Unistrut: Medical Support Structure Guide
Unistrut: Medical Support Structure Guide
1
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
8 KEY CONSIDERATIONS WHEN INVESTING IN
ENGINEERED MEDICAL SUPPORT SYSTEMS
When it comes to construction, medical settings are in a constant state of flux: new equipment is
installed to provide better patient care; space is reconfigured to maximize efficiencies and ROI; and
new wings are added to accommodate more patients. Larger hospitals are often in a state of
permanent construction.
While many people will see the important medical equipment suspended from the ceiling, few will ever
notice the support systems that hold them in place above the ceiling tiles. Medical support structures
are used to suspend equipment, including X-ray machines, motion-sensitive surgical equipment, and
other critical medical devices. These machines don’t come with a means of attachment from the
manufacturer, so medical support systems are specially designed with channel and fittings to help
anchor each machine to the ceiling for safe use.
The constant shifts in the medical field can make it difficult to determine how you should approach
working with medical support structures. Unistrut Service Company has been providing medical
support structure solutions for hospitals, clinics, and medical centers since we opened our doors in
1940. This experience has led us to create a comprehensive collection of articles about medical support
best practices and other topics that can benefit you from beginning of a project to its completion.
If you’d like to learn more about the advantages of Unistrut ceiling structures for medical applications
or want to request a quote, contact us online or give us a call at (877) 706-5926 to talk to one of our
experts today.
2
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
TABLE OF CONTENTS
Overhead Support Structure Mounting Options for Buildings with Inadequate Structural
Members ................................................................................................................. 11
Designing Unistrut Support Systems for Radiology and Medical Applications: Common
Problems................................................................................................................. 20
3
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
5 Mistakes to Avoid - Medical Equipment Support Structures
Visit any hospital, doctor’s office, or outpatient clinic and you’ll see all types of medical equipment
suspended overhead. The systems in plain view do amazing things ranging from detecting the smallest
anomaly on an X-ray to providing a surgeon the lighting needed to perform a delicate operation. What
most of us never see are the support structures securing the equipment overhead.
We’ve designed support structures for medical equipment for many years. This experience means we
have first-hand knowledge of how (and why) things go wrong. Here’s some friendly advice on critical
mistakes to avoid during the design and installation phases of medical supports.
One of the most common mistakes we see is an over-reliance on fabricated, red iron supports. We
aren’t saying red iron supports are always bad. In fact, we use them for projects with heavier load
requirements. The key here is a design that pairs red iron with Unistrut channel and fittings.
The problem with designs based exclusively on fabricated structural steel is ease of modification.
Medical equipment support structures frequently require adjustments during installation. Even small
system tweaks to work around conduit, pipes, or HVAC duct work present in locations other than the
areas called out in the original drawings–or minor variances in deck height–may require welding and
another union trade to get involved. In each of these cases, an inefficient design concept can increase–
and potentially double–your labor costs.
Field welding in a medical setting doesn’t just drive up labor costs. It also creates dust and releases
potentially harmful gases into the air. Try telling the nurse manager you want to weld next to an active
operating room—this never goes well.
Having your system designed by Unistrut Service Company eliminates many of the potential problems
mentioned above because we have a thorough understanding of medical applications. We also
understand how to select the proper materials during system design. Here’s our best advice on things
to avoid when choosing materials:
4
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
3. Failure to Understand Deflection and Rotation Criteria
When folks don’t understand OEM requirements for support structures, trouble isn’t far behind. For
example, some medical support structures can have moment loads over 12,000 ft. lbs. Remember, the
equipment manufacturers have strict criteria for deflection and rotation. Although you’ll see some
variance between different manufacturers, typical industry standards include:
Excessive deflection will cause poor images. In extreme cases, you may be dealing with a finished room
(paint, flooring, ceiling, etc.) and the equipment vendor may not be able to calibrate equipment. Failing
to meet the manufacturer’s specifications could end up forcing you to gut the ceiling and rework the
structure.
Excessive plate rotation can cause “boom drift” where the equipment does not stay where the doctor or
nurse has placed it. Boom drift can also cause internal clutches and brakes to fail—and when this
happens, the manufacturer won’t honor their warranty because the support structure is not to spec.
Protecting the equipment is an important design goal, but you also need to think about people. When
staff and patients are positioned beneath systems that can easily weigh well more than 1,000 pounds
(the new Flexmove system from Philips weighs 4,000 lbs.), you begin to understand why support
structure design is so important. In each of the scenarios just described, the contractor can be held
responsible for damages. The moral here is simple—make sure you understand the required deflection
and rotation criteria.
4. Improper Anchoring
The best-designed strut support system is of no value when improperly anchored. Many booms require
a “hybrid” adhesive system due to excessive dynamic loading. Because they are not intended for
dynamic loading applications, mechanical anchors can “rock” in the drilled hole, causing movement.
This motion doesn’t just cause poor equipment performance—it can yield catastrophic results.
5
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
5. Missing the Big Picture
Our last discussion point involves vision—and thinking with an eye towards the future. The owner could
change equipment manufacturers after the drawings are approved but before the installation starts. Or,
the owner might decide to change manufacturers a few years down the road. It’s important to think
about ways to make the system design more “universal” to accommodate these types of changes.
Planning ahead during the design phase could save your client thousands of dollars later.
Overhead medical support structures may look rather simple, but a lack of vision and planning can yield
a system that does not meet your client’s future needs. On the other hand, if you take the time to
design a system that is easily modified downstream, your client will sing your praises when the time
comes to make an equipment change.
6
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Support Structures for Medical Applications: Why
Accurately Calculating Load, Deflection, and Rotation
Matters
Thanks to its ease of installation and adjustability, Unistrut channel is often specified during the
construction of overhead medical equipment support systems. The safe and effective use of
catheterization c arms, radiology equipment, lights, and service booms suspended by Unistrut support
structures requires proper calculations of load, deflection, and rotation to ensure both optimal
equipment performance and the safety of your installation.
One common mistake is the misuse of the beam load tables found in the Unistrut General Engineering
Catalog and on the Unistrut Service Company website. Please note that the standard “beam charts”
shown on the next page provide the maximum allowable uniform load. Most actual cases will require
some type of “reduction factor” to properly determine the actual load capacity of the strut.
7
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
To help engineers and architects make accurate calculations, we also include notes and sample
calculations as shown here:
1. Beam loads are given in total uniform load (W Lbs.) not uniform load (w lbs./ft or w lbs./in).
2. Beam loads are based on a simple span and assumed to be adequately laterally braced. Unbraced
spans can reduce beam load carrying capacity.
8
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
3. For pierced channel, multiply beam loads by the following factor:
5. For concentrated midspan point loads, multiply beam loads by 50% and the corresponding deflection
by 80%.
Sample Calculations to Demonstrate Beam Loading Charts and Load Reduction Factors
Sample No. 1: Say we have a 6’ span of P1000sl and want to see what the load capacity is for a point
load. Per the charts, P1000 is good for a maximum allowable uniform load (not load per foot) of 560 lbs.
In referencing the notes below, we have the following load reductions:
Sample No. 2: Say we have a 5’ span of P1001 and want to see the load capacity for a point load. Per the
charts, p1001 is good for a maximum allowable uniform load (not load per foot) of 1,910 lbs. In
referencing the notes below, we have the following load reductions:
Note that these assume that the strut connection can handle the load. It is the responsibility of you and
your engineer to review all calculations and connections, and to verify that all items are installed per
Unistrut requirements. Unistrut Service Company takes no responsibility for the misuse of information
provided. Local codes may dictate more stringent requirements. Catheterization and X-ray equipment
are also highly sensitive to deflection and/or rotation.
9
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
The “typical” Catheterization or Radiology support requires <1/16” deflection, and the “typical” light or
service boom requires < .2 degrees of rotation.
Designing supports for overhead medical equipment solely on material stress without considering
deflection/rotation will compromise both the performance of your equipment and the safety of your
personnel and patients. For example, an inadequate overhead support structure may cause excessive
wear and eventual failure of service boom brakes and clutches.
With an inadequate support grid, heavy service booms may initially perform sufficiently, but with time,
the interior boom components will begin to wear and continually fail. Eventually, the dynamic load may
cause failure of the support, causing the equipment to come crashing down. Making accurate
calculations of load, deflection, and rotation when designing your overhead ceiling support grid will
ensure your medical equipment performs to manufacturer specifications while keeping lab technicians
and patients safe.
10
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Overhead Support Structure Mounting Options for Buildings
with Inadequate Structural Members
Many Unistrut applications require connections to steel columns, beams, or concrete, but what
happens when these structural members aren't strong enough to handle the loads imposed by the
system?
For example, what happens when you want to suspend a 1,000-pound X-ray system overhead, but the
building can't handle the load and meet the stringent deflection requirements of all major equipment
manufacturers? Our support structure for a GE X-ray system illustrates how our design experience
created a solution to overcome a building's structural limitations.
Most of the X-ray system support structures we design are for hospitals or buildings that can handle
significant loads. In this case, we were dealing with a building originally designed for retail use. The
architect charged with converting the space to medical use worried about the strength of the building's
structural members and an engineer commissioned to analyze the situation confirmed these concerns.
Further complicating matters, this was a rush job—which is often the case with medical projects—and
the architect wanted uninterrupted sight lines for the new space.
Before hanging any strut, we needed to start with a structural steel superstructure consisting of four 3x3
square tube columns nestled within the wall cavities and six overhead beams approximately two feet
above the ceiling. Strategically placing the upright columns in this manner and connecting them to the
overhead beams created an out-of-sight superstructure from which to hang the channel without
cluttering up the radiology room's floor plan. The superstructure was also designed so it can be utilized
during future room renovations.
With the suitable structural steel in place, we added a support system made from Unistrut P1000 and
P1001 back-to-back channel, P2786 beam clamps, P2751 trolleys, and P2484 and P1359 angular fittings.
For readers new to the Unistrut System, the images below illustrate some of the fittings and hardware
used to complete this project:
11
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Unistrut P2751 Four Wheel Loop Trolley Unistrut P2751 4 Wheel Loop Trolley
Unistrut P2484 - 7 Hole 90 Degree Gusseted Fitting Unistrut P2484 - 7 Hole 90 Degree Gusseted Fitting
12
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Unistrut P1359 4-Hole 90 Degree Fitting Unistrut P1359 4-Hole 90 Degree Fitting
13
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
In most cases, we find ways to attach to existing structural members, but this is not always a viable
option. By leveraging years of design experience, we completed this project on time and on budget—
despite the limitations of the building.
14
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
4 Options to Consider Before Reusing an Overhead Medical
Support Structure
The inevitable equipment upgrades and remodeling projects common to hospital settings often prompt
questions regarding the merits of repurposing an existing overhead support system versus a new
installation.
Strong and stable systems ensure proper functioning of equipment and protect manufacturer’s
warranties of highly sophisticated lighting and imaging systems weighing hundreds or thousands of
pounds. Patient liability and employee safety are also a concern. Before any decision is made regarding
the use of an existing overhead support structure, it’s important to consider all available options to
make an informed decision.
On the surface, the least expensive option is to assume that since the existing structure held the old
equipment, it’s suitable for reuse. Although this may be true, there are no guarantees that the existing
support structure is suitable for the new equipment. If problems arise, the equipment manufacturer will
claim that the general contractor has final responsibility for the strength and stability of the mounting
structure.
Re-purposing is your least expensive option, but this approach also has the most potential downside
because nobody has assessed the structure’s suitability for the new application. Your project may also
experience delays if the contractor discovers problems mid-project. Worse yet, the new equipment may
malfunction or even fall during use. With these outcomes in mind, the reuse of an existing support
structure has potential hidden costs that may far exceed anticipated savings.
The second option is to hire an engineer to review the existing structure and compare the support
system to standard design practices. This additional step often unveils missing bracing, loose hardware,
and improper design concepts that can save substantial time downstream. The last thing an architect,
general contractor, or construction manager wants to tell the project manager is that their project is
facing delays because the existing support structure is insufficient to handle the new equipment loads.
Although a site visit is not fail-safe, a simple engineering judgment goes a long way toward spotting
potential problems. In some cases, repairs and modifications to the existing structure may improve
system performance and safety. If you do elect to reuse the existing support structure, we recommend
having a competent carpenter perform a “nut and bolt” check to ensure that the structure’s hardware
remains properly torqued.
15
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Option No. 3: Conduct a Formal Assessment of the Existing Structure
A third option is to hire an engineering firm like Unistrut Service Company to conduct a formal
assessment of the existing structure. Unlike a simple site visit, this option includes a complete
engineering review, including load calculations.
In a best possible case scenario, the engineering study may find that existing structure is suitable for re-
use and the general contractors can move forward installing the new equipment. If the study discovers
design flaws or structural issues, the complexity and feasibility of repairs and modifications depends on
the original fabrication method. Older support structures fabricated using Unistrut or a similar style of
channel lend themselves to field modification, but most of the structural steel and red iron supports we
see in the field require welding. The byproducts of welding (fumes, dust, and potential explosions from
sparks near oxygen) are problematic in hospital settings.
While you may be tempted to explore this option, remember that the combined costs of the
engineering assessment and potential repairs may significantly exceed the investment required to
replace the entire system from scratch. It’s also important to note this step is solely a design analysis;
there is likely no warranty on the lighting, cath lab, X-ray, patient lift, or boom system if a weld should
fail or break.
The only ways that ensure the equipment manufacturer will honor a warranty include removal and
installation of a new support structure backed by engineering drawings and PE seals, or making
modifications (again, backed by engineering drawings with PE stamps when necessary). These options
may seem unnecessary, but when you factor in the costs associated with voided equipment warranties
and potential patient liability, new or thoroughly-reviewed support structures are the most cost-
effective solutions over time.
As an example, we were once hired to assess the suitability of a Cath Lab support structure we designed
over 17 years ago. In this case, the new equipment’s support structure requirements were remarkably
similar to the old equipment. The owner hired us to confirm the original calculations, perform a nut and
bolt inspection (re-torqueing), and add any additional changes. In this case, no additional changes were
necessary.
16
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Here is one of the original drawings, which features our old address and phone number:
If you are wondering what to do with an existing overhead support structure, remember to explore your
options with an engineering company that understands the complexities of hospital and medical
applications. A suitable overhead support structure will help ensure proper and accurate operation of
your equipment while keeping patients and staff out of harm’s way.
17
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Retrofitting Radiology Room Support Structures
Clients often ask us about reusing existing radiology room support structures when swapping out older
machines for newer equipment. When the size and weight of the systems are similar, clients assume we
can retrofit their existing support structure. Sometimes we can recycle an existing support structure
with some minor tweaks, but in other cases, we can’t.
For the sake of argument, let’s assume the owner is swapping a GE system for a Philips or vice versa.
Both systems are similarly sized, weighing about 1,000 pounds each. With this information in mind, you
might think that reusing the support structure is a slam dunk, but we can’t begin to make this call
before removing the ceiling tiles and inspecting the existing system.
If we are dealing with fabricated red iron supports, it may be difficult to mount the new equipment
without making significant modifications, including welding. Welding is always problematic in a
hospital setting due to fumes, dust, and the risk an open flame poses around bottled gases. On the
other hand, if the support structure is modular, strut-based system, the odds of repurposing go up, but
there is a catch.
The general contractor has final responsibility for the strength and stability of the mounting structure—
not the X-ray equipment manufacturer. If the equipment fails, the manufacturer may point to an
inadequate support structure and void the warranty. How do we determine if the existing structure is
adequate? We start by referencing the existing system's engineering calculations and drawings to
assess the structure strength. If we did the original work, this information is archived in our system.
In cases where another vendor completed the work, we need to secure the original drawings and
calculations or re-engineer the system. The engineering review may determine the support structure is
compatible as is, or that it requires minor modifications. The key is having the engineering data in hand
to protect your warranty and the patients and personnel near suspended equipment that can weigh
more than 1,000 pounds. An engineering review may seem like an unnecessary step to some, but it is
vital to ensure safe operation of the new system.
To address the original question—yes, there are specific instances where we do repurpose existing
systems. For example, we recently fielded an inquiry regarding reusing a 10-year-old GE 3 rail system.
After years of reliable service, a decision was made to remodel and outfit a radiology room with
equipment from another manufacturer. The owner wanted a slightly lower ceiling, and they were keen
on keeping project costs to a minimum.
18
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
The original drawings and calculations verified the feasibility of mounting the Unistrut support
structure beneath an existing GE 3 rail system on spacing as mandated by Philips. The finished project
shown below illustrates what we can do with the proper support documentation in hand:
The next picture is from the same hospital. When this radiology room was remodeled, we again
consulted our original drawings and calculations before mounting P5500T rails below the existing grid
to support new GE equipment.
Overhead medical equipment support structures are not unlike the foundation of a house. We build on
an existing foundation, but only when the structure is sound. The analogy used here is a bit simplistic,
but now you should have a better understanding of the information required to make an informed
decision.
19
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Designing Unistrut Support Systems for Radiology and
Medical Applications: Common Problems
We often receive calls from contractors, architects, and engineers wanting to play an active role in the
design of a Unistrut Medical Equipment Support System. Since one of the most common applications is
a Radiology (X-Ray) grid, let’s discuss some design issues associated with these types of installations.
One design that we frequently see is adding structural steel beams (I Beams, or Wideflange Beams)
perpendicular to the Unistrut, but just 3-1/4” above the ceiling (equal to the height of the P1001 ceiling
channel). There are a few problems in doing this. We will address a few of them below.
Design Load
Most Radiology rooms are designed for a 1,000 lb. load anywhere on the system. There are some that
are higher and some lower, but this load gives a basic idea for this discussion. The ideal beam clamp to
attach P1001 Unistrut to the beam is a P2786, which is rated for 2,000 lbs./pair. Unfortunately, these are
wrap-around style beam clamps, and would extend below the ceiling, something that is typically not
acceptable. There are alternative clamps, but they do not have the same load rating.
Deflection
Industry standards require system deflection to be below 1/16”. Spanning structural steel across a
room, most likely around 15’ or so, will exceed the deflection requirements of the system.
Steel Tolerances
Most radiology systems have certain requirements for plumb and level. Because most structural steel is
not fabricated to the tolerances that the equipment drawings require, chances are good that you are
dealing with steel that is at least 1/4” or 1/2” off over that span. Simply bolting P1001 below this does
not fix the problem.
Now you may ask, “What do I do for our Unistrut system?” We recommend having the structural steel
several inches above the ceiling. Having the steel above the ceiling will allow the installation of
additional Unistrut members, allowing infinite adjustment within the vertical members to get the
system plumb and level.
20
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Medical Support Structures: Exam Lights Versus Surgical
Lights
Now and then, we receive contractor inquiries about pricing for overhead lighting support systems. In
many instances, the contractor is working from drawings supplied by an architect and they are looking
for pricing information on design and installation services. We are always eager to help, but when a
drawing has generic references to “surgery/exam” light details, we need additional clarification before
moving forward. Here’s why.
Most exam lights are relatively small and lightweight. Unistrut supports used to suspend exam lights
usually consist of a single vertical member with two braces as shown in the photographs below:
21
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Surgical lighting systems are much larger (most are in the 24” diameter range), and of course, much
heavier. Unistrut support structures surgical lights typically consist of four vertical members and up to
eight braces as shown in the photo below:
What may seem like a minor detail is rather significant because an exam light requires a different
support structure than a surgical light. Now that you understand the difference, let’s talk about a few
scenarios where a lack of drawing clarity can cause some problems.
22
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
Exam Lights vs. Surgical Lights Issues
This first potential problem is confusion during the quotation process. It’s possible to end up comparing
a quote for an exam light support system with a quote to build a surgical light support structure. The
surgical light support system will come in much higher and the owner won’t be able to make an apples-
to-apples comparison. It's also worth noting that a much sturdier surgical light support system is
overkill for an exam lighting application.
To be a good steward of the owner's resources, you'll want a support structure that fits the application.
Ultimately, we'll need to know the manufacturer of the lighting system (e.g., Steris, Stryker, etc.)
because there are slight nuances to each brand that must be accounted for during design. When
requesting a quote for a Unistrut support structure, it’s always important to supply accurate and
detailed information. Sometimes this may seem like an unnecessary extra step, but doing so will ensure
that your support structure is appropriate for your application. You may even save some money as well.
23
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
How and Why You Should Compare Quotes
Have you ever been puzzled by contractor bids with significant price discrepancies? Sometimes a low
bid means your contractor is cutting corners to hit a price point or business is slow. A higher bid may
signal a contractor that is buried in jobs or testing the waters to see how his pricing compares with the
competition. In other cases, a higher bid may mean better design, workmanship, and materials.
It’s always important to make apples-to-apples comparisons and to fight the temptation to dismiss
quotes exclusively based on price. If your request for a bid returns two quotes that differ only on price
and the materials and workmanship from both firms is similar, entertain the low bid. On the other hand,
if there are significant differences in the quotes, you need to better understand what you are being
asked to buy. Ask yourself some simple questions:
• What are the pros and cons of each contractor’s materials choices?
• How do the design concepts differ? Does one design lend itself to a more efficient installation?
• How long will the installation be in service?
• Is the ability to modify the installation mid-project or down-stream important?
• Is support for field issues important?
We recently received a call from The Cleveland Clinic to revisit a project our team quoted more than 10
years ago. We were not the “low bidder” and the contract for a ceiling-mounted support structure for
operating room (OR) lights was awarded to another contractor. This year’s renovation of the OR
includes plans to change out the lights in the same location.
During selective demolition, one of the welds broke. According to an outside structural engineer, poor
design and installation methods, which included a hodge-podge of welded, fabricated steel, and
channel of unknown origin, caused the system to fail and future remodeling incorporating this structure
would have posed significant challenges.
24
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com
The picture below is from a different contractor’s installation, but it illustrates the same basic points.
The channel in the picture looks like modular strut, but it is not genuine Unistrut material. Close
examination also reveals mismatched channel in different profile configurations (and fittings) from
multiple manufacturers.
Unfortunately, the low bidder used fittings and channel from multiple sources for this installation, so it
was not possible to reuse the existing structure. The Unistrut Service Company team remedied this
situation by designing a proper solution to allow for a quick installation and modularity.
For the Cleveland Clinic job, making repairs to the existing structure would have required tenting and
welding in an active operatory. This was a bad idea, as the estimated costs of the repairs would nearly
exceed starting over from scratch.
Both the decision to accept the lowest bid and a failure to appreciate the significant differences
between the two approaches to the support structure design came back to haunt our client. With this
information in hand, our client opted for a new medical equipment support structure designed and
installed by Unistrut Service Company, not only so that it may potentially be reworked in the future, but
because it’s a wise decision to utilize a company that specializes in this type of work.
25
Unistrut Service Company | 24400 Sperry Drive Cleveland, Ohio 44145 | 877-706-5926 | www.unistrutohio.com