SECTION 16290 Power Measurement and Control Rev 0
SECTION 16290 Power Measurement and Control Rev 0
~\
-<-~'I ~\..1J1 (jJJ..
\"'"""""'"J
t.J.Q1
~1.b11 w~1
.. ..
- -'I
Y""'
SECTION 16290:
KINGDOM
OFSAUDIARABIA ~~~I ~j-iJ1~I
lorJubail&Yanbu
RoyalCommission ~~W~I~1
SECTION 16290
POWER MEASUREMENT AND CONTROL
TABLE OF CONTENTS
Item No Title Page No
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 2
1.05 DEFINITIONS....................................................................................................... 5
1.06 SUBMITTALS....................................................................................................... 7
PART 1 GENERAL
A. This Section specifies the minimum technical requirements for design engineering,
furnishing, manpower, installing, supervision, testing and commissioning, of
functional protective relays, meters, instruments and control systems as per the
Contract Documents.
B. The Contractor shall, as part of his full responsibility and scope, check the ratings
and/or sizes of those components whose ratings or sizes are specified in the
Contract Drawings/Documents. When this check indicates that the specified ratings
or sizes are not adequate, the Contractor shall notify the Royal Commission and take
the necessary action/changes with approval of the Royal Commission.
C. The Contractor shall also check and verify every requirement, aspects and details
necessary for interfacing, coordinating and integrating with new or existing systems
and equipment.
B. AC Meters
C. Selector Switches
D. Diagram of Connections
E. DC Metering
F. Instrument Transformers
G. Fuses
H. Device Identifications
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials and products. In case of conflict between these standards and
the text of this Specification, the Specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment conforming to
one group of codes and standards.
Code)
1.05 DEFINITIONS
C. analog meter: A scale and pointer meter capable of indicating a continuous range of
values.
D. automatic transfer switch: A switch designed to sense the loss of one power
source and automatically transfer the load to another source of power.
E. burden: The input impedance of a measuring circuit (expressed in ohms) or the load
on the secondary of a transformer (expressed in volt-amp or watt). In potential or
current transformers, burden is the maximum load the transformer can support while
operating within its accuracy rating.
H. demand meter: A device or system of devices that indicates and/or records the
number of kilowatts used over a period of time.
K. flush mounted: An outlet intended to be installed flush with the surface of a panel or
a piece of equipment.
L. frequency meter: An instrument used to measure the rate at which AC voltages are
generated.
O. light emitting diode (LED): A solid state light source that emits variable light, or (in
micro switch modulated LED controls) invisible, infrared radiation.
R. metering equipment: The equipment and devices used for measuring, controlling
and monitoring the electrical power which includes indicating meters, instrument
transformers, protective relays, fuses and other control devices including wiring and
alarm circuitry.
T. microprocessor: A solid state device built onto a single silicon chip capable of being
programmed to perform a large number of tasks. It is usually the central processing
unit of computers, programmable logic controls and other control systems.
U. power factor meter: An instrument that measures the power factor of the system.
W. solid state relay (or relay unit): A static relay or relay unit constructed exclusively of
solid state components.
X. terminal block: This component is used to join wires together to make electrical
connections. This block is designed to fit where space is limited. The different parts
of the terminal blocks are the insert, screw, and wire protector. The insert is where
the wire is placed. It is located underneath each “chimney.” The screws are located in
each chimney. When the screws are tightened down on the wires, the wire protectors
enhance the electrical connections.
AA. watthour meter: An indicating instrument that displays the kilowatt-hour output
continuously for recording purposes.
BB. wattmeter: An instrument that measures real power of the circuit in watts, in which it
is connected.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
1. All vendor drawings and product data sheets and specifications as listed
below:
a) List of manufacturers.
j) Certificates of Compliance.
2. The Contractor shall submit field test reports after the completion of Testing
and Commissioning.
A. The Contractor shall be responsible for the quality of Work and shall develop and
propose programs and methods of construction and testing to achieve the specified
quality to the approval of the Royal Commission in accordance with
SECTION 01450.
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
A. General
1. All the metering panels and metering equipment shall be tested at the factory
in accordance with the latest approved manufacturing codes and standards.
The Contractor shall notify the Royal Commission in writing not less than
30 days prior to the scheduled starting date of the factory tests.
2. The Royal Commission reserves the right of deputing their representative for
witnessing the factory testing.
3. Upon completion of factory tests, and before shipment of the metering panels
and metering equipment, the Contractor shall submit 5 certified copies of test
reports not later than 10 days after the completion of all factory tests for review
and approval by the Royal Commission.
A. All the metering panels and metering equipment installed indoors shall be suitable for
continuous operation under the following service conditions:
a) Maximum of 40°C.
b) Minimum of 0°C.
B. All the metering panels and metering equipment installed outdoor shall be suitable for
continuous operation under the following service conditions:
a) Maximum of 50°C.
2. Altitude
C. All the metering panels and metering equipment to be installed in classified areas as
indicated in the Contract Drawings/Documents shall be suitable for such installation
as per NEC Article 500 or other relevant standards, as specified in par. 1.04.
A. The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
4. The Contractor shall be held responsible for any damage to the materials or
equipment during storage, handling and transportation.
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. However procurement of all goods and
products manufactured out-of-Kingdom or in kingdom must be approved by the Royal
Commission.
B. The Contractor shall furnish all the equipment and materials specified in the Contract
Drawings/Documents. These equipment and materials shall be complete, operable,
new, and of the highest quality available.
A. General
A. General
2. All the indicating meters and instruments (with analog indication or digital
display) and the relevant devices shall be manufactured and tested in
accordance to relevant standards specified in par. 1.04.
3. Relays, Indicating meters and instruments shall be suitable for use in the
service conditions as stated in par. 1.10.
4. Voltage and current ratings of the relays, meters and instruments shall be as
specified in the Contract Drawings/Documents.
B. The following relays, meters, instruments and contactors shall be furnished along
with the metering panel in main switchboards or distribution panels of AC and DC
systems at rated 600 V and below.
d) One trip relay (94) to trip the breaker in case of activation of any fault
relay mentioned above and to block the auto changeover scheme.
3. For each station auxiliary transformer, provide one 3 element KWH meter with
maximum demand indicator, one ammeter with phase selector switch, one
voltmeter with phase selector switch.
4. For each bus, provide one voltmeter with phase selector switch.
5. For Bus-tie breaker feeder, provide one ammeter with phase selector switch.
7. For more details on switching, monitoring, protection and control devices and
application on metering or monitoring panel in main switchboard or motor
control centers at rated 600 V and below, refer to SECTION 16440.
1. Relays
d) All relays shall have test terminal block facilities. Test facilities shall be
mounted on front of the rack.
e) Relay setting and time delay range shall be as specified in the Contract
Drawings/Documents.
g) Light Emitting Diodes (LED) type indicators with current limiting series
resistor shall be provided.
2. AC Meters
f) The scales plates shall have a permanent white finish with black
graduation and numerals.
g) The scales shall preferably be circular type (270°) for easy readability.
h) The instrument transformer ratio for which the instrument has been
graduated shall be prominently marked.
k) The mega watt hour (MWH) meter cases shall be flush mounted and
draw out type. This draw out feature shall permit the meters to be
withdrawn from the cases without opening current transformers
secondary circuits, disturbing service or requiring disconnection of
leads. The built in test facilities shall permit meters to be tested in place
without requiring other switchboard mounted test device.
l) The digital power demand meters shall have a minimum life of 10 years.
The meters shall be shock-resistant, dust-protected and weather-proof.
The display character size shall be minimum 5 mm wide and 8 mm high.
The resolution shall be minimum 0.1%.
n) Types of Meters
1) Ammeter
(a) Shall be provided with moving iron type for AC and moving
coil type for DC, and shall conform to the relevant
standards specified in par. 1.04.
(b) Shall be provided to operate on a current transformer for
the measurement of line current.
(c) Shall be provided with instantaneous and maximum
demand indicators.
(d) Accuracy class of the ammeter shall be as given in
Table 2A.
2) Voltmeter
(a) Shall be moving iron type for AC and moving coil type for
DC, and shall conform to the relevant standards specified
in par. 1.04.
(b) Shall be provided to operate on a potential transformer for
the measurement of phase-to-phase and phase to neutral
voltage.
(c) Accuracy class of the voltmeter shall be as given in
Table 2A.
3) Wattmeter
(a) Shall be provided totally iron enclosed electrodynamics
type, and shall conform to the relevant standards specified
in par. 104.
(b) Shall be capable of carrying 1.2 times continuous full load
current.
(c) Accuracy class of the Wattmeter shall be as given in
Table 2A.
4) Watthour Meter
(a) Shall be provided suitable to connect either for direct or
through current transformer, and shall conform to the
relevant standards specified in par. 104.
(b) Maximum rating for direct connection shall be 10 amp. For
connection through current transformers, either 1 or 5 amp
secondary current windings may be used.
(c) Accuracy class of the watthour meter shall be as given in
Table 2A.
(d) Shall meet accuracy requirements for dual voltage, and
these dual voltages shall be as specified in the Contract
Drawings/Documents.
(e) Watthour meter designed for dual voltage use shall be
calibrated for one voltage, and this calibration voltage shall
be indicated on the nameplate.
(f) Terminal cover shall be made of the same material with that
of the meter case, terminal cover shall be provided with
sealable retaining screws and shall be suitable for sealing
wire.
apply to synchroscopes.
(c) All meters and instruments shall withstand overloads of
short duration.
(d) The duration of each overload shall be as per applicable
standards specified in par. 1.04.
q) Accuracy of Meters
1) All metering devices shall have the following accuracy classes in
Table 2A in conformance with IEC 60521, IEC 60051 or
equivalent ANSI, unless otherwise specified in the Contract
Drawings/Documents:
Wattmeter Class 1
Class 2 (Whole current)
Watthour Meter
Class 1 (CT, CT-VT operated)
Frequency Meter Class 0.5
r) Selector Switches
1) Refer to SECTION 16440 for selector and synchronizing switches,
pushbuttons, and indicating lights.
s) Diagram of Connections
1) A diagram of connections giving the following particulars shall be
supplied with the indicating instruments:
(a) The wiring diagram indicating connections to and from the
instrument.
(b) For a poly phase instrument, the phase sequence of supply
(R, Y, B, anticlockwise) shall be indicated.
(c) The marking of phase indication shall be R, Y, and B.
3. DC Meter
b) Shall be calibrated for lead resistance and shunt connection (if any).
4. Instrument Transformers
5. Fuses
6. Device Identification
c) The devices mounted on the front door shall also bear an identification
tag from inside.
a) For AC System
1) Two service transformers shall feed auxiliary load of the entire
substation auxiliaries. One transformer shall be capable of feeding
the entire load in case of emergency/shut down of other
transformer.
2) The bus shall be operated in split bus mode with bus tiebreaker
normally open.
3) In case of failure of any one incoming feeder, the other shall take
over the entire load by closing bus tie breaker after an
adjustable time delay of 0 to 30 seconds.
4) On restoration of the source, the changeover shall be manual
only.
5) The scheme shall also have provision for manual operation which
shall be achieved by manual live changeover scheme
incorporating a 3-position selector switch to trip the desired
selection without bypassing the protection requirements of
automatic sensing and disconnection of faulty section.
6) Short duration paralleling shall be permitted during manual
transfer operations only.
7) An alarm will be activated followed by tripping of Tie Breaker, after
an adjustable time delay of 0 to 60 seconds when all
3 breakers are closed.
8) The Automatic Transfer Switching Scheme (ATS) control supply
shall be 125 V AC, automatically selected to and derived from the
healthy incomer supply.
9) In case of fault (other than under/over voltage) this auto transfer
scheme shall be blocked by the trip relay.
b) For DC System
1) An Auto Transfer Scheme (ATS) shall be provided in case of a
DC System with 3 chargers. The third charger acts as standby
with automatic changeover in the event of failure of either of the
remaining 2 chargers.
2) In the Main DC distribution board, each DC bus shall have a
circuit breaker at the charger incomer.
3) In the event of failure of any one charger, its supply to the
respective DC bus shall trip automatically and the standby
charger shall take over the load of that faulty charger immediately.
4) For this purpose ATS shall receive a charger failure signal from
the charger panel.
5) On restoration of the faulty charger, the changeover shall be
manual only.
6) Both the breakers of the standby charger feeding 2 DC buses
shall not be ON at any given time.
D. For more details on switching, protection, control and metering equipment, refer to
SECTION 16440 for medium voltage switchgear and medium voltage motor
controller.
PART 3 EXECUTION
3.01 GENERAL
A. The Contractor shall provide all materials, equipment, and labor as deemed
necessary to show proper execution of the work.
C. All equipment/materials moved to the installation site shall be inspected for damage
or deterioration during storage.
D. The Contractor shall verify all the tag numbers and nameplates for the equipment
and device numbers with the details specified on the Contract Drawings/Documents.
F. After the installation is completed and properly adjusted, the Contractor shall conduct
operating tests. The various equipment and systems shall be demonstrated to
operate in accordance with the requirements of this Specification. Tests shall be
performed in the presence of the Royal Commission’s representative. The Contractor
shall provide electric power, instruments, special tools, safety gears, and personnel
necessary for performing the various tests.
A. General
2. The Contractor shall be responsible in installing the metering panel within the
main distribution panelboard or switchgear protection and control systems, and
shall include all related work on related systems, whether existing or new, to
provide satisfactory interfaces and overall integrated systems.
4. Upper edge of protective relays and meters shall not be higher than 2 m to
allow convenient maintenance, inspection, target reset and testing from ground
level.
5. The bottom of any relay or test block shall not be less than 300 mm from floor
level.
6. All the setting and adjusting of protective devices shall be based on final
protection system coordination studies.
7. All wiring within the panels shall be installed and tested at the factory unless
otherwise specified in the Contract Drawings/Documents.
8. The site termination of power and control wiring to the equipment or protective
devices shall be completed as per the approved Drawings.
11. Each relay, meters, fuses, instruments and control/test switches shall be
identified permanently in the form of engraved or embossed on the external
and internal side of the metering panel, device numbers shall be in accordance
with relevant standards specified in par. 1.04 or as per the Contract
Drawings/Documents.
A. General
1. The Contractor shall carry out all site tests in accordance with approved test
procedure to ensure that the equipment and materials comply with this
Specification and operational requirements. All tests shall be subject to
witnessing by the Royal Commission’s representatives.
2. At least 4 weeks prior to scheduled tests, the Contractor shall submit to the
Royal Commission an outline of the plan and procedures to be used in
performing the site inspection and site tests. This outline shall include a brief
description of the test equipment, connection diagrams, proposed tests and
procedures, test sheets, calculations, reference drawings and
minimum/maximum test and performance values in conformance with
applicable standards which shall be used to determine conformance with the
specification and acceptability of the equipment and installation.
1. Metering equipment and metering panel within the Low and Medium voltage
main distribution panel or switchgears shall be tested and checked for the
following:
k) After energizing and with load currents, perform phase angle checks
using the voltage and current phase or quantities at the relays to verify
correct connections. For current only relays, use metering potential for
reference.
C. Update and finalize coordination studies including time-curve sheets and relay setting
sheets.
END OF SECTION