3500/22M Transient Data Interface Module: Datasheet
3500/22M Transient Data Interface Module: Datasheet
Datasheet
Bently Nevada Machinery Condition Monitoring
Description
The 3500/22M Transient Data Interface (TDI) is the interface
between the 3500 monitoring system and compatible
software (System 1 Condition Monitoring and Diagnostic
software and 3500 System Configuration software). The TDI
combines the function of a 3500/20 Rack Interface Module
(RIM) with the data collection capability of a communication
processor such as TDXnet.
Document: 161581
Rev. T
3500/22M Transient Data Interface Module
Datasheet
Specifications Controls
Inputs Front Panel
Clears latched alarms and Timed
Power Rack reset OK Channel Defeat in the rack.
Consumption 10.5 Watts button Performs same function as “Rack
Reset” contact on I/O module
Data
Address Used to set the rack address:
Front Panel USB-B
switch 127 possible addresses
10Base-T/ 10Base-T or 100Base-TX
Used to place 3500 rack in
100Base-TX I/O Ethernet, autosensing
either “RUN” mode or
100Base-FX Fiber-Optic “PROGRAM” mode. RUN mode
100Base-FX I/O
Ethernet allows for normal operation of
the rack and locks out
Outputs configuration changes.
PROGRAM mode allows for
Front Panel LEDs normal operation of the rack
Indicates when the 3500/22M is and also allows for local or
OK LED remote rack configuration. The
operating properly Configuration
key can be removed from the
Indicates when the 3500/22M is Keylock
rack in either position, allowing
TX/RX LED communicating with the other
the switch to remain in either
modules in the rack
the RUN or PROGRAM position.
Indicates when the 3500 rack is in Locking the switch in the RUN
TM LED
Trip Multiply mode position allows you to restrict
CONFIG OK Indicates that the 3500 rack has a unauthorized rack
LED valid configuration reconfiguration. Locking the
switch in PROGRAM position
I/O Module OK Relay allows remote reconfiguration
Indicates when the 3500 rack is of a rack at any time.
operating normally or when a
fault has been detected within
the rack. User can select either an
Function
“OPEN” or “CLOSED” contact to
annunciate a NOT OK condition.
This relay always operates as
“Normally Energized”.
Standard OK Relay is rated to 5A
@ 24 Vdc/120 Vac, 120
Watts/600 VA Switched Power
Ratings (maximum)
OK Relay with gold-plated
contacts is rated down to 1 mA
@ 1 Vdc (minimum)
Arc
Arc suppressors are provided.
Protection
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships,
Offshore Units, and High Speed and Light
Craft
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC
T4 Gc;
Class I, Zone 2: AEx/Ex ec nC ic IIC
T4 Gc;
Class I, Division 2, Groups A, B, C,
and D;
T4 @ Ta= -20˚C to +65˚C (-4˚F to
+149˚F)
When installed per drawing 149243
or 149244.
ATEX/IECEx
II 3 G
Ex nA nC ic IIC T4 Gc
Ex ec nC ic IIC T4/T5 Gc
T4 @ Ta= -20˚C to +65˚C (-4˚F to
+149˚F)
When installed per drawing 149243
or 149244.
3500/22-AA-BB-CC 138131-AAA
A: Transient Data Interface Type
A: Cable Length
01 Standard (use for standard monitoring applications)
006 6 feet (1.8 m)
B: I/O Module Type
010 10 feet (3.0 m)
01 10Base-T/100Base-TX Ethernet
025 25 feet (12.2 m)
02 100Base-FX (Fiber Optic) Ethernet
040 40 feet (12.2 m)
10Base-T/100Base-TX Ethernet with gold-plated OK
03 050 50 feet (15.2 m)
Relay contacts
100Base-FX (fiber optic) Ethernet with gold-plated 075 75 feet (22.9 m)
04
OK Relay contacts 085 85 feet (25.9 m)
C: Agency Approval 100 100 feet (30.5 m)
00 None 120 120 feet (36.6 m)
01 CSA/NRTL/C (Class 1, Division 2) 150 150 feet (45.7 m)
02 Multi (CSA, ATEX, IECEx) 200 200 feet (61.0 m)
250 250 feet (76.2 m)
3500 22M Dynamic Data Enabling 320 320 feet (97. m)
Disk
Standard lengths for 10Base-T/100Base-TX cabling are
This disk enables the number of channels of shown above.
dynamic data (i.e., the ability to collect
waveforms) that the TDI will support. There are
Fiber Optic Cable
two levels of dynamic data. Steady-State points 100 Base-FX fiber optic cable with MT-RJ
are channels that collect waveform data due female connectors.
either to a software command or to an alarm
event, and therefore support current values,
scheduled waveform capture, and alarm data
161756-AAA
capture. Transient points provide all the
function of a Steady-State point with the A: Cable Length in feet up to 1300 ft (400m)
additional capability of waveform collection 010 to 500 10 ft. to 500 ft. in 10 ft. increments only
due to parameter variations such as machine 500 to 1300 500 ft. to 1300 ft. in 100 ft. increments only
speed.
Spares
3500/09-AAA-BBB
Standard Transient Data Interface Module
288055-01
with USB cable
A: Steady-State Points 123M4610* 10 foot A to B USB cable
000 to 672 Steady-State Points
Compatibility
When upgrading your 3500 rack from a 3500/20
RIM to a 3500/22 TDI, there may be 3500 M
modules (e.g. 3500/40M) that are not
compatible with the 3500/22. Please check with
[email protected] for additional details.
CAUTION
Upgrade advisory.
If the RIM I/O is left in the rack
when installing a new TDI, it will
damage the TDI.
Please perform the upgrade in
this order:
1)Remove RIM
2)Remove RIM I/O
3) Insert TDI I/O
4) Insert TDI.
Network Requirements
For complete information on network
requirements, refer to the 3500 Hardening Guide
[document 106M9733]. This document can be
requested at bntechsupport.com.