Control Strategies For Power System in Island Operation
Control Strategies For Power System in Island Operation
net/publication/290202869
CITATION READS
1 416
2 authors, including:
Karel Maslo
CEPS
34 PUBLICATIONS 102 CITATIONS
SEE PROFILE
All content following this page was uploaded by Karel Maslo on 21 February 2017.
Abstract: Supervisory active power and frequency (P-f) control together with reactive power and voltage control (Q-V) represent two
main and usually separated processes to keep system indicators (frequency and voltage) within permissible limits. Generally, the
hierarchical structure of both domains is very similar. It contains local primary control, secondary control and tertiary control. This
system ensures coordination of active and reactive power production and optimization. This paper deals with particular cases of P-f and
Q-V control strategies in island operation when a part of system is electrically separated from the main interconnected system. This
operation condition occurs rarely on transmission system level, however the control systems on all levels should be adjusted properly
and transmission system operators should have prepared a plan to manage such extraordinary situation. Different possibilities for
co-operation of secondary and primary controls are investigated and evaluated. All possibilities mentioned thereinafter are simulated by
dynamic model of power system. Special attention is paid to study cases with successful strategies, which represent secure transition
from normal to island operation mode. Investigated cases lead to recommendation to operate primary controls independently and
decentrally. In case of situation when system indicators (frequency, voltage) are out of their limits, turbine governors should be
switched to proportional speed control and excitation control to terminal voltage control.
Keywords: Power-system control, island operation, dynamic models, primary and secondary controls.
tertiary one. Due to the fact that tertiary level of The Q-V domain control is showed on the right side
controlling system is focused towards optimization the of Fig. 1. Primary voltage control is implemented by
study cases are aimed to primary and secondary levels the Automatic Voltage Regulator (AVR). It initiates a
of the system. For brief description and distinction fast variation in the excitation of generator when
between primary (decentralized) and secondary generator terminal voltage (UG) changes. So-called
(centralized) levels see Fig. 1. load compensation is usually used for generators
Secondary voltage control is described in papers operating parallel to the power grid. This function is
[4-6] and secondary frequency control—(so-called performed by reactive current IR correction of voltage
LFC load frequency control) is described in papers reference value UGRef. Resulting static generator
[7-10] in more details. characteristic (dependence of terminal voltage UG on
P-f domain control is depicted in the left side of Fig. 1. terminal reactive current IR or reactive power QG) is
Primary frequency control is a decentralized function of shown below the block labelled “Q control” on Fig. 1.
the turbine governor and it is implemented by frequency In this case generator virtually controls the voltage in
correction of power reference value PS. Resulting static external point, usually in the middle of the step-up
turbine characteristic (dependence of generator output transformer.
PG on frequency deviation f) is shown below the block Secondary Voltage Control (SVC) distributes
labelled “P control” in the Fig. 1. reactive power among relevant generators within a
Secondary control or Load Frequency Control (LFC) given zone of the network in order to maintain
is a centralised automatic function to control the power scheduled voltage level USched at so-called pilot nodes.
generation in a control area. Its main purpose is to
3. Case Studies
maintain interchange power flow P at the scheduled
value PSched and to restore the frequency f in case of a Two case studies were carried out to evaluate
frequency deviation originating from the control area. different control strategies:
Control Strategies for Power System in Island Operation 3
(1) Transition into large island with power (4) Speed control with manual changing of
surplus—influence of P-f control; reference speed.
(2) Transition into small island with power In cases 3 and 4 turbines operate in power control
deficiency—influence of Q-V control. mode before transition into island operation then they
These cases are analyzed in following chapters. are automatically switched over from power control
mode to speed control mode when frequency deviation
3.1 Large Surplus Island—LFC and Turbine Control
exceeds |f| > 200 mHz.
Coordination
Fig. 2 shows block scheme of turbine control with
Large island represents the entire Czech Republic symbolic illustration of these four control modes in
which is disconnected from the rest of continental more details (but still very simplified). Under normal
Europe synchronous system (former UCTE). This network conditions, steam turbine operates in power
control area exports ∆P = 3,300 MW before control mode and a boiler is in pressure control
disconnection. (so-called boiler follow mode). In case of large
Four control modes are taken into account in island frequency deviations (f > 200 mHz) an island
operation for investigation: operation is detected and turbine control is switched
(1) Turbine power control with remote control from over from power control to proportional speed control
LFC in P-f mode; mode. Fast valving is activated in case of near network
(2) Turbine power control with remote control from faults (short circuits) and it rapidly reduces the
LFC in f mode (so-called flat mode); mechanical power to decrease accelerating power of
(3) Speed control with automatic remote correction steam turbine-generator to ensure dynamic stability.
n of reference speed from LFC; Proportional-Integral (PI) speed governor (so-called
transducer transforms electrical signal to oil pressure 6
500
control after transition into island operation and
400
switched over into speed control as well, but the Fig. 4 Frequency deviation time courses for strategies
and for surplus island.
reference speed is changed automatically by
correction signal n from the LFC. Fig. 5 explains the different dynamic behavior.
Fig. 3 shows simulation results for cases and . It In the control mode the reference power PS is
is obvious that frequency deviation is unstable and remotely adjusted by LFC. However after passing into
very soon exceeds limit f = 2.5 Hz which drives surplus island (total turbine power is greater than
disconnection of units from the grid in both cases. consumption and network losses) generator power
However switching of LFC to the flat mode (f control) decreases (generated power must be equal to
does not prevent the system from frequency collapse consumption and losses all the time). Turbine PI power
and subsequent black out. control increases turbine power PT to restore reference
Fig. 4 shows simulation results for cases and . power PS, thereby speed and frequency increase. This
Frequency deviations are stable. Limit 90 mHz for positive feedback causes frequency collapse of the
automatic resynchronisation is reached in 15 minutes. incurred island. Changing LFC to f mode does not
In case all commands for decreasing of the reference improve the situation, because LFC is too slow to
speed are done manually at selected units in seven steps. decrease significantly reference power PS. Reference
In case some units are remotely controlled from LFC, power PS is necessary to decrease within several
that sends correction signal of reference speed seconds after transition into island. It must be
automatically. In this case, frequency is changed more emphasized, that turbine and generator powers are
smoothly and this control mode is more comfortable for different values during transient phenomena. The
system dispatchers and plant operators. difference between them causes speed and frequency
Control Strategies for Power System in Island Operation 5
[MW] PT [MW] PS
200 190
150
PG 140
100
90
50
PS PG PT
0 40
0 2 4 6 8 10 12 14 16 18 20 22 t[s]
24 0 2 4 6 8 10 12 14 t[min]
(a) (b)
Fig. 5 Generator and turbine power (PG and PT) and reference power PS for (a) case and (b) case .
51,4
51,2
51
50,8
50,6
50,4
50,2
50
49,8
49,6
Zone WEST
49,4 Zone South East
Zone North East
49,2
49
22:09:30,0
22:10:00,0
22:10:30,0
22:11:00,0
22:11:30,0
22:12:00,0
22:12:30,0
22:13:00,0
22:13:30,0
22:14:00,0
22:14:30,0
22:15:00,0
22:15:30,0
22:16:00,0
22:16:30,0
22:17:00,0
22:17:30,0
22:18:00,0
22:18:30,0
22:19:00,0
22:19:30,0
22:20:00,0
Fig. 6 Measured frequency during UCTE splitting on 4.11.2006 (according to [12]).
deviations (due to accelerating power on the right side balance between prime movers output and consumption)
of swing equation). Sometimes you can read that there in the incurred island. The small difference between PT
is imbalance between load and power generation in and PG equals to generator losses.
power system. It is not accurate. Power balance The simulations show that switching from power
between generated power (measured on generator control into speed control is necessary for stable island
terminals) and consumption and losses is maintained operation. This solution proved its efficiency during a
naturally according to Kirchhoff’s laws. system-wide incident on 4th November 2006, when
In control mode the reference power PS is UCTE synchronous zone split into three islands (see
remotely adjusted by LFC to increase power to Final report [12]). The Czech Republic was part of the
scheduled power exchange, but turbine control is northeast island, where power surplus was more than
switched into proportional speed control mode. Turbine 10 GW and instantaneous frequency reached nearly
adjusts its power PT to generator power PG and this 51.4 Hz (see Fig. 6).
control mode is able to ensure power balance (it means Due to the immediate power decrease in this island,
6 Control Strategies for Power System in Island Operation
the frequency was stabilised on 50.3 Hz in the first 30 Fig. 7 shows block scheme of excitation control in
seconds. The Czech Republic participated by power more detail with symbolical illustration of these two
decrease of 950 MW—the largest portion of power in control modes.
the island (not taking into account switching off In the first case SVC changes reference reactive
windmills in the eastern Germany and Austria). Due to power of the controlled unit. Excitation control is in Q
switching over from power to speed control the mode, which means that it controls generator reactive
K-factor of the Czech Republic control area increased power QG to maintain reference power QS. In the
more than four times, from normal value 730 MW/Hz second case , excitation control operates in a basic
(for primary frequency control) to approximately 3,300 voltage mode, which means that it controls generator
MW/Hz (in emergency speed control). terminal voltage UG to maintain reference value UGRef.
3.2 Small Island—SVC and AVR Coordination Fig. 8 shows the simulation results for cases and .
The result shows that voltages time courses are stable
Small island represents three substations connected in both cases, but in case the voltage exceeds 110%
by two 400 kV lines with summary charging reactive threshold (upper limit of normal operation condition).
power about 115 MVAr. Total consumption in
1.2
u [pu]
substations represents 810 MW and generation in
monitored area is 286 MW before disconnection. One
1.15
substation operates as pilot node equipped with
secondary voltage controller (SVC). One 200 MW unit
1.1
is remotely controlled from this SVC.
Two control modes are taken into account in island
operation of the unit: 1.05
[pu] QS
[pu]
0.2 0.2
0.1 0.1
0 0
0 20 40 60 80 100 t [s]
120 0 20 40 60 80 100 t [s]
120
‐0.1 ‐0.1
QG
QS
‐0.2 ‐0.2
QG
‐0.3 ‐0.3
(a)(b)
Fig. 9 Generator and reference reactive powers (QG and QS) for (a) case and (b) case .
continental Europe synchronous area) into island [6] A. Berizzi, M. Merlo, P. Marannino, F. Zanellini , S. Corsi,
operation. It means switching over turbine control into M. Pozzi, Dynamic performances of the hierarchical
voltage regulation: The Italian EHV system case, in:
proportional speed control mode and excitation control
Proceedings of the 15th Power Systems Computation
into the terminal voltage control mode. Conference, 2005.
[7] T. Inoue, H. Amano, K. Hanamoto, W. Wayama, Y.
References Ichikawa, Development of load frequency control
[1] ENTSO-E Network code for requirements for grid simulation tool, CIGRE Session, 2010.
connection applicable to all generators [Online], [8] J.L. Agüero, M.C. Beroqui, F. Issouribehere, Grid
http://networkcodes.entsoe.eu/wp-content/uploads/2013/0 frequency control: Secondary frequency control tuning
8/130308_Final_Version_NC_RfG1.pdf. taking into account distributed primary frequency control, in:
[2] H.B. Ross, N. Zhu, J. Giri, B. Kindel, An AGC IEEE Power Engineering Society General Meeting, 2010.
implementation for system islanding and restoration [9] D.D. Rasolomampionona, A modified power system
conditions, IEEE Trans. Power Syst. 9 (3) (1994) model for AGC analysis, in: Proceedings of the IEEE
1399-1410. Power Tech Conference, 2009.
[3] J.L. Sancha, M.L. Llorens, J.M. Moreno, B. Meyer, J.F. [10] S.St. Iliescu, I. Fagarasan, C. Soare, D. Ilisiu, F. Biliboaca,
Vernotte, W.W. Price, J.J. Sanchez-Gasca, Application of Process modelling for load frequency control in power
long-term simulation programs for analysis of system systems, in: Proceedings of the IEEE Power Tech
islanding, IEEE Trans. Power Syst. 12 (1) (1997) 189-197. Conference, 2009.
[4] V. Ilea, C. Bovo, M. Merloa, A. Berizzia, P. Marannino, [11] K. Máslo, C.A. Nucci, A. Borghetti, I. Petružela, Power
Reactive power flow optimization in power systems with system dynamics during large power imbalance phenomena,
hierarchical voltage control, in: Proceedings of the 17th in: Proceedings of the 12th IEEE MELECON, 2004.
Power Systems Computation Conference, 2011. [12] System disturbance on 4 November 2006, Final report of
[5] M.D. Ilik, X. Liu, G. Leung, M. Athans, Ch. Vialas, P. UCTE [Online], https://www.entsoe.eu/fileadmin/user_
Pruvot, Improved secondary and new tertiary voltage upload/_library/publications/ce/otherreports/Final-Report
control, IEEE Trans. Power Syst. 10 (4) (1995)1851-1862. -20070130.pdf.