving to alarm log
= Saving to event log or to measurement log (if it is a measurement).
Since protocol events are not configurable, we shall speak in the remainder of the
chapter only of configuration of the events associated with the local logs.
For each type of variable, it is possible to choose how to process the variable for its
associated saving (with alarm or not, criterion for saving in an internal log).
The following table summarizes how to save these events for each type of variable.
This table is valid for each type of internal log (except the system log).
Event TSS TSD TM CNT Comments
Change of state Saving upon detecting any change of
state of the variable
Upon loss of closing Saving upon detecting the loss of
position of the closed state (although
without being open)
Regular saving Saving of the variable's state at fixed
periods of time
High threshold Saving upon exceeding a high
threshold
Low threshold Saving upon exceeding a low
threshold
Dead band Saving upon % variation of the
variable
Active maximum Saving of the maximum value reached
over a given period
Example of events configuration for a TM.
Active minimum Saving of the minimum value reached
Configuration available in the Settings/Variable
over a given period
configuration page and then by clicking on the variable
Note: Configuration available in the Settings/Variable
Variable configuration page and then
name TMx.
by clicking on the name of a variable.
NT00243-EN-03 61
Commissioning Variable configuration
In the local logs, events are registered with a brief descriptive text corresponding to
the change of state of the variable and a date and time of occurrence saved by the
T200 for locating them in time.
On a permanent connection (RS232, RS485, OF, GPRS, 3G, LL), it is therefore not
necessary to use the remote alarm function because the retransmission of
information between the T200 and the Supervisor theoretically takes place fairly
regularly or even continuously (e.g. polling).
Note that the "Alarm configuration"" section is displayed in the configuration page for
the variable only if the protocol is configured as Master/Master and if at least one of
the communication ports is of the non-permanent
permanent type.
Settings available in the Settings/Variable configuration
page and then by clicking on the name of the variable.
Alarm levels in PSTN or GSM:
On a PSTN or GSM link, three configurable access levels associated with an alarm
allow definition of the various ways of processing calls during retransmission of an
alarm:
In PSTN or GSM, the T200 attempts to join the Supervisor three times on the main
telephone number, then if this fails makes three further attempts on the backup
telephone number. If the call still does not get through, the calls are stopped unless
a new alarm occurs, which reinitiates the call sequence from the normal number.
The call sequences take into account
count the time delays configured in the "Protocol"
page (refer to the Protocol manual for more details).
In radio mode, the T200 attempts to send a frame over the radio network to the
Supervisor to retransmit the change of state information. If the call does
d not get
through, the T200 attempts to call the Supervisor indefinitely without any restriction
regarding the number of attempts. The call sequences take into account the time
delays configured in the "Protocol" page. It is recommended not to configure
excessively short time delays so as not to mobilize the radio network constantly
(refer to the Protocol manual for more details).
In all cases, receipt of the event triggering an alarm by the SCADA system causes
acknowledgement of the alarm.
If the alarm information does not reach the Supervisor, no acknowledgement is
performed.
NB: This box is checked by the T200 only for alarm retransmissions on non-
non
permanent links. This is not managed for permanent links.
62 NT00243-EN-03
Commissioning Variable configuration
Configuration of a TCD:
General parameters:
Parameter Description
Variable Customization of the variable name.
name:
Type: Type of variable, double or single: "Double" by default for a TCD
(unmodifiable).
Access: Defines the level of accessibility of this variable (administrator, operator,
monitoring). The level of accessibility is defined with the login and password
used for access to the Web server.
Order: The SCADA order can be reversed depending on the hardware configuration
of the digital outputs of the T200 (active on low level
le or on high level).
Class: Allows a variable to be associated with a defined class. It is advisable to
group together those variables having an information link in the same class
so as to make reading in the pages of the Web server easier.
Logical Logical address assigned to this variable by the T200. This is in fact the
address: logical name of the variable (TCD+No.) (unmodifiable).
Internal Internal address assigned to this variable by the T200. This is in fact a
address: Modbus address for the internal bus link between the CONTROL module
and the COM card (unmodifiable).
Logical A TCD is always associated with a TSD. The T200 automatically assigns the
address of TSD which is associated with this variable (in theory, should
sh not be
associated modified).
input:
External Address providing access to this variable in read/write mode from the
address: Supervisor via the protocol. The address is specific to each protocol used
(Modbus, IEC, DNP3).
The basic T200 includes for each variable the configuration of the external
addresses corresponding to the installed protocol.
An address set to "-"" is made inaccessible from the Supervisor.
Note: Refer to the manual for the protocol which is installed on
o the T200 for details
concerning the external address tables.
NT00243-EN-03 63
Commissioning Variable configuration
Configuration of a TSS:
General parameters:
Parameter Description
Variable Customization of the variable name.
name:
Type: Type of variable, double or single: "Single" by default for a TSS
(unmodifiable).
Logical Logical address assigned to this variable automatically by the T200. This is
address: in fact the logical name of the variable (TSS+No.) (unmodifiable).
Class: Allows a variable to be associated with a defined class. It is advisable to
group together those variables having the same information link in the same
class so as to make reading in the pages of the Web server easier.
Access: Defines the level of accessibility of this variable (administrator, operator,
monitoring). The level of accessibility is defined
def with the login and password
used for access to the Web server.
Internal Internal address assigned to this variable by the T200. This is in fact a
address: Modbus address for the internal link between the CONTROL module and the
COM card (unmodifiable).
External Address providing access to this variable in read/write mode from the
address: Supervisor via the protocol. The address is specific to each protocol used
(Modbus, IEC, DNP3).
The basic T200 includes for each variable the configuration of the external
addresses corresponding to the installed protocol.
An address set to "-"" is made inaccessible from the Supervisor.
Active status Allows definition of a text and a colour to be displayed in the "Monitoring"
definition: and "Control" pages to represent
esent the active state of the variable (binary
value 1).
Inactive Allows definition of a text and a colour to be displayed in the "Monitoring"
status and "Control" pages to represent the inactive state of the variable (binary
definition: value 0).
Note: Refer to the manual for the protocol which is installed on the T200 for details
concerning the external address tables.
64 NT00243-EN-03
Commissioning Variable configuration
Record configuration:
Parameter Description
"Activate" Check this box to activate saving of the variable in the event log according
check box to the following configured criteria.
On active Check this box to save a change of state in the active state of the variable
in the event log.
On inactive Check this box to save a change of state in the inactive state of the
variable in the event log.
Alarm configuration:
By alarm is meant the saving of changes of state in the alarm log, but also:
- In PSTN or GSM mode:: call sequence to the Supervisor then retransmission of
the alarm corresponding to the change of state.
- In radio mode:: sending of a frame to the Supervisor to retransmit the alarm
corresponding to the change of state.
Comment: The alarms are not used on permanent links. The following
configuration should not be used for a permanent link:
Parameter Description
"Activate" Check this box to activate saving of the variable in the alarm log according
check box: to the following configured criteria.
On active: Check this box to save a change of state in the active state of the variable
in the alarm log.
On inactive: Check this box to save a change of state in the inactive state of the
variable in the alarm log.
Alarm level: Three configurable levels corresponding to the various possibilities for
alarm retransmission to the Supervisor (see section on "Alarm
" reporting /
Alarm acknowledgement"
"Time-delayed Check this box if the alarm is to be retransmitted to the Supervisor only
alarm" check after a configurable time delay.
box:
Time-delayed Choice
ce of the unit (hour, minute, second) and the waiting time before
alarm: retransmission of the alarm.
TSS test:
The "TSS test" button at the bottom of the TSS configuration page allows the TSS
to be made active (fictitiously) for a few seconds (10 seconds).
That makes it possible, for example, to perform testing of state retransmission to the
Supervisor, although without being obliged actually to generate the change of state
for this TSS.
NT00243-EN-03 65
Commissioning Variable configuration
General parameters:
Parameter Description
Type: Type of variable, double or single: "Double" by default for a TSD
(unmodifiable).
Other status: Allows definition of a text and a colour to be displayed in the "Monitoring"
and "Control" pages to represent the undefined state of the variable.
Record configuration:
Parameter Description
On status Check this box to save any change of state of the variable in the event log.
change:
On leaving Check this box to save the loss of the switch closed state (loss of the active
close: state of the variable) in the event log.
Alarm configuration:
Parameter Description
On status Check this box to save any change of state of the variable in the alarm log.
change:
On leaving Check this box to save the loss of the switch closed state (loss of the active
close: state of the variable) in the alarm log.
66 NT00243-EN-03
Commissioning Variable configuration
Configuration of a TM:
General parameters:
Parameter Description
Variable Customization of the variable name.
name:
Correction Allows definition of a correction factor for display of the measurement in the
factor: Monitoring page. The default factors to be configured for each TM of a T200
series 3 are as follows:
- Phase current: "Direct/10"
- Mains voltage: "Direct"
Note: This factor doeses not change the format of the measurement sent in
the protocol frame.
NB: For compatibility of measurements with the T200 series 1 and 2 or with
an L500 type supervisor, configure as follows:
"8-bit measurement"" check box for compatibility of T200 - Phase current: "Direct
series 2 or L500 type TMs - Mains voltage: "Direct*100"
Excerpted from the page: "Settings/Automat. control"
control - Also check that the "8-bit
bit measurement" box is checked in the
"Miscellaneous" section of the "Settings/Automatic
Settings/Automatic control"
control page of the
CONTROL module concerned by this TM.
Logical Logical address assigned to this variable by the T200. This is in fact the
address: logical name of the variable (TM+No.) (unmodifiable).
Class: Allows a variable to be associated with a defined class. It is advisable to
group together those variables having an information link in the same class
so as to make reading in the pages of o the Web server easier.
Access: Defines the level of accessibility of this variable (administrator, operator,
monitoring). The level of accessibility is defined with the login and password
used for access to the Web server.
Internal Internal address assigned to this variable by the T200. This is in fact a
address: Modbus address for the internal link between the CONTROL module and the
COM card (unmodifiable).
External Address providing access to this variable in read/write mode from the
address: Supervisor
rvisor via the protocol. The address is specific to each protocol used
(Modbus, IEC, DNP3).
The basic T200 includes for each variable the configuration of the external
addresses corresponding to the installed protocol.
An address set to "-"" is made inaccessible
inacces from the Supervisor.
Unit: Unit to be associated with measurement for display in "Monitoring"
" page.
Max. scale Should correspond to the maximum value that can be taken in practice by
value: the measurement value. For "Raw" or "Normalized" type measurements,
me this
Max. value is used for calculation during measurement retransmission to the
SCADA system or for display in the Monitoring page. (see note 2 below).
NB: The value configured influences the precision of the measurement.
Min. scale Should correspond to the minimum value that can be taken in practice by the
value: measurement value. For "Raw" or "Normalized" type measurements, this
Min. value is used for calculation during measurement retransmission to the
SCADA system or for display in the Monitoring page. (see note 2 below).
NB: The value configured influences the precision of the measurement.
NT00243-EN-03 67
Commissioning Variable configuration
Note: Refer to the manual for the protocol which is installed on the T200 for details
concerning the external address tables.
Direct (or adjusted) value: corresponds to the real value in the reference unit
(does not take into account the configured
red "Min. and Max. scale" values).
Raw (or normalized) value: corresponds to a value calculated and scaled in
accordance with a formula taking into account the configured "Min. and Max.
scale" values. (see the protocol User Manual for details concerning
measurement calculation).
The choice of "Normalized" or "Adjusted" configuration is generally made in the
"Protocol" page.
Periodic treatment:
Parameter Description
"Log" check box: Check this box to activate saving of the measurement in the
measurement log according to the criteria configured below.
Period: Can be used to choose the period for saving of the measurement in the
measurement log.
Type: Can be used to choose how to save the measurement:
- "Averaged": mean of measurements over the configured
configure period
- "Sampled": instantaneous measurement at each configured period
"Event" check Check this box to activate saving of the measurement in the protocol
box: event stack according to the period criteria configured below. (see
notes 1 and 2 below)
Period: Can be used to choose the period for saving of the measurement in the
protocol stack and/or the alarm log
"Dial up" check Check this box to activate saving of the measurement in the alarm log
box: and sending of a frame to the Supervisor according to the period
criterion configured above.
Comment: The alarms are not used on permanent links. The "Call" check box
should not be used for a permanent link.
Note 2: The Modbus protocol of the T200 does not enable measurements to be
saved in the protocol event stack. It is therefore no use checking the "Events" box
for this protocol.
The solution for retransmitting the measurements in Modbus protocol is:
- On a permanent link: They will be read during the next interrogations coming from
the Supervisor. There is therefore nothing special to do.
- On a non-permanent
permanent link: Check the "Call" box to retransmit it immediately (or
after the configured period), or wait for the next interrogation by
b the Supervisor.
Threshold treatment:
Parameter Description
"Log" check box: Check this box to activate saving of the measurement in the
measurement log according to the criteria configured below.
High threshold: Check the box to activate saving of the measurement upon exceeding
the high threshold.
High threshold Configure the high threshold value which will cause processing of the
value defined records.
Low threshold: Check the box to activate saving of the measurement upon exceeding
the low threshold.
Low threshold Configure the low threshold value which will cause processing of the
value defined records.
"Dial up" check Check this box to activate saving of the measurement in the alarm log
box: and sending of a frame to the Supervisor according to the threshold
criteria configured above.
Comment: The alarms are not used on permanent links. The "Call" check box
should not be used for a permanent link.
68 NT00243-EN-03
Commissioning Variable configuration
Dead band:
Parameter Description
"Log" check box: Check this box to activate saving of the measurement in the
measurement log according to the % criterion configured below.
Method: Fixed: A fixed change in the value of the variable results in an
associated processing operation (saving, alarm).
Percentage: A change in percentage of the variable results in an
associated processing operation.
Value: Configure the minimum variation percentage or the minimum fixed
value of measurement variation which will cause processing of the
defined records.
Minimum change: Whatever the method (fixed or percentage), a minimum change in the
value of the TM is necessary for the variable to be processed (event,
alarm, etc.).
"Event" check Check this box to activate saving of the measurement in the protocol
box: event stack according to the % criterion configured above. (see notes 1
and 2 below)
"Dial up" check Check this box to activate saving of the measurement in the alarm log
box: and sending of a frame to the Supervisor according to the % criterion
configured above.
Comment: The alarms are not used on permanent links. The "Call" check box
should not be used for a permanent link.
Note 3: On software V2.xx, the "Method" andnd "Minimum change" parameters are
not available. Processing is performed on a percentage and without a minimum
change.
NT00243-EN-03 69
Commissioning Variable configuration
Configuration of a CNT:
General parameters:
Parameter Description
Variable Customization of the variable name.
name:
Correction Allows definition of a correction factor for display of the counter in the
factor: Monitoring page.
Note: This factor does not change the format of the counter sent in the
protocol frame.
(default factor: "Direct")
Logical Logical address assigned to this is variable by the T200. This is in fact the
address: logical name of the variable (CNT+No.) (unmodifiable).
Class: Allows a variable to be associated with a defined class. It is advisable to
group together those variables having an information link in the same
class so as to make reading in the pages of the Web server easier.
Access: Defines the level of accessibility of this variable (administrator, operator,
monitoring). The level of accessibility is defined with the login and
password used for access to the Web server.
Internal Internal address assigned to this variable by the T200. This is in fact a
address: Modbus address for the internal link between the CONTROL module and
the COM card (unmodifiable).
External Address providing access to this variable in read/write mode from the
address: Supervisor via the protocol. The address is specific to each protocol used
(Modbus, IEC, DNP3).
The basic T200 includes for each variable the configuration of the external
addresses corresponding to the installed protocol.
protoc
An address set to "-"" is made inaccessible from the Supervisor.
Unit: Unit to be associated with the counter for display in the "Monitoring"
" page.
(by default: with no unit)
Max. scale Should correspond to the maximum value that can be taken in practice by
value: the counter value. For "Raw" or "Normalized" type measurements, this
Max. value is used for scaling of the display in the monitoring page only.
(See note 2 below).
NB: The value configured influences the precision of the counter.
Min. scale Should correspond to the minimum value that can be taken in practice by
value: the counter value. For "Raw" or "Normalized" type measurements, this
Min. value is used for scaling of the display in the monitoring page only.
(See note 2 below).
NB: The valuelue configured influences the precision of the counter.
TCD reset Address of the remote internal command to define the "Preset" value for
address : the counter.
70 NT00243-EN-03
Commissioning Variable configuration
Note: Refer to the manual for the protocol which is installed on the T200 for details
concerning the external address tables.
Note 2:: The T200 manages measurement display in the "Monitoring" page
according to two formats:
Internal counting:
Parameter Description
Type of object Selection of the variable type on which the counter is incremented
(Digital or Analogue)
Object Name of the variable to which the counter is assigned
Counting method Depending on the type of object, the methods displayed are as follows:
For a DI type variable:
Pulse counter: The counter is incremented at each switchover of the
variable to high state.
Time counter: The T200 calculates the period during which the
variable is in the high or low state.
ate. The display in the monitoring page is
in the form "day, hour, minute, second".
Integrating meter: Over a given range of time (integration period), the
T200 calculates the number of high states of the variable.
For example, the integrating meter makes
make it possible to obtain power
values from a power meter with pulse output.
Routine processing:
Parameter Description
"Recording" Check this box to activate saving of the counter in the measurement log
check box: according to the criterion configured below.
"Event" check Check this box to activate saving of the counter in the protocol event
box: stack according to the period criterion configured below. (see notes 1
and 2 below)
Period: Can be used to choose the period for saving of the counter in the
measurement log and in the protocol
proto stack to the Supervisor.
Note 2: The Modbus protocol of the T200 does not enable counters to be saved in
the protocol event stack. It is therefore no use checking the "Events" box for this
protocol.
NT00243-EN-03 71
Commissioning Variable configuration
Processing on threshold:
Parameter Description
"Recording" Check this box to activate saving of the counter in the measurement log
check box: according to the value criterion configured below.
"Event" check Check this box to activate saving of the counter in the protocol event
ev
box: stack according to the criterion configured below.
Value Configure the minimum value which will cause processing of the
records defined above.
Dead band:
Parameter Description
"Recording" Check this box to activate saving of the counter in the measurement log
check box: according to the % criterion configured below.
"Event" check Check this box to activate saving of the counter in the protocol event
box: stack according to the criterion configured below.
Value as %: Configure the minimum counter variation percentage which will cause
processing of the records defined above.
- "Event" box only checked: Saving of the TM or CNT in the protocol stack without
call sequence to the Supervisor (general case of the permanent link, except in
Modbus protocol).
- "Event" + "Dial up" boxes checked:: Saving of the TM in the protocol stack and
call to the Supervisor (general case of the non-permanent
permanent link).
Not applicable with CNT.
- "Dial up" box only checked:: Call to the Supervisor without saving of the TM in
the protocol stack (specific case of the non-permanent
permanent link in Modbus protocol).
Not applicable with CNT.
72 NT00243-EN-03
Commissioning Class configuration
Note: The variable configuration page also adopts the same organization of
variables by class.
Creating a class:
To create a new class, simply enter its name in the empty "Class name" field and
click on the associated "Save" button.
Once the class has been created, it is then possible to configure a variable of the
T200 to be attached to that class (see chapter on "Customization
Customization of T200
variables").
Modifying a class:
Class configuration page
Modification concerns only the change of class name e or the possibility of making a
class visible or invisible in the pages of the Web server.
To modify the name of a class, simply change the title in the class entry field and
click on the associated "Save" button.
Creation of a new class A specific check box can be used to define whether a class and the variables
associated with that class will be visible in the monitoring pages ("Monitoring"
( and
"Control" pages).
Selection of this check box and a click on the "Save" button makes the class visible
in the pages (and conversely for deselection).
Deleting a class:
A specific check box in the page can be used to delete an existing class.
Selection of this check box and a click on the "Delete" button permanently erases
the selected class.
Check boxes: "Deletion" and "Monitoring" Note: It is not possible to erase a class if variables are still attached to that class.
NT00243-EN-03 73
Commissioning Tests
74 NT00243-EN-03
Operation Control and monitoring
5 Operation
5.1 Operating mode
Easergy T200 S can be used locally via the Control module or remotely from a
remote control station, depending on the position of the “Local/Remote” switch.
sw
An indicator lamp showing the status of the equipment is located at the top of the
control panel (front panel of the Control module).
A PC can be connected to the "COM" module to provide further information about
the status of Easergy T200 S and its operating history.
NT00243-EN-03 75
Operation Control and monitoring
76 NT00243-EN-03
Maintenance Information display
6 Maintenance
General
The equipment does not require regular maintenance.
The integrated battery test keeps users informed of the battery availability status.
Note: Replacement fuses are provided in the “accessories” bag attached inside the
basic enclosure.
The T200 has certain tools to perform maintenance or fault finding on the
equipment.
This requires a PC-compatible
compatible microcomputer with Internet Explorer (or an
equivalent software) installed. It is then possible to read the internal states of the
equipment and the events stored in memory by the e T200 (see also section on
Commissioning).
The tools available for maintenance and fault finding are as follows:
Monitoring page
This menu allows viewing of all the states and information managed by the T200:
The switch state: “Open”, “Closed” or “locked”;
Stored fault currents: “I Max.” and “I Max. transient” on each phase;
Current measurement on each phase, average current and neutral current;
Operation counter value;
The automatic control status, ON or OFF;
Equipment faults;
The operating mode: local or remote;
AC supply OFF, Delayed AC supply OFF;
The state of digital inputs 1 to 8;
The state of digital outputs 1 to 4.
Comment: The indications are refreshed every second.
Comment: A diagnostic through the state of the indicator lamps on the front panel
is not always adequate to find the cause of a fault. A lit indicator lamp indicates the
presence of a fault, but it is often necessary to consult the logs or the “Monitoring”
page to determine precisely the cause of a fault.
Event log
NT00243-EN-03 77
Maintenance Diagnostics via the front panel indicator
lamps and logs
6.1 Diagnostics via the front panel indicator lamps and logs
Symptoms Possible causes Solutions Log*
Easergy T200: no
Modbus
communication between the
Replace the Control module and/or the Communication module communication
Control module and the
fault
Communication module
The battery charger output Check the charger and the battery. If necessary, replace the Power Charger fault
voltage is too high or too low Supply module and/or the battery
The “Equipment
fault” LED on the No power supply to the See “48 V LED extinguished” in the symptom column below Motorization
Control module switchgear power supply
is lit. failure
(you are advised
to connect a PC to Loss of battery capacity or See "Battery fault LED lit" in the symptom column below Battery fault
the Control charge fault
module to
determine the Accessory
No telecommunications power
cause of the fault: See “external 12 V LED extinguished” in the symptom column below equipment power
supply (Radio or Modem)
“Visualization" supply failure
page) Connect the PC to the COM module and consult the logs. Configuration
Configuration loss: Reconfigure the T200. loss or memory
Problem on the Control
Other faults:: perform resetting on the power supply card. fault or program
module
If the fault persists, replace the CPU card. error or
parameter error
The Control module software Press the key Reset on the Power Supply module.
is faulty If the LED does not go out after a few seconds, replace the CPU card.
Replace the gF type 2 A HRC fuse, 10 x 38 mm, in the lower Power supply
AC supply fuse blown
enclosure panel. failure
The output connector of the Power supply
The "AC supply mains fuse holder is Put the connector back in place on the power supply card. failure
OFF" LED on the disconnected
front panel of the No supply to the enclosure Connect the AC supply.
Power Supply Check the cause of the AC supply outage. If the AC supply remains
module is lit AC Enclosure power supply cut
OFF, run another supply cycle by pressing the Reset button on the
OFF off automatically due to
Power Supply module. If the power supply doess not restart, change
prolonged AC supply outage
the Power Supply module and/or the battery.
Wait for the AC supply voltage to be reinstated (the enclosure is now Power supply
Temporary AC supply outage
running on battery) failure
Check that AC supply is ON and that the charger is supplying 12 V.
The "Battery
To do this, disconnect the battery and measure the voltage on the
fault" LED on the
Loss of battery capacity or rack battery connector.
ector. If the voltage is null, replace the Power Supply
front panel of the Battery fault
charge fault module. Otherwise, after reconnecting the battery, reset the Power
Power Supply
Supply module to trigger a battery test; if the problem recurs after
module is lit
charging for 24 hours, replace the battery.
Replace the 5 x 20 mm, 0.8 A semi time-lag lag fuse on the Power supply
Fuse blown
module.
The "Rack 12 V" If the “AC supply OFF” LED is Check the cause of the AC supply outage. If the AC supply remains
LED on the front lit, the enclosure supply has OFF, run another supply cycle by pressing the Reset button on the
panel of the been cut off automatically due Power Supply module. If the power supply does not restart, change
Power Supply to a long AC supply outage the Power Supply module and/or the battery.
module is Enclosure power supply cut
Check the charger and the battery. If necessary, replace the Power
extinguished off automatically due to a drop
Supply module and/or the battery.
in the 12 V voltage
Power Supply module failure Replace the Power Supply module.
(*) The events can be consulted in one or more of the various available logs:
Event log;
Alarm log;
System log.
In these logs, the information appears in the form "TSSxx - Information (log column) - Fault".
78 NT00243-EN-03
Maintenance Diagnostics via the front panel indicator
lamps and logs
Symptoms Possible causes Solutions Log*
Replace the 5 x 20 mm, 0.4 A semi time-lag
lag fuse on the Power Supply Accessory
Fuse blown
module. equipment
Consumption at the output > Check the transmission equipment and reinstate the supply by power supply
1.3 A ± 0.3 A for 3 min pressing the Reset button on the Power supply module. failure
If the “AC supply OFF” LED is Check the cause of the AC supply outage. If the AC supply remains
The "external 12 V" lit, the enclosure supply has OFF, run another supply cycle by pressing the Reset button on the
LED on the front been cut off automatically due Power Supply module. If the power supply does not restart, change
panel of the Power to a long AC supply outage the Power Supply module and/or the battery.
Supply module is Enclosure power supply cut
extinguished Check the charger and the battery. If necessary, replace the Power
off automatically due to a
Supply module and/or the battery.
drop in the 12 V voltage
Accessory
equipment
Power Supply module failure Replace the Power Supply module.
power supply
failure
Replace the 5 x 20 mm, 5 A time-lag Motorization
Fuse blown fuse on the CPU card of the Control module in the left-hand
left part of the power supply
enclosure. failure
If the “AC supply OFF” LED is Check the cause of the AC supply outage. If the AC supply remains
lit, the enclosure supply has OFF, run another supply cycle by pressing the Reset button on the
been cut off automatically due Power Supply module. If the power supply does not restart, change
to a long AC supply outage the Power Supply module and/or the battery.
The "48 V" LED on Motorization power supply cut Check the charger and the battery. If necessary, replace the Power
the front panel of off automatically due to a Supply module and/or the battery.
the Power Supply drop in the 48 V voltage
module is Power supply cut off following Following the 48V cutoff, if the temperature of the charger drops in
extinguished overheating of the power less than one minute, the 48V power supply returns automatically. On
Motorization
supply card charger (e.g. the other hand, if the temperature does not drop 1 minute after the 48V
power supply
excessive power cut-off, a manual reset should be performed on the power supply card
failure
consumption on the to restore the 48V power supply (thermal protection requiring action). If
motorization 48 V) the problem persists, replace the power supply card.
T200 CPU card failure Replace the T200 CPU card. Motorization
power supply
Power Supply module failure Replace the Power Supply module. failure
The equipment is not
Power up the equipment.
powered up
All the Control Replace the 5 x 20 mm, 0.8 A semi time-lag
lag fuse on the Power supply
module indicator Supply fuse blown
module.
lamps are
Control module failure Replace the Control module.
extinguished
The card program is no
Reset by pressing the Reset button on the Power Supply module.
longer running
The equipment is not
The Communication Power up the equipment.
powered up
module "ON" LED is
Replace the 5 x 20 mm, 0.8 A semi time-lag
lag fuse on the Power supply
extinguished Supply fuse blown
module.
Connect the PC to the COM module. Refer to the system log to Interface or
Configuration problem on one determine the error. Check the conformity of configuration of the COM modem
The Communication of the COM or CONTROL and/or CONTROL modules of the T200 (example of fault: initialization
module "Fault" modules or internal incompatibility of the configured modem with that installed on the COM error (x)
LED is lit connection fault between the card or internal connection problem between one of the CONTROL / Control
modules modules and the COM module). If the fault persists, replace the Module error
module presumed to be defective. (x)
Stop the USB driver, disconnect the USB cable from the
The Communication The Communication module
Communication module, then press the Reset key on the Power
module "Fault" LED software is faulty, or starting RESET
Supply module. If the LED does not go out after a few seconds,
flashes rapidly with USB cable connected.
replace the Communication module.
The Communication The Communication
ommunication module With the USB cable disconnected and the USB driver stopped, press
module "Fault" LED software is faulty the Reset key on the Power Supply module. If the LED does not go out
flashes slowly after a few seconds, replace the Communication module.
NT00114EN 79
Maintenance Diagnostics via the front panel indicator
lamps and logs
Other diagnostics
Event Possible causes Solutions
Check:
the connection of the battery (the command on switches cannot work if the
Operation orders not The switch order was not battery is not connected)
executed executed the position of the “Local/Remote” switch;
the validity of the order issued;
the connection between Easergy T200 and the switches.
It is recommended to wait for about fifteen seconds before resetting the device
following a change in configuration parameters of the T200.
Device reset performed
Loss of T200 Use the "OFF line Configurator" configuration generation tool provided in
immediately after a change in
configuration appendix (on the Easergy CD) to create a configuration file (text file) according to
the device's configuration
the options
ns used on the T200. Then load this file on the T200 via the
"Maintenance / Save-Restore"
Restore" menu of the embedded Web server.
The loading process
manages only the file format
with .zip extension. The
Error during software software must therefore not
Start the loading operation again without unzipping the software
loading be unzipped before loading it
on the T200.
(file with .mem extension not
managed)
80 NT00243-EN-03
Maintenance Power supplies
Switch off the AC supply outside the equipment or on the safety fuse block within the
enclosure.
Disconnect the supply to the battery circuit:
Unplug the battery connector under the rack.
All the LEDs on the front panels of the rack should now be extinguished.
The Easergy T200 S enclosure is now powered down.
IMPORTANT NOTE: There is no need to alter the cables when connecting the
toroid and power supply cables to the cubicle. The cables must never be modified.
Battery maintenance:
Replacing the battery
IMPORTANT NOTE: Before
fore carrying out any work on the battery, disconnect it from the equipment by
Use batteries having recent production unplugging the connector from the base under the rack.
dates (less than three months' old). Remove the battery by sliding it outwards, raise the terminal covers and undo the two
Do not store more than six months terminal nuts, then disconnect the Faston
aston lugs from the connecting cord.
without recharging. To install a new battery, repeat this sequence in the reverse order.
Do not throw the batteries away. Servicing and storing the batteries
Sealed lead batteries are used. The advantages of this type of battery include the fact that
there is no risk of explosion, no acid leakage and no servicing requirement.
However, this type of battery has its limitations:
Limited number or recharging cycles;
Average service life of 10 years, with ageing accelerated by temperatures outside
the recommended range;
Ageing during storage (do not store for more than six months without recharging, as
this type of battery does not withstand a total discharge);
Difficult to predict the end of battery service life.
The Power Supply module is designed to optimize the characteristics of the battery.
A battery fault alarm informs the remote control system of an imminent discharge.
Note: the battery is an important element for the unit because the command on switches
cannot operate without the battery connected and charged.
charge
Replacing fuses
Replacement fuses are provided in the “accessories” bag attached inside the enclosure.
“AC supply” fuse
This fuse is located in the lower panel of the enclosure.
gG type HRC fuse of rating 2 A, 10 x 38 mm.
“Rack power supply” fuse
The fuse
use protecting the power supply to all the electronic modules is located on the Power
Supply module card.
Fuse: 5 x 20 mm, 0.8 A semi-time-lag.
“External 12 V supply” fuse
The fuse is located on the Power Supply card.
Fuse: 5 x 20 mm, 4 A time-lag.
“48 V supply” fuse
The fuse is located on the CPU card of the Control module.
This card is located in the left-hand
hand part of the rack. It is accessible after removing the
control panel (front of the Control module).
Fuse: 5 x 20 mm, 5 A time-lag.
NT00243-EN-03 81
Maintenance Card replacement
82 NT00243-EN-03
Appendix A Configurable parameters
Page: Home
Sub-page Section Parameter / button Configuration Comments
range
Home Back to home page
Local/Remote Local/Remote Local: normal access. Remote: simplified access (images
and logos not loaded)
Choice of Language Français/
language English/Português/Es
pagnõl/Deutsch
User User name No restriction Confirmation by OK (by default: "Easergy")
Password No restriction Confirmation by OK
An incorrect user or password opens a "User" session (by
default: "Easergy")
Page: Monitoring
Sub-page Section Parameter / button Configuration Comments
range
Classes Channel x Access to the corresponding class states
T200 information Access to the corresponding class states
T200 internal faults Access to the corresponding class states
Automatic controls Access to the corresponding class states
Digital inputs Access to the corresponding class states
Page: Control
Sub-page Section Parameter / button Configuration Comments
range
Channel x Operation preset Allows the operation counter value to be changed
Channel x F-O control Allows the switch status to be changed
T200 ON/OFF control Allows the automatic control status to be changed
information
Digital inputs F-O control Allows the state of the digital outputs to be changed
Page: Diagnostic
Sub-page Section Parameter / button Configuration Comments
range
Alarm log Clear log The "Ack" box is checked when the SCADA system has
acknowledged the alarm
The "Clear log" button clears the log's content
Event log Clear log The "Clear log" button clears the log's content
System log Clear log The "Clear log" button clears the log's content
Measurement Clear log The "Clear log" button clears the log's content
log
File transfer Alarms.csv Transfers the alarms log in Excel file form
"Save" saves the file to the PC
"Open" opens the file under Excel
Events.csv Same as for the events log
System.csv Same as for the system log
Measures.csv Same as for the measurements log
NT00243-EN-03 83
Appendix A Configurable parameters
Page: Maintenance
Sub-page Section Parameter / button Configuration range Comments
84 NT00243-EN-03
Appendix A Configurable parameters
Page: Maintenance
Sub-page Section Parameter / button Configuration range Comments
NT00243-EN-03 85
Appendix A Configurable parameters
Page: Settings
Sub-page Section Parameter / button Configuration range Comments
Protocol Refer to the User Manual for the protocol used for more information.
TCP/IP protocol Refer to the User Manual for the protocol used for more information.
Port 1 or 2 Direct RS232 Baud rate 200 to 38400 baud Frame transmission rate (600, 1200 bds only with FSK radio, 1200 with LL,
or RS485 1200 or 2400 bds with FFSK radio)
Transmission or Radio Parity None or Space or Even or Transmission parity
or PSTN Odd
or GSM line Stop bits 1 or 2 Stop bit in frame
or LL Frame error on noisy Yes or no The start of the frame can be filtered or not to avoid reading any noise
outgoing cable
Frame error on line at Yes or no Any holes in the frame can be filtered or not
rest
Delay before response 0 to 10000 ms In 10 ms increments. Upon reception, wait before sending the response to
avoid frame overlapping (by default:0 ms)
DTR management: Checked or not Data Terminal Ready. DTR is used by the T200 to indicate that it is ready
for transmission
DTR - RTS delay: 0 to 10000 ms In 10 ms increments. Time delay to be complied with between rising of the
DTR and RTS signals. In external radio, this corresponds to the time delay
between the send order and carrier rise. (By default: 0 ms)
RTS management Checked or not Request To Send. If this option is selected, the RTS signal will be managed
during transmission exchanges with the modem.
CTS management Checked or not Clear To Send. The modem enables the CTS as soon as ready after RTS
enabling by the T200
RTS to CTS delay 10 to 10000 ms In 10 ms increments. Time delay between receiving the RTS and sending
the CTS by the modem (by default: 20 ms).
RTS (or CTS) to 0 to 1000 ms In increments of 10 ms. Time delay between rise of RTS (or CTS if
message delay: managed) and sending the message.
Message to RTS delay 0 to 10000 ms In 10 ms increments. Time delay between the end of the message and RTS
falling by the T200 (by default: 20 ms)
DTR management Checked or not Data Terminal Ready. The modem causes the DTR to rise after powering
up or when it is Clear To Send
CD management Checked or not Carrier Detect. The carrier can be used by the modem to detect reception of
a message.
LL Type of line 2-wire or 4-wire Choice of type of leased line used.
PSTN or GSM Calling party call delay 1 to 600 s Allows the call to be released when the T200 is called after the configured
time delay (by default: 30 s)
Called party call delay 1 to 600 s Allows the call to be released when the SCADA system is called after the
configured time delay. (By default: 60 s)
Telephone No. (normal) 0 to 9, P, T or space Main telephone No. to be used in case of alarm retransmission
Telephone No. 0 to 9, P, T or space Backup telephone No. to be used in case of alarm retransmission if main
(backup) No. cannot be reached.
Modem init. sequence No restriction. Record AT commands necessary to initialize the PSTN modem. With internal PSTN
consistent AT commands mode, default AT commands not modifiable. (By default:
&F0%S0=12S0=1&K0%C0E0&W0&Y0)
PSTN Type of dialling Pulse or voice frequency Type of dialling used for alarm retransmission.
GSM PIN code 0000 to 9999 PIN code of the GSM card.
SMS service centre No. 0 to 9, P, T or space Telephone No. of the SMS service centre (gateway for SMS's)
User SMS No. 0 to 9, P, T or space Telephone No. of the user for sending SMS's.
RS485 Polarization Checked or not checked Activates polarization of the T200 end line. The RS485 line should be
polarized at one termination only, generally on the Master side.
End-of-line
line resistance Checked or not checked Active the T200 end load resistance. The RS485 line should be loaded at
both its terminations.
Type of line 2-wire or 4-wire Choice of type of transmission used: 2-wire
2 or 4-wire.
GPRS or 3G Access Point Name No restriction. Name of GPRS/3G access point provided by the GPRS/3G network
(APN) operator.
PIN Number 0000 to 9999 PIN code of the GSM card.
Daily disconnect Checked or not checked Override setting of automatic disconnection/reconnection of the T200 to the
GPRS/3G network at a fixed time. In the event of loss of connection with the
network, this process allows the T200 to reconnect, because it cannot do so
by itself autonomously.
Disconnection hour: 0 to 23 Configuration of the selected daily disconnection time according to the
criteria described in "Daily
Daily disconnection".
disconnection
PPP session timeout 1 to 60 min Configuration of the delay maximum before disconnection of T200 from
GPRS/3G network, in case of no data transfer detected by the T200
Specific Ping IP adress Consistent The ping makes it possible to verify and measure the quality of the
IP address, e.g. equipment's connection with another device connected to the Ethernet
192.168.2.169 network. Enter the known IP address of another device capable of receiving
the packet corresponding to the ping allowing this quality to be measured.
Ping test Button that can be used to set the ping test manually to verify T200
connection to the GPRS/3G network. The T200 then displays the result of
the test: "Ping Ok" or "Ping failed".
failed
Ping time interval 1 to 360 min Delay between two successive automatic “Test ping”
Ping attemps 0 to 10 Number of maximum attempts for the “Test ping” process in case of no
response from remote IP address.
Ping Timeout 1 to 360 s Maximum delay to wait for the response during the “Test ping” to define
“Ping error”.
Authentication Checked or not checked When the GPRS/3G network requires authentication in the connection
phase, activate this function by checking the box.
Encryption protocols accepted: PAP, CHAP, MSCHAP, MSCHAP V2
Login No restriction Configuration of the login used for authentication. Configure this field only if
the "Authentication"" option has been checked.
Password No restriction Configuration of the password used for authentication. Configure this field
only if the "Authentication"" option has been checked.
Save Allows the configuration to be taken into account
86 NT00243-EN-03
Appendix A Configurable parameters
Page: Settings
Sub-page Section Parameter / button Configuration range Comments
NT00243-EN-03 87
Appendix A Configurable parameters
Page: Settings
Sub-page Section Parameter / button Configuration range Comments
88 NT00243-EN-03
Appendix A Configurable parameters
Page: Settings
Sub-page Section Parameter / button Configuration range Comments
NT00243-EN-03 89
Appendix A Configurable parameters
Page: Settings
Sub-page Section Parameter / button Configuration range Comments
90 NT00243-EN-03
Appendix B General characteristics
Charging time 10 h to 24 h
Capacity 12 Vdc - 24 Ah
Battery Total discharge, periodic tests every 12 hours (10A during 100 ms).
Monitoring Successful test if U Bat.> 11,2V, at the end of the test.
Two consecutive unsuccessful tests generate battery fault
Power reserve at 20°C Up to 16 h + 10 open/close cycles (in radio communications)
Service life at 20°C 10 years
Characteristics
Insulation (50 Hz/1 min.): 10 kV
AC supply input IEC 60 255-4
Impulse wave (1.2 / 50 µs): 5 kV
Dielectric
Insulation (50 Hz/1 min.): 2 kV
Toroid input IEC 60 255-4
Impulse wave (1.2 / 50 µs): 5 kV
Level 4: 4 kV (mains and sensors),
Rapid transients IEC 61 000-4-4
2 kV (other circuits)
Electrostatic discharges IEC 61 000-4-2 Level 3; 6 kV on disconnected 8 kV contact
Radiated electromagnetic
IEC 61 000-4-3 80 MHz - 1 GHz - 10 V/m
field
Electromagnetic Radio frequency on FSM IEC 61 000-4-6 0.15 MHz to 80 MHz – 10 V rms
Damped oscillatory waves IEC 61 000-4-12 2.5 kV common mode, 1 kV differential mode
Pulsed magnetic field IEC 61 000-4-9 1000 A/m peak
Impulse waves IEC 61 000-4-5 Coupling between line wires 1 kV, between wire and frame earth 2 kV
50 Hz magnetic fields IEC 61 000-4-8 30 A/m continuous-duty
duty and 300 A/m 1 to 3 s
Temperature –25°C to +55°C
NT00243-EN-03 91
Easergy T200S Personal notes
92 NT00243-EN-03
Easergy T200S Personal notes
NT00243-EN-03 93
Easergy T200S Personal notes
94 NT00243-EN-03
Easergy T200S Personal notes
NT00243-EN-03 95
Schneider Electric Industries SAS As standards, specifications and designs change from time to time,
please ask for confirmation of the information given in this publication.
Schneider Electric Telecontrol
839 chemin des Batterses
Z.I. Ouest
01700 St Maurice de Beynost
Tel : +33 (0)4 78 55 13 13
Fax : +33 (0)4 78 55 50 00
http://www.schneider-electric.com
E-mail : [email protected]
Publication: Schneider Electric Telecontrol - Made in France
Production: Schneider Electric Telecontrol - Made in France
NT00243-EN-03 11/2013 Impression: Schneider Electric Telecontrol - Made in France