C690 D5
Diesel Generator Set
Certified to ISO9001 and ISO9002 for generator set design and Alternator: Stamford HC series alternator.
manufacture. Type:Revolving magnetic field, single bearing, 4 pole, brushless, drip
proof structure, in accordance with GB755, BS5000, and IEC34-1.
Cummins provides full quality assurance and is responsible for the Stator:Taper slot structure, 2/3 pitch windings, effectively
warranty of generator sets including engine, alternator and control suppressing waveform distortion of third harmonic current and output
system. voltage under non-linear load.
Rotor:Flexible driving disc connected to engine directly, perfect
Worldwide service network ensures 24 hours after-sale service and the damper winding reduces parallel oscillation.
supply of parts and accessories. Cooling system:Directly drive centrifugal blower fan.
.
Control System: PowerCommand® control system based on
microprocessor.
Engine Specifications
Model KTAA19-G6A
Configuration Cast iron, in-line, 6-cylinder
Displacement, L 18.9
Compression ratio 13.0:1
Aspiration Turbocharged and air-to-air aftercooled
Fuel system Direct injection
Bore* stroke, mm 159*159
Rated speed, rpm 1500
Governor type Electronic
Starting voltage 24V, negative ground
Battery charging alternator 24V,35A
Cold starting current, CCA 900 (-18℃)
Lube oil capacity, L 50
Combustion air (standby), m³/s 0.75
Coolant capacity, L 26.5
Maximum fuel flow, L/hr 242
Maximum fuel inlet resistance, mmHg 101.6
Alternator Specifications
Protection class IP23
Insulation system Class H
Standard temperature rise Standby, 150℃(at 40℃ ambient temperature)
Exciting type Self-exciting
AC waveform total harmonic distortion <1.5% no load, <5% 3-phase balanced linear load
Telephone influence factor(TIF) <50(per NEMA MG1-22.43)
Telephone harmonic factor(THF) <2%
Exhaust
Exhaust gas flow at set rated load (standby), m 3/min 148.68
Exhaust gas temperature (standby), ℃ 446
Maximum exhaust back pressure, kPa 10
Model Dim “A”(mm) Dim “B”(mm) Dim “C”(mm) Weight* Dry Weigh(
t kg)
C690 D5 3684 1454 2000 4700
The outlines are for illustrativ e purposes only, not used for installation design.
Please refer to genset outline draw ing for exact representation of this model for installation design.
Ratings Definitions:
Emergency Standby Power (ESP): Prime Power (PRP):
Applicable for supplying power to varying electrical load for the Applicable for supplying power to varying electrical load for unlimited
duration of power interruption of a reliable utility source. Emergency hours. Prime Power (PRP) is in accordance with GB.T2820/ISO
Standby Power (ESP) is in accordance with GB.T2820/ISO 8528. 8528. A 10% overload capability is available in accordance with ISO
The effective oil limited power is in accordance with ISO 3046, AS 3046, AS 2789, DIN 6271 and BS 5514.
2789, DIN 6271 and BS 5514.
2
HCI534F/544F
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
3
HCI534F/544F
50 Winding 311
Hz THREE PHASE EFFICIENCY CURVES
4
HCI534F/544F
60 Winding 311
Hz THREE PHASE EFFICIENCY CURVES
5
HCI534F/544F
Winding 311
50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30
25 25
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 0 200 400 600 800 1000 1200 1400 1600 1800
LOCKED ROTOR kVA LOCKED ROTOR kVA
60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30
25 25
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 0 200 400 600 800 1000 1200 1400 1600 1800 2000
LOCKED ROTOR kVA LOCKED ROTOR kVA
6
HCI534F/544F
Hz
SYMMETRICAL
ASYMMETRICAL
10000
CURRENT (Amps)
1000
100
0.001 0.01 0.1 1 10
TIME (secs)
60 100000
Hz
SYMMETRICAL
ASYMMETRICAL
10000
CURRENT (Amps)
1000
100
0.001 0.01 0.1 1 10
TIME (secs)
7
HCI534F/544F
Winding 311 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254
kVA 620 620 620 600 670 670 670 650 710 710 710 690 738 738 738 715
kW 496 496 496 480 536 536 536 520 568 568 568 552 590 590 590 572
Efficiency (%) 95.0 95.2 95.3 95.4 94.8 95.0 95.1 95.3 94.6 94.8 94.9 95.1 94.4 94.6 94.8 95.1
kW Input 522 521 520 503 565 564 564 546 600 599 599 580 625 624 623 601
Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277
kVA 688 719 731 750 738 775 800 825 781 819 848 875 806 844 878 906
kW 550 575 585 600 590 620 640 660 625 655 678 700 645 675 702 725
Efficiency (%) 95.1 95.2 95.3 95.3 95.0 95.0 95.1 95.1 94.8 94.9 94.9 95.0 94.7 94.8 94.8 94.9
kW Input 579 604 614 630 621 653 673 694 659 690 715 737 681 712 741 764
DIMENSIONS
© 2006 TD_HCI5F.GB_10.06_04_GB
PowerCommand®
1.2 control system
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or
service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1567c (5/10) Page 1 of 6
designed for reliable operation in harsh environments.
PowerCommand digital The main control board is a fully encapsulated module
generator set control that is protected from the elements.
• Modbus interface - for interconnecting to customer
PCC 1302 equipment.
• Configurable inputs and outputs - Four discrete inputs
and two dry contact relay outputs.
• Warranty and service - Backed by a comprehensive
warranty and worldwide distributor service network.
• Certifications - Suitable for use on generator sets that
are designed, manufactured, tested and certified to
relevant UL, NFPA, ISO, IEC, Mil Std., CE and CSA
standards.
Features:
• LED indicating lamps
- genset running
- remote start
- not in auto
- shutdown
- warning
- auto
- manual and stop
• 128 x 128 pixels graphic LED backlight LCD.
• Two tactile feel membrane switches for LCD defined
operation. The functions of these switches are defined
dynamically on the LCD.
• Seven tactile feel membrane switches dedicated
screen navigation buttons for up, down, left, right, ok,
home and cancel.
• Six tactile feel membrane switches dedicated to
control for auto, stop, manual, manual start, fault reset
and lamp test/panel lamps.
• Two tactile feel membrane switches dedicated to
control of circuit breaker (where applicable).
• Allows for complete genset control setup.
Our energy working for you.™
www.cumminspower.com
©2010 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins
Inc. PowerCommand, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or
service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1567c (5/10) Page 5 of 6
• Certifications: Suitable for use on generator sets that The HMI is designed for proper operation in ambient
are designed, manufactured, tested and certified to temperatures from -20 ºC (-4 ºF) to +70 ºC (158 ºF), and
relevant UL, NFPA, ISO, IEC, Mil Std., CE and CSA for storage from -30 ºC (-22 ºF) to +80 ºC (176 ºF).
standards.
The control board is fully encapsulated to provide
LCD languages supported: English, Spanish, French, superior resistance to dust and moisture. Display panel
German, Italian, Greek, Dutch, Portuguese, Finnish, has a single membrane surface, which is impervious to
Norwegian, Danish, Russian and Chinese Characters. effects of dust, moisture, oil and exhaust fumes. This
Communications connections include: panel uses a sealed membrane to provide long reliable
service life in harsh environments.
- PC tool interface - This RS-485 communication port
allows the HMI to communicate with a personal The control system is specifically designed and tested for
computer running InPower. resistance to RFI/EMI and to resist effects of vibration to
- This RS-485 communication port allows the HMI to provide a long reliable life when mounted on a generator
communicate with the main control board. set. The control includes transient voltage surge
suppression to provide compliance to referenced
Mechanical drawing standards.
Certifications
PowerCommand meets or exceeds the requirements of
the following codes and standards:
- NFPA 110 for level 1 and 2 systems.
- ISO 8528-4: 1993 compliance, controls and
switchgear.
- CE marking: The control system is suitable for use on
generator sets to be CE-marked.
- EN 50081-1,2 residential/light industrial emissions or
industrial emissions.
- EN 50082-1,2 residential/light industrial or industrial
susceptibility.
Software - ISO 7637-2, level 2; DC supply surge voltage test.
InPower (beyond 6.0 version) is a PC-based software - Mil Std 202C, Method 101 and ASTM B117: Salt fog
service tool that is designed to directly communicate to test.
PowerCommand generator sets and transfer switches, to - PowerCommand control systems and generator sets
facilitate service and monitoring of these products. are designed and manufactured in ISO 9001 certified
facilities.
Environment - UL 508 recognized or Listed and suitable for use on UL
2200 Listed generator sets.
The control is designed for proper operation without - CSA C282-M1999 compliance.
recalibration in ambient temperatures from -40 ºC - CSA 22.2 No. 14 M91 industrial controls.
(-40 º F) to +70º C (158 ºF), and for storage from -55 ºC
(-67 ºF) to +80 ºC (176 ºF). Control will operate with Warranty
humidity up to 95%, non-condensing.
All components and subsystems are covered by an
express limited one year warranty. Other optional and
extended factory warranties and local distributor
maintenance agreements are available.