MODULE 3 - March2017
MODULE 3 - March2017
• COMFORT AIRCONDITIONING .
• SUMMER AIR-CONDITIONING.
• WINTER AIR-CONDITIONING.
• YEAR ROUND AIR-CONDITIONING.
BYPASS FACTOR-A • IF T1 IS INLET TEMPERATURE OF AIR & T2 IS
MEASURE OF EFFICIENCY TEMPERATURE OF THE COIL, THEN THE
TEMP. OF AIR COMING OUT OF THE COIL
WILL BE LESS THAN THE TEMP. T2. ASSUME
IT TO BE T3, WHERE (T3<T2). BUT, T3>T1.
ONE KG OF AIR IS PASSED OVER THE COIL AT
TEMP. T1 & IS COMING OUT AT TEMP. T3.
IT CAN BE SAID THAT B KG OUT OF ONE KG
IS BYPASSED & REMAINING (1-B) KG OF AIR
IS COMING OUT WITH A TEMPERATURE T3.
BALANCING THE ENTHALPIES, B=T2-T3/T2-T1,
PERFORMANCE OF COIL IS WHERE B IS BYPASS FACTOR OF THE COIL.
BETTER WITH LOWER BYPASS
FACTOR. THE FACTOR (1-B) IS THE MASS ACTUALLY
COMING IN PERFECT CONTACT WITH THE
COILS SO IT IS TERMED AS EFFICIENCY OF
HEATING COIL.
PSYCHROMETRIC PROCESSES & BYPASS FACTOR
CALCULATIONS
4- REQUIRED COMFORT CONDITION BYPASS FACTOR OF COOLING COIL= (2-3)/(2-1) , EFFICIENCYOF HUMIDIFIER= T3-T4/T3-T5 X 100
5
4
AIR VIA ADIABATIC HUMIDIFIER
2 3 1
AIR PASSED THRU COOLING COIL SENSIBLE
COOLING
WARM,HUMID
SUMMER AC SYSTEM (HOT &
HUMID CONDITIONS) • EG-MUMBAI-32 DEG, 75% R.H. REQ. COMFORT
COND. – 24 DEG, 60% R.H.
• FIRST AIR IS PASSED THRU THE COOLING COIL
FOR DEHUMIDIFICATION & IT LEAVES THE
COOLING COIL AS THE COOLING TEMPERATURE
IS BELOW THE DEW POINT TEMPERATURE OF
INCOMING AIR. THE BYPASS FACTOR OF
COOLING COIL = DIST.(2-3)/DIST.(2-1)
• GENERAL FORMULA FOR BY-PASS FACTOR =
INITIAL COOLING/DEHUMIDF. COIL: COIL TEMP-OUTGOING TEMP (i.e. FINAL
1: ATMOSPHERIC CONDITION
CONDITION) / COIL TEMP - INCOMING
2: COOLING COIL TEMP
TEMPERATURE (i.e. INITIAL CONDITION)
3: COOLED AIR
HEATING COIL • THE AIR ENTERS THE HEATING COIL AT (3) &
3: INITIAL CONDITION COMES OUT AT (5), THE BYPASS FACTOR OF THE
4: HEATING COIL TEMPERATURE HEATING COIL = DIST.(4-5)/DIST.(4-3).
5: CONDITIONED AIR • An adiabatic process is any process occurring without
gain or loss of heat within a system (i.e. during the
1: ATMOSPHERIC CONDITION process the system is thermodynamically isolated-
5: FINAL REQUIRED COMFORT COND. there is no heat transfer with the surroundings). This is
the opposite of a diabatic process, where there is heat
transfer.
WINTER AIR-CONDITIONING SYSTEM FOR MILD COLD WEATHER
• WINTER COND. OF 15 DEG CELSIUS & 80% RH.
• 1=ATMOSPHERIC CONDITION
• 6=REQ. COMFORT CONDITION
• AIR IS PASSED THRU THE RESISTANCE HEATER WHICH IS KNOWN AS PRE-
HEATING COIL & THEN IS PASSED THRU THE HUMIDIFIER & AGAIN THRU
THE SECOND HEATER.
WINTER AIR-CONDITIONING SYSTEM FOR MILD COLD
WEATHER
1=ATMOSPHERIC CONDITION
6=REQ. COMFORT CONDITION
EFFECTIVENESS OF DIFF.EQP & THEIR CAPACITIES
1=ATMOSPHERIC CONDITION
6=REQ. COMFORT CONDITION
VARIOUS AIR CONDITIONING PROCESSES
• Cooling with dehumidification of air.
• Cooling with Adiabatic Humidification of air. (SPRAY
CHAMBER)
• Adiabatic Chemical dehumidification. (PASSING THRU SOLID
ABSORBENT BED/LIQUID ABSORBENT SPRAY)
• Humidification by steam injection.
• Mixing of air-streams.
• An adiabatic process is any process occurring without gain or
loss of heat within a system (i.e. during the process the
system is thermodynamically isolated- there is no heat
transfer with the surroundings). This is the opposite of
a diabatic process, where there is heat transfer.
YEAR-ROUND AIR-CONDITIONING
The following are the basic parts for a window unit air conditioner.
Exterior
•Adjustable louvers
•Control panel
•Front grill
•Thermostat sensor
Interior
•Blower
•Partition
•Fan
•Compressor
•Condenser coil
•Evaporator coil
•Filter
The window unit offers the following advantages:
1. Each room or area in which a unit is installed has separate temperature control.
2. No ducts are required.
3. Installation is quite simple; therefore, construction changes are usually not required.
These PTAC systems which are frequently used in hotels have two separate units
(terminal packages), the evaporative unit on the interior and the condensing unit on
the exterior, with tubing passing through the wall and connecting them.
This minimizes the interior system footprint and allows each room to be adjusted
independently.
PTAC systems may be adapted to provide heating in cold weather, either directly by
using an electric strip, gas or other heater, or by reversing the refrigerant flow to heat
the interior and draw heat from the exterior air, converting the air conditioner into a
heat pump.
While room air conditioning provides maximum flexibility, when used to cool many
rooms at a time it is generally more expensive than central air conditioning.
Split portable units have certain advantages as in that :
1.interior noise and size of the internal unit can be greatly reduced due to the
external location of the compressor, and
2. the water collected can be pumped to the outdoor unit using a pump, avoiding the
need to drain water from the indoor unit periodically when running in cooling mode.
•is that a surface exterior to the building, such as a balcony must be provided for the
external compressor unit to be located.
•Most split system air conditioners do not introduce outside air for ventilation, and
only perform a temperature control function.
•It is, however, possible to add ventilation ducting to some split systems, so that they
do bring fresh air into the room.
•Also Split ACs are costlier than Window ACs.
That’s all for Module - 3
Thanks….