Steam Systems II Transcript
Steam Systems II Transcript
Welcome to Steam Systems Part II: Impact of Boiler Sizing, Pressure, and Velocity.
Slide 2
Slide 3
For best viewing results, we recommend that you maximize your browser window now.
The screen controls allow you to navigate through the eLearning experience. Using your
browser controls may disrupt the normal play of the course. Click the paperclip icon, to
download supplemental information for this course. Click the Notes tab to read a
Slide 4
• Describe a useful measure of boiler efficiency and the impact of boiler size on
efficiency
• Describe the impact of air and non-condensable gases in the steam system
Slide 5
Steam has come a long way from its traditional associations with locomotives and the
technology. Without it, our food, textile, chemical, medical, power, heating and
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Steam provides a means of transporting controllable amounts of energy from a central,
automated boiler house, where it can be efficiently and economically generated, to the
point of use. Therefore, as steam moves around a plant, it can be considered to be both
For many reasons, steam is one of the most widely used commodities for conveying
heat energy. Its use is popular throughout industry for a broad range of tasks from
Slide 6
Boilers and all associated firing equipment should be designed and sized for maximum
efficiency. Boiler manufacturers have improved their equipment designs to provide this
maximum efficiency, when the equipment is new, sized correctly for the load conditions,
Slide 7
There are many different efficiencies that are claimed when discussing boilers but the
The first method is input-output. This is the ratio of kJ or BTU output divided by kJ or
The second method is heat balance. This method considers stack temperature and
losses, excess air levels, and radiation and convection losses. Therefore, the heat
balance calculation for fuel-to-steam efficiency is 100 minus the total percent stack
Slide 8
The sizing of a boiler for a particular application is not a simple task. Steam usages vary
based upon the percentage of boiler load that is used for heating versus process and
then combining those loads. These potentially wide load variations are generally
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
overcome by installing not just one large boiler but possibly two smaller units or a large
Slide 9
Boiler turndown is a ratio of the capacity at full fire as compared to its lowest firing
point before shut-down. Old boilers may have only two firing positions, low and high.
Newer boilers fire over a wider range of capacities. Depending on the controls, there
may be fixed setting points or fully variable settings. If a 1,200 kW or 4.1 million BTU/hr
boiler can fire as low as 120 kW or 410,000 BTUs/hr, then it has a 10:1 turndown ratio.
Turndown ratios are important for boilers that must operate over a wide range of
boiler sized to match the load. Boilers that have a wide turn-down ratio are therefore
typically more efficient at meeting variable loads. Boiler manufacturers will usually
recommend that the turndown ratio from maximum load to low load not exceed 4:1.
Turndown ratios exceeding 4:1 will increase the firing cycles and decrease efficiency.
Slide 10
Boilers must run a purge cycle at the start of each on-cycle to assure that there is no
accumulation of explosive gases in the fire box. Depending on the local code, air must
be blown through the boiler to perform a multiple air exchange of the fire box. This cold
air also removes heat from the boiler. Flames tend to be the most unstable and
radiation heat transfer is at its lowest at start-up. Therefore, boilers are the least
Reducing the number of on-cycles should therefore increase boiler efficiency over a
longer period of operating time. Boiler cycling also affects emissions. A boiler operating
at low load conditions can cycle as frequently as 12 times per hour, or 288 times a day.
With each cycle, pre- and post-purge air flow removes heat from the boiler and sends it
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
out the stack. This energy loss can be eliminated by keeping the boiler on at low firing
rates.
Note that every time the boiler cycles off, the start-up requires about one to two
minutes to place the boiler back on line. And, if there’s a sudden load demand, the start-
up sequence cannot be accelerated. Keeping the boiler on line assures the quickest
response to load changes. Frequent cycling also accelerates wear of boiler components.
increases.
Slide 11
Once the boiler or boilers have been sized for their steam output, with either joules or
BTUs or kg/hr or lb/hr, then the operating pressures have to be determined. Boiler
The steam distribution system is an important link between the steam source and the
steam user. It must supply good quality steam at the required rate and at the right
pressure. It must do this with a minimum of heat loss, and be economical in capital cost.
Slide 12
usage in the plant needing the highest pressure. We must remember however, that as
the steam passes through the distribution pipe work, it will lose some of its pressure
due to resistance to flow. Additionally, some of it will condense due to loss of heat from
the piping. Therefore, allowance should be made for this pressure loss when deciding
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
So when operating pressure is determined, the following is taken into account:
• The degree of pressure drop along the pipe due to resistance of flow (friction) and
Slide 13
actually required. However, selecting a boiler with a much greater operating pressure
than is required, and then operating it at a lower pressure will cause a loss in efficiency
the boiler’s design, even if this is higher than needed for the plant.
Pressure reduction to the levels needed by the steam using equipment can then take
place through pressure reduction stations close to the steam users themselves. The
individual reducing valves will be smaller in size, will tend to give tighter control of
reduced pressures, and will emit less noise. Problems of having a whole plant dependent
on a single reducing station are avoided, and the effects on the steam users of pressure
drops through the pipe work (which change with varying loads) will disappear.
Slide 14
So, why does a boiler operated at lower pressures lose efficiency? The efficiency loss
comes from increased radiation and convection losses. Another area of efficiency loss
comes from the lower quality (dryness) of the steam produced due to increased water
level in the boiler and the increased steam bubble size because of the lower operating
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
pressures internally. The reasoning behind this is clear when consideration is given to
what happens in the water and steam space in the boiler. Energy flows into the boiler
water through the outer surface of the tubes and if the water is already at saturation
temperature, bubbles of steam are produced. These bubbles then rise to the surface
Foaming occurs when steam bubbles arrive at the surface faster than they can burst,
Slide 15
The volume of a given weight of steam contained in the bubbles depends directly on
the pressure at which the boiler is operating. If this pressure is lower than the design
pressure, the volume in the bubbles is greater. It follows that as this volume increases,
the apparent water level is raised. The volume of the steam space above the water level
break the surface and less room for separation of water droplets is available above the
surface. Further, the steam moving towards the crown or steam take-off valve must
move at greater velocity with a higher volume moving across a smaller space. All of
these factors tend to encourage carryover of water droplets with the steam.
Priming occurs when the volume of the steam space is decreased and the speed of
steam across the surface increases, drawing foam and water droplets to the steam
outlet. A sudden increase in steam demand can then cause a slug of boiler water to
Slide 16
There are a number of reasons that favor carrying the steam close to the points of use
at a high pressure, near to that of the boiler. The use of such pressure means that the
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
size of the distribution mains is reduced. The smaller mains have smaller heat losses and
operating pressure that the vessel was designed for. The boiler’s operating pressure has
a definite impact on the potential of priming or foaming and carryover which can cause
serious problems not only for the system but for the boiler also.
Slide 17
Many of the boiler manufacturers today design their equipment to provide 99.5% dry
saturated steam to be generated and admitted into the distribution system. This means
that less than 1/2 of 1% of the volume exiting the boiler will be water, not steam. In
practice, steam often carries tiny droplets of water with it which cannot be described as
dry saturated steam. Steam quality is described by its dryness fraction, the portion of
completely dry steam present in the steam being considered. The steam becomes wet
if water droplets in suspension are present in the steam space, carrying no latent heat
content.
For example, the latent heat energy of 7 bars g or about 100 PSIG steam is 2048 kJ/kg
or 882 BTUs per pound (assuming 99.5% dryness) but, if this steam is only 95% dry,
then the heat content of this steam is only 0.95 X 2048 = 1946 kJ/kg or 0.95 X 882 =
838 BTUs per pound. The small droplets of water in wet steam have weight but occupy
negligible space. The volume of wet steam is less than that of dry saturated steam.
Therefore, steam separators are used at boiler off takes to ensure dry quality steam.
Slide 18
The velocity of the steam flow out of the boiler, at designed operating pressure, is
established by the outlet nozzle of the boiler itself. Target velocities of 30 meters per
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
second or 6,000 feet per minute (fpm) or less have become commonplace as design
criteria. These lower velocities provide for less noise, reduced pressure losses, more
efficient condensate drainage, reduced waterhammer potential, and less piping erosion.
Slide 19
temperature differences in the surroundings and the insulation losses, the steam gives
up its heat and condenses. Although it may not travel as fast as the steam, the
condensate (water) is still going to erode the bottom of the pipe. This erosion is
accelerated with the velocity of the steam, therefore the lower the steam velocity, the
Slide 20
Waterhammer occurs when a slug of water, pushed by steam pressure along a pipe
rather than draining away at the low points, is suddenly stopped by impact on a valve or
fitting such as a pipe bend or tee. The velocities that such slugs of water can achieve
are not often appreciated. They can be much higher than the normal steam velocity in
When these velocities are destroyed, the kinetic energy in the water is converted into
pressure energy and a pressure shock is applied to the obstruction. In mild cases, there
is noise and perhaps movement of the pipe. More severe cases lead to fracture of the
pipe or fittings with almost explosive effect, and consequent escape of the steam at the
fracture.
Slide 21
Waterhammer is avoided completely if steps are taken to ensure that water is drained
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Careful consideration of steam main drainage can help in avoiding damage to the
steam main and possible injury or even loss of life. Steam main drainage offers a better
Slide 22
As a review, it is important that the steam velocity, the piping and the nozzle sizing, be
The appropriately sized pipe must be chosen to carry the required amount of steam at
the local pressure. An undersized pipe means high pressure drops and velocities, noise,
and erosion. An oversized pipe is unnecessarily expensive to install and heat losses from
Slide 23
Steam pipes may be sized so that the pressure drop along them is below an acceptable
limit, or so that velocities along them are not too high. In saturated steam lines,
reasonable maximum velocities are often taken between 24 and 36 meters per second
or 4,800 and 7,200 ft per minute. These velocities should only be exceeded where the
Here is an exercise for you to try using the chart. Steam flow is 450 kg/h. Find pipe
size for a system operating at 7 bars g. Or if you prefer to work in US units, steam flow
is 1,000 lb/h. Find pipe size for a system operating at 100 psig. The answer is given in
the document titled Steam Velocity Chart Example, which you can download from the
paperclip icon.
Slide 24
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
The steam system piping and associated equipment, containing this high heat energy
source (steam), will constantly be a source of radiation losses. A simple but often
overlooked energy savings is to insulate all the piping, steam and condensate, and all
temperature of 15°C will radiate about 2700 KJ per hour of operation. The latent heat
In US units, a single foot of 3” pipe with 100 psig steam in it exposed to an ambient
temperature of 60 °F will radiate 778 BTUs per hour of operation. The latent heat
Nearly 1.5 kg of steam per hour per metre of pipe is condensed just in distributing this
valuable energy supply to the point of usage. This is equivalent to nearly a pound of
steam per hour per foot of pipe. Flanges, valves, strainers and equipment will waste
much more energy than a single foot of pipe. The net effect is the consumption of
For more information about this, please click the paperclip icon and download the
Slide 25
We know that when steam comes into contact with a cooler surface, it gives up its
latent heat and condenses. As condensation takes place, the condensate begins to form
a film of water. It is a fact that water has a surprisingly high resistance to heat transfer.
A film of water only 0.25mm or 1/100 of an inch thick offers the same resistance to
heat transfer as a 12.5 mm or 1/2 inch thick layer of iron or a 127 mm or 5 inch thick
layer of copper. The air and other non-condensable gases in the steam cause a variety
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
of problems to steam systems. Foremost is the reduction of area to deliver the steam.
Air is a simple bi-product of steam generation. It is in all steam systems and should be
dealt with accordingly. The problem occurs when the air collects in the system.
Slide 26
Air and other non-condensable gases are released when steam is generated and passed
down the distribution with the steam. It will collect in areas of high steam consumption
such as heat exchangers, but will also collect at high points and at the end of the steam
piping. If a steam line feeds a series of heat exchangers, such as cooking kettles the air
collects at the end of the main line. The last kettle, therefore, would be fed with a
Slide 27
Air cannot hold the temperature or latent heat of steam. It will, therefore, initially cause
accepted that a thin layer of air only 1.0 mm or 1/25th of an inch thick can offer the
same resistance to the flow of heat as a layer of water 25 mm or 1 inch thick. Even a
small amount of air in a steam system will cause fairly drastic temperature losses. Let’s
look at an example of this. 7 bars g or 100 PSIG of saturated steam has a temperature
of 170°C/338°F. If, in this steam, there existed a 10% by volume mixture of air, the
Another major problem with air in the steam system is that it will be absorbed into the
condensate. This reduces the pH of the condensate and creates a substance known as
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
carbonic acid. The acidity of the condensate will then attack the piping, heat exchange
equipment, or any other part of the steam system that it comes into contact with.
Slide 28
The use of Thermostatic Air Vents will help remove the accumulating air and rid the
system of the adverse effects. Air Vents are nothing more than thermostatically-
actuated steam traps positioned in the system where the air will collect. Proper design
procedures require air vents to be located at high points, at the end of the steam main
We will see more about the effective distribution of steam in the next class in this
series.
Slide 29
efficiency
efficiency
balance method
• Turndown ratios are important for boilers that must operate over a wide
range of capacities/demands
determined
• Running a purge cycle at the beginning of each on-cycle is important to rid the
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
• An over-sized boiler will turn off and on many times per day, and every purge
Slide 30
• It also produces lower quality, wet steam due to carryover and is at risk
of priming
• It is best to carry steam at high pressure to the point of usage- allowing for
smaller distribution mains with lower capital cost and less heat loss
• Temperature differences in the system cause steam to give up its heat and
condense
• Lower steam velocities result in less erosion, less pressure loss, better
avoided if steps are taken to ensure water is drained away before accumulating
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
• Air and other non-condensable gases are released when steam is generated and
Thermostatic air vents will help remove accumulating air and rid the system of adverse
effects
Slide 31
Slide 32
To test your knowledge of the course material, click the Knowledge Checkpoint
The Knowledge Checkpoint link is located under BROWSE CATALOG on the left
Slide 33
We are dedicated to providing you with relevant, cutting edge education on topics
pertinent to energy efficiency. Please take our brief survey and tell us how we’re doing.
How do you begin? It’s easy! Click on the “Home” icon, located in the right corner of
your screen. Click on the “Course Surveys" link on the left side of the screen under
“Browse Catalog.” Select the course title you have just completed and take our brief
survey.
©2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.