TCC Sample Generator Coordination

This document shows a one-line diagram of a power system with a 65kW generator and related equipment. It includes plots of fault current over time for different fault locations and protective device settings. The plots show the generator's fault current contribution and its ability to withstand a fault before sustaining damage. Circuit breaker interrupting ratings and cable ratings are also indicated.

Uploaded by

wenify
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views

TCC Sample Generator Coordination

This document shows a one-line diagram of a power system with a 65kW generator and related equipment. It includes plots of fault current over time for different fault locations and protective device settings. The plots show the generator's fault current contribution and its ability to withstand a fault before sustaining damage. Circuit breaker interrupting ratings and cable ratings are also indicated.

Uploaded by

wenify
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 100 Bus1 (Nom. kV=0.208, Plot Ref. kV=0.

208) 65KW GEN‐1/2
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

300 65KW GEN-1/2 300


FLA = 225.5

100 100

50 50
339.3 A, 26.3 s

30 30

65KW GEN-1/2
Stator Damage Curve
65 kW
10 10
65KW GEN‐1/2
5 5
CB-1/2 BREAKER
Seconds

Seconds
817.1 A, 2.88 s
Square-D Micrologic 3.3 (PP)
3 3
Sensor = 250
Ir = 225 A (225 Amps)
tr = 1.0
Ii = 4 x In (1000 Amps)

1 1

.5 .5

CU 100 ft
.3 .3
Cable1 - P
1 - 3/C 3/0 AWG 1‐3/C 3/0
Copper Rubber
Tc = 90C
.1
Plotted - 1 x 3/0 AWG
.1
0.208 kV
2451 A, 0.0495 s

.05 .05
CB‐1/2 BREAKER
.03 .03
CB-1/2 BREAKER - 3P 250 A
7.528kA @ 0.208kV
(Sym)

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 Bus1 (Nom. kV=0.208, Plot Ref. kV=0.208)

Protective Device Settings

Project: Date: 12-16-2020


Location: Rev: Base
Contract: Fault: Phase