CETS HIGHVOLT Water Terminationsystem
CETS HIGHVOLT Water Terminationsystem
7.90/3
Situation & Application Cable Terminations
HV tests of extruded cables require special measures for The general principle is based on the field-control by using
the connection of the HV source to the cable under test. Water- deionised water with a specific, controllable conductivity together
controlled cable end termination systems allow a reliable and with its high dielectric constant. As cable diameters can vary the
easy handle of this connection. The required international electric field distribution can change significantly within the same
standards and requirements for testing cables are all fulfilled by cable end termination. Thus a suitable field-control is needed,
using our cable end termination systems (IEC 60840 / 30-150kV, that means the correct conductivity within the cable termination is
IEC 62067 / 150-550kV, IEC 60060-1, IEC 60060-2, IEC 60270). crucial and thus an important design factor of the cable end
terminations. Furthermore, one negative consequence of using
Cable End Termination Systems (CETS) are designed and water with limited conductivity as a medium for the correct field-
manufactured for routine and type testing of medium, high control, electric energy is dissipated within the water. This may
and extra high voltage plastic-insulated cables. Additionally, lead to a significant and unwanted temperature rise. This effect is
the system can also be operated in the framework of avoided by the application of an effective cooling system for the
development tests and other applications as: water and by choosing the correct conductivity.
• HV AC withstand tests The main components of the cable end termination system
• PD measurement tests (the terminations are PD free up consist of two cable end terminations CET for each end of the
to the rated voltage of the system) cable to be tested and the water conditioning unit, CEU, see title
• HV impulse (LI and SI) tests figure. Additionally, accessories like silicone sealing compound,
• Step-up tests deionisation resin, water tubes and spare parts complete this
• HV AC long term tests (the system is designed for testing system. The cable is inserted from below into the end
continuous duty cycle) termination for voltages up to 800 kV, Fig. 1.
• C/tan δ measurement on request (special preparation of
the cable ends without changing of water end The termination CET is designed as a 2-tube system in
terminations) which the deionised water circulates. Together with the water
conditioning unit a closed water system is formed. Each cable
Notice, CETS are not intended for cable operation or service after termination is connected by two hoses to the water conditioning
installation. In addition, if high current tests above 100 A are unit, see title figure.
needed, this has to be considered from case to case.
Fig. 1: View of a cable end termination for 300 kV, CET 300/120
Water Processing Unit
Two water processing units, type CEU are available to Via a fibre optic link and by the PROFIBUS system, the
cover all needs for the voltage levels from 100 kV up to 800 kV. water conditioning unit can be incorporated in the HIGHVOLT
Design and geometry of the cables to be tested change the field control and measurement system of high voltage AC and LI
distribution and energy losses within the cable end termination. sources.
The water conditioning unit is the key component which controls This allows visualization on a central display, the remote control
both conductivity and temperature of the water circulating through of all parameters and the starting of all processes of the CEU.
the cable end terminations. Furthermore, for very high voltage applications and power, two
CEUs can be controlled by only one touch panel, as the two
water conditioning units can be connected by one optical fibre
The water conditioning unit (Fig. 4) is equipped with a link.
sufficient water reservoir which holds the deionised water.
Together with the two cable terminations, which are connected by
four hoses with the water conditioning unit, a closed water system As heat losses rise strongly with the increase of the applied
is formed, see title figure. By an effective pump, the water is voltage level and by decrease of the cable diameter (volume of
circulated with a flow rate of 30 l/min. or 60 l/min. through the water is increased), cooling capacities for the CEUs cover two
cable end terminations. With the help of a heat exchanger the ranges. The smallest CEU has a maximum cooling capacity of
excess heat is taken away by external cooling water. The 60 kW and the larger version is equipped with a cooling capacity
conductivity is controlled by a deionisation resin contained in a of 120 kW.
bottle. The arrangement of this bottle within the water circulating
system in conjunction with the conductivity control allows a very
long life time of about one year, even if the system is used
intensively.
Type designation for the cable end termination systems and The cable terminations alone:
their components is as follows:
CET a/b G
The system (consisting of two cable end terminations together a rated voltage
with the water conditioning unit): b maximum cable diameter in mm across
CETS a/b-c semi-conducting layer
G guard electrode for tan δ measurement
a rated voltage in kV
(as option)
b maximum cable diameter in mm across
semi-conducting layer Example: CET 350/120 is a pair of cable end termination for
c maximum cooling capacity in kW 350 kV, 120 mm across semi-conducting layer
Example: CETS 350/120-60 is a system for 350 kV, 120 mm The water conditioning unit:
across semi-conducting layer, 60 kW cooling capacity
CEU c R
c maximum cooling capacity
Further technical information about the components can be found
in the HIGHVOLT Data Sheets No. 7.93 and 7.95 R remote control (as option)
Example: CEU 120 means a water conditioning unit with 120 kW
cooling capacity
© HIGHVOLT Prüftechnik Dresden GmbH - 2013/09- 7-90-3.doc Subject to change without prior notice