UL Informative Report IEC60730-1 BridgeSwitch
UL Informative Report IEC60730-1 BridgeSwitch
0
TRF Template 2017-05-17
Test Report issued under the responsibility of:
TEST REPORT
IEC 60730-1
Automatic electrical controls for household and similar use
Test specification:
Standard ......................................... : IEC 60730-1:2013, AMD1:2015
Test procedure ............................... : Informative Report
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC60730_1I
Test Report Form(s) Originator .... : UL(US)
Master TRF ..................................... : 2017-08-25
Copyright © 2017 IEC System of Conformity Assessment Schemes for Electrotechnical Equipment
and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and
appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
Test item description ....................... : BridgeSwitch Motor Protection Integrated Circuit (IC)
Trade Mark ........................................ :
Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):
Summary of testing: As this is an Informative report, testing referenced in the 60335-1 Test
Report referenced below, was done for reference only and not necessarily following requirements
of the CB Scheme and/or the UL LLC. accreditation requirements.
Tests performed (name of test and test Testing location:
clause):
See 60335-1 Report for tests considered See 60335-1 Report for tests considered necessary
necessary per the end product standard per the end product standard
European Group Differences (for this type of product it was determined there was no need to publish a
separate Group Differences TRF)
General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
This report makes reference to EMC Report and Software Report. When applicable to the evaluated
control, the official IEC60730_1I (SOF) and IEC60730_1I (EMC) shall be used.
The BridgeSwitch™ family of integrated circuits have integral high and low-side FETs that drive an
external motor coil and provide protection to that motor. From the rectified DC input, the internal FETs
switch the DC to provide a switched output to each motor coil under normal conditions, and are used to
provide a micro-interrupt to introduce impedance in the output path to the motor under abnormal
conditions, such as overload, stalled rotor and loss of phase. These devices may be constructed with
differently rated FETs which are associated with different models as shown on Page 1 with different
continuous current ratings. The ICs have external resistors – called RXL for the low side and RXH for the
high side FET – of certain resistance values to set the current limit threshold. For example, for the 3.0A
rated model, a 100kohms selection for these resistors will result in a current limit threshold of 1.5A (-0.50
factor from graph x 3.0A); and a 44.2kohm selection of resistors in the design would result in 3.0A (1.0
factor from graph x 3.0A). The components are normally provided with an input of a DC high-voltage bus
where the typical application is to have the nominal input voltage of AC240V rectified, for DC340V.
The IC is considered suitable to be used in a protective electronic circuit (PEC, using 60335-1
terminology and clauses below) to mitigate the following abnormal conditions using the inherent
current protection logic:
• Stalled motor/locked rotor per Clause 19.7;
• Loss of phase protection per Clause 19.8; although the loss of phase is typically considered losing
one phase for a three-phase AC system, such testing was conducted for losing one of the DC
phases of a three-phase DC brushless motor.
• Motor overload per Clause 19.9;
From IEC60730-1, the micro-interruption of the output voltage to the motor was evaluated as a Type 2.Y
control with Class B hardware control function (no software dependency). These IC’s will need to have
additionaly hardware circuitry functioning in conjunction with them to constitute the entire end appliance
“control”. Many clauses of this Report were marked as “N/A” due to the fact the entire control would then
need to have additional applicable clauses evaluated per the 60730-1 and 60335-1 Standards.
Three ICs were tested in a reference design called DER-654, which is a board assembly detailed in
Attachment 2, configured to have RXL and RXH resistors for limiting the values shown therein, and tested
with a representative motor (Shunde Hopmotion, Type 57BL110S30-3150TFO)
Notes on Evaluation:
• Only the inherent current protection features were considered in this evaluation (for their suitability
to be used in the PECS identified above).
• The EMC immunity testing of the protective electronic circuit (PEC) per Clause 19.11.4 should be
considered in the end product evaluation.
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
3 GENERAL REQUIREMENTS P
Controls are so designed and constructed that in P
normal use, they function so as not to cause injury
to persons or damage to surrounding property,
even in the event of such carelessness as may
occur in normal use
5 RATINGS P
5.1 Maximum rated voltage (V) ................................... : DC340V nominal P
6 CLASSIFICATION P
6.1 Nature of supply .................................................... : Rectified DC bus of AC240V input
6.2 Type of load and power factor ............................... : External DC brushless motor
Drives external motor with integral
6.3 Purpose ................................................................. :
overload/overcurrent protection
6.4 Features of automatic action, Type 1 or Type 2.... : Type 2.Y as required by IEC60335-1
6.5 Degree of protection provided by enclosure per IEC
60529 and control pollution situation ...................…:
6.6 Method of connection. .............................................. :
6.7
Ambient temperature limits of the switch ahead:
Tmin(°C).; Tmax (°C) .................................................... :
Integrated control, to be assessed
6.8 Protection against electric shock ............................. :
in the end appliance
Micro-interruption; to be assessed
6.9 Circuit disconnection or interruption......................... :
in the end appliance
6.10
Number of cycles of actuation (M) of each manual -
action ......................................................................... :
Number of cycles of actuation (A) of each automatic
6.11
action ......................................................................... :
Temperature limits of the mounting surface of the Not more than 20K above ambient
6.12
control (°C or K) ........................................................ :
6.13
Value of proof tracking index (PTI) for the insulation
material used ............................................................ :
Period of the electrical stress across insulating parts Long period
6.14 supporting live parts, and between live parts and
earthed metal (short or long period)......................... :
6.15 Construction ............................................................. : Integrated control
6.16
Ageing requirements (type Y) of end-product
equipment ................................................................ :
6.17 Use of thermistor (Annex J) .................................... :
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
7 INFORMATION P
7.2.1 Information required for controls and the appropriate method for providing this information
is as indicated in Table 1
1 – Manufacturer’s name or trademark Marked on IC P
(Method C). .............................................................. :
2 – Unique type reference (Method C) ................... : Marked on IC P
3 – Rated voltage or rated voltage range in volts N/A
(Method C) ............................................................... :
4 – Nature of supply (Method C) ............................. : N/A
5 – Frequency, if other than for range 50 Hz to 60 N/A
Hz inclusive (Method C) .......................................... :
6 – Purpose of control (Method D or E) .................. : D P
6a – Construction of control (Method X) ................. : D P
7 – The type of load controlled by each circuit D P
(Method C) ............................................................... :
15 – Degree of protection by enclosure: N/A
(Method C) ............................................................... :
17 – Terminals for external conductors (Method C): N/A
18 – Terminals for external conductors which N/A
accept a wider range of conductor sizes,
(Method D or E) ....................................................... :
19 – Method of connection and disconnection for N/A
screwless terminals (Method D) .............................. :
20 – Details of any special conductors which are N/A
intended to be connected to terminals for internal
conductors (Method D) ............................................ :
21 – Maximum temperature of terminals for internal N/A
conductors, if higher than 85°C (Method X) ........... :
22 – Temperature limits of the switch head, if Tmin N/A
lower than 0°C, or Tmax other than 55°C (Method C):
23 – Temperature limits of mounting surfaces (Ts) N/A
(Method C) ............................................................... :
24 – Classification of control according to protection Integrated control P
against electric shock (Method X) ........................... :
25 – For Class II controls, the symbol for Class II N/A
construction (Method C) .......................................... :
26 – Number of cycles of actuation (M) for each No manual action N/A
manual action (Method X) ....................................... :
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
11 CONSTRUCTION REQUIREMENTS P
11.1.1 Insulating materials P
Wood, cotton, silk, ordinary paper etc. not used as P
insulation unless impregnated
11.1.2 Current carrying parts other than threaded parts of terminals, if made of brass: P
- contain at least 50% copper if cast or from bar P
- contain at least 58% copper if from rolled sheet P
Non-detachable cords of Class I controls provided N/A
11.1.3.1 with a green/yellow conductor insulation and
properly connected
Non-detachable cords: green/yellow conductor not N/A
11.1.3.2
connected to other than earthing terminals
11.2 Protection against electric shock N/A
11.2.1 Double insulation No such insulation provided N/A
- basic insulation and supplementary insulation can No such insulation provided N/A
be tested separately, or
- properties of both insulations are otherwise N/A
provided
11.2.2 Infringement of double or reinforced insulation in Class II controls: N/A
- creepage distances and clearances not reduced N/A
below values of Cl. 20 by wear
- creepage distances and clearances not reduced to N/A
less than 50% of values of Cl. 20 by parts becoming
loose (wires, screws, nuts, etc.)
11.2.3 Integrated conductors N/A
No reduction of creepage distances and clearances N/A
11.2.3.1 below values of Cl. 20; conductors rigid, fixed or
insulated
Insulation, if any, cannot be damaged during N/A
11.2.3.2
mounting or in normal use
11.2.4 Sheath of flexible cord used as supplementary insulation: N/A
- not subjected to undue mechanical or thermal N/A
stresses
- insulation properties comply with IEC 60227-1 or N/A
IEC 60245-1
TRF No. IEC60730_1I
Page 23 of 96 Report No. 4788685352
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
14 HEATING P
Controls and their supporting surfaces did not See 60335-1 Report P
14.1
exceed normal use temperatures
14.1.2 Temperatures recorded during Heating Test did not N/A
exceed the values in Table 13
14.2 Terminals fitted with external conductors of the
intermediate cross-sectional area (mm²) .................:
Attachment method M, Y or Z: cords as declared or
14.2.1
supplied (mm²) ......................................................... :
Terminals for flexible and fixed conductors:
14.2.2
appropriate flexible cord (mm²) ............................... :
Terminals not for external conductors: conductors of
14.2.3 minimum cross-sectional area or as declared in
Clause 7.2 (mm²) ..................................................... :
In-line cord controls tested on a dull, black painted N/A
14.3
plywood
Independently mounted controls tested as in normal N/A
14.3.1
use
14.4 Electrical conditions P
- voltage (V): most unfavourable value between 240 x 1.414 x 0.94 = 319V
0.94 and 1.06 times UR .......................................... : 240 x 1.414 x 1.06 = 360V
- voltage (V) if circuit not voltage sensitive: min.
10% of UR ............................................................... :
- current (A): most unfavourable value between
0.94 and 1.06 times I R .......................................... :
For circuits and contacts other than for external Motor load of max 3A for highest
14.4.1 loads, load(s) as specified by the manufacturer: rated model
voltage (V); current (A) ............................................ :
Actuating members placed in most unfavourable N/A
14.4.2
position
14.4.3 Contacts initially closed at rated current and voltage N/A
14.4.3.1 Temperature sensing controls: N/A
- temperature of sensing element is raised or N/A
lowered (5 ± 1) °C from operating temperature such
that contacts are then in closed position
- operating temperature (°C) ................................... :
- temperature for heating test (°C) .......................... :
For controls other than temperature sensing, N/A
14.4.3.2 sensing element maintained as near to the point of
opening as practical
The most arduous operating sequence or segment N/A
14.4.3.4
selected for other automatic controls
14.5 Controls were tested in an appropriate heating and/or refrigerating apparatus N/A
TRF No. IEC60730_1I
Page 37 of 96 Report No. 4788685352
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
17 ENDURANCE N/A
17.2 Electrical conditions for the tests............................. : N/A
Type of circuit N/A
Rated voltage (V) ; test voltage (V) ........................ :
Rated current (A) ; test current (A) ......................... :
Rated frequency (Hz) ............................................. :
17.3 Thermal conditions for parts other than temperature sensing elements N/A
Accessible parts: tested at room temperature (°C) :
Mounting surface temperature: Ts max (°C) .......... :
Remainder of switch head, temperature: Tmax(°C) . :
If Tmin is less than 0 °C; switch head maintained at
Tmin (°C) ................................................................... :
17.4 Manual and mechanical conditions for the tests N/A
17.4.2 Slow speed test N/A
High speed test N/A
Accelerated speed test N/A
17.4.4 Controls with limited movement of the actuating member N/A
Dwell period at each reversal of direction (s) ........ :
Applied torque ( rotary controls ) (Nm) ................... :
Applied force ( non-rotary controls ) (N) ................. :
Controls with rotary actuation, movement not limited in either direction: N/A
- 3/4 of cycles clockwise (number of cycles) ......... :
- 1/4 of cycles anti-clockwise (number of cycles) ... :
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
24 COMPONENTS N/A
Transformers intended to supply power to a SELV-
circuit or PELV-circuit are of the safety isolating
24.1 N/A
type and comply with the relevant requirements of
IEC 61558-2-6
Capacitors connected between two line conductors
for between a line conductor and the neutral or
between hazardous live parts and protective earth N/A
are in accordance with IEC 60384-14 and used in
accordance with its rated values
Fuses comply with requirements of IEC 60127-1 or
N/A
IEC 60269-1
Controls that incorporate a transformer as the
source of supply to a SELV-circuit or PELV-circuit
24.1.1 N/A
were subjected to an output test with the primary
energized at the upper limit of the rated voltage
Switch mode power supplies or transformers used
in converters comply with the requirements of IEC N/A
61558-2-16
Under any non-capacitive conditions of loading
(from no load to the short-circuiting of any or all
secondary SELV- or PELV-circuit terminals) and
N/A
without disturbing internal connections, the
secondary output voltage did not exceed limits
specified in 2.1.5
The secondary output power at the terminals to an
isolated limited secondary circuit did not exceed
100 VA and the secondary output current did not See attached TABLE 24.1 N/A
exceed 8 A after 1 min of operation with overcurrent
protection ................................................................. :
Components other than those of 24.1: checked
24.2 when carrying out the tests of this standard or/and See attached TABLE 24.1 / 24.2 N/A
complies with appropriate safety standard ............. :
Annex U is not applicable to relays used as
24.3 N/A
components in a control. ........................................ :
24.4.1 Overload test for switch mode power supplies not covered under 24.2.1 N/A
Each output winding, or section of a tapped
winding, is overloaded in turn, one at a time, while
24.4.1.1 the other windings are kept loaded or unloaded, N/A
whichever load conditions of normal use is the least
favourable
The overload is carried out by connecting a variable
24.4.1.2 resistor (or an electronic load) across the winding or N/A
the rectified output
The resistor is adjusted as quickly as possible and
N/A
readjusted after 1 min to maintain the overload
No further readjustments are done after that N/A
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
27 ABNORMAL OPERATION P
27.2 Burnout test (for controls incorporating electro-magnets) N/A
27.2.1 Control mechanism blocked in position when control is de-energized: N/A
- energized at rated frequency and rated voltage
N/A
(17.2.2, 17.2.3 and 17.2.3.2)
- duration: 7 h or until burnout ................................ : N/A
27.2.2 Compliance (burnout test): N/A
- no emission of flame or molten metal after test N/A
- no evidence of damage impairing compliance with
N/A
this standard
- no evidence of dielectric breakdown (Cl. 13.2) N/A
27.2.3 Blocked mechanical output test (abnormal temperature test) N/A
During blocked output test: Temperatures did not
N/A
exceed indicated limits in Table 26 ...................... :
Test not required on controls, if no protective device
N/A
cycles and temperatures exceed limits in Table 13
Test carried out at room-temperature and rated
N/A
voltage (V) for 24h .................................................. :
The average temperature was within the limits
27.2.3.2 during both the second and the twenty-fourth hours N/A
of the test
During the test, power was continually supplied to
27.2.3.3 N/A
the motor
Immediately upon completion of the test, the motor
27.2.3.4 was capable of withstanding the electric strength N/A
test (Clause 13)
27.5 Overload tests N/A
Controls without protective devices and without
incorporated fuses loaded for 1 h with the
N/A
conventional tripping current for the fuse,
anticipated during installation .................................. :
Controls protected by protective devices (including
fuses) loaded such that an overload current of 0.95
times the protective device rating flows through the N/A
circuit for 4 hours or until temperatures stabilize,
whichever is shorter................................................. :
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
- 75 ± 2°C, or .......................................................... :
- as declared (°C) .................................................... :
G.5.2 Ball-pressure test 2 N/A
Temperature during ball pressure test is Tb ± 2 °C
N/A
where Tb is equal to the higher of:
- Tb (°C): 100 °C if Tmax = 30-54 °C ..................... :
- Tb (°C): 125 °C if Tmax = 55-84 °C ...................... :
- Tb (°C): (Tmax + 40) °C if Tmax 85 °C .............. :
- Tb (°C): 20 K in excess of the max. temperature
during tests of Cl. 14 (°C), if higher ......................... :
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
J.17.18.7.1.
For a sensing thermistor: N/A
3
-50 cycles of operation starting at 25oC ± 5K and
increasing the temperature to 120% of maximum N/A
sensing temperature ................................................. :
J.17.18.7.2 Endurance N/A
Samples subjected to overload test, J.17.18.7.1 are
J.17.18.7.2.
operated at the conditions specified in a) or b) for N/A
1
the number of cycles specified in Table J.12
a)inrush-current limiting – tested at Vmax and Imax
N/A
with rated capacitance value in parallel with the load
Vmax .......................................................................... : N/A
Imax ............................................................................ : N/A
Number of cycles ...................................................... : N/A
b) Sensing – cycled between 25oC ± 5K and the
N/A
maximum operating temperature.
Maximum sensing temperature ............................... : N/A
Number of cycles ...................................................... : N/A
Cold operational cycling (for inrush current-limiting
J.17.18.8 N/A
NTC thermistors)
Following the cycling specified in J.17.18.8.2,
J.17.18.8.1 N/A
thermistors checked for compliance with Table J.8
Three samples subjected to 1000 cycles of
operation at Vmax conducting Imax of current, at an
J.17.18.8.2 N/A
ambient temperature of 0oC or at manufacturer’s
specified temperature, whichever is lower............... :
Each cycle covered that portion of the R/T curve
from the starting temperature to steady-state N/A
conditions
J.20 Creepage distances, clearances and distances through insulation N/A
J.20.1.14 Clearance N/A
Clearance between live parts connected electrically
J.20.1.14.1 to the mains supply and accessible surfaces or N/A
parts in compliance with requirements of 20.1
Clearance between live parts providing functional
J.20.1.14.2 N/A
insulation in compliance with requirements of 20.1
J.20.2.5 Creepage distance N/A
Creepage distance between live parts connected
electrically to the mains
J.20.2.5.1 N/A
supply and accessible surfaces or parts were in
compliance with the requirements of 20.2
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
After conditioning, each sample wrapped in aluminium foil was subjected to the electric
P.3.5 N/A
strength test, Cl. P.3.1 between:
- leads A, B, and C individually and common lead
P3.6 N/A
(figure P.1)
- no evidence of flashover or breakdown N/A
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
When the supply of SELV or PELV circuits is obtained from supply mains of higher
N/A
voltages, it is either
– through a safety isolating transformer, or N/A
– a converter with separate windings providing
N/A
equivalent insulation, and
Control declared IPX7 subjected to second fault
analysis (item 73 of Table 1) for the circuits and
insulation between windings of the converter; as
N/A
result of second fault the ELV value of 0 V was not
exceeded. The current between the poles of the
output complied with H.8.1.10.
Compliance is checked by inspection,
measurement and when performing the appropriate N/A
test(s) in the order of this standard.
Protective screening consists of a conductive
screen interposed between hazardous-live-parts of
T.3.2.1 N/A
the control, installation, or system and the protected
part (e.g. a SELV-circuit or a PELV circuit).
The protective screen permanently connected to
the protective earthing and the connection complies N/A
with Clause 9; and
– itself complies with the requirements of Clause 9 N/A
Basic insulation is required between SELV- / PELV-
T.3.3 circuits and other SELV-/ PELV-systems or earth N/A
and is rated for the highest voltage present
Component connected between the separated
circuits withstands the electric stresses specified for
the insulation which it bridges and its impedance
N/A
limits the prospective current flow through the
component to the steady-state current indicated in
H.8.1.10 and H.11.2.5 for protective impedance.
T.3.4 Protective bonding N/A
The requirements for protective bonding - see
N/A
clause 9 of this standard
For the installation of controls which consist of parts
of the fixed electrical installation of a building, the
N/A
requirements for protective bonding in IEC
standards for installation of buildings apply.
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
test # Measured voltage between pins (VRMS) Average voltage (V): < 34 V
Supplementary information:
9.3.1 TABLE: Connection between earthing terminal and parts is of low resistance N/A
terminal No. Duration, until steady Measured potential drop calculated resistance (Ω):
conditions (min) (V) ≤0.1 Ω
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
Supplementary information:
Supplementary information:
Tab size (mm x mm) axial push (N) axial pull (N) result
identification code
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
flexible cords No. of conductors rated current rated voltage No. of rate of flexings %
used in product in cord (A) (V) flexings per min. broken
Supplementary information:
Supplementary information:
Control type Pull (N) No. of pulls applied Torque (Nm) Comments
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
12.3 TABLE: Leakage current test (for in-line cord and free -standing controls) N/A
Circuit identification Position of switch S1 Class of control Measured leakage current, (mA)
Supplementary information:
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
13.3.3 TABLE: Leakage current test (for in-line cord and free -standing controls) N/A
Circuit identification Position of switch S1 Class of control Measured leakage current, (mA)
Supplementary information:
thermocouple locations max. temperature measured, (oC) temperature limit, (oC) Verdict
Supplementary information:
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
Supplementary information:
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
Insulation or disconnection Test potential applied between Test voltage applied (V) Flashover/
tested the following circuits breakdown
Supplementary information:
Supplementary information:
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
Requirements for case B (20.1.7, 20.1.12) met (cl 20.1 Note 2) ... : N/A
Creepage distance Cd
Nominal Pollution Required Cd measured Required Cl Cl measured
and clearance Cl across
Volt, (V) degree Cd, (mm) (mm) (mm) (mm)
(type of insulation)
full disconnection
micro-disconnection
electronic
disconnection
Supplementary information:
Abbreviations for types of insulation: F - functional, B - basic, S – supplementary, R – reinforced
See Main Test Report for additional details.
Supplementary information:
PTI results are from VDE testing of material with report kept on file.
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
21A TABLE: Resistance to heat and fire - Glow wire tests N/A
Object/ Glow wire test (GWT); (°C)
Part No./ Manufacturer/
Material 650 750 Verdict
trademark 550 850
te ti te ti
The test specimen passed the glow wire test (GWT) with no ignition [(te – ti) ≤ 2s] (Yes/No) :
If no, then surrounding parts passed the needle-flame test of annex E (Yes/No) .................. :
The test specimen passed the test by virtue of most of the flaming material being withdrawn with
the glow-wire (Yes/No)?........................................................................................................ :
Ignition of the specified layer placed underneath the test specimen (Yes/No)..................... :
Supplementary information:
550 °C GWT not relevant (or applicable) to parts of material classified at least HB40 or if relevant HBF
The GWIT pre-selection option, the 850 °C GWFI pre-selection option, and the 850 °C GWT are not relevant (or
applicable) for attended appliances.
secondary winding maximum output voltage maximum output current maximum power
tested (V) (A) (VA)
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
Supplementary information:
1) Provided evidence ensures the agreed level of compliance. See OD-CB2039.
2) Description line content is optional. Main line description needs to clearly detail the component used for
testing
b) 1.5 x max
f) no rupture
e) creepage
and 13.2 for
d) Clause 8
temp. of Cl.
of ext. fuse
clearance
Winding Max Max Max declared
Winding
T, (°C) Voltage overload Power (W) (T1,57)
c) as
and
(V) peak current
14
BI
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
Supplementary information:
Supplementary information:
Supplementary information:
IEC 60730-1
Clause Requirement + Test Result - Remark Verdict
thermocouple locations Max. temperature measured, (°C) Temperature limit, (°C) Verdict
Supplementary information:
Supplementary information:
See
Attachment 3
short circuiting
Supplementary information:
a) No flames
Requirement + Test
c) as declared (H57)
basic insulation
IEC 60730-1
e) creepage and
clearance
f) no rupture of ext.
fuses or
f) complies with a), b)
and d)
Result - Remark
g) as declared in H58
TABLE: Electrical / electronic component fault modes
Observations
P
Report No. 4788685352
Verdict
Page 96 of 96 Report No. 4788685352
A completed list of used test equipment shall be provided in the Test Reports when a Customer’s Testing
Facility according to CTF stage 1 or CTF stage 2 procedure has been used.
Note: This page may be removed when CTF stage 1 or CTF stage 2 are not used. See also clause 4.8 in
OD 2020 for more details.
Testing / measuring
Measurement / Last Calibration Calibration
Clause equipment / material used, Range used
testing date due date
(Equipment ID)
N/A; N/A; Informative N/A; Informative N/A; N/A; Informative N/A;
Informa Report/Testing Report/Testing Informative Report/Testing Informative
tive Report/Testin Report/Testi
Report/ g ng
Testing