0% found this document useful (0 votes)
416 views

Manual Modbus TCP Communication Module 3RW5 en-US

Siemens Sirius Soft Starter Communication Module Modbus TCP for 3RW5
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
416 views

Manual Modbus TCP Communication Module 3RW5 en-US

Siemens Sirius Soft Starter Communication Module Modbus TCP for 3RW5
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 106

Siemens Industry Online

___________________
Support 1

___________________
Safety information 2

Industrial Controls
___________________
Description 3

___________________
Mounting and dismantling 4
Soft starters and solid-state
switching devices
___________________
Connecting 5
SIRIUS 3RW5 Modbus TCP
communication module
___________________
Configuring 6
Manual

___________________
Messages and diagnostics 7

___________________
Maintenance and service 8

___________________
Technical data 9

___________________
Dimension drawings 10

___________________
Circuit diagrams 11

___________________
Appendix A

03/2018
A5E43676481002A/RS-AA/001
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG A5E43676481002A/RS-AA/001 Copyright © Siemens AG 2018.


Division Digital Factory Ⓟ 03/2018 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Siemens Industry Online Support ............................................................................................................ 7


1.1 Technical Assistance ................................................................................................................ 9
1.2 Additional documentation ......................................................................................................... 9
1.3 Siemens Industry Online Support app ....................................................................................11
2 Safety information ................................................................................................................................. 13
2.1 Security information ................................................................................................................13
2.2 ESD Guidelines .......................................................................................................................14
2.3 Data security in automation ....................................................................................................16
2.4 Recycling and disposal ...........................................................................................................17
3 Description ............................................................................................................................................ 19
3.1 Hardware configuration ...........................................................................................................20
3.2 Modbus TCP functions............................................................................................................21
3.3 frame structure ........................................................................................................................23
3.4 Interaction interfaces...............................................................................................................24
3.5 Operating modes and master control function ........................................................................25
3.6 Modbus TCP cable .................................................................................................................27
3.7 Accessories .............................................................................................................................28
3.7.1 SIRIUS Soft Starter ES (TIA Portal) .......................................................................................28
4 Mounting and dismantling ..................................................................................................................... 29
4.1 Mounting the 3RW5 communication module ..........................................................................29
4.1.1 Mounting the 3RW5 communication module on the 3RW5 Soft Starter ................................29
4.1.2 Break out the cover of the slot ................................................................................................30
4.1.3 Mount the 3RW5 communication module in the slot of the 3RW5 Soft Starter ......................32
4.2 Removing the 3RW5 communication module ........................................................................33
5 Connecting ........................................................................................................................................... 35
5.1 Connecting the bus connector ................................................................................................35
5.2 Removing the bus connector ..................................................................................................37
6 Configuring ........................................................................................................................................... 39
6.1 Configuring the 3RW5 Soft Starter in the Modbus TCP system. ............................................39
6.2 Configuring the 3RW5 Soft Starter .........................................................................................41
6.2.1 Configuring 3RW5 soft starters without 3RW5 HMI High Feature .........................................41
6.2.2 Configuring 3RW5 soft starters with the aid of a 3RW5 HMI High Feature............................42
6.2.3 IP parameters .........................................................................................................................44
6.3 Operation on failure of the bus connection to the controller ...................................................45

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 3
Table of contents

7 Messages and diagnostics .................................................................................................................... 47


7.1 LED display ............................................................................................................................ 48
7.1.1 Device LEDs on the 3RW5 communication module .............................................................. 48
7.1.2 Status and error displays ....................................................................................................... 49
7.2 Function Codes ...................................................................................................................... 51
7.2.1 Function Codes 01 (Read Coils) and 02 (Read Discrete Inputs) .......................................... 53
7.2.2 Function Codes 03 (Read Holding Registers) and 04 (Read Input Registers) ...................... 54
7.2.3 Function Code 05 (Write Single Coil)..................................................................................... 55
7.2.4 Function Code 06 (Write Single Register) ............................................................................. 56
7.2.5 Function Code 15 (Write Multiple Coils) ................................................................................ 57
7.2.6 Function Code 16 (Write Multiple Registers) ......................................................................... 58
7.2.7 Function Code 23 (Read/Write Multiple Registers) ............................................................... 59
7.3 Error codes ............................................................................................................................. 61
7.3.1 Exception Responses ............................................................................................................ 61
7.3.2 Supported error codes ........................................................................................................... 61
7.4 Faults and remedial measures............................................................................................... 62
7.5 Messages about the mode ..................................................................................................... 62
8 Maintenance and service ...................................................................................................................... 63
8.1 Firmware update .................................................................................................................... 63
8.1.1 Perform the firmware update using micro SD memory card (3RW5 HMI High Feature)....... 64
8.2 Replacing the 3RW5 communication module ........................................................................ 65
8.3 Restoring factory settings ...................................................................................................... 66
9 Technical data ...................................................................................................................................... 67
9.1 Technical data in Siemens Industry Online Support .............................................................. 67
10 Dimension drawings .............................................................................................................................. 69
10.1 CAx data ................................................................................................................................ 69
11 Circuit diagrams .................................................................................................................................... 71
11.1 CAx data ................................................................................................................................ 71
A Appendix .............................................................................................................................................. 73
A.1 Data formats ........................................................................................................................... 73
A.1.1 Current values as percentages .............................................................................................. 73
A.1.2 Statistic data........................................................................................................................... 74
A.1.3 Maximum pointer.................................................................................................................... 74
A.2 Data tables ............................................................................................................................. 75
A.2.1 Byte arrangement................................................................................................................... 75
A.2.2 Specifications ......................................................................................................................... 75
A.2.3 Memory image ....................................................................................................................... 76
A.2.4 Node flash test ....................................................................................................................... 76
A.2.5 I&M0 - Communication .......................................................................................................... 77
A.2.6 I&M0 - Basic unit .................................................................................................................... 77
A.2.7 I&M1 - Basic unit .................................................................................................................... 78
A.2.8 I&M2 - Basic unit .................................................................................................................... 78
A.2.9 I&M3 - Basic unit .................................................................................................................... 78

SIRIUS 3RW5 Modbus TCP communication module


4 Manual, 03/2018, A5E43676481002A/RS-AA/001
Table of contents

A.2.10 I&M0 - HMI HF ........................................................................................................................79


A.2.11 Energy management...............................................................................................................79
A.2.12 Process image input (PII) .......................................................................................................80
A.2.13 Process image output (PIQ) ...................................................................................................81
A.2.14 Soft starter diagnostics ...........................................................................................................82
A.2.15 Measured values .....................................................................................................................86
A.2.16 Statistic data ...........................................................................................................................87
A.2.17 Maximum pointer ....................................................................................................................88
A.2.18 Parameters .............................................................................................................................89
A.2.19 Communication parameters ....................................................................................................99
A.2.20 HMI diagnostics ....................................................................................................................100
A.2.21 HMI basic parameters ...........................................................................................................101
Glossary ............................................................................................................................................. 103
Index................................................................................................................................................... 105

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 5
Table of contents

SIRIUS 3RW5 Modbus TCP communication module


6 Manual, 03/2018, A5E43676481002A/RS-AA/001
Siemens Industry Online Support 1
Information and service
At Siemens Industry Online Support you can obtain up-to-date information from our global
support database quickly and simply. To accompany our products and systems, we offer a
wealth of information and services that provide support in every phase of the lifecycle of your
machine or plant – from planning and implementation and commissioning, right through to
maintenance and modernization:
● Product support
● Application examples
● Services
● Forum
● mySupport
Link: Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/)

Product support
Here you will find all the information and comprehensive know-how for your product:
● FAQs
Our replies to frequently asked questions.
● Manuals/operating instructions
Read online or download, available as PDF or individually configurable.
● Certificates
Clearly sorted according to approving authority, type and country.
● Characteristics
For support in planning and configuring your system.
● Product announcements
The latest information and news concerning our products.
● Downloads
Here you will find updates, service packs, HSPs and much more for your product.
● Application examples
Function blocks, background and system descriptions, performance statements,
demonstration systems, and application examples, clearly explained and represented.
● Technical data
Technical product data for support in planning and implementing your project.
Link: Product support (https://support.industry.siemens.com/cs/ww/en/ps)

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 7
Siemens Industry Online Support
1.1 Technical Assistance

mySupport
With "mySupport", your personal work area, you get the very best out of your Industry Online
Support experience. Everything enables you to find the right information - every time.
The following functions are now available:
● Personal Messages
Your personal mailbox for exchanging information and managing your contacts
● Requests
Use our online form for specific solution suggestions, or send your technical inquiry
directly to a specialist in Technical Support
● Notifications
Make sure you always have the latest information - individually tailored to your needs
● Filter
Simple management and re-use of your filter settings from Product Support and the
Technical Forum
● Favorites / Tagging
Create your own knowledge database by assigning "Favorites" and "Tags" to documents
– simply and efficiently
● Entries last viewed
Clear presentation of your last viewed entries
● Documentation
Configure your individual documentation from different manuals – quickly and without
complications
● Personal data
Change personal data and contact information here
● CAx data
Simple access to thousands of items of CAx data such as 3D models, 2D dimension
drawings, EPLAN macros, and much more

SIRIUS 3RW5 Modbus TCP communication module


8 Manual, 03/2018, A5E43676481002A/RS-AA/001
Siemens Industry Online Support
1.1 Technical Assistance

1.1 Technical Assistance


Using the support request form in Online Support you can send your query directly to our
Technical Assistance. After describing your query in a few guided steps, you will immediately
be provided with possible suggestions for solving the problem.

Technical Assistance: Telephone: +49 (0) 911-895-5900 (8:00 a.m. - 5:00 p.m. CET) Fax: +49 (0)
911-895-5907
E-mail (mailto:[email protected])
Internet
(https://support.industry.siemens.com/my/WW/en/requests#createRequest)

1.2 Additional documentation

Manuals / online help


At this point, you will find further manuals and online help that may be of interest to you for
your automation system. They are available to download from the Internet free of charge.
You can create your own individual system documentation in mySupport.
● 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404)
● Manual for the 3RW52 soft starter
(https://support.industry.siemens.com/cs/ww/en/view/109753751)
● Manual for the 3RW55 soft starter
(https://support.industry.siemens.com/cs/ww/en/view/109753752)
● Manuals for the 3RW5 soft starter
(https://support.industry.siemens.com/cs/ww/en/ps/16212/man)
● Manual for the 3RW5 Modbus TCP communication module
(https://support.industry.siemens.com/cs/ww/en/view/109753755)
● Manual for the 3RW5 PROFINET communication module
(https://support.industry.siemens.com/cs/ww/en/view/109753754)
● Manual for the 3RW5 PROFIBUS communication module
(https://support.industry.siemens.com/cs/ww/en/view/109753753)
● "System Software for S7-300/400, System and Standard Functions" reference manual
(https://support.industry.siemens.com/cs/ww/en/view/1214574)
● Online help for SIRIUS Soft Starter ES (TIA Portal)
● Online help for STEP 7
● EMC Guide (http://www.siemens.com/emc-guideline)
● UL Guide (http://www.siemens.com/UL508A)
● IEC Guide (http://www.siemens.com/iec60204)

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 9
Siemens Industry Online Support
1.2 Additional documentation

Interesting links
● Manuals in Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/man)
● FAQs on 3RW5 Soft Starters
(https://support.industry.siemens.com/cs/ww/en/ps/16212/faq)
● Downloads for 3RW5 Soft Starters
(https://support.industry.siemens.com/cs/ww/en/ps/16212/dl)
● Product support for STEP 7 (TIA Portal)
(https://support.industry.siemens.com/cs/ww/en/ps/14672)
● SIMATIC Modbus/TCP - The easy way to interface SIMATIC controllers to multi-vendor
systems (http://w3.siemens.com/mcms/human-machine-interface/en/customized-
products/customized-software/Pages/default.aspx?tabcardname=simatic%20modbus/tcp)
● FAQ "How do you program and assign parameters to the Modbus/TCP communication
between S7-1500 CPU and S7-1200 CPU?
(https://support.industry.siemens.com/cs/ww/en/view/102020340)
● Premium Efficiency - Efficiency class IE3
(http://w3.siemens.com/mcms/topics/en/application-
consulting/ie3ready/Pages/Default.aspx)

SIRIUS 3RW5 Modbus TCP communication module


10 Manual, 03/2018, A5E43676481002A/RS-AA/001
Siemens Industry Online Support
1.3 Siemens Industry Online Support app

1.3 Siemens Industry Online Support app

Siemens Industry Online Support app


You can use the Siemens Industry Online Support app to access all the device-specific
information available on the Siemens Industry Online Support portal for a particular article
number, including operating instructions, manuals, datasheets, FAQs etc.
The Siemens Industry Online Support app is available for iOS, Android or Windows Phone
devices. You can download the app from the following links:

Link for Android Link for iOS Link for Windows Phone

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 11
Siemens Industry Online Support
1.3 Siemens Industry Online Support app

SIRIUS 3RW5 Modbus TCP communication module


12 Manual, 03/2018, A5E43676481002A/RS-AA/001
Safety information 2
2.1 Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines, and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be
connected to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or network
segmentation) are in place.
For additional information on industrial security measures that may be implemented, please
visit:
https://www.siemens.com/industrialsecurity
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customer’s exposure
to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
https://www.siemens.com/industrialsecurity.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 13
Safety information
2.2 ESD Guidelines

2.2 ESD Guidelines

ESD
All electronic modules are equipped with large-scale integrated ICs or components. Due to
their design, these electronic elements are highly sensitive to overvoltage, and thus to any
electrostatic discharge.
The acronym ESD has become the established designation for such Electrostatic Sensitive
Devices. This is also the international abbreviation for such devices.
ESD modules are identified by the following symbol:

NOTICE
Electrostatic discharge
ESD devices can be destroyed by voltages well below the threshold of human perception.
These static voltages develop when you touch a component or electrical connection of a
device without having discharged your own body. The electrostatic discharge current may
lead to latent failure of a module, that is, this damage may not be apparent immediately, but
in operation may cause malfunction.

SIRIUS 3RW5 Modbus TCP communication module


14 Manual, 03/2018, A5E43676481002A/RS-AA/001
Safety information
2.2 ESD Guidelines

Electrostatic charging
Anyone who is not connected to the electrical potential of their surroundings can be
electrostatically charged.
The diagram below shows the maximum electrostatic voltage which may build up on a
person coming into contact with the materials specified in the diagram. These values
correspond to IEC 801-2 specifications.

Basic protective measures against electrostatic discharge


● Make sure the grounding is good:
When working with electrostatically sensitive devices, make sure that the person, the
workstation and the packaging are properly grounded. In this way, you can avoid
becoming electrostatically charged.
● Avoid direct contact:
You should only touch ESD components if this is unavoidable (for example, during
maintenance work). Handle the modules without touching any chip pins or PCB traces. In
this way, the discharged energy cannot reach or damage sensitive devices.
Discharge your body before you start taking any measurements on a module. Do so by
touching grounded metallic parts. Use only grounded measuring instruments.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 15
Safety information
2.3 Data security in automation

2.3 Data security in automation


The topic of data security and access protection (security) is becoming more and more
important in industrial environments. Increased networking of entire industrial plants, vertical
integration and networking of the levels within a company, and new technologies, such as
remote maintenance, are resulting in more increased requirements for protection of the
industrial plant. Security is the generic term for all protection measures:
● Loss of confidentiality due to unauthorized accessing of data
● Loss of integrity due to data manipulation
● Loss of availability due to destruction of data
To provide protection from manipulation in sensitive plant and production networks, it is not
enough to apply data security solutions for offices to industrial applications without any
adaptation.

Requirements
The special requirements of communication in an industrial environment
(e.g. communication in real time) result in additional requirements for security in industrial
use:
● Protection against interaction between automated cells
● Protection of network segments
● Protection from unauthorized access
● Scalability of the security functionality
● No influence on the network structure.

Threats
Threats can arise from external and internal manipulation. Loss of data security is not always
caused by deliberate actions.
Internal threats arise due to:
● Technical faults
● Operating errors
● Errors in programs
This internal hazards are compounded by external threats. The external hazards do not differ
from the known threats in the office environment:
● Computer viruses and computer worms
● Trojan horses
● Unauthorized access
● Password phishing.
Password phishing means attempting to get a user to divulge access data and passwords by
masquerading as a different identity in an e-mail.

SIRIUS 3RW5 Modbus TCP communication module


16 Manual, 03/2018, A5E43676481002A/RS-AA/001
Safety information
2.4 Recycling and disposal

Precautions
The most important precautions against manipulation and loss of data security in an
industrial environment are:
● Filtering and verification of data traffic through virtual private networks (VPN). A virtual
private network is used to exchange private data in a public network (e.g. the Internet).
The most common VPN technology is IPsec. IPsec is a collection of protocols based on
the IP protocol at the network layer.
● Segmentation into protected automation cells. The aim of this concept is to protect
devices in the network through security modules. A group of protected devices forms a
protected automation cell. Only security modules in the same group or the device
protected by you can be interchanged.
● Authentication (identification) of the networked devices. The security modules identify
themselves to each other via a secure (encrypted) channel using authentication
procedures. This prevents access to a protected segment by unauthorized persons from
outside.
● Encryption of the data traffic. The confidentiality of the data is ensured by encrypting the
data traffic. For this purpose, every security module is given a VPN certificate which
includes the encryption key.

VDI guidelines on information security in industrial automation


The VDI/VDE Association of German Engineers "Measurement and Automation" has
published a guideline for implementation of a security architecture in the industrial
environment in the VDI guideline "VDI/VDE 2182 Sheet 1, IT Security for Industrial
Automation - General Model". You will find the guideline under "VDI Standards" on the VDI
home page: VDI guidelines (http://www.vdi.de/43460.0.html)

2.4 Recycling and disposal


For environmentally friendly recycling and disposal of your old device, please contact a
company certified for the disposal of electronic waste and dispose of the device in
accordance with the regulations in your country.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 17
Safety information
2.4 Recycling and disposal

SIRIUS 3RW5 Modbus TCP communication module


18 Manual, 03/2018, A5E43676481002A/RS-AA/001
Description 3
You can equip SIRIUS soft starters of the 3RW5 series with an optional
3RW5 communication module and therefore also with network functionality. Using the
3RW5 communication module, you integrate the 3RW5 soft starters into the associated
network environment with their complete functionality.
The 3RW5 soft starters are equipped with a slot for fitting the 3RW5 communication
modules.

Preconditions for using the 3RW5 communication modules on the 3RW5 soft starter
● Programmable logic controller (PLC, e.g. SIMATIC S7-1500) or a PC as the Modbus
client
● For use with a PLC: PC / programming device with installed configuration software of
controller (e.g. STEP 7)
● Parameterization software (e.g. SIRIUS Soft Starter ES (TIA Portal), only possible via
local interface on the 3RW5 HMI High Feature) (optional)
● Basic knowledge of the following areas:
– General electrical engineering
– Drive technology
– Automation technology
– Handling the automation system and the software used

Target group
The manual is intended for everyone involved in the following tasks:
● Planning and configuring systems
● Installation
● Commissioning
● Service and maintenance

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 19
Description
3.1 Hardware configuration

3.1 Hardware configuration


3RW5 Modbus TCP communication module with article number 3RW5980-0CT00:

① Mounting hole
② LED display
③ Plug-in connection to the basic unit
④ Fieldbus connection (RJ45 socket)

SIRIUS 3RW5 Modbus TCP communication module


20 Manual, 03/2018, A5E43676481002A/RS-AA/001
Description
3.2 Modbus TCP functions

3.2 Modbus TCP functions

Modbus TCP
Modbus TCP is a bus system according to the standard IEC 61784-2 CPF 15/1 with the
transmission protocol Modbus. Modbus TCP is based on a client/server architecture and
transmits data linearly.
As the client, the controller has the initiative in data transmission and transmits requests to
the server. The requests contain the Function Code and additional data. A server cannot
transmit information to the client autonomously. The 3RW5 soft starter works as the server
and can only respond to the requests of the client. The 3RW5 soft starter supplies the
relevant feedback messages to the bits and registers retrieved by the client or takes over the
bits and registers written by the client into the internal memory. No requests can be
transferred from server to server.
The server processes the requests of the client and answers within a certain time with one of
the following acknowledgments:
● Requested data
● Error code
You can find more information about the telegram structure in chapter "frame structure
(Page 23)".

Assignment of data to Modbus addresses with Modbus TCP


All data of the 3RW5 Soft Starter are available in datasets or in the process image.
To be addressable via Modbus, the data in these datasets or in this process image are
converted to Modbus data formats.

Data access to Data type according to Modbus nomenclature


Read-only bits Discrete Inputs
Readable and writable bits Coils
Read-only data sets and words (16-bit) Input Registers
Read/write data sets and words Holding Registers

1 Coil corresponds to 1 bit.


1 Register corresponds to 1 word (2 bytes).
You can find more information about access to the memory areas in chapter
"Function Codes (Page 51)".

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 21
Description
3.2 Modbus TCP functions

Connection monitoring function - "TCP keep-alive monitoring"


To avoid blocking the communication link permanently if the communication partner fails,
Modbus TCP provides the "TCP keep-alive monitoring" function for monitoring the
connection.
The following parameters can be permanently set for this purpose:
● Keep-alive time: 300 s
● Keep-alive maximum attempts: 1
● Keep-alive interval: 75 s
If no TCP data transmission is detected within 375 seconds, the "TCP keep-alive monitoring"
function signals connection broken and ends the communication link automatically. On a
broken connection, the 3RW5 soft starter responds as set in parameter "Response to
CPU/Master Stop" (Page 45).

Connection monitoring function - Access monitoring of the control source


An independent connection monitoring function monitors the write access of the authorized
Modbus client within the access monitoring time. Only the Modbus client, which is the first to
set up a communication link to the server, is authorized for this access.
A write access of the Modbus client to the server (process image outputs (PIQ), parameter)
must be repeated regularly. If the write process is not repeated for the duration of the access
monitoring time, the 3RW5 soft starter interprets this condition as a broken connection to the
Modbus client. The 3RW5 soft starter responds as set in the parameter "Response to
CPU/Master Stop" (Page 45).
You will find the "Access monitoring time" parameter in the data table "Communication
parameters" (Page 99). The factory setting is 5 seconds.

SIRIUS 3RW5 Modbus TCP communication module


22 Manual, 03/2018, A5E43676481002A/RS-AA/001
Description
3.3 frame structure

3.3 frame structure


The data traffic between the client and the server and the corresponding answer from the
server to the client starts with the Address Field, followed by the Function Code. Following
this, the data (Data) are transferred. The structure of the Data depends on the function code
used. In the response telegram of the server to the client, the same Address Field and the
same Function Code are entered. The Data are filled according to the requested data.

● Address Field: This address is used to address a defined server on the bus.
● Function Code: Defines the server function requested with the telegram.
● Data = Telegram data: Function-code-dependent administration data and net data. When
transferring the register data, the high byte is always transferred first, followed by the low
byte, in accordance with the Modbus specification.
You will find more information on Function Codes in Chapter Function Codes (Page 51).

Exception Responses
You will find more information on exception responses in Chapter Error codes (Page 61).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 23
Description
3.4 Interaction interfaces

3.4 Interaction interfaces

① SIRIUS 3RW5 soft starter (illustration similar)


② LED display on 3RW5 soft starter
③ Modbus TCP (via 3RW5 Modbus TCP communication module)
④ PC / programming device with configuration software of controller (e.g. STEP 7)
⑤ Programmable logic controller (e.g. SIMATIC S7-1500)
⑥ PC with Modbus client
⑦ Motor
⑧ PC with SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
⑨ 3RW5 HMI High Feature (accessories depend on 3RW5 soft starter)
⑩ 3RW5 HMI Standard (accessories depend on 3RW5 soft starter)

Options for data transfer

3RW5 HMI High 3RW5 HMI SIRIUS Soft Starter Fieldbus via 3RW5 3RW5 soft starter
Feature Standard ES (TIA Portal)1) communication
module
Monitoring ✓ ✓ ✓ ✓ LEDs
(via user program)
Diagnostics ✓ ✓ ✓ ✓ LEDs
Control ✓ ✓ ✓ ✓ Via input IN
Parameterization o - o o o

o: Depends on the 3RW5 soft starter


1) via local interface on the 3RW5 HMI High Feature

SIRIUS 3RW5 Modbus TCP communication module


24 Manual, 03/2018, A5E43676481002A/RS-AA/001
Description
3.5 Operating modes and master control function

3.5 Operating modes and master control function


The following modes are available (in ascending order of priority):

Operating mode Control source Control of the 3RW5 soft starter Priority
Automatic Fieldbus Modbus client (e.g. PLC) controls Lowest
Manual - - Connection abort (depending on the 3RW5 soft starter -
operation and parameterization)
local Input controlled Digital inputs Input actions control ↓
3RW5 HMI controlled 3RW5 HMI 3RW5 HMI controlled ↓
PC controlled Local interface SIRIUS Soft Starter ES (TIA Portal) controlled Highest

If the connection to the control source is aborted, the control priority automatically switches
back to the lowest priority of the current mode.
Depending on the 3RW5 soft starter and the parameter assignment, the lowest priority in
operating mode "Manual operation local" is "Input controlled" in the following cases:
● 3RW52 soft starter
● 3RW55 soft starter with one of the following parameter assignments:
– Input action "Manual operation local" is parameterized and switched on.
– A controlling input action (e.g. "Motor CW") is parameterized, but the input action
"Manual operation local" is not parameterized.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 25
Description
3.5 Operating modes and master control function

Sets the operating mode


A higher-priority mode can actively take over as master control from a lower-priority mode at
any time; the reverse is not possible.
The master control function can only be returned to the mode with the lowest priority. Control
sources with higher priority must take the master control function from the mode with the
lowest priority.
A mode with lower priority can only take the master control function back while the motor is
switched off.
The mode with higher priority takes over or receives the master control function from the
current mode in the following ways:
● The mode with higher priority actively takes over the master control function:
– Digital inputs: By switching on the input action "Manual operation local", if this is
parameterized (depending on the 3RW5 soft starter).
– 3RW5 HMI: With the action "LOCAL / REMOTE"
– SIRIUS Soft Starter ES (TIA Portal)
● If the input action "Manual operation local" is not parameterized or available (depending
on the 3RW5 soft starter), the digital inputs obtain the master control function from a
mode of lower priority in one of the following ways:
– Via the "Manual operation local - input controlled" bit in the data table
"Process image outputs (PIQ)" (Page 81).
The mode with the lowest priority receives or takes over the master control function from the
current mode in the following ways:
● The mode with higher priority actively returns the master control function:
– Digital inputs: By switching off the input action "Manual operation local", if this is
parameterized (depending on the 3RW5 soft starter).
– 3RW5 HMI: With the action "LOCAL / REMOTE"
– SIRIUS Soft Starter ES (TIA Portal)
● If the input action "Manual operation local" is not parameterized or available (depending
on the 3RW5 soft starter), the mode with the lowest priority can actively obtain the master
control function from the digital inputs or on connection abort:
– Via the "Manual operation local - input controlled" bit in the data table
"Process image outputs (PIQ)" (Page 81).

Messages about the mode


You will find more information on messages in chapter Messages about the mode (Page 62).

SIRIUS 3RW5 Modbus TCP communication module


26 Manual, 03/2018, A5E43676481002A/RS-AA/001
Description
3.6 Modbus TCP cable

3.6 Modbus TCP cable


For connection, use only angled industrial bus connectors with a RJ45 socket for Industrial
Ethernet.

Illustration similar

NOTICE
Damage to the cable, bus connector and 3RW5 communication module
If you use unsuitable bus connectors, the following can happen:
• The hinged cover of the 3RW5 soft starter does not close.
• The connecting cable is impermissibly bent.
• The bus connector or the 3RW5 communication module is damaged.
Use bus connectors with a right-angled cable outlet and dimensions that match the
recommended bus connector.

Recommended bus connector

Article number Description


6GK1901-1BB20-2AA0 Industrial Ethernet FastConnect RJ45 Plug 90 2x 2, RJ45 plug connector
(10/100 Mbit/s) with rugged metal housing and FC connecting method, for
IE FC cable 2x 2; 90° cable outlet

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 27
Description
3.7 Accessories

3.7 Accessories

3.7.1 SIRIUS Soft Starter ES (TIA Portal)


SIRIUS Soft Starter ES (TIA Portal) is the central software for configuration, commissioning,
operation, and diagnostics of 3RW5 soft starters.
You connect your PC / programming device to the 3RW5 soft starter via the local interface
on the 3RW5 HMI High Feature.
By displaying all operating data, service data and diagnostics data, SIRIUS Soft Starter ES
(TIA Portal) supplies reliable information, helping to avoid faults, or to quickly locate and
eliminate them if they occur.
SIRIUS Soft Starter ES (TIA Portal) can be downloaded from the Internet
(https://support.industry.siemens.com/cs/ww/en/ps/24231/dl).

SIRIUS 3RW5 Modbus TCP communication module


28 Manual, 03/2018, A5E43676481002A/RS-AA/001
Mounting and dismantling 4
4.1 Mounting the 3RW5 communication module

4.1.1 Mounting the 3RW5 communication module on the 3RW5 Soft Starter

Requirements
● 3RW5 soft starter

NOTICE
Damage to property due to electrical voltage
Switch off the power to the 3RW5 soft starter before starting work
(main and control supply voltage).

Procedure
1. Break out the cover of the slot. (Page 30)
2. Mount the 3RW5 communication module. (Page 32)

Result
You have mounted the 3RW5 communication module in the 3RW5 soft starter, which you
can connect to the fieldbus (Page 35) via the 3RW5 communication module.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 29
Mounting and dismantling
4.1 Mounting the 3RW5 communication module

4.1.2 Break out the cover of the slot

Requirements
● Sharp, robust knife or diagonal cutter

Procedure

CAUTION
Sharp edges.
Risk of injury from sharp edges or burrs.
Make sure that there are no sharp-edged burrs on the connecting webs and the preset
breaking points after knocking out. If necessary, deburr these spots professionally to avoid
injury.

NOTICE
Damage to property
Hold the cover tight so that it does not fall into the interior.
Ensure that no further foreign matter can get into the slot.

SIRIUS 3RW5 Modbus TCP communication module


30 Manual, 03/2018, A5E43676481002A/RS-AA/001
Mounting and dismantling
4.1 Mounting the 3RW5 communication module

Illustration similar
A View at an angle from above.
B View at an angle from below.

1. Cut through the connecting webs of the cover. Use a sharp and robust knife or a diagonal
cutter.
2. Lift the cover with a finger on the top side of the device and break the cover at the preset
breaking point toward the outside.
3. Press the second part of the cover toward the interior of the device and break the cover
inward at the preset breaking point.

Result
You can mount the 3RW5 communication module in the slot of the 3RW5 soft starter.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 31
Mounting and dismantling
4.1 Mounting the 3RW5 communication module

4.1.3 Mount the 3RW5 communication module in the slot of the 3RW5 Soft Starter

Requirements
● Screwdriver PH1

Note
A magnetic screwdriver simplifies assembly.

Procedure

Illustration similar

1. Push the 3RW5 communication module into the slot.


2. Secure the 3RW5 communication module with the fastening screws supplied at the lower
and upper mounting holes.

Result
You have mounted the 3RW5 communication module in the 3RW5 soft starter, which you
can connect to the fieldbus (Page 35) via the 3RW5 communication module.

SIRIUS 3RW5 Modbus TCP communication module


32 Manual, 03/2018, A5E43676481002A/RS-AA/001
Mounting and dismantling
4.2 Removing the 3RW5 communication module

4.2 Removing the 3RW5 communication module

Requirements
● Removed bus connector (Page 37)
● Screwdriver PH1
● Slotted screwdriver with blade width 5.5 to 8 mm

NOTICE
Damage to property due to electrical voltage
Switch off the power to the 3RW5 soft starter before starting work (main and control supply
voltage).

Note
A magnetic screwdriver simplifies disassembly.

Procedure

NOTICE
Damage to property
Ensure that no foreign matter can get into the slot.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 33
Mounting and dismantling
4.2 Removing the 3RW5 communication module

Illustration similar

1. Remove the fastening screws from 3RW5 communication module.


2. There is a small gap above the upper mounting hole on the 3RW5 communication
module between the 3RW5 communication module and the 3RW5 soft starter. Insert the
slotted screwdriver into this gap from above.
3. Turn the slotted screwdriver 90°. The turning movement lifts the 3RW5 communication
module slightly out of the slot of the 3RW5 soft starter.
4. Pull the 3RW5 communication module out of the slot of the 3RW5 soft starter with your
fingers.

Result
You have removed the 3RW5 communication module and can now mount another
3RW5 communication module.

SIRIUS 3RW5 Modbus TCP communication module


34 Manual, 03/2018, A5E43676481002A/RS-AA/001
Connecting 5
5.1 Connecting the bus connector

Requirements
● Mounted 3RW5 communication module
● Bus connector (Page 27)
● Cable tie

Note
Malfunctions caused by EMC interference
The purpose of shielding cables is to attenuate (dampen) magnetic, electrical or
electromagnetic interference fields. Connect the cable shield of the fieldbus cable to system
ground with low impedance to that interference currents on the cable shield can be
conducted to ground.
Generally follow the instructions in the EMC Guide (http://www.siemens.com/emc-guideline)
and implement the measures stated in it for shielding the cables and for connecting the
shield.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 35
Connecting
5.1 Connecting the bus connector

Procedure

Illustration similar

1. Plug the bus connector of the cable into the socket of the 3RW5 communication module.
2. Secure the cable with a cable tie.

Result
The 3RW5 communication module is now properly mounted and connected. You can
integrate the 3RW5 soft starter into the associated network environment.

SIRIUS 3RW5 Modbus TCP communication module


36 Manual, 03/2018, A5E43676481002A/RS-AA/001
Connecting
5.2 Removing the bus connector

5.2 Removing the bus connector

Requirements
● Diagonal cutter
● Slotted screwdriver with blade width < 2.5 mm

Procedure

Illustration similar

1. Carefully cut through the cable ties with a diagonal cutter and remove the cable tie. Take
care that you do not damage the cable.
2. Insert the slotted screwdriver into the opening on the bus connector (depending on which
bus connector is used).
3. Hold back the locking bolt of the bus connector with the slotted screwdriver. Press the
slotted screwdriver slightly to the left to do this.
4. Pull the bus connector of the cable out of the socket of the 3RW5 communication module.

Result
You have disconnected the 3RW5 communication module from the bus connection.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 37
Connecting
5.2 Removing the bus connector

SIRIUS 3RW5 Modbus TCP communication module


38 Manual, 03/2018, A5E43676481002A/RS-AA/001
Configuring 6
6.1 Configuring the 3RW5 Soft Starter in the Modbus TCP system.

Requirements
● Mounted 3RW5 Modbus TCP communication module
The 3RW5 soft starter automatically detects the presence of the 3RW5 communication
module when it is switched on.
● Modbus TCP system
– Client (PC / programming device, or programmable logic controller,
e.g. SIMATIC S7-1500)
– Server (3RW5 Modbus TCP communication module)
● Configuration software of the controller (e.g. STEP 7)
● Parameterization software, e.g.
– SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
– Modbus client
● Depending on the control, additional communication components may be necessary for
Modbus TCP. Additional information can be found on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/102020340).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 39
Configuring
6.1 Configuring the 3RW5 Soft Starter in the Modbus TCP system.

Procedure
1. Configure the 3RW5 soft starter in the Modbus TCP system.
The following procedures are possible:
– Configuring 3RW5 soft starters without 3RW5 HMI High Feature (Page 41)
– Configuring 3RW5 soft starters with the aid of a 3RW5 HMI High Feature (Page 42)
2. Parameterize the 3RW5 soft starter. In particular, note the information in chapter
Operation on failure of the bus connection to the controller (Page 45). You will find more
information on parameterization in the Manual of the 3RW5 soft starter.
Depending on the selection and equipment of the 3RW5 soft starter, you can
parameterize the 3RW5 soft starter in different ways via the 3RW5 communication
module:
– Modbus client on PC with Modbus TCP connection
– Configuration software of the controller on PC / programming device with
Modbus TCP connection

Note
During parameterization, it is possible to select impossible combinations of
interdependent values. In the "Soft starter diagnostics" data table (Page 82) the diagnosis
"InvalidParameter" is then signaled. You will find the dependencies of the parameters in
the Manual of the 3RW5 soft starter.

Result
The 3RW5 soft starter is integrated into the Modbus TCP system as a server and
parameterized. You can program the controller and commission the 3RW5 soft starter in the
Modbus TCP system.

SIRIUS 3RW5 Modbus TCP communication module


40 Manual, 03/2018, A5E43676481002A/RS-AA/001
Configuring
6.2 Configuring the 3RW5 Soft Starter

6.2 Configuring the 3RW5 Soft Starter

6.2.1 Configuring 3RW5 soft starters without 3RW5 HMI High Feature

Requirements
● Connection of the 3RW5 soft starter via Modbus TCP
● Switched on control supply voltage on the 3RW5 soft starter
● IP parameter (factory setting)
You will find the factory setting (default) of the IP parameters in the data table
"Communication parameters" (Page 99).

Procedure

① Programmable logic controller / client (e.g. SIMATIC S7-1500)


② PC or programming device with configuration software of controller
③ Modbus TCP
④ SIRIUS 3RW5 soft starter / server
... : Steps to be taken in the procedure
1. Start the Modbus client in your automation system and address the server
(3RW5 soft starter) using the IP parameter (factory setting).
When using a SIMATIC S7-1500, for example, integrate the FB "MB_CLIENT" into the
user program.
2. By means of the data table "Communication parameters" (Page 99) set the required
IP parameters in the 3RW5 soft starter.
Note the information in chapter IP parameters (Page 44).
3. Enter the modified IP parameters of the server in the Modbus client.
Note the information in chapter IP parameters (Page 44).
4. Load the configuration into the client (if necessary).

Result
The 3RW5 soft starter is configured in the Modbus TCP system and can communicate with
other Modbus TCP devices via the 3RW5 Modbus TCP communication module.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 41
Configuring
6.2 Configuring the 3RW5 Soft Starter

6.2.2 Configuring 3RW5 soft starters with the aid of a 3RW5 HMI High Feature

Requirements
● Input device (3RW5 HMI High Feature, PC)
● Switched on control supply voltage on the 3RW5 soft starter

Procedure

① Programmable logic controller / client (e.g. SIMATIC S7-1500)


② PC or programming device with configuration software of controller and Modbus client (optional)
③ Modbus TCP
④ SIRIUS 3RW5 soft starter / server
⑤ PC with SIRIUS Soft Starter ES (TIA Portal)
⑥ 3RW5 HMI High Feature (accessories depend on 3RW5 soft starter)
... : Steps to be taken in the procedure

SIRIUS 3RW5 Modbus TCP communication module


42 Manual, 03/2018, A5E43676481002A/RS-AA/001
Configuring
6.2 Configuring the 3RW5 Soft Starter

1. Set the required IP parameters in the 3RW5 soft starter.


The following procedures are possible:
– Via SIRIUS Soft Starter ES (TIA Portal) over the LAN interface on the 3RW5 HMI High
Feature
– Via the 3RW5 HMI High Feature
Menu: "Parameter > Communication > Modbus TCP > IP address"
Menu: "Parameter > Communication > Modbus TCP > Subnet mask"
Menu: "Parameter > Communication > Modbus TCP > Address of router"
You will find more information on operating the 3RW5 HMI High Feature in the Manual
of the 3RW5 soft starter.
Note the information in chapter IP parameters (Page 44).
2. Start the Modbus client in your automation system and address the server (3RW5 soft
starter) using the previously set IP parameter.
When using a SIMATIC S7-1500, for example, integrate the FB "MB_CLIENT" into the
user program.
Note the information in chapter IP parameters (Page 44).
3. Load the configuration into the client (if necessary).

Result
The 3RW5 soft starter is configured in the Modbus TCP system and can communicate with
other Modbus TCP devices via the 3RW5 Modbus TCP communication module.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 43
Configuring
6.2 Configuring the 3RW5 Soft Starter

6.2.3 IP parameters
All Modbus TCP devices are capable of using the TCP/IP protocol. Before the 3RW5 soft
starter can be addressed as a server by a client, it must have IP parameters. The IP
parameters of the 3RW5 soft starter must match the IP parameters in the configuration, in
order for the client to communicate.

IP parameters
● IP address
● Subnet mask
● Address of router
You will find the factory setting (default) of the IP parameters in the data table
"Communication parameters" (Page 99).

Static IP parameters
The IP parameters set in the 3RW5 soft starter are stored in the 3RW5 soft starter. The IP
parameters of the 3RW5 soft starter must match the IP parameters in the configuration.

Note
Restarting the communication interface
Any change in the IP parameters via SIRIUS Soft Starter ES (TIA Portal) requires a restart of
the communication interface.
A new start interrupts all Modbus TCP links and reestablishes them afterward.

MAC address
Via the MAC address, the 3RW5 communication module can be accessed via LAN. You can
read the MAC address on the front of the 3RW5 communication module or display it on the
3RW5 HMI High Feature.
Menu: "Parameter > Communication > Modbus TCP > MAC address"

SIRIUS 3RW5 Modbus TCP communication module


44 Manual, 03/2018, A5E43676481002A/RS-AA/001
Configuring
6.3 Operation on failure of the bus connection to the controller

6.3 Operation on failure of the bus connection to the controller


An interruption in the connection between the 3RW5 soft starter and the controller must not
result in an undefined plant status.
Depending on the 3RW5 soft starter, you can set parameters that define the behavior of the
3RW5 soft starter on interruption of the connection with the controller in "Automatic" mode.
The 3RW52 soft starter does not support the parameters. If there is a connection interruption
to the controller, all the bits of the process image outputs (PIQ) are set to 0.

Parameters

Parameters Description
Response to CPU / Master Stop With this parameter, you define how the 3RW5 soft starter will behave if a
CPU / Master stop occurs:
• Last value

The 3RW5 soft starter does not change the process image output. The current
control commands are retained.
• Substitute value (factory setting)

The process image output of the 3RW5 soft starter is automatically changed to
the values defined in the following parameter "Substitute value".
Substitute value* In the event of a bus failure, the 3RW5 soft starter is controlled by a corresponding
substitute process image output (depending on the 3RW5 soft starter).
• Motor CW
• Motor CCW
• Reset
• Emergency start
• Creep speed
• Output 1
• Output 2
• Parameter set bit 0
• Parameter set bit 1
• Disable Quick-stop
• Output 3
• Pump cleaning mode
• Manual operation local - input controlled
• Use alternative stopping mode
• Motor standstill

* In the 3RW5 HMI High Feature, the parameter is only visible if "Substitute value" is selected in the parameter
"Response to CPU / Master Stop".

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 45
Configuring
6.3 Operation on failure of the bus connection to the controller

Setting options
You can set the parameters in the following ways:
● SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
● 3RW5 HMI High Feature
Menu: "Parameter > Soft Starter > Additional parameters > Operation with CPU / master"
You will find more information on operating the 3RW5 HMI High Feature in the Manual of
the 3RW5 soft starter.
● User program via the "Parameters" data table (Page 89)

SIRIUS 3RW5 Modbus TCP communication module


46 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics 7
The 3RW5 communication module provides you with the following diagnostics options:
● LED display (Page 48)
● 3RW5 HMI High Feature
Menu: "Diagnostics > Communication"
You will find more information on operating the 3RW5 HMI High Feature in the Manual of
the 3RW5 soft starter.
● SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
● Controller (e.g. SIMATIC S7-1500) or a PC as the Modbus client
Note the information in chapters frame structure (Page 23), Function Codes (Page 51),
and Error codes (Page 61).
You will find faults and remedial measures for the 3RW5 communication module in chapter
Faults and remedial measures (Page 62).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 47
Messages and diagnostics
7.1 LED display

7.1 LED display

7.1.1 Device LEDs on the 3RW5 communication module


The diagnostics of the 3RW5 communication module is displayed by LEDs on the
3RW5 communication module under the hinged cover of the 3RW5 soft starter. The LEDs
briefly light up simultaneously at the start-up of the 3RW5 communication module (LED test).

LED display on the 3RW5 communication module

① DIAG (red / green)


② BUS (red / green)
③ LINK (green)

SIRIUS 3RW5 Modbus TCP communication module


48 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.1 LED display

7.1.2 Status and error displays

"DIAG" LED

State Meaning
Device exchanging data with the client.

Lights up green
• The 3RW5 soft starter is not configured.

Flashes green • The 3RW5 communication module is starting.


• The 3RW5 communication module is being parameterized.
• Factory settings are being restored.
• Device not performing data exchange.
Hardware or firmware defective.

Lights up red
• Group error (only if the 3RW5 communication module is malfunctioning)

Flashes red • Switchover from old to new firmware after firmware update
(flashes briefly)
The "node flash test" was activated.

Flashes green / red


No supply voltage available.
Off

"BUS" LED

State Meaning
Device performing data exchange (3RW5 soft starter in Automatic mode).

Lights up green
Bus error, e.g.:
• Timeout for TCP keep-alive monitoring.
Lights up red
• Modbus TCP cable not connected.

• Configuring error

Flashes red • Device not performing data exchange (e.g. controller is in stop state).
• Switchover from old to new firmware after firmware update
(flashes briefly)
No supply voltage available.
Off

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 49
Messages and diagnostics
7.1 LED display

"LINK" LED

State Meaning
There is a TCP connection between the 3RW5 communication module and
a communication partner (e.g. client).
Lights up green
The "node flash test" was activated.

Flashes green
• There is no TCP connection between the 3RW5 communication module
Off and a communication partner (e.g. client).
• No supply voltage available.

SIRIUS 3RW5 Modbus TCP communication module


50 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.2 Function Codes

7.2 Function Codes


The Function Code defines the meaning of the telegram and defines the telegram structure.

Overview of the function codes

Function Code (decimal/hexadecimal) Designation according to Modbus specification


01 / 0x01 (Page 53) Read Coils
02 / 0x02 (Page 53) Read Discrete Inputs
03 / 0x03 (Page 54) Read Holding Registers
04 / 0x04 (Page 54) Read Input Registers
05 / 0x05 (Page 55) Write Single Coil
06 / 0x06 (Page 56) Write Single Register
15 / 0x0F (Page 57) Write Multiple Coils
16 / 0x10 (Page 58) Write Multiple Registers
23 / 0x17 (Page 59) Read/Write Multiple Registers

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 51
Messages and diagnostics
7.2 Function Codes

Access to memory areas


Two memory areas are used in the 3RW5 Soft Starter:
● A memory area for addressing the bit information
● A memory area for addressing the register information
The Function Codes for bit information (01, 02, 05, 15) thus always access the bit memory
area. The Function Codes for register information (03, 04, 06, 16, 23) always access the
register memory area.
Whether information is read-only (r) or read/writeable (r/w) is stated in the data tables in
chapter Data tables (Page 75).

SIRIUS 3RW5 Modbus TCP communication module


52 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.2 Function Codes

7.2.1 Function Codes 01 (Read Coils) and 02 (Read Discrete Inputs)


These functions enable the reading of individual bits from the 3RW5 bit memory area by the
MODBUS client system.
Function Codes 01 and 02 behave in the same way here and supply an identical feedback
signal. A valid offset from the bit memory area is expected as the start address. Up to
2000 bits can be read per telegram.
If a number that is not equal to a multiple of eight bits is called up, the remaining bits are
filled with zeros. The number of bytes n always refers to the number of fully returned bytes.

Note
Start address and number of Coils
The start address and the number of coils must be within the valid range.

Request telegram

Address Field Function Code Start address Number of bits


7 bytes 1 byte 2 bytes 2 bytes
- 0x01 0x84EF 0x0001

Response telegram

Address Field Function Code Number of bytes n Bit status


7 bytes 1 byte 1 byte n bytes
- 0x01 0x01 0x80

Example
Reading in bypass operation mode "internal bypass" (Operation / bypass active):
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The bit address of "Operation / bypass active" is 0x84EF.
● As feedback, the status "Operation / bypass active" (bit 7) is returned with a logical one
(0x80).
You will find the data table for the soft starter diagnostics in chapter Soft starter diagnostics
(Page 82).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 53
Messages and diagnostics
7.2 Function Codes

7.2.2 Function Codes 03 (Read Holding Registers) and 04 (Read Input Registers)
These functions enable the MODBUS client system to read registers from the 3RW5 register
memory area.
Function Codes 03 and 04 behave in the same way here and supply an identical feedback
signal. A valid offset from the register memory area is expected as the start address. Up to
125 registers per frame can be read.

Request telegram

Address Field Function Code Start address Number of registers


7 bytes 1 byte 2 bytes 2 bytes
- 0x03 0x880F 0x0006

Response telegram

Address Field Function Code Number of bytes Register value


7 bytes 1 byte 1 byte n registers
- 0x03 0x0C 0x0000 0x2710 0x0000
0x2710 0x0000 0x2710

Example
Reading in the rms phase currents:
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The phase currents start at register address 0x880F and include 6 registers.
● As feedback, the measured values of the current rms phase currents (I L1, I L2, I L3) are
returned with 100 A (0x0000 0x2710) each.
You can find the data table for the measured values in chapter Measured values (Page 86).

SIRIUS 3RW5 Modbus TCP communication module


54 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.2 Function Codes

7.2.3 Function Code 05 (Write Single Coil)


This function enables the Modbus client system to write an individual bit from the 3RW5 bit
memory area.
A valid address from the bit memory area is expected as the start address. The selected
address must be designated as writable in the data tables in chapter Data tables (Page 75).

Request telegram

Address Field Function Code Start address Data


7 bytes 1 byte 2 bytes 2 bytes
- 0x05 0x8200 0x0001

Response telegram

Address Field Function Code Start address Data


7 bytes 1 byte 2 bytes 2 bytes
- 0x05 0x8200 0x0001

Example
Setting the bit address of the "Motor CW" command to a logical one:
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The bit address of "Motor CW" is 0x8200.
You will find the data table for the process image output in chapter Process image output
(PIQ) (Page 81).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 55
Messages and diagnostics
7.2 Function Codes

7.2.4 Function Code 06 (Write Single Register)


This function enables the Modbus client system to write an individual register from the 3RW5
register memory area.
A valid address from the register memory area is expected as the start address. The
selected address must be designated as writable in the data tables in chapter Data tables
(Page 75).

Request telegram

Address Field Function Code Start address Data


7 bytes 1 byte 2 bytes 2 bytes
- 0x06 0x9409 0x0005

Response telegram

Address Field Function Code Start address Data


7 bytes 1 byte 2 bytes 2 bytes
- 0x06 0x9409 0x0005

Example
Setting the starting mode "Voltage ramp + Current limiting":
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The register address of the starting mode is 0x9409.
● For the starting mode "Voltage ramp + Current limiting" the value 5 is transmitted to the
3RW5 soft starter (0x0005).
You can find the data table for the parameters in Parameters (Page 89).

SIRIUS 3RW5 Modbus TCP communication module


56 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.2 Function Codes

7.2.5 Function Code 15 (Write Multiple Coils)


This function enables the Modbus client system to write several bits from the 3RW5 bit
memory area.
A valid address from the bit memory area is expected as the start address. The selected
address must be designated as writable in the data tables in chapter Data tables (Page 75).
When writing several bits, they must be identified as a "writable" coherent block. A bit area
that is interrupted by read-only bits cannot be written to as a block.

Request telegram

Address Field Function Code Start address Number of bits Number of bytes Data
7 bytes 1 byte 2 bytes 2 bytes 1 byte n bytes
- 0x0F 0x8200 0x0007 0x01 0x41

Response telegram

Address Field Function Code Start address Number of bits


7 bytes 1 byte 2 bytes 2 bytes
- 0x0F 0x8200 0x0007

Example
Setting the bit addresses of the "Motor CW" and "Creep speed" commands to a logical one:
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The bit addresses of the commands are:
– "Motor CW": 0x8200
– "Creep speed": 0x8206
● The remaining bits of the byte are controlled with a logical zero (0x41).
You will find the data table for the process image output in chapter Process image output
(PIQ) (Page 81).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 57
Messages and diagnostics
7.2 Function Codes

7.2.6 Function Code 16 (Write Multiple Registers)


This function enables the Modbus client system to write several registers from the 3RW5
register memory area.
A valid address from the register memory area is expected as the start address. The
selected address must be designated as writable in the data tables in chapter Data tables
(Page 75).
When writing several registers, they must be identified as a "writable" coherent block. A
register area that is interrupted by read-only registers cannot be written to as a block.

Request telegram

Address Field Function Code Start address Number of registers Number of bytes Data
7 bytes 1 byte 2 bytes 2 bytes 1 byte n x 2 bytes
- 0x10 0x9403 0x0002 0x04 0x0000 0x2710

Response telegram

Address Field Function Code Start address Number of registers


7 bytes 1 byte 2 bytes 2 bytes
- 0x10 0x9403 0x0002

Example
Setting the rated operational current Ie to 100 A:
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The register address of the rated operational current Ie is 0x9403.
● The rated operational current Ie occupies 2 registers.
● The value 100 A is transmitted to the 3RW5 soft starter (0x0000 0x2710).
You can find the data table for the parameters in Parameters (Page 89).

SIRIUS 3RW5 Modbus TCP communication module


58 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.2 Function Codes

7.2.7 Function Code 23 (Read/Write Multiple Registers)


This function enables the Modbus client system to write and read several registers from
3RW5 register memory area using a single function call.

Note
Read/Write Multiple Registers
With the FC 23, it is only possible to access the process image output (PIQ) and the process
image input (PII).

The write operation is the first executed operation here. This function is the typically used
function call for outputting cyclic data in the 3RW5 soft starter and for reading back inputs or
device statuses.
A valid address from the bit memory area is expected as the start address. The selected
address must be designated as writable in the data tables in chapter Data tables (Page 75).

Request telegram

Address Field Function Code Start address read Number of registers


operation (read access)
7 bytes 1 byte 2 bytes 2 bytes
- 0x17 0x8000 0x0008

Start address write Number of registers N Number of bytes Data (write access)
operation (write access) (write access)
2 bytes 2 bytes 1 byte N x 2 bytes
0x8200 0x0001 0x01 0x0041

Response telegram

Address Field Function Code Number of bytes N Data


7 bytes 1 byte 1 byte N x 2 bytes
- 0x17 0x0010 -

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 59
Messages and diagnostics
7.2 Function Codes

Example
Setting the bit addresses of the "Motor CW" and "Creep speed" commands to a logical one
and reading the process image input:
● Address field: The address of the 3RW5 soft starter is not entered in the example (-).
● The commands start in register address 0x8200. The bit addresses of the commands are:
– "Motor CW": 0x8200
– "Creep speed": 0x8206
● The remaining bits of the byte are controlled with a logical zero (0x41).
● The process image input starts at register address 0x8000 and occupies 8 registers.
● As feedback, the process image input is returned. In the example, the returned data are
not entered (-). Note that the requested commands are not returned as a new status in
the exact same cycle because implementation of the commands takes a while. The new
status is not returned in the process image input until several communication cycles later.
You will find the data tables for the process image output and process image input in
chapters Process image output (PIQ) (Page 81) and Process image input (PII) (Page 80).

SIRIUS 3RW5 Modbus TCP communication module


60 Manual, 03/2018, A5E43676481002A/RS-AA/001
Messages and diagnostics
7.3 Error codes

7.3 Error codes

7.3.1 Exception Responses

Operating principle
When the server detects an error in the request telegram from the client (illegal register
address, for example), the server sets the highest value bit in the function code of the
response telegram: Requested function code + 80h. This step is followed by transmission of
a byte with the Exception Code that describes the cause of the error.

Typical exception code frame


The exception code telegram from the server has the following structure, for example:
● Address Field: The address of the 3RW5 Soft Starter is not entered in the example (-).
● Requested Function Code: 5
● Exception code: 2
Response telegram from server:

Address Field Function Code Error code


- 85H (= 0x85) 02H (= 0x02)

7.3.2 Supported error codes

Error code Meaning in Cause Brief description


accordance with
Modbus specification
1 (= 0x01) Illegal function Illegal The requested function code is not supported. Pay particular attention
function code to chapter Function Codes (Page 51).
2 (= 0x02) Illegal data address Illegal bit or Address does not exist. For functions that work with an addressing
register range, all addresses affected by the request are checked.
address on
the server
3 (= 0x03) Illegal data value Server has The number of addresses is not correct. The number of parameters for
illegal data the requested function was too high (or 0)
value
4 (= 0x04) Failure in associated Server has There is an unspecified server error that prevented execution of the
device internal error request.
6 (= 0x06) Busy, rejected Server is not The device is busy and unable to process the request at this time. This
message ready to can occur following a parameterization operation via Modbus when the
receive new parameter values are transferred to the device.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 61
Messages and diagnostics
7.4 Faults and remedial measures

7.4 Faults and remedial measures


The following table describes possible faults and remedies for the 3RW5 communication
module. Faults and remedies for the 3RW5 soft starter can be found in the Manual of the
3RW5 soft starter.

Fault No.* Fault Cause Remedy


303 Bus error - • Check the bus connection.
• Check the bus parameters.
• The fault is acknowledged automatically
once it has been rectified.

*visible on the display of the 3RW5 HMI Standard

7.5 Messages about the mode


The following message bits in the "Soft starter diagnostics" data table (Page 82) clearly
indicate which control source currently has control priority:
● Automatic mode (①)
● Manual operation local (②)
● Manual operation local - input controlled (③)
● Manual operation local - HMI controlled (④)
● Manual operation local - PC controlled (⑤)
● Connection abort in manual mode (⑥)

Automatic Manual Control priority is with:


Manual operation local
① ② ③ ④ ⑤ ⑥
0 0 0 0 0 0 Message is not permitted.
1 0 0 0 0 0 Modbus client (e.g. PLC) controlling via fieldbus.
0 1 0 0 0 1 No control source.
0 1 1 0 0 0 Digital input controlling.
0 1 0 1 0 0 HMI controlling.
0 1 0 0 1 0 PC controlled via local interface.

For more information on setting the operating mode, see chapter Operating modes and
master control function (Page 25).

SIRIUS 3RW5 Modbus TCP communication module


62 Manual, 03/2018, A5E43676481002A/RS-AA/001
Maintenance and service 8
8.1 Firmware update
During operation, it may be necessary to update the firmware (e.g. to extend the available
functions). You update the firmware of the device with the help of firmware files. The
retentive data is retained after the firmware has been updated.
Firmware updates are provided to you on the Internet. You can perform a firmware update
for the following devices:
● 3RW5 soft starter
● 3RW5 HMI High Feature
● 3RW5 communication module

Requirements
● Valid firmware update
Link (https://support.industry.siemens.com/cs/ww/en/ps/16212/dl)

Procedure
1. Make sure that the motor is switched off and you do not start the motor during the
firmware update.
A control command for starting the motor is not supported during the firmware update.
Make sure that the main supply voltage is only applied to the 3RW5 soft starter when it is
necessary.
2. Perform the update of the device firmware.
The following procedures are possible:
– With a micro SD memory card via the 3RW5 HMI High Feature (Page 64)
– Via SIRIUS Soft Starter ES (TIA Portal) via the LAN interface on the 3RW5 HMI High
Feature

Result
You have performed a firmware update for the selected device. The selected device
automatically restarts and the firmware update is documented in the device logbook.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 63
Maintenance and service
8.1 Firmware update

8.1.1 Perform the firmware update using micro SD memory card


(3RW5 HMI High Feature)

Requirements
● Micro SD memory card with valid firmware file (*.udp)
● You are in menu "Memory Card > FW Update"

Procedure

Note
Access to micro SD memory card.
Please note that the micro SD memory card is in the 3RW5 HMI High Feature during
updating of the firmware.
Premature removal of the micro SD memory card from the 3RW5 HMI High Feature is not
permissible and will terminate updating of the firmware. Data could also be lost.

1. Select the folder of the respective device.


2. Select the firmware file of the device and confirm with "OK".
You can see the firmware update is being performed from the progress bar on the
display.
Following successful updating of the firmware, the respective device then restarts
automatically.
3. Check the new firmware version in the "Overview" menu.

Result
You have performed a firmware update for the selected device using the micro SD memory
card. The firmware update is documented in the device logbook.

More information
You will find more information on operating the 3RW5 HMI High Feature in the Manual of the
3RW5 soft starter.

SIRIUS 3RW5 Modbus TCP communication module


64 Manual, 03/2018, A5E43676481002A/RS-AA/001
Maintenance and service
8.2 Replacing the 3RW5 communication module

8.2 Replacing the 3RW5 communication module


Communication parameters are stored in the 3RW5 communication module and not
automatically transferred into the replacement device.
Observe the following chapters on the communication parameters:
● Configuring the 3RW5 Soft Starter (Page 41)
● Communication parameters (Page 99)

Note
Backing up communication parameters on micro SD memory card
Depending on the 3RW5 soft starter, you can back up the communication parameters to a
micro SD memory card via the 3RW5 HMI High Feature.

You will find more information on backing up the configuration data to a micro SD memory
card and on operating the 3RW5 HMI High Feature in the Manual of the 3RW5 soft starter.

Requirements

NOTICE
Damage to property due to electrical voltage
Switch off the power to the 3RW5 soft starter before starting work (main and control supply
voltage).

Procedure
1. Remove the bus connector. (Page 37)
2. Remove the 3RW5 communication module. (Page 33)
3. Mount the 3RW5 communication module. (Page 32)
4. Connect the 3RW5 communication module to the bus connection. (Page 35)

Result
You have replaced the 3RW5 communication module and can commission the 3RW5 soft
starter in the bus connection.
Set the communication parameters anew. If you backed up the communication parameters
to a micro SD memory card before replacement, you can transfer them from the micro SD
memory card to the replacement device.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 65
Maintenance and service
8.3 Restoring factory settings

8.3 Restoring factory settings

Effects of the factory setting


The following devices can be reset to the factory setting:
● 3RW5 soft starter
– The parameters of the 3RW5 soft starter are reset to the factory setting
(depending on the 3RW5 soft starter).
– User accounts are deleted (depending on the 3RW5 soft starter).
– An automatic restart of the 3RW5 soft starter is performed.
● 3RW5 communication module
– The parameters of the 3RW5 communication module are reset.
● 3RW5 HMI High Feature
– The parameters of the 3RW5 HMI High Feature and the PIN for access protection are
reset to the factory setting.
● All devices
– The 3RW5 soft starter, the 3RW5 communication module, and the 3RW5 HMI High
Feature are reset to the factory settings, as described above.

Procedure
1. Make sure that the motor is switched off and that you do not start the motor while
restoring the factory settings. Make sure that the main supply voltage is only applied to
the 3RW5 soft starter when it is necessary.
2. Restore the factory settings.
The following procedures are possible:
– Via SIRIUS Soft Starter ES (TIA Portal) over the LAN interface on the 3RW5 HMI High
Feature
– Via the 3RW5 HMI High Feature
You will find more information on operating the 3RW5 HMI High Feature in the Manual
of the 3RW5 soft starter.

Result
The factory setting of the selected device or all devices is restored.

SIRIUS 3RW5 Modbus TCP communication module


66 Manual, 03/2018, A5E43676481002A/RS-AA/001
Technical data 9
9.1 Technical data in Siemens Industry Online Support

Technical data sheet


You can also find the technical data of the product at Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/16212/td).
1. Enter the full article number of the desired device in the "Product" field, and confirm with
the Enter key.
2. Click the "Technical data link.

Overview tables technical data


You will find overview tables with technical data in the "Product information" tab in our online
ordering system
(https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10024029?tree=CatalogTr
ee).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 67
Technical data
9.1 Technical data in Siemens Industry Online Support

SIRIUS 3RW5 Modbus TCP communication module


68 Manual, 03/2018, A5E43676481002A/RS-AA/001
Dimension drawings 10
10.1 CAx data
You can find the CAx data in the Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/16212/td).
1. Enter the full article number of the desired device in the "Product" field, and confirm with
the Enter key.
2. Click the "CAx data link.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 69
Dimension drawings
10.1 CAx data

SIRIUS 3RW5 Modbus TCP communication module


70 Manual, 03/2018, A5E43676481002A/RS-AA/001
Circuit diagrams 11
11.1 CAx data
You can find the CAx data in the Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/16212/td).
1. Enter the full article number of the desired device in the "Product" field, and confirm with
the Enter key.
2. Click the "CAx data link.

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 71
Circuit diagrams
11.1 CAx data

SIRIUS 3RW5 Modbus TCP communication module


72 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix A
A.1 Data formats

A.1.1 Current values as percentages


Current values are coded as percentages in different current formats:
● 6-bit current format
● 8-bit current format
● 9-bit current format

Examples of current values


The following values are examples of current values expressed as percentages:
● Phase currents I L1, I L2, I L3 (8-bit current format)
● Last tripping current (9-bit current format)
You will find a complete overview of all measured values in chapter Measured values
(Page 86).

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 73
Appendix
A.1 Data formats

A.1.2 Statistic data


Statistic data group together the operating states from the past that are relevant to the load.

Examples of statistic data


The following values are examples of statistic data:
● Operating hours
– Motor operating hours
– Operating hours of the device (3RW5 Soft Starter)
● Number of motor overload trips
● Number of starts motor CW
● Number of starts motor CCW
You will find a complete overview of the statistic data in chapter Statistic data (Page 87).

A.1.3 Maximum pointer


Maximum pointers are stored extreme values of measured values from the past and are
used for preventive diagnostics. Maximum pointers are stored in the device and can be
deleted at any time.

Examples of maximum pointers


The following values are examples of maximum pointers:
● Number of motor overload trips
● Minimum and maximum phase current I L1, I L2, I L3
● Minimum and maximum line-to-line voltages
● Minimum and maximum line frequency
You will find a complete overview of the maximum pointers in chapter Maximum pointer
(Page 88).

SIRIUS 3RW5 Modbus TCP communication module


74 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2 Data tables

A.2.1 Byte arrangement


When data longer than one byte are stored, the bytes are arranged as follows ("big endian"):

1 register corresponds to 1 word (2 bytes).

A.2.2 Specifications
The following specifications apply in the data tables:
● Addresses are represented as hexadecimal values.
● The access to undefined addresses is illegal and generates an error message.
● Non-relevant (reserved) entries are not listed.
Fill these entries with "0" when writing.
● In data tables for parameters, codes are shown in square brackets "[...]". "[D*]" describes
the default coding.

Object number (Obj. No.)


The object number (Obj. No.) is used for unique identification of all parameters available in
the 3RW5 soft starter. In the case of a parameterization error, the object number of the faulty
parameter is displayed in data table "Soft starter diagnostics" (Page 82) under
"Faulty parameter number".

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 75
Appendix
A.2 Data tables

A.2.3 Memory image

Hexadecimal address Chapter


Commands
0x0000 Node flash test (Page 76)
Identification data
0x00C1 I&M0 - Communication (Page 77)
0x0181 I&M0 - Basic unit (Page 77)
0x01A1 I&M1 - Basic unit (Page 78)
0x01C1 I&M2 - Basic unit (Page 78)
0x01E1 I&M3 - Basic unit (Page 78)
0x0241 I&M0 - HMI HF (Page 79)
Energy management (Page 79)
0x09C1 Phase current I L1 (rms)
0x09C3 Phase current I L2 (rms)
0x09C5 Phase current I L3 (rms)
0x09C7 Phase current average (rms)
0x0A47 Active power PL1..3
0x0A61 Active energy import (total)
3RW5 basic unit
0x8000 Process image input (PII) (Page 80)
0x8200 Process image output (PIQ) (Page 81)
0x8400 Soft starter diagnostics (Page 82)
0x8800 Measured values (Page 86)
0x8C00 Statistic data (Page 87)
0x9000 Maximum pointer (Page 88)
0x9400 Parameters (Page 89)
Modbus TCP communication
0xA100 Communication parameters (Page 99)
3RW5 HMI High Feature
0xB000 HMI diagnostics (Page 100)
0xB100 HMI parameters (Page 101)

A.2.4 Node flash test


For the station flash test (Node flash test) only write access (w) is possible via Function
Codes 05 and 06.

Register address Bit address Content Access


0x0000 0x0000 Node flash test start w
0x0001 Node flash test end w
0x0002 ... 0x0015 Reserved -

SIRIUS 3RW5 Modbus TCP communication module


76 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.5 I&M0 - Communication


For the device overview (I&M0) only read access (r) is possible via Function Codes 03
and 04.

Register Content Access


Address Quantity
0x00C1 5 RESERVED r
0x00C6 1 MANUFACTURER_ID r
0x00C7 10 ORDER_ID r
0x00D1 8 SERIAL_NUMBER r
0x00D9 1 HARDWARE_REVISION r
0x00DA 2 SOFTWARE_REVISION r
0x00DC 1 REV_COUNTER r
0x00DD 1 PROFILE_ID r
0x00DE 1 PROFILE_SPECIFIC_TYPE r
0x00DF 1 IM_VERSION r
0x00E0 1 IM_SUPPORTED r

A.2.6 I&M0 - Basic unit


For the device overview (I&M0) only read access (r) is possible via Function Codes 03
and 04.

Register Content Access


Address Quantity
0x0181 5 RESERVED r
0x0186 1 MANUFACTURER_ID r
0x0187 10 ORDER_ID r
0x0191 8 SERIAL_NUMBER r
0x0199 1 HARDWARE_REVISION r
0x019A 2 SOFTWARE_REVISION r
0x019C 1 REV_COUNTER r
0x019D 1 PROFILE_ID r
0x019E 1 PROFILE_SPECIFIC_TYPE r
0x019F 1 IM_VERSION r
0x01A0 1 IM_SUPPORTED r

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 77
Appendix
A.2 Data tables

A.2.7 I&M1 - Basic unit


For access to the function tag and location tag (I&M1) read access (r) is possible via
Function Codes 03 and 04. Write access (w) is possible via function codes 06 and 16.

Register Content Access


Address Quantity
0x01A1 5 RESERVED r
0x01A6 16 TAG_FUNCTION r/w
0x01B6 11 TAG_LOCATION r/w

A.2.8 I&M2 - Basic unit


For access to the installation date (I&M2) read access (r) is possible via Function Codes 03
and 04. Write access (w) is possible via function codes 06 and 16.

Register Content Access


Address Quantity
0x01C1 5 RESERVED r
0x01C6 8 INSTALLATION_DATE r/w
0x01CE 19 RESERVED r

A.2.9 I&M3 - Basic unit


For access to the description (I&M3) read access (r) is possible via Function Codes 03
and 04. Write access (w) is possible via function codes 06 and 16.

Register Content Access


Address Quantity
0x01E1 5 RESERVED r
0x01E6 27 DESCRIPTOR r/w

SIRIUS 3RW5 Modbus TCP communication module


78 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.10 I&M0 - HMI HF


For the device overview (I&M0) only read access (r) is possible via Function Codes 03
and 04.

Register Content Access


Address Quantity
0x0241 5 RESERVED r
0x0246 1 MANUFACTURER_ID r
0x0247 10 ORDER_ID r
0x0251 8 SERIAL_NUMBER r
0x0259 1 HARDWARE_REVISION r
0x025A 2 SOFTWARE_REVISION r
0x025C 1 REV_COUNTER r
0x025D 1 PROFILE_ID r
0x025E 1 PROFILE_SPECIFIC_TYPE r
0x025F 1 IM_VERSION r
0x0260 1 IM_SUPPORTED r

A.2.11 Energy management


Only read access (r) to the energy management is possible via Function Codes 03 and 04.

Register Data format Content 3RW


Address Quantity 521) 552)
0x09C1 2 Float32 Phase current I L1 (rms) r r
0x09C3 2 Float32 Phase current I L2 (rms) r r
0x09C5 2 Float32 Phase current I L3 (rms) r r
0x09C7 2 Float32 Phase current average (rms) r r
0x0A47 2 Float32 Active power PL1..3 - r
0x0A61 2 Float32 Active energy import (total) - r
1) Supported by SIRIUS 3RW52 soft starter
2) Supported by SIRIUS 3RW55 soft starter

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 79
Appendix
A.2 Data tables

A.2.12 Process image input (PII)


For access to the process image input (PII) only read access (r) is possible via Function
Codes 01, 02, 03, 04 and 23.

Register Byte Bit address Data format Process image 3RW


Address high / low 521) 552)
0x8000 high 0x8000 Bool Ready (automatic) r r
0x8001 Bool Motor On r r
0x8002 Bool Group error r r
0x8003 Bool Group warning r r
0x8004 Bool Input 1 r r
0x8005 Bool Input 2 - r
0x8006 Bool Input 3 - r
0x8007 Bool Input 4 - r
low 0x8008 Bool Motor current Iact-bit0 r r
0x8009 Bool Motor current Iact-bit1 r r
0x800A Bool Motor current Iact-bit2 r r
0x800B Bool Motor current Iact-bit3 r r
0x800C Bool Motor current Iact-bit4 r r
0x800D Bool Motor current Iact-bit5 r r
0x800E Bool Manual operation local r r
0x800F Bool Ramp operation r r
0x8001 high 0x8010 Bool Motor CW r r
0x8011 Bool Motor CCW - r
0x8014 Bool Start mode active r r
0x8015 Bool Operation / bypass active r r
0x8016 Bool Stop mode active r r
0x8017 Bool Test operation active - r
low 0x8018 Bool Thermal motor model overload r r
0x8019 Bool Temperature sensor overload r r
0x801A Bool Switching element overload r r
0x801B Bool Cooling time active r r
0x801C Bool Device error r r
0x801D Bool Automatic parameterization active - r
0x8002 high 0x8020 Float32 Measured value 1 r r
0x8004 high 0x8040 Float32 Measured value 2 r r
0x8006 high 0x8060 Float32 Measured value 3 r r
1) Supported by SIRIUS 3RW52 soft starter
2) Supported by SIRIUS 3RW55 soft starter

SIRIUS 3RW5 Modbus TCP communication module


80 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.13 Process image output (PIQ)


Read (r) and write (w) access to the process image output (PIQ) is possible.
● Read access via Function Codes 01, 02, 03, and 04
● Write access via function codes 05, 06, 15, and 16
● Read and write access combined via function code 23

Register Byte Bit address Data format Process image 3RW


Address high / low 521) 552)
0x8200 high 0x8200 Bool Motor CW r/w r/w
0x8201 Bool Motor CCW - r/w
0x8203 Bool Reset r/w r/w
0x8204 Bool Emergency start - r/w
0x8205 Bool Self-test (user-test) r/w r/w
0x8206 Bool Creep speed - r/w
low 0x8208 Bool Output 1 - r/w
0x8209 Bool Output 2 - r/w
0x820A Bool Parameter set bit 0* - r/w
0x820B Bool Parameter set bit 1* - r/w
0x820F Bool Disable Quick-stop - r/w
0x8201 high 0x8210 Bool Output 3 - r/w
0x8213 Bool Pump cleaning mode - r/w
low 0x8218 Bool Manual operation local - input controlled r/w r/w
0x8219 Bool Use alternative stopping mode - r/w
0x821A Bool Motor standstill - r/w
1) Supported by SIRIUS 3RW52 soft starter
2) Supported by SIRIUS 3RW55 soft starter
* Explanation in the following table

More information
The following table describes the assignment of the process images "Parameter set bit 0"
and "Parameter set bit 1":

Process image Process image error Parameter set 1 (PS1) Parameter set 2 (PS2) Parameter set 3 (PS3)
Parameter set bit 0 1 0 1 0
Parameter set bit 1 1 0 0 1

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 81
Appendix
A.2 Data tables

A.2.14 Soft starter diagnostics


For access to the soft starter diagnostics only read access (r) is possible via Function Codes
01, 02, 03 and 04.

Register Byte Bit address Data format Soft starter diagnostics 3RW
Address high / low 521) 552)
0x8400 high 0x8400 Bool Ready (automatic) r r
0x8401 Bool Motor CW r r
0x8402 Bool Motor CCW - r
0x8403 Bool Switching element overload r r
0x8404 Bool Switching element defective r r
0x8405 Bool Emergency start active - r
0x8406 Bool Group error r r
0x8407 Bool Group warning r r
low 0x8409 Bool No main power r r
0x840B Bool Start mode active r r
0x840C Bool Stop mode active r r
0x840E Bool Electrical braking active - r
0x840F Bool Creep speed active - r
0x8401 high 0x8410 Bool Temperature sensor overload r r
0x8411 Bool Temperature sensor wire break r r
0x8412 Bool Temperature sensor short-circuit r r
0x8413 Bool Thermal motor model overload r r
0x8414 Bool Motor overload shutoff r r
0x8415 Bool Idle time active - r
0x8416 Bool Cooling time active r r
low 0x841B Bool Current limiting active r r
0x841E Bool Generator operation - r
0x841F Bool Input control - r
0x8402 high 0x8420 Bool Asymmetry limit - error exceeded - r
0x8421 Bool Asymmetry shutoff - r
0x8422 Bool Current limit error exceeded - r
0x8423 Bool Current limit error undershot - r
0x8424 Bool Current error limit shutoff - r
low 0x8428 Bool Input 1 r r
0x8429 Bool Input 2 - r
0x842A Bool Input 3 - r
0x842B Bool Input 4 - r
0x8403 high 0x8430 Bool Ground fault limit error exceeded - r
0x8432 Bool Quick stop active - r
0x8436 Bool Maximum pointer reset - r
0x8437 Bool Electronics supply voltage too low r r

SIRIUS 3RW5 Modbus TCP communication module


82 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

Register Byte Bit address Data format Soft starter diagnostics 3RW
Address high / low 521) 552)
low 0x8438 Bool Bus error r r
0x8439 Bool CPU/Master STOP r r
0x843A Bool Automatic mode r r
0x843B Bool Operating mode manual r r
0x843C Bool Manual operation local r r
0x843E Bool Connection abort in manual mode r r
0x843F Bool Error process image - r
0x8404 high 0x8440 Bool Parameter assignment active - r
0x8441 Bool InvalidParameter - r
0x8442 Bool Parameters cannot be changed in ON state - r
0x8443 Bool Parameters disable CPU/master active - r
0x8444 Bool No external start parameters received - r
low 0x8448 Bool Self-test active - r
0x844A Bool Error during self-test r r
0x844B Bool Factory settings restored r r
0x8405 high 0x8450 Unsigned16 Parameter number error3) - r
0x8406 high 0x8463 Bool Preset unequal actual configuration r r
0x8465 Bool Temperature sensor overload - r
0x8466 Bool Temperature sensor wire break - r
0x8467 Bool Temperature sensor short-circuit - r
low 0x8468 Bool Parameter set 1 active - r
0x8469 Bool Parameter set 2 active - r
0x846A Bool Parameter set 3 active - r
0x846C Bool Parameter set change not possible - r
0x846E Bool Preset unequal actual configuration - r
0x846F Bool Type of motor connection wrong - r
0x8407 high 0x8472 Bool Motor heating active - r
0x8473 Bool DC braking active - r
0x8474 Bool Dynamic DC braking active - r
0x8475 Bool Type of motor connection star/delta r r
0x8476 Bool Type of motor connection inside-delta r r
0x8477 Bool Motor connection type unknown r r
low 0x8478 Bool Load missing r r
0x847A Bool Phase failure L1 r r
0x847B Bool Phase failure L2 r r
0x847C Bool Phase failure L3 r r
0x847D Bool Main power rotation right r r
0x847E Bool Main power rotation left r r
0x847F Bool Supply voltage too high - r

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 83
Appendix
A.2 Data tables

Register Byte Bit address Data format Soft starter diagnostics 3RW
Address high / low 521) 552)
0x8408 low 0x8488 Bool Output 1 active r r
0x8489 Bool Output 2 active r r
0x848A Bool Output 3 active r r
0x848B Bool Output 4 active - r
0x848C Bool Output 1 - Time active - r
0x848D Bool Output 2 - Time active - r
0x848F Bool Output 4 - Time active - r
0x8409 low 0x8499 Bool Ready to start for motor ON r r
0x849B Bool Bypass defective r r
0x849C Bool Bypass protective shutoff r r
0x849D Bool Switching element L1 defective r r
0x849E Bool Switching element L2 defective r r
0x849F Bool Switching element L3 defective r r
0x840A high 0x84A0 Bool Thermal motor model deactivated r r
0x84A3 Bool Phase angle control failure r r
low 0x84A8 Bool Switching element cooling time active r r
0x84A9 Bool Switching element for Start too hot r r
0x84AA Bool Current measuring range overshot r r
0x840B high 0x84B0 Bool Automatic mode r r
0x84B1 Bool Operating mode manual r r
0x84B2 Bool Manual operation bus - PC controlled r r
0x84B3 Bool Manual operation local r r
0x84B4 Bool Manual operation local - input controlled r r
0x84B5 Bool Manual operation local - HMI controlled r r
0x84B6 Bool Manual operation local - PC controlled r r
low 0x84B8 Bool Manual operation local - web server controlled - r
0x840C low 0x84C8 Bool Device error r r
0x840E high 0x84E0 Bool FWUpdateRejected r r
0x84E1 Bool FWUpdateActive r r
0x84E2 Bool FWUpdateSuccessful r r
0x84E3 Bool FW update unsuccessful r r
low 0x84EF Bool Operation / bypass active r r
0x8415 high 0x8556 Bool Normal operation active - r
low 0x855B Bool Test operation active - r
0x841A high 0x85A2 Bool Remaining time for tripping warning limit undershot - r
0x85A3 Bool Motor heating warning limit exceeded r r
0x85A4 Bool Warning current limit exceeded - r
0x85A5 Bool Warning current limit undershot - r
0x85A6 Bool Warning asymmetry limit exceeded - r
0x85A7 Bool Warning ground fault limit exceeded - r

SIRIUS 3RW5 Modbus TCP communication module


84 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

Register Byte Bit address Data format Soft starter diagnostics 3RW
Address high / low 521) 552)
0x841B low 0x85B8 Bool Pump cleaning active - r
0x841C high 0x85C5 Bool Analog output underflow - r
low 0x85CD Bool Analog output overflow - r
0x841E high 0x85E0 Bool Missing initialization after maintenance r r
low 0x85E8 Bool Monitoring of switching frequency time running - r
0x85E9 Bool Switching frequency time error - r
0x85EB Bool Switching frequency time error - r
0x85EF Bool Switching frequency lock active - r
0x841F high 0x85F0 Bool Emergency operation enabled - r
0x85F1 Bool Emergency operation active - r
0x85F2 Bool Emergency start enabled - r
low 0x85F9 Bool Alternative stopping mode active - r
0x8420 low 0x8608 Bool Main power rotation faulty - r
0x860B Bool Main power rotation faulty - r
0x8421 low 0x861D Bool Check fan r r
0x8422 low 0x8629 Bool Load missing - r
0x862C Bool Supply voltage too high - r
0x862F Bool No main power r r
0x8423 high 0x8631 Bool Phase failure L1 - r
0x8633 Bool Phase failure L2 - r
0x8635 Bool Phase failure L3 - r
0x8424 low 0x864A Bool Active power warning limit exceeded - r
0x864B Bool Active power warning limit undershot - r
0x864C Bool Active power error limit exceeded - r
0x864D Bool Active power error limit undershot - r
0x864E Bool Active power error limit shutoff - r
0x8426 low 0x8668 Bool Supply voltage not permitted for test - r
0x8669 Bool Supply voltage required for test - r
0x866D Bool Test with small load active - r
0x8428 high 0x8680 Bool Operating temperature too high r r
0x8688 Bool Automatic parameterization active - r
0x8429 high 0x8692 Bool Starting time warning limit exceeded - r
0x8693 Bool Starting time warning limit undershot - r
low 0x8698 Bool Logbook application - error deleted r r
0x869A Bool Logbook application - warning deleted - r
0x869C Bool Logbook application - event deleted - r
0x869D Bool Logbook service - error deleted - r
0x869F Bool Logbook service - event deleted - r
1) Supported by SIRIUS 3RW52 soft starter
2) Supported by SIRIUS 3RW55 soft starter
3) Object number of the incorrect parameter from the data table "Parameters"

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 85
Appendix
A.2 Data tables

A.2.15 Measured values


Only read access (r) to the measured values is possible via Function Codes 03 and 04.

Register Byte Data format Measured value Range of Increment 3RW


Address high / low values 521) 552)
0x8801 high Unsigned8 Phase current I L1 (%) 0 … 796.9 % 3.125 % r r
low Unsigned8 Phase current I L2 (%) 0 … 796.9 % 3.125 % r r
0x8802 high Unsigned8 Phase current I L3 (%) 0 … 796.9 % 3.125 % r r
0x8803 high Unsigned16 Remaining motor cooling time 0 … 1 800 s 0.1 s r r
0x8804 low Unsigned8 Asymmetry 0 … 100 % 1% - r
0x8805 high Unsigned16 Motor temperature rise 0 … 1 000 % 1% r r
0x8809 high Unsigned8 Output frequency 0 … 100 Hz 0.5 Hz - r
0x880B high Unsigned8 Line frequency 0 … 100 Hz 0.5 Hz - r
0x880C high Unsigned16 Line-to-line voltage U L1-L2 0 … 1 500 V 0.1 V - r
0x880D high Unsigned16 Line-to-line voltage U L2-L3 0 … 1 500 V 0.1 V - r
0x880E high Unsigned16 Line-to-line voltage U L3-L1 0 … 1 500 V 0.1 V - r
0x880F high Signed32 Phase current I L1 (rms) -20 000 … 0.01 A r r
20 000 A
0x8811 high Signed32 Phase current I L2 (rms) -20 000 … 0.01 A r r
20 000 A
0x8813 high Signed32 Phase current I L3 (rms) -20 000 … 0.01 A r r
20 000 A
0x8816 low Unsigned8 Switching element heating 0 … 250 % 1% r r
0x8817 high Unsigned16 Remaining switching element cooling time 0 … 1 800 s 0.1 s r r
0x8818 high Unsigned16 Remaining time for motor overload protection 0 … 6 500 s 0.1 s - r
0x8819 high Signed32 Active power PL1..3 -2 147 483 … 0.1 W - r
2 147 483 W
0x881B high Unsigned16 Torque 0… 1 Nm - r
65 535 Nm
0x881C high Unsigned8 Power factor L1..3 0…1 0.01 - r
0x8820 high Unsigned16 Remaining switching frequency monitoring 0 … 65 535 s 1s - r
time
0x8821 high Unsigned8 Phase current average (%) 0 … 796.9 % 3.125 % r r
0x8823 high Signed32 Phase current average (rms) -20 000 … 0.01 A r r
20 000 A
0x8825 high Signed32 Maximum phase current (rms) -20 000 … 0.01 A - r
20 000 A
1) Supported by SIRIUS 3RW52 soft starter
2) Supported by SIRIUS 3RW55 soft starter

SIRIUS 3RW5 Modbus TCP communication module


86 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.16 Statistic data


Only read access (r) to the statistical data is possible via Function Codes 03 and 04. The
data table "Statistic data" is not supported by the 3RW52 soft starter.

Register Byte Data format Statistic data Range of values Increment 3RW551)
Address high / low
0x8C01 high Unsigned8 Phase current max (%) 0 … 796.9 % 3.125 % r
0x8C02 high Unsigned16 Last tripping current IA (%) 0 … 1 000 % 3.125 % r
0x8C03 high Unsigned32 Operating hours - device 0… 1s r
4 294 967 295 s
0x8C05 high Unsigned32 Number of starts motor CW 0 … 4 294 967 295 1 r
0x8C07 high Unsigned32 Number of starts motor CCW 0 … 4 294 967 295 1 r
0x8C09 high Unsigned16 Number of motor overload trips 0 … 65 535 1 r
0x8C0B high Signed32 Maximum phase current (rms) -20 000 … 20 000 A 0.01 A r
0x8C0D high Signed32 Last tripping current IA (rms) -20 000 … 20 000 A 0.01 A r
0x8C0F high Unsigned32 Operating hours - motor 0… 1s r
4 294 967 295 s
0x8C11 high Unsigned32 Operating hours - motor current = 0… 1s r
18 ... 49.9% x Iemax 4 294 967 295 s
0x8C13 high Unsigned32 Operating hours - motor current = 0… 1s r
50 ... 89.9% x Iemax 4 294 967 295 s
0x8C15 high Unsigned32 Operating hours - motor current = 0… 1s r
90 ... 119.9% x Iemax 4 294 967 295 s
0x8C17 high Unsigned32 Operating hours - motor current = 0… 1s r
120 ... 1000% x Iemax 4 294 967 295 s
0x8C1A high Unsigned16 Number of switching element overload 0 … 65 535 1 r
trips
0x8C1B high Unsigned16 Number of bypass overload trips 0 … 65 535 1 r
0x8C1F high Unsigned32 Number of electrical braking stops 0 … 4 294 967 295 1 r
0x8C21 high Unsigned32 Number of starts output 1 0 … 4 294 967 295 1 r
0x8C23 high Unsigned32 Number of starts output 2 0 … 4 294 967 295 1 r
0x8C25 high Unsigned32 Number of starts output 3 0 … 4 294 967 295 1 r
0x8C27 high Unsigned32 Number of starts output 4 0 … 4 294 967 295 1 r
0x8C3B high Unsigned64 Active energy import (total) 0… 1 Ws r
4 294 967 295 Ws
0x8C3F high Unsigned64 Active energy export (total) 0… 1 Ws r
4 294 967 295 Ws
0x8C43 high Unsigned16 Last real starting time 0 … 1 000 s 0.1 s r
1) Supported by SIRIUS 3RW55 soft starter

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 87
Appendix
A.2 Data tables

A.2.17 Maximum pointer


Only read access (r) to the maximum pointers is possible via Function Codes 03 and 04. The
data table "Maximum pointers" is not supported by the 3RW52 soft starter.

Register Byte Data format Maximum pointer Range of values Increment 3RW551)
Address high / low
0x9001 high Unsigned8 Minimum phase current I L1 (%) 0 … 796.9 % 3.125 % r
low Unsigned8 Phase current I L2 min (%) 0 … 796.9 % 3.125 % r
0x9002 high Unsigned8 Phase current I L3 min (%) 0 … 796.9 % 3.125 % r
0x9003 high Unsigned8 Maximum phase current I L1 (%) 0 … 796.9 % 3.125 % r
low Unsigned8 Phase current I L2 max (%) 0 … 796.9 % 3.125 % r
0x9004 high Unsigned8 Phase current I L3 max (%) 0 … 796.9 % 3.125 % r
0x9005 high Unsigned16 Maximum trigger current 0 … 1000 % 3.125 % r
0x9006 high Unsigned16 Number of motor overload trips 0 … 65 535 1 r
0x9007 high Signed32 Maximum trigger current -20 000 … 20 000 A 0.01 A r
0x9009 high Signed32 Minimum phase current I L1 (rms) -20 000 … 20 000 A 0.01 A r
0x900B high Signed32 Phase current I L2 min (rms) -20 000 … 20 000 A 0.01 A r
0x900D high Signed32 Phase current I L3 min (rms) -20 000 … 20 000 A 0.01 A r
0x900F high Signed32 Maximum phase current I L1 (rms) -20 000 … 20 000 A 0.01 A r
0x9011 high Signed32 Phase current I L2 max (rms) -20 000 … 20 000 A 0.01 A r
0x9013 high Signed32 Phase current I L3 max (rms) -20 000 … 20 000 A 0.01 A r
0x9015 high Unsigned16 Line-to-line voltage U L1-L2 min 0 … 1 500 V 0.1 V r
0x9016 high Unsigned16 Line-to-line voltage U L2-L3 min 0 … 1 500 V 0.1 V r
0x9017 high Unsigned16 Line-to-line voltage U L3-L1 min 0 … 1 500 V 0.1 V r
0x9018 high Unsigned16 Line-to-line voltage U L1-L2 max 0 … 1 500 V 0.1 V r
0x9019 high Unsigned16 Line-to-line voltage U L2-L3 max 0 … 1 500 V 0.1 V r
0x901A high Unsigned16 Line-to-line voltage U L3-L1 max 0 … 1 500 V 0.1 V r
0x901D low Unsigned8 Maximum switching element heating 0 … 250 % 1% r
0x901E high Unsigned8 Minimum line frequency 0 … 100 Hz 0.5 Hz r
low Unsigned8 Maximum line frequency 0 … 100 Hz 0.5 Hz r
0x901F high Unsigned32 Operating hours - motor current = 0 … 4 294 967 295 s 1s r
18 ... 49.9% x Ie
0x9021 high Unsigned32 Operating hours - motor current = 0 … 4 294 967 295 s 1s r
50 ... 89.9% x Ie
0x9023 high Unsigned32 Operating hours - motor current = 0 … 4 294 967 295 s 1s r
90...119.9% x Ie
0x9025 high Unsigned32 Operating hours - motor current = 0 … 4 294 967 295 s 1s r
120...1000% x Ie
0x9027 high Unsigned32 Operating hours - device 0 … 4 294 967 295 s 1s r
0x902B high Signed32 Starting current I max (rms) -20 000 … 20 000 A 0.01 A r
0x902D high Signed32 Starting current I L1 max (rms) -20 000 … 20 000 A 0.01 A r
0x902F high Signed32 Starting current I L2 max (rms) -20 000 … 20 000 A 0.01 A r
0x9031 high Signed32 Starting current I L3 max (rms) -20 000 … 20 000 A 0.01 A r
1) Supported by SIRIUS 3RW55 soft starter

SIRIUS 3RW5 Modbus TCP communication module


88 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.18 Parameters
Read access (r) to the parameters is possible via Function Codes 03 and 04. Write access
(w) is possible for individual parameters via function codes 06 and 16.

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x9401 high Bit4 Automatic parameterization [0 ... 2] - - r/w
[2313] [0] Off [0]
[1] ON - with preset
starting time
[2] ON - with preset
starting time and current
limit
0x9402 high Unsigned16 Preset starting time 0 … 360 s 0.1 s - r/w
[2315] [0 … 3 600] [100]
0x9403 high Unsigned32 Rated operational current Ie - 0.01 A r r/w
[130] SIRIUS 3RW55 soft starter, 2.5 … 22.5 A 0.01 A - [250]
High Feature, 13 A, 3-phase [250 … 2 250]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 3.5 … 31.1 A 0.01 A - [350]
High Feature, 18 A, 3-phase [350 … 3 110]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 5 … 43.3 A 0.01 A - [500]
High Feature, 25 A, 3-phase [500 … 4 330]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 6.5 … 55.4 A 0.01 A - [650]
High Feature, 32 A, 3-phase [650 … 5 540]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 7.5 … 65.8 A 0.01 A - [750]
High Feature, 38 A, 3-phase [750 … 6 580]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 5 … 43.3 A 0.01 A - [500]
High Feature, 25 A / 690 V, [500 … 4 330]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 10 … 81.4 A 0.01 A - [1 000]
High Feature, 47 A, 3-phase [1 000 … 8 140]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 13 … 109 A 0.01 A - [1 300]
High Feature, 63 A, 3-phase [1 300 … 10 900]
controlled, motor overload
protection, torque control

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 89
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
SIRIUS 3RW55 soft starter, 16 … 133 A 0.01 A - [1 600]
High Feature, 77 A, 3-phase [1 600 … 13 300]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 19 … 161 A 0.01 A - [1 900]
High Feature, 93 A, 3-phase [1 900 … 16 100]
controlled, motor overload
protection, torque control
SIRIUS 3RW55 soft starter, 23 … 195 A 0.01 A - [2 300]
High Feature, 113 A, [2 300 … 19 500]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 29 … 247 A 0.01 A - [2 900]
High Feature, 143 A, [2 900 … 24 700]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 34 … 296 A 0.01 A - [3 400]
High Feature, 171 A, [3 400 … 29 600]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 42 … 363 A 0.01 A - [4 200]
High Feature, 210 A, [4 200 … 36 300]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 50 … 433 A 0.01 A - [5 000]
High Feature, 250 A, [5 000 … 43 300]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 63 … 545 A 0.01 A - [6 300]
High Feature, 315 A, [6 300 … 54 500]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 74 … 640 A 0.01 A - [7 400]
High Feature, 370 A, [7 400 … 64 000]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 94 … 814 A 0.01 A - [9 400]
High Feature, 470 A, [9 400 … 81 400]
3-phase controlled, motor
overload protection, torque
control

SIRIUS 3RW5 Modbus TCP communication module


90 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
SIRIUS 3RW55 soft starter, 114 … 987 A 0.01 A - [11 400]
High Feature, 570 A, [11 400 … 98 700]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 126 … 1 091 A 0.01 A - [12 600]
High Feature, 630 A, [12 600 … 109 100]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 144 … 1 247 A 0.01 A - [14 400]
High Feature, 720 A, [14 400 … 124 700]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 168 … 1 454 A 0.01 A - [16 800]
High Feature, 840 A, [16 800 … 145 400]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 220 … 1 905 A 0.01 A - [22 000]
High Feature, 1100 A, [22 000 … 190 500]
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter, 256 … 2 217 A 0.01 A - [25 600]
High Feature, 1280 A, [25 600 … 221 700]
3-phase controlled, motor
overload protection, torque
control
0x9405 high Unsigned8 Service factor 1 … 1.15 0.01 - r/w
[2212] [100 … 115] [100]
0x9406 high Unsigned16 Rated torque 0 … 10 000 Nm 1 Nm - r/w
[113] [0 … 10 000] [0]
0x9407 high Unsigned16 Rated operating speed 500 … 3 600 rpm 1 rpm - r/w
[104] [500 … 3 600] [1500]
0x9408 high Bit4 Motor connection type [0 ... 2] - - r/w
[228] [0] Automatic detection [0]
[1] Star/delta
[2] Inside_delta
0x9409 high Bit4 Starting mode [0 ... 6] - r r/w
[167] [0] Direct [5] [5]
[1] Voltage ramp
[2] Torque control
[3] Motor heating
[5] Voltage ramp +
Current limiting
[6] Torque control +
Current limiting

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 91
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x940A high Unsigned8 Start voltage 20 … 100 % 5% r r/w
[40] [4 … 20] [6] [6]
0x940B high Unsigned16 Current limiting value 125 … 800 % 1% r r/w
[235] [125 … 800] [400] [400]
0x940C high Unsigned8 Starting torque 10 … 100 % 5% - r/w
[172] [2 … 20] [2]
0x940D high Unsigned8 Limiting torque 20 … 200 % 5% - r/w
[118] [4 … 40] [30]
0x940E high Unsigned16 Ramp-up time 0 … 360 s 0.1 s r r/w
[170] [0 … 3 600] [100] [100]
0x940F high Unsigned16 Maximum starting time 0 … 1 000 s 0.1 s - r/w
[169] [0 … 10 000] [0]
0x9410 high Unsigned8 Breakaway time 0…2s 0.01 s - r/w
[116] [0 … 200] [0]
0x9411 high Unsigned8 Breakaway voltage 40 … 100 % 5% - r/w
[117] [8 … 20] [8]
0x9412 high Unsigned8 Motor heating power 1 … 100 % 1% - r/w
[119] [1 … 100] [20]
0x9413 high Bit4 Stopping mode [0 ... 5] - r r/w
[168] [0] Coasting down [1] [0]
[1] Voltage ramp
[2] Torque control
[3] Pump stopping mode
[4] DC braking
[5] Dynamic DC braking
0x9414 high Unsigned16 Stopping time 0 … 360 s 0.1 s r r/w
[171] [0 … 3 600] [0] [100]
0x9415 high Unsigned8 Stopping torque 10 … 100 % 5% - r/w
[173] [2 … 20] [2]
0x9416 high Unsigned8 Dynamic braking torque 20 … 100 % 5% - r/w
[178] [4 … 20] [10]
0x9417 high Unsigned8 DC braking torque 20 … 100 % 5% - r/w
[47] [4 … 20] [10]
0x9418 high Bit4 Alternative stopping mode [0 ... 5] - - r/w
[2326] [0] Coasting down [0]
[2] Torque control
[3] Pump stopping mode
[4] DC braking
[5] Dynamic DC braking
0x9419 high Unsigned16 Alternative stopping time 0 … 360 s 0.1 s - r/w
[2327] [0 … 3 600] [100]
0x941A high Unsigned8 Alternative stopping torque 10 … 100 % 5% - r/w
[2329] [2 … 20] [2]
0x941B high Unsigned8 Alternative dynamic braking 20 … 100 % 5% - r/w
[2332] torque [4 … 20] [10]

SIRIUS 3RW5 Modbus TCP communication module


92 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x941C high Unsigned8 Alternative DC braking 20 … 100 % 5% - r/w
[2331] torque [4 … 20] [10]
0x941D high Bit4 Tripping class [0 ... 15] - r r/w
[6] [0] CLASS 10E [3] [0]
[1] CLASS 20E
[2] CLASS 30E
[3] CLASS 10A
[15] CLASS OFF
0x941E high Unsigned16 Warning limit - remaining 0 … 500 s 1s - r/w
[2211] time for tripping [0 … 500] [0]
0x941F high Unsigned8 Motor heating warning limit 0 … 99 % 1% - r/w
[2210] [0 … 99] [0]
0x9420 high Bit2 Response to overload [0 ... 1] - r r/w
[5] thermal motor model [0] Turn off without [0] [0]
restart
[1] Turn off with restart
0x9421 high Unsigned8 Recovery time 60 … 1 800 s 30 s - r/w
[7] [2 … 60] [10]
0x9422 high Bit4 Temperature sensor [0 ... 2] - - r/w
[9] [0] Deactivated [0]
[1] Thermoclick
[2] PTC type A
0x9423 high Bit2 Response to overload [0 ... 2] - r r/w
[10] temperature sensor [0] Turn off without [0] [0]
restart
[1] Turn off with restart
[2] Warn
0x9424 high Unsigned8 Creep speed factor right 3 … 21 1 - r/w
[43] [3 … 21] [7]
0x9425 high Unsigned8 Creep speed torque right 20 … 100 % 5% - r/w
[44] [4 … 20] [10]
0x9426 high Unsigned8 Creep speed factor left 3 … 21 1 - r/w
[198] [3 … 21] [7]
0x9427 high Unsigned8 Creep speed torque left 20 … 100 % 5% - r/w
[199] [4 … 20] [10]
0x9428 high Unsigned16 Current upper limit error 50 … 400 % 5% - r/w
[2337] [50 … 400] [0]
[0] Deactivated
0x9429 high Unsigned16 Current upper limit warning 50 … 400 % 5% - r/w
[2338] [50 … 400] [0]
[0] Deactivated
0x942A high Unsigned8 Current lower limit error 20 … 100 % 5% - r/w
[2340] [20 … 100] [0]
[0] Deactivated

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 93
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x942B high Unsigned8 Current lower limit warning 20 … 100 % 5% - r/w
[2341] [20 … 100] [0]
[0] Deactivated
0x942C high Unsigned32 Active power reference 0 … 2 000 000 W 1W - r/w
[2250] value [0 … 2 000 000] [0]
0x942E high Unsigned16 Active power upper limit 0 … 400 % 1% - r/w
[2251] error [0 … 400] [0]
0x942F high Unsigned16 Active power upper limit 0 … 400 % 1% - r/w
[2252] warning [0 … 400] [0]
0x9430 high Unsigned8 Active power lower limit 0 … 100 % 1% - r/w
[2254] error [0 … 100] [0]
0x9431 high Unsigned8 Active power lower limit 0 … 100 % 1% - r/w
[2255] warning [0 … 100] [0]
0x9432 high Unsigned16 Starting time upper limit 0 … 400 % 1% - r/w
[2317] warning [0 … 400] [0]
0x9433 high Unsigned8 Starting time lower limit 0 … 100 % 1% - r/w
[2320] warning [0 … 100] [0]
0x9434 high Bit4 Warning asymmetry limit 10 … 60 % 5% - r/w
[2218] [2 … 12] [0]
[0] Deactivated
0x9435 high Bit4 Asymmetry limit error 10 … 60 % 5% - r/w
[21] [2 … 12] [6]
[0] Deactivated
0x9436 high Unsigned8 Ground fault limit warning 10 … 95 % 5% - r/w
[2220] [2 … 19] [0]
[0] Deactivated
0x9437 high Unsigned8 Ground fault limit error 10 … 95 % 5% - r/w
[2294] [2 … 19] [4]
[0] Deactivated
0x9438 high Bit4 Emergency start [0 ... 1] - - r/w
[2242] [0] Disable [1]
[1] Manually enable/
disable
0x943A high Unsigned8 Input 1-Action [0 ... 45] - - r/w
[194] [0] No action [16]
[6] Manual operation local
[7] Emergency start
[10] Creep speed
[11] Quick-stop
[12] Reset
[16] Motor CW with PS1
[17] Motor CCW with PS1
[18] Motor CW with PS2
[19] Motor CCW with PS2
[20] Motor CW with PS3
[21] Motor CCW with PS3

SIRIUS 3RW5 Modbus TCP communication module


94 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
[43] Motor standstill
[44] Use alternative
stopping mode
[45] Pump cleaning mode
0x943B high Unsigned8 Input 2-Action (see Input 1-Action) - - r/w
[195] [0]
0x943C high Unsigned8 Input 3-Action (see Input 1-Action) - - r/w
[196] [0]
0x943D high Unsigned8 Input 4-Action (see Input 1-Action) - - r/w
[197] [12]
0x943E high Unsigned8 Output 1-Action [0 ... 201] - r r/w
[163] [0] No action [14] [13]
[1] Control source
PIQ-DO-1.0 output 1
[2] Control source
PIQ-DO-1.1 output 2
[6] Control source input 1
[7] Control source input 2
[8] Control source input 3
[9] Control source input 4
[10] Start-up
[11] Operation / bypass
[12] Run-down
[13] On time motor (RUN)
[14] Control command
MOTOR ON
[16] DC braking contactor
[18] Device on
[19] Operation /
Run-down
[31] Group warning
[32] Group error
[33] Bus error
[34] Device error
[38] Ready to start for
motor ON
[41] Generator operation
[42] Pump cleaning active
[43] Alternative stopping
mode active
[44] CM - maintenance
demanded
[45] CM - error
[180] Control source PIQ-
DO 2.0 output 3
[200] Reversing
switching element - right
[201] Reversing
switching element - left
0x943F high Unsigned16 Output 1-Time 0 … 6 500 s 0.1 s - r/w
[159] [0 … 65 000] [0]

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 95
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x9440 high Unsigned16 Output 1-Time 2 0 … 6 500 s 0.1 s - r/w
[2333] [0 … 65 000] [0]
0x9441 high Unsigned8 Output 2-Action (see Output 1-Action) - - r/w
[164] [0]
0x9442 high Unsigned16 Output 2-Time 0 … 6 500 s 0.1 s - r/w
[160] [0 … 65 000] [0]
0x9443 high Unsigned16 Output 2-Time 2 0 … 6 500 s 0.1 s - r/w
[2334] [0 … 65 000] [0]
0x9444 high Unsigned8 Output 4-Action (see Output 1-Action) - - r/w
[166] [0]
0x9445 high Unsigned16 Output 4-Time 0 … 6 500 s 0.1 s - r/w
[162] [0 … 65 000] [0]
0x9446 high Unsigned16 Output 4-Time 2 0 … 6 500 s 0.1 s - r/w
[2336] [0 … 65 000] [0]
0x9447 high Unsigned8 Analog output - signal type [0 ... 3] - r r/w
[2222] [0] Deactivated [2] [0]
[2] 4-20mA
[3] 0-10V
0x9448 high Unsigned16 Analog output - measured [0 ... 632] - - r/w
[2223] value [0] Deactivated [0]
[502] Motor temperature
rise
[504] Phase current I
L1 (%)
[505] Phase current I
L2 (%)
[506] Phase current I
L3 (%)
[510] Line-to-line voltage
U L1-L2
[511] Line-to-line voltage
U L2-L3
[512] Line-to-line voltage
U L3-L1
[513] Phase current I
L1 (rms)
[514] Phase current I
L2 (rms)
[515] Phase current I
L3 (rms)
[518] Switching element
heating
[521] Active power PL1..3
[523] Power factor L1..3
[528] Phase current
average (%)
[530] Phase current
average (rms)
[632] Active energy
import (total)

SIRIUS 3RW5 Modbus TCP communication module


96 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x9449 high Unsigned32 Analog output - range start 0 … 4 294 967 295 1 r r/w
[2224] value [0 … 4 294 967 295] [0] [0]
0x944B high Unsigned32 Analog output - range end 0 … 4 294 967 295 1 r r/w
[2225] value [0 … 4 294 967 295] [96] [27 648]
0x944E high Bool Response to CPU/Master [0 ... 1] - - r/w
[34] Stop [0] Switch substitute [0]
value
[1] Keep last value
0x944F high Bit32 Substitute value - - - r/w
[35] [0]
0x9452 high Bit2 Response to overload [0 ... 1] - r r/w
[140] switching element [0] Turn off without [0] [0]
restart
[1] Turn off with restart
0x9453 high Bit4 Response to faulty main [1 ... 2] - - r/w
[232] power [1] Group error only at [1]
ON command
[2] Warn
0x9454 high Bit4 Response to preset unequal [0 ... 4] - - r/w
[129] actual configuration [0] Turn off [0]
[1] Warn
[4] Ignore
0x9455 high Bit4 Pump cleaning mode [0 ... 1] - - r/w
[2344] [0] Deactivated [0]
[1] Manual
low Bit4 Pump cleaning - start/stop [1 ... 5] - - r/w
[2345] parameters [1] Parameter set 1 [5]
[2] Parameter set 2
[3] Parameter set 3
[5] Operating parameters
0x9456 high Unsigned8 Pump cleaning - time 0 ... 30 s 1s - r/w
[2346] [0 ... 30] [20]
low Unsigned8 Pump cleaning - cycles 0 ... 10 1 - r/w
[2347] [0 ... 10] [3]
0x9457 high Unsigned16 Current limiting value - 125 ... 800 % 1% - r/w
[2352] automatic parameterization [125 ... 800] [400]

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 97
Appendix
A.2 Data tables

Register Byte Data format Parameters Range of values Increment 3RW


Address high / low [Obj. No.] [encoding] 521) 552)
[D*] [D*]
0x945C high Unsigned16 Measured value 1 [20 000 ... 20 006] - - r/w
[2002] [20 000] Phase current I [20 000]
L1 (rms)
[20 001] Phase current I
L2 (rms)
[20 002] Phase current I
L3 (rms)
[20 003] Phase current
average (rms)
[20 004] Active energy
import (total)
[20 005] Active power
PL1..3
[20 006] Power factor
L1..3
0x945D high Unsigned16 Measured value 2 (see Measured value 1) - - r/w
[2003] [20 001]
0x945E high Unsigned16 Measured value 3 (see Measured value 1) - - r/w
[2004] [20 002]
1) Supported by SIRIUS 3RW52 soft starter
2) Supported by SIRIUS 3RW55 soft starter
* Default coding

Dependencies
During parameterization, it is possible to select impossible combinations of interdependent
values. In the "Soft starter diagnostics" data table (Page 82) the diagnosis
"InvalidParameter" is then signaled. You will find the dependencies of the parameters in the
Manual of the 3RW5 soft starter.

SIRIUS 3RW5 Modbus TCP communication module


98 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.19 Communication parameters


Read access (r) to the communication parameters is possible via Function Codes 03 and 04.
Write access (w) is possible for individual communication parameters via function codes 06
and 16.

Register Byte Data format Parameters Range of values Default Access


Address high / low [encoding]
0xA102 high Unsigned32 Access monitoring time [5 000 ... 10 000] 5 000 r/w
[5 000] 5 s
[10 000] 10 s
- - Unsigned32 IP address - - -
(Byte3.Byte2.Byte1.Byte0)
0xA10E high Byte 3 [0 ... 255] 192 r/w
low Byte 2 [0 ... 255] 168 r/w
0xA10F high Byte 1 [0 ... 255] 42 r/w
low Byte 0 [0 ... 255] 99 r/w
- - Unsigned32 Subnet mask - - -
(Byte3.Byte2.Byte1.Byte0)
0xA110 high Byte 3 [0 ... 255] 255 r/w
low Byte 2 [0 ... 255] 255 r/w
0xA111 high Byte 1 [0 ... 255] 255 r/w
low Byte 0 [0 ... 255] 0 r/w
- - Unsigned32 Address of router - - -
(Byte3.Byte2.Byte1.Byte0)
0xA112 high Byte 3 [0 ... 255] 0 r/w
low Byte 2 [0 ... 255] 0 r/w
0xA113 high Byte 1 [0 ... 255] 0 r/w
low Byte 0 [0 ... 255] 0 r/w
0xA114 high OctetString6 MAC address - - r

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 99
Appendix
A.2 Data tables

A.2.20 HMI diagnostics


For access to the HMI diagnostics only read access (r) is possible via Function Codes 01,
02, 03 and 04.

Register Byte Bit address Data format HMI diagnostics 3RW5


Address high / low HMI HF1)
0xB000 high 0xB000 Bool HMIFault r
0xB001 Bool Run r
low 0xB008 Bool Factory settings restored r
0xB001 high 0xB010 Bool FWUpdateRejected r
0xB011 Bool FWUpdateActive r
0xB012 Bool FWUpdateSuccessful r
0xB013 Bool FWUpdateUnsuccessful r
0xB014 Bool Invalid signature FW update r
low 0xB018 Bool Self-test active r
0xB01A Bool Error during self-test r
0xB002 high 0xB020 Bool Device assigned r
0xB021 Bool Device incompatible r
0xB022 Bool Incorrect interface r
0xB023 Bool Incorrect HMI r
0xB024 Bool HMI not configured r
0xB004 high 0xB040 Bool MemoryModuleActive r
0xB041 Bool MemoryModuleAccessError r
0xB042 Bool MemoryModulePlugged r
0xB043 Bool MemoryModuleWriteProtected r
low 0xB048 Bool Local interface active r
0xB049 Bool local interface defective r
0xB04B Bool Local interface data invalid r
0xB005 high 0xB050 Bool InvalidParameter r
low 0xB058 Bool Local interface disabled due to flooding r
0xB05A Bool First access denied r
0xB05B Bool Configuration Access Changed r
0xB05C Bool Unauthorized Access Denied r
0xB05D Bool AddressFilterConfigured r
0xB05E Bool SecureChannelEstablishing r
0xB05F Bool Encryption not correct r
0xB006 high 0xB060 Bool Timeout Secured Connection r
0xB061 Bool SecuredConnectionEnded r
0xB062 Bool Useful data protected r
0xB063 Bool User Account Set Up r
low 0xB068 Bool No device answer r
0xB007 high 0xB070 Bool Write Error r
0xB071 Bool ReadError r
0xB072 Bool FileSystemError r
1) Supported by 3RW5 HMI High Feature

SIRIUS 3RW5 Modbus TCP communication module


100 Manual, 03/2018, A5E43676481002A/RS-AA/001
Appendix
A.2 Data tables

A.2.21 HMI basic parameters


Read access (r) to the HMI basic parameters is possible via Function Codes 03 and 04.
Write access (w) is possible for individual HMI basic parameters via function codes 06 and
16.

Register Byte Data format Parameters Range of values Increment 3RW5


Address high / low [encoding] HMI HF1)
[D*]
0xB100 high Unsigned8 Language [0 ... 254] - r/w
[0] English [0]
[1] German
[2] French
[3] Spanish
[4] Italian
[5] Chinese
[6] Portuguese
[254] Loadable language
0xB101 high Unsigned16 Display shutdown delay 1 … 60 min 1 min r/w
[1 … 60] [5]
[0] Deactivated
0xB102 high Bool Display time [0 ... 1] - r/w
[0] Disable [0]
[1] Enable
0xB103 high Bool Do Control After Logoff [0 … 1] - r/w
[0] Stop motor and give back control [0]
[1] Continue with motor control
1) Supported by 3RW5 HMI High Feature
* Default coding

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 101
Appendix
A.2 Data tables

SIRIUS 3RW5 Modbus TCP communication module


102 Manual, 03/2018, A5E43676481002A/RS-AA/001
Glossary

Configuration
Configuration is the systematic arrangement, setting, and networking of the individual
3RW5 soft starters within the device or network view.

Configuring
This section refers to the configuration and parameterization of 3RW5 soft starters.

Diagnostics
Data that is transferred from the 3RW5 soft starter and indicates the current operating status.

Fieldbus
Industrial communication system that connects a large number of field devices such as
probes (sensors), final controlling elements, and drives (actuators) to a control device.

I&M data
Identification and maintenance data.
Information stored in a module that helps you to check the plant configuration, to locate
hardware modifications in a plant, or to remedy faults in a plant. I&M data enable modules to
be uniquely identified online.

IP address
To enable a Modbus TCP device to be addressed as a node on Industrial Ethernet, this
Modbus TCP device requires an IP address that is unique within the network. The IP
address is made up of 4 decimal numbers with a range of values from 0 through 255. The
decimal numbers are separated by a decimal point.
The IP address is made up as follows:
● Address of the (sub)net
● Address of the station (host or network node)

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 103
Glossary

MAC address
The MAC address is a worldwide unique device identification and is assigned to each
Modbus TCP device during production. The Modbus TCP device can be accessed via the
MAC address via LAN.
The MAC address is 6 bytes long and has the following structure:
● 3 bytes for the manufacturer ID
● 3 bytes with a device identifier (consecutive number).
The MAC address can generally be read from the front on the device,
e.g.: 08-00-06-6B-80-C0.

Messages
Data that is transferred from the 3RW5 soft starter and indicates the current operating status.

Parameterization
Parameterization is the definition of parameters using the parameterization software.

PII/PIQ
Process image input/process image output

Reading data
Data are transferred from the 3RW5 soft starter.

Receive data
Data that are transferred to the 3RW5 soft starter.

SIRIUS Soft Starter ES (TIA Portal)


SIRIUS Soft Starter ES (TIA Portal) is the central software for commissioning, operating, and
diagnostics of the SIRIUS 3RW5 soft starter series.

STEP 7
The basic STEP 7 software is the standard tool for the SIMATIC S7, SIMATIC C7, and
SIMATIC WinAC automation systems.

Writing data
Data are transferred to the 3RW5 soft starter.

SIRIUS 3RW5 Modbus TCP communication module


104 Manual, 03/2018, A5E43676481002A/RS-AA/001
Index

Communication parameters, 99
Energy management, 79
3 HMI basic parameters, 101
HMI diagnostics, 100
3D model, 8
I&M0 - Basic unit, 77
3RW5, 19
I&M0 - Communication, 77
3RW5 HMI High Feature
I&M0 - HMI HF, 79
Diagnostics, 47
I&M1 - Basic unit, 78
Firmware update, 64
I&M2 - Basic unit, 78
IP parameters, 43
I&M3 - Basic unit, 78
Operation with CPU / Master, 46
Maximum pointer, 88
3RW5 soft starter, 19
Measured values, 86
Node flash test, 76
Parameters, 89
A
Process image input (PII), 80
Access monitoring, 22 Process image output (PIQ), 81
Access to memory areas, 52 Soft starter diagnostics, 82
Address of router, 44 Specifications, 75
App Statistic data, 87
Siemens Industry Online Support, 11 Data transfer, 24
Article number, 20 Diagnostics
Assignment of the data, 21 3RW5 HMI High Feature, 47
Diagnostics options, 47
Diagnostics options, 47
B Dimension drawings, 8
Disposal, 17
Bus connector, 27
Connecting, 35
Pull out, 37
E
Byte arrangements, 75
EPLAN macros, 8
Error codes, 61
C ESD guidelines, 14
Exception responses, 23
CAx data, 8, 69, 71
Exception Responses, 61
Communication module, 19
Communication parameters, 65
Configuring, 39
F
Connecting cable, 27
Connection monitoring, 22 Factory setting, 66
Cover of the slot, 30 FAQs, 10
Current values, 73 Faults, 62
Firmware update, 63
Function code, 23
D Function Code, 51
Data, 23
Data security, 16
Data table
Byte arrangements, 75

SIRIUS 3RW5 Modbus TCP communication module


Manual, 03/2018, A5E43676481002A/RS-AA/001 105
Index

G P
Guidelines PLC, 19
ESD guidelines, 14 Process image input (PII), 80
Guidelines on information security in industrial Process image output (PIQ), 81
automation, 17 Product data sheet, 69, 71

H R
Hardware configuration, 20 Recommended bus connector, 27
Recycling, 17
References, 9
I Remedial measures, 62
Removal, 33
Industrial Ethernet, 27
Replacing, 65
Interaction interfaces, 24
IP address, 44
IP parameters, 44
S
SIRIUS 3RW5 soft starter, 19
K SIRIUS Soft Starter ES (TIA Portal), 28
Slot, 19
Knowledge, 19
Statistic data, 74
Subnet mask, 44
L
LED display, 48 T
Target group, 19
Technical Assistance, 9
M
Telegram structure, 23
MAC address, 44
Manuals, 9
Maximum pointer, 74 V
Memory image, 76
VDI guideline, 17
Micro SD memory card, 64, 65
Modbus TCP, 21
Mounting, 29, 32

N
Network environment, 19
Node flash test, 76, 76

O
Object number, 75
Online help, 9
Operating mode, 25, 62

SIRIUS 3RW5 Modbus TCP communication module


106 Manual, 03/2018, A5E43676481002A/RS-AA/001

You might also like