0% found this document useful (0 votes)
95 views

MAN3059-0 Odyssey Programming Manual

This document provides an operations and programming manual for a fire alarm control panel that complies with EN54 standards. It describes the panel's functions for responding to fires including overriding delays, evacuating via all alarm devices, silencing outputs, and resetting the system. It also details disabling zones and includes a table of contents that lists sections on the front panel controls and indicators, conditional responses, test functions, and menu navigation.

Uploaded by

sqamar68
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
95 views

MAN3059-0 Odyssey Programming Manual

This document provides an operations and programming manual for a fire alarm control panel that complies with EN54 standards. It describes the panel's functions for responding to fires including overriding delays, evacuating via all alarm devices, silencing outputs, and resetting the system. It also details disabling zones and includes a table of contents that lists sections on the front panel controls and indicators, conditional responses, test functions, and menu navigation.

Uploaded by

sqamar68
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

Fire Alarm Control Panel

(EN54- 2 & 4)

Operation & Onsite Programming


Manual

MAN3059-0
Responding to a Fire
Access Level 1
Indicators Controls

 
The OVERRIDE key is pressed to override any delays to outputs

Access Level 2

 The EVACUATE key is pressed to turn ON all alarm devices.

 The SILENCE/RESOUND key is pressed to silence any silence-able outputs that have been
activated.

The ALARMS LED will be illuminated to indicate that the silence-able outputs have been silenced and
resound is available. The operation of the SILENCE key will be logged.

 The RESET key is pressed to reset the fire condition. All outputs activated in response to the
fire will deactivate and the panel will revert to the normal condition providing there are no other abnormal
conditions present. – RESET IS LOGGED.

Disabling a Zone
The following example DISABLES a ZONE. Place the Keyswitch in the ENABLED position.
CONTROL MENU
1►ZONE 3|PANEL
Press  2|DEVICE 4|GLOBAL CONTROL

Then to open the “Control” menu. By following


the screen prompts select the type of control, 1 to 4. Once selected simply step through the menu again to
implement.

Press  to open the “Zone” menu.


Selecting the Zone Control menu prompts the user to
select the zone number using the generic zone point Zzzz <status>
selection screen followed by the corresponding zone <zone descriptor>
control menu. (Sounder access is available at Level 3 1:DISABLE INPUTS 2:DISABLE SOUNDERS
only) 3:SILENT WALK TEST 4:WALK TEST DEVICE►
TABLE OF CONTENTS Page No.

1.  About This Manual.................................................................................................................... 2 


1.1  Introduction .................................................................................................................... 2 
1.2  System Overview ........................................................................................................... 2 
1.3  System Components ...................................................................................................... 2 
2.  System Functions ..................................................................................................................... 2 
2.1  I/O Control ...................................................................................................................... 3 
2.2  Evacuation ..................................................................................................................... 3 
2.3  Class Change................................................................................................................. 3 
2.4  Disable/Enable ............................................................................................................... 3 
2.5  Silence/Resound ............................................................................................................ 3 
2.6  System Response times ................................................................................................ 3 
2.7  Sounder and Strobe Synchronisation and Silencing Options ........................................ 3 
3.  Front Panel Controls, Indicators ............................................................................................. 4 
3.1  Levels of Access ............................................................................................................ 4 
3.1.1  Passwords.......................................................................................................... 4 
3.1.2  Misplaced Password .......................................................................................... 5 
3.2  System Controls & Indicators......................................................................................... 6 
3.3  Liquid Crystal Display .................................................................................................... 8 
4.  Displayed Conditional Responses........................................................................................ 10 
4.1  Normal Condition ......................................................................................................... 10 
4.2  Fire Condition ............................................................................................................... 11 
4.3  Fault Condition ............................................................................................................. 12 
4.3.1  System Fault Condition .................................................................................... 12 
4.4  Pre-Alarm Condition ..................................................................................................... 14 
4.5  Emergency Condition................................................................................................... 14 
4.6  Security Condition ........................................................................................................ 14 
4.7  User Condition ............................................................................................................. 14 
4.8  Disabled Condition ....................................................................................................... 15 
4.9  Other Conditions .......................................................................................................... 15 
5.  Test Functions ........................................................................................................................ 16 
5.1  Loop Test ..................................................................................................................... 16 
5.2  Lamp Test .................................................................................................................... 16 
5.3  Walk Test ..................................................................................................................... 17 
5.4  Device Locator ............................................................................................................. 18 
6.  Menu Structure ....................................................................................................................... 19 
6.1  Menu Layout and Navigation ....................................................................................... 19 
6.1.1  Generic Point Selection Screens ..................................................................... 20 
6.1.2  Zone Point Selection ........................................................................................ 20 
6.1.3  Loop Point Selection ........................................................................................ 20 
6.1.4  Loop Device Point Selection ............................................................................ 20 
6.1.5  Sub-Address Point Selection ........................................................................... 20 
6.1.6  Add-On Point Selection.................................................................................... 21 
6.1.7  Panel Input Point Selection .............................................................................. 21 
6.1.8  Panel Output Point Selection ........................................................................... 21 
6.1.9  Password User ID Selection ............................................................................ 21 
7.  MENU STRUCTURE & NAVIGATION..................................................................................... 22 
7.1  Menu > Display ............................................................................................................ 22 
7.1.1  Menu->Display->About .................................................................................... 22 
7.2  Menu > Control ............................................................................................................ 23 
7.2.1  Menu > Control > Zone .................................................................................... 23 
7.2.2  Menu > Control > Device ................................................................................. 24 
7.2.3  Menu >Control > Panel .................................................................................... 25 
7.2.3.1  Menu->Control->Panel->Input ................................................................. 25 
7.2.3.2  Menu->Control->Panel->Output .............................................................. 26 
7.2.3.2.1  Menu->Control->Panel->Output->Supervised O/P 26 
7.2.3.2.2  Menu->Control->Panel->Output->Relay O/P 26 
7.2.3.2.3  Menu->Control->Panel->Output->Open Collector O/P 26 
7.2.3.2.4  Menu->Control->Panel->Output->Auxiliary O/P 26 
7.2.3.3  Menu->Control->Panel->Add-On............................................................. 26 
7.2.3.4  Menu->Control->Panel->Loop ................................................................. 27 
7.2.3.5  Menu->Control->Panel->Printer .............................................................. 27 
7.2.3.6  Menu->Control->Panel->Power ............................................................... 27 
7.2.3.7  Menu->Control->Panel->Delay Mode ...................................................... 28 
7.2.4  Menu ->Control > Global Control ..................................................................... 28 
7.3  Menu.> Events ............................................................................................................. 28 
7.3.1  Menu->Events->Print ....................................................................................... 28 
7.3.2  Menu->Events->Delete .................................................................................... 28 
7.3.3  Menu->Events->Goto....................................................................................... 29 
7.4  Menu > Tools ............................................................................................................... 29 
7.4.1  Menu->Tools->Dirty Devices ........................................................................... 29 
7.4.2  Menu->Tools->Loop Statistics ......................................................................... 29 
7.5  Menu > Setup............................................................................................................... 30 
7.5.1  Menu->Setup->Date and Time ........................................................................ 30 
7.5.1.1  Menu->Setup->Date and Time->Date ..................................................... 30 
7.5.1.2  Menu->Setup->Date and Time->Time ..................................................... 30 
7.5.2  Menu->Setup->Day/Night ................................................................................ 30 
7.5.2.1  Menu->Setup->Day/Night->Day .............................................................. 31 
7.5.3  Menu->Setup->Earth Monitoring ..................................................................... 31 
7.5.4  Menu->Setup->Passwords .............................................................................. 31 
7.6  Menu > Programming .................................................................................................. 32 
7.6.1  Menu->Programming->Zone............................................................................ 32 
7.6.2  Menu->Programming->Device ......................................................................... 33 
7.6.2.1  Menu->Programming->Device->Add ....................................................... 34 
7.6.2.2  Menu->Programming->Device->Delete ................................................... 34 
7.6.2.3  Menu->Programming->Device->Edit ....................................................... 34 
7.6.2.4  Menu->Programming->Device->Edit – Sub Input ................................... 35 
7.6.2.5  Menu->Programming->Device->Edit – Sub Output................................. 36 
7.6.3  Menu->Programming->Panel........................................................................... 38 
7.6.3.1  Menu->Programming->Panel->Input ....................................................... 38 
7.6.3.2  Menu->Programming->Panel->Output .................................................... 39 
7.6.3.3  Menu->Programming->Panel->Loop ....................................................... 41 
7.6.3.4  Menu->Programming->Panel->Descriptor............................................... 41 
7.6.4  Menu->Programming->Sounders .................................................................... 41 
7.6.4.1  Menu->Programming->Sounders->Global Activation.............................. 41 
7.6.4.2  Menu->Programming->Sounders->Zone Activation ................................ 42 
7.6.5  Menu->Programming->Learn Options ............................................................. 42 
7.6.5.1  Menu->Programming->Learn Options->Auto Learn ................................ 42 
7.6.5.2  Menu->Programming->Learn Options->Extra Devices ........................... 43 
7.6.5.3  Menu->Programming->Learn Options->Mismatched Devices ................ 43 
7.6.5.4  Menu->Programming->Learn Options->Missing Devices ....................... 43 
7.6.6  Menu->Programming->Version ....................................................................... 44 
7.7  Event Logging .............................................................................................................. 45 
8.  Compatible Devices ............................................................................................................... 46 
9.  Complete Menu Structure ...................................................................................................... 48 
ODYSSEY OPERATION & ONSITE PROGRAMMING
1. About This Manual
1.1 Introduction
This manual contains all the information required to operate the Odyssey Fire Alarm Control Panel
(FACP) and perform on site programming functions. The first step in becoming a proficient operator
is to become familiar with and understand the “Menu Structure” (see Section 9) and the keys used to
navigate through it. Once this concept along with the screen prompts that are displayed during the
navigation process are understood the user will find the operation of the Odyssey Fire Alarm Control
Panel (FACP) a simple task.
1.2 System Overview
The purpose of the FACP is to monitor changes in inputs, report those changes and update selected
outputs as programmed using the LoopMaster Configuration software.
The FACP processes changes in the inputs fire, fault, pre-alarm, emergency, security, user,
transparent and system and has a built-in menu structure to view its status, perform operational
tests, and to some degree modify the panel’s configuration and programming without the use of the
LoopMaster Configuration software.
The Odyssey FACP is compliant with EN54-2 and EN54-4.
In addition to the mandatory requirements of EN54-2 the Odyssey meets the following optional
features with requirements:
 7.8 Output to fire alarm devices
 7.9 Control of fire alarm routing equipment
 7.9.1 Output to fire alarm routing equipment
 7.9.2 Alarm Confirmation input from fire alarm routing equipment
 7.11 Delays to outputs
 7.12 Dependencies on more than one alarm signal Type A, B and C
 8.3 Fault signals from points
 8.9 Output to fault warning routing equipment
 9.5 Disablement of each addressable points
 10 Test condition
1.3 System Components
The following diagram illustrates the main components of the system and their connectivity

Addressable
Loop Devices
- Apollo
Parallel
Printer

Main Termination
Board

Front Panel ICC


- 1-2 Analogue Loops
- 4 Supervised Inputs
- 40 X 4 Line LCD
- LED Indicators - 4 Monitored Outputs
- Buzzer - 3 Relay Outputs
- Keys - 2 Aux Outputs Power Supply Unit
- Parallel Printer Port - RS232 / USB Port
- Add On Port - RS485 Port Add Ons
- PSU Interface

RS485 Add On
Modules PC
- 30 Max per Panel TCP / IP
Serial Modem

Figure 1: The Odyssey Concept

2. System Functions
System functions are the key functions that provide the mechanism to change the way the panel
responds to a condition, and the way an input/output behaves to a situation. It is therefore important
the engineer has a good understanding of the functions described below.
2
ODYSSEY OPERATION & ONSITE PROGRAMMING
2.1 I/O Control
There is a mechanism for controlling the inputs & outputs connected to the FACP through the front
panel programming menu. This feature controls all the outputs, sounders, strobes/beacons and
settings for alert & evacuation.
2.2 Evacuation
This feature is available as part of the user interface of the front panel and selecting this button will
trigger an evacuate condition. This will illuminate the Fire condition LED, is latching and supports
silence/resound. Individual sounders/strobes/beacons can be disabled from responding to an
evacuate condition.
2.3 Class Change
With class change when the input is asserted, the sounders/outputs that have been configured to
respond to a class change will be activated. When the input is switched off, the sounders/outputs are
de-activated – non-latching.
2.4 Disable/Enable
This feature is also available as part of the user interface of the front panel. It is possible to enable or
disable inputs and outputs connected to the FACP. Inputs include zones, loops and loop devices.
Outputs include sounders, strobes/beacons etc.
2.5 Silence/Resound
This feature is available as part of the user interface of the front panel. This is a toggle button &
pressing it once will cause the activated sounders, relays & beacons to be silenced (If they are
configured with a silence-able attribute) and pressing the button again will cause the same devices
to re-sound (referred to as a “toggling action”).
However, for devices that are not configured to be silenced, pressing the Silence/Resound button
will have no effect and they will continue to sound / operate as programmed.
2.6 System Response times
The panel reports a fire from a detector within 10 seconds and fire conditions originating from an
MCP are be reported within 1 second.
Alarm devices (sounders, strobes and beacons) are activated within 3 seconds of a MCP being
operated.
2.7 Sounder and Strobe Synchronisation and Silencing Options
The FACP supports the Apollo synchronisation scheme. All loop sounders and beacons within the
panel are synchronised.
Silencing is panel (network) wide, with sounders (or beacons/strobes) being configured as non-
silence-able and the resound is toggled with the silence key.

3
ODYSSEY OPERATION & ONSITE PROGRAMMING
3. Front Panel Controls, Indicators
The Front Panel Control Card interfaces to the Main Control Board by way of CN5, and supports;
 all the controls and functional indicators
 the FACP Reset
 the Configuration (CONFIG) control
 Serial or Parallel Printer port

Figure 2: Front Panel Layout


3.1 Levels of Access
The FACP supports three levels of access:
Access Level 1 (Untrained User):
The FACP is in Access Level 1 by default.
Only the OVERRIDE, PREVIOUS, NEXT, SILENCE BUZZER and LAMP TEST controls are active.
Access Level 2 (Authorised User):
To enter Access Level 2 the user has to enter a password using the alpha numeric keys. The
password entry screen will be presented if any higher access level key is pressed. Alternatively
turning the Keyswitch to the ON position will force the panel into access level 2. The user is able to
navigate through the menu system in access level 2 however the ENTER PASSWORD menu item
will be displayed in place of the PROGRAMMING and SETUP menus.

Note: PROGRAMMING and SETUP menus are not accessible during a Fire condition
If ENTER PASSWORD is selected, the password entry screen will be presented allowing the user to
enter the access level 3 password. The user is able to enter any access level password when the
password screen is presented.
The access level 1 controls are active as well as SILENCE RESOUND, RESET, EVACUATE and
MENU ENTER controls. All menu items are active apart from the programming menu.
Access Level 3 (Authorised Service Technician/Engineer):
All access level 1 and 2 controls, PROGRAMMING, SETUP menus and individual sounder output
disable options are active.
If ENTER PASSWORD is selected, the password entry screen will be presented allowing the user to
enter the access level 3 password.
3.1.1 Passwords
The FACP will support 99 user programmable passwords. Each password includes an access level
which can be either 2 or 3 corresponding to the access levels and a unique ID which ranges from 1
to 99. There is also a facility in the access level 3 SETUP menu to add, edit or delete passwords.

4
ODYSSEY OPERATION & ONSITE PROGRAMMING

Note: Onsite programming only allows for the editing of ID1 and ID2 all other ID’s need to be
set using the LoopMaster configuration tool
All passwords are a 4 digit numeric entry and the system default passwords are as follows:
ID Password Access Level
1 3333 3
2 User Defined User Defined
Password Conditions
1. All password IDs that have not been assigned a password are set to access level 1 to
prevent false entries.
2. The entering of a password will be logged using the ID.
3. If no key is pressed for 5 minutes the access level will timeout to the default access level
being 2 or 1 depending on the key-switch position.
4. The access level timeout and key-switch operations will also be logged.
5. The intervals between key presses when entering the password must not exceed 30
seconds otherwise the password entry screen will timeout returning the panel to the default
access level.
6. The FACP can also be forced to the default access level by pressing the CANCEL key 4
times while default screen is displayed.
3.1.2 Misplaced Password
In the situation, where access to the panel is required, and the passwords are not available, there is
a facility for the appropriate service personnel to gain access to the panel.
The procedure is as follows:

1.
The password “
# , , , , ,
# ” is entered.
2.
The panel responds by displaying a unique 10 digit key
3.
Contact the local Eurotech Service Centre and they will issue a temporary password
4.
The temporary password is entered, and access is gained to the panel. The operator can
now access the password menu and set the passwords up as appropriate for the installation
The temporary password will be deleted, the next time a password is successfully entered into the
FACP.

5
ODYSSEY OPERATION & ONSITE PROGRAMMING
3.2 System Controls & Indicators
The front panel has fourteen push button controls, a key switch and an alpha numeric keypad.
Controls, Normal – Enabled (Key Switch)

CONTROLS ENABLE KEY SWITCH. = OFF, = ON


If the key switch is in the OFF position (access level 1), then the OVERRIDE, PREVIOUS, NEXT,
SILENCE BUZZER and LAMP TEST controls are active.
If the key switch is in the ON position (access level 2), then the SILENCE RESOUND, RESET,
EVACUATE and MENU ENTER controls are also active.
The key switch is optional. If the key switch is not used, then a pass-code is entered (using the alpha
numeric keys) to gain access to level 2 or 3.

Note: Keys, when pressed, will present an audible feedback “beep” to the user.
Delay Active / Override
Available at access level 1 and above

DELAY ACTIVE

OVERRIDE

Delay Active – Indicator is illuminated steady when one or more zones are configured
with Investigation delays and Delay Mode is active. The indicator will flash if any Investigation delay
timer is running.
If the override control or evacuate control is activated while the investigation delay timer is running,
then the indicator will go steady and the investigation zone enters the fire condition.
The indicator will only be OFF if:
 The Delay Mode is OFF
 No investigation delays are configured
 The panel has switched to day or night mode where no delays have been configured.
Override – Momentary push button. - (EN54-2:1997, clause 7.11), When Delay Mode is ON and one
or more zones configured with investigation delays have their delay timer running, activating the
OVERRIDE control overrides the investigation delay timer allowing the zone or zones to enter the
fire condition immediately.
Alarm - Silence / Resound Alarms
Available at access level 2 and above

ALARMS

SILENCE
RESOUND

Alarms – The indicator is lit when the sounders configured to be silence-able have been
silenced in response to any activation sources, indicating the resound function is active.
Silence Resound – Momentary push button. Used to silence any alarm devices and resound them
by way of a “Toggle” function if the ALARMS indicator is illuminated. Only alarm devices configured
with the silence-able attribute set shall respond to silence/resound. Silenced alarm devices shall
automatically resound on the occurrence of a new fire event.
Pre-Alarm / Previous 
Available at access level 1 and above

PRE-ALARM

Pre-alarm – Illuminated when one or more devices are in the pre-alarm condition and not
disabled
6
ODYSSEY OPERATION & ONSITE PROGRAMMING
Previous Momentary push button. Used to scroll the LCD display to view the previous available
entry.
Fire Output / Next 
Available at access level 1 and above

FIRE OUTPUT

Fire Output – Illuminated steady if a designated fire output has been activated and
flashes if a FARE input is configured and active and remains so until the fire alarm condition is reset.
Next  Momentary push button. Used to scroll the LCD display to view the next available entry.
Fire / Silence Buzzer
Available at access level 2 for the alarm buzzer, available at access level 1 and above for the
fault buzzer

FIRE

SILENCE
BUZZER

Fire – Indicator is illuminated when one or more devices are reporting a FIRE condition
or the evacuate control has been activated.
Silence Buzzer – Silences the panel buzzer. Buzzer is activated under the following conditions:
Alarm Buzzer -
 Fire condition
Fault Buzzer -
 Fault with loop devices
 Fault with the loops
 Fault with the fire alarm routing equipment or fault warning routing equipment
 Fault with alarm devices or circuit
 Fault with connected modules, cards and boards
 Fault with secondary power supply
 Fault with main power supply
Fault / Reset
Available at access level 2 and above

FAULT

RESET

Fault – Indicator illuminated when there are one or more faults on the system.
 Fault with loop devices
 Fault with the loops
 Fault with the fire alarm routing equipment or fault warning routing equipment
 Fault with alarm devices or circuit
 Fault with connected modules, cards and boards
 Fault with secondary power supply
 Fault with main power supply
 Lit in conjunction with System Fault indicator
Reset – Momentary push button. Pressing RESET returns the FACP to its normal default state, by
clearing all fire alarm conditions, updating the relevant indicators and outputs. If fault conditions are
cleared they shall be re-established within 20 seconds
Disabled – Evacuate
Available at access level 2 and above

7
ODYSSEY OPERATION & ONSITE PROGRAMMING

DISABLED

EVACUATE

Disabled – The indicator is illuminated when one or more zone detectors, loop devices or
panel outputs are disabled.
Evacuate - Momentary push button. Turns on all alarm devices, illuminates the FIRE indicator,
activates the output to the fire alarm routing equipment and announces the evacuate condition on
the LCD.
Also if there any alarm devices configured with delays, the evacuate key will override these and
force the alarm devices into evacuate.

 Note: If there are any zones configured for Investigation or Dependency A, B or C, these shall
be bypassed when the EVACUATE key is pressed.
LAMP TEST
Lamp Test – Pressed for 2 to 3 seconds turns ON all indicators (including any ancillary
cards), segments of the LCD and the local buzzer in a logical sequence.

CANCEL
Cancel – Used to cancel a navigation step or entry in the MENU function
1 2
ABC
3
DEF

4
GHI
5
JKL
6
MNO

7
PQRS
8
TUV
9
WXYZ

MENU 0 #
ENTER
*
MENU / ENTER, 0-9, *, #, CANCEL and ◄▼▲► - Provides a means for entering the menu system,
and carrying out interrogation, control and programming activities
POWER
Illuminated to show the presence of mains power and flashes when the
mains have failed
SYSTEM FAULT
Illuminated when the FACP is unable to provide mandatory functions.
Indicator is latched, until cleared by the RESET control
EARTH FAULT
Illuminated when there is an earth fault detected on the panel
ALARMS STATUS
Illuminated steady if any of the alarm devices (sounders and/or strobes)
have been disabled and flashes if any of the alarm devices (sounders and/or strobes) are in fault.
Disable has priority over fault
FIRE OUTPUT STATUS
Illuminated steady if the fire output has been disabled and flashes if the fire
output is in fault (open or short circuit condition). Disable has priority over fault
TEST
Illuminated when the panel is in the “Walk Test” mode.
ZONE 1
Illuminated when the associated zone1-32 is in alarm.
3.3 Liquid Crystal Display
LCD is used to display abnormal conditions and for interrogation, control and programming activities.
When the FACP is in its normal state a default screen is displayed.
Backlight (refer to EN54.2:1997: 12.8.5):
The associated backlight is energised;
 In access level 1 during initialisation
 For 1 hour if a new fire or fault event occurs
 For 25 seconds following any key press, otherwise it shall be switched OFF.
In access level 2 or higher the backlight shall always be ON.

8
ODYSSEY OPERATION & ONSITE PROGRAMMING
Alarm, Fault and Isolate information are accessed through the Main Menu.
RN1 RN2 C1 PRINTER R1
PARALLEL SERIAL Q2 R2
C2
Q1 LCD BACK
RN3
U3 C3 LIGHT

R3
RN4 RN5 R4
CN3 CN1
U2
U1 CN2 R5

C5
R6 R7 C4 R8 C9 R10

D35
P WR
R9 R13
BUZZER N1236 SYST

D34
R11 CN4
SILENCE
R12
FLT

LCD CONNECTOR
C8
C7
Q4 Q3 ETH

D36
D49
LK1 FLT
ALM

D37
STAT
D48
FAULT
BUZZER
FIRE
D38
+ O/PD39
R14
TEST
BZ1
RN6

U4 RN7
C10
Q5 FRONT
Q6
U7 C11 RN8
RN9
D46 D45
RN10
U6 D44 D43 D42 D41 D40
PANEL I/F
U5
CONFIG
SW27

R15
C13

C12 DISABLED FAULT FIRE FIRE OUTPUT PRE-ALARM U8 ALARMS DELAY ACTIVE C14
C15 CN5
RN11 C16 U9 C17
C18 RN12 D33 Q7
D47 R17

C19 R18 DIAGNOSTIC R20


C20 R16
TH1 RESET R19

C22
U10 C21
C23 C24 R21
SW28 C29
C26 U11 C25
C27
CN6 ZONES 1 - 32 R22
C31
RN14 C28
COMMS C30
RN13 U12 D25 D21 U14 D17 D13 D9 D5 D1
RN15 RN16
U15 U16
D29
RN17

U13 D2
D26 D22 D18 D14 D10 D6

RN18
C32 C33
RN19 RN20 C35
R23 D30 C34
R27 C36 R24 R25
L1 L2
D31 D27 D23 D19 D15 D11 PWR LINK D7
PWR LINK D3
R26
CN9 CN10
CN8
C37 R28
D28 D24 D20 D16 D12 D8 D4
KEY CN7 JTAG
R29 D32
SWITCH Zone 29-32 Zone 25-28 Zone 21-24 Zone 17-20 Zone 13-16 Zone 9-12 Zone 5-8 Zone 1-4

Figure 3: Control Card PCB Layout

9
ODYSSEY OPERATION & ONSITE PROGRAMMING
4. Displayed Conditional Responses
4.1 Normal Condition
The POWER LED is illuminated meaning the mains voltage is present, and all other indicators are
off. The 4 x 40 LCD will display the;
DD/MM/YYYY HH:MM ACCESS LEVEL 1 current date, time and access level on line 1
USER DESCRIPTOR LINE 1 configured user descriptors of customer/site
USER DESCRIPTOR LINE 2 specific information on lines 2 and 3
SYSTEM STATUS DAY-NIGHT/MAN I/O system status - day-night and manual I/O
active information on line 4
In the above screen, ACCESS LEVEL corresponds to the currently active user access level.
In Zone mode, if there is an individual device or input that is disabled within a zone consisting of
more then one input, the panel exhibits a partially disabled status and displays the following:
Selecting DEVICE► sets the panel into device mode allowing the individual conditions to be
displayed, scrolled and controlled.
Display =

<DATE> <TIME> ACCESS LEVEL: 1


<USER DESCRIPTOR LINE 1>
<USER DESCRIPTOR LINE 2>
PARTIAL DISABLE DEVICE►

The default screen is not displayed if there is an abnormal status present on the system. The highest
priority scrollable status screen is displayed in its place.

 Note: Individual disablement of sounders and the Partial Disable condition are additional
features which fall outside the scope of EN54.2. The display of the individual disablements are
suppressed during the fire alarm condition however they may be interrogated via the Menu->Display-
>Disable menu in this instance. Only the global disablement/re-enablement of sounders is compliant
with EN54.2.
Furthermore after any interrogation at the front panel by the user, the display reverts to the highest
priority scrollable status screen or default screen 5 minutes after the last key press. The exception to
this timeout is when an alarm is present on the system where the keypad timeout is 30 seconds in
this case.

10
ODYSSEY OPERATION & ONSITE PROGRAMMING
4.2 Fire Condition
If an input or device is activated and it is configured to generate a fire condition the FACP responds
to the fire as follows:
 Common FIRE LED will turn on steady
 Assigned zone fire LED will illuminate
 Panel buzzer will sound continuously
 Fire condition to be reported to the LCD (time ordered buffer 100 entries deep)
 The fire event will be logged and printed, where a printer is fitted.
 The panel fire output will activate
 All outputs configured to operate under a fire condition will operate
The fire condition will be displayed on the LCD in the following format:
Zone with active Fire condition
The LCD displays the fire status screen and indicates the most recent zone in Fire by way of the
zone LED indicators

Zzzz FIRE
<zone descriptor>
<date> <time> CONTROL*
ZONE FIRE XXX OF XXX DEVICE►

The LCD will display the zone in which the fire originated and can be scrolled through all zones in
fire using the PREVIOUS and NEXT keys.

 Note: Only fires will be scrollable by default when fires are present on the system. Other events
are viewable via the Display menu when fires are present.
“CONTROL*” Indicates that the control menu hotkey is available; pressing the “*” key on the numeric
keypad will allow direct entry into the control menu for the current point being displayed. This
requires level 2 access.
The user can perform the following actions in response to a fire:
 The SILENCE/RESOUND key is used to silence any silence-able outputs that have been
activated in response to the fire condition. The ALARMS LED will be illuminate to indicate
that the sounders have been silenced and resound is available. The operation of the
SILENCE key will be logged. (This operation is only available at access level 2)
 The OVERRIDE key can be used to override any delays to outputs (EN54-2:1997, clause
7.11). (This operation is available at access level 1)
 The EVACUATE key can be pressed to turn all alarm devices.
 The RESET key can be used to reset the fire condition. All outputs activated in response to
the fire will deactivate and the panel will revert to the normal condition providing there are no
other abnormal conditions present. (This operation is only available at access level 2)
The FACP also displays fires in Device mode. Pressing the “DEVICE►” forward button allows the
panel to display all the devices or inputs on the system that are in fire.

<point location> FIRE


<point descriptor> <type>
<date> <time> CONTROL*
FIRE XXX OF XXX ◄ZONE

Pressing the Zone back key or a keypad time out will return the panel to displaying fire in zone
mode.
Use the ▲ (up) (down) arrows to cycle through the inputs and devices that are in fire.
Device Alarm LED activation
Due to the limited current available from the analogue loop, the number of alarm LED’s allowed to be
illuminated simultaneously is limited to the first 10 devices in fire on each loop; after this limit is
reached any new devices in fire will not have its alarm LED illuminated until the original fires have
been cleared on that loop.

11
ODYSSEY OPERATION & ONSITE PROGRAMMING
4.3 Fault Condition
When the system registers a fault condition:
 Common FAULT LED will be illuminated
 Corresponding front panel fault LED will illuminate
 Assigned zone fault LED will flash
 Panel buzzer will sound intermittently
 Fault condition to be reported to the LCD.
 The fault event will be logged and printed, where a printer is fitted.
 The panel fault output will activate
 All outputs configured to operate under a fault condition will operate
The fault condition will be displayed on the LCD in the following format:

Zzzz FAULT
<zone descriptor>
<date> <time> CONTROL*
FAULT XXX OFXXX DEVICE►

Only zoned input types shall be displayed collectively as a zone.

<point location> FAULT


<point descriptor> <type>
<date> <time> CONTROL*
FAULT XXX OF XXX ◄DEVICE

Faults originating from sounders, outputs and un-zoned modules on loops, add-ons or the panel
main termination board shall be displayed individually as shown here.
Pressing the “DEVICE►” forward button will allow the panel to display all the individual inputs,
outputs and modules in fault.
Selecting “CONTROL*” will allow direct entry into the control menu for the current point or zone
being displayed (This operation is only available at access level 2).
4.3.1 System Fault Condition
(EN54.2:1997: 8.5, 13.4, 13.6, 13.7a)
The System Fault condition is activated if the FACP fails to provide mandatory functions. When a
system fault condition occurs, the panel buzzer, System Fault and General Fault indicators shall be
activated.
Mandatory functions failures include:
 Critical hardware failure on Main Termination Board (MTB) – The system fault condition is
driven by hardware for this failure and can be cleared by hardware reset or power cycle of
the MTB if the hardware is not damaged.
 Reset of the CPU on the MTB while the MTB maintains power – The panel shall re-initialise
if possible and the system fault condition shall be driven by software. In this case the fault
buzzer is silence-able at access level 1 or higher by using the SILENCE BUZZER control
and the system fault can be cleared by activating the RESET control at access level 2 or
higher. If the RESET control is activated at access level 1, the user shall be prompted to
enter a password; successful entry of an access level 2 or 3 password shall complete the
action.
 Loss of communications with the Front Panel (FP) – The system fault condition shall be
hardware driven on the FP via the software in MTB and can be cleared by hardware reset or
power cycle of the FP if it is not damaged. The system fault condition is not resettable or
silence-able whilst the condition is driven by hardware. Upon successful reset of the FP, the
system fault condition shall remain latched and shall be driven by software. In this case the
condition is silence-able at Access level 1 by using the SILENCE BUZZER control and reset-
able at access level 2 or higher by using the RESET control.
 Memory corruption (checked hourly) – The system fault condition shall be driven by
software. The panel shall be forced to diagnostics mode and all outputs shall be switched
off. The system fault buzzer may be silenced in this instance by using the SILENCE
BUZZER control access level 1 or higher and cleared by activating the RESET control at
access level 2 or higher.
12
ODYSSEY OPERATION & ONSITE PROGRAMMING
 Exception due to software failure in MTB – The system fault condition shall be hardware
driven via software when panel reboots and can be silenced and cleared by pressing the
STAR ‘*’ key on the FP provided the key-switch is in the access level 2 position. The
exception codes shall be presented on the LCD for service support and the system shall
remain in boot mode until resolved.
The following screen shall be presented if the system fault condition is driven by software for
mandatory functions failures 2, 3 and 4 above:

SYSTEM FAULT: <fault status>

PRESS <RESET> TO CLEAR

Fault statuses include:


 “REBOOT DETECTED”
 “MEMORY CORRUPTION”
 “FRONT PANEL FAIL”
If the system is forced into diagnostics mode upon a memory corruption (mandatory functions failure
4 above) and the access level 2 keyswitch is active, the above screen shall be displayed as shown.
If the access level 2 keyswitch is off when this occurs, the bottom line screen shall read “ACTIVATE
KEY-SWITCH TO ALLOW RESET” in place of “PRESS <RESET> TO CLEAR”.
If the panel is forced into boot mode upon a software exception (mandatory functions failure 5
above), a screen such as the following shall be presented

!EXCEPTION! – PRESS * TO SILENCE


SR = 0x200000DF PC = 0x00437283 # = 0x00
BOOT VER: 1.01.0

Note: The silence feature is only available if the access level 2 keyswitch is active
In the event of a software exception these numbers should be recorded and reported to a customer
support representative.

Note: Sections 5.4 to 5.8 contain examples of device mode screens. Zone mode screens will
display the Zone mode descriptor. See section 5.3 for example.

13
ODYSSEY OPERATION & ONSITE PROGRAMMING
4.4 Pre-Alarm Condition
When a Pre-Alarm event occurs, the following actions take place.
 The associated LED will operate
 The condition will be reported on the LCD.
 The event will be logged and printed, where a printer is fitted.
 All outputs configured to operate under this condition will operate

<point location> PRE-ALARM


<point descriptor> <type>
<date> <time> CONTROL*
PRE-ALARM XXX OF XXX ◄ZONE

4.5 Emergency Condition


When an Emergency event occurs, the following actions take place.
 The condition will be reported on the LCD.
 The event will be logged and printed, where a printer is fitted.
 All outputs configured to operate under this condition will operate

<point location> EMERGENCY


<point descriptor> <type>
<date> <time> CONTROL*
EMERGENCY XXX OF XXX ◄ZONE

4.6 Security Condition


When a Security event occurs, the following actions take place.
 The condition will be reported on the LCD.
 The event will be logged and printed, where a printer is fitted.
 All outputs configured to operate under this condition will operate

<point location> SECURITY


<point descriptor> <type>
<date> <time> CONTROL*
SECURITY XXX OF XXX ◄ZONE

4.7 User Condition


When a User event occurs, the following actions take place.
 The condition will be reported on the LCD.
 The event will be logged and printed, where a printer is fitted.
 All outputs configured to operate under this condition will operate

<point location> USER


<point descriptor> <type>
<date> <time> CONTROL*
USER XXX OF XXX ◄ZONE

14
ODYSSEY OPERATION & ONSITE PROGRAMMING
4.8 Disabled Condition
When the user disables an input, output or zone the associated configured outputs will no longer
operate and will no longer effect panel conditions. The system registers a disabled condition as
follows:
 Common DISABLED LED will be illuminated
 Disabled condition to be reported to the LCD.
 The disable event will be logged and printed, where a printer is fitted.
 All outputs configured to operate under a disabled condition will operate

<point location> DISABLED


<point descriptor> <type>
<date> <time> CONTROL*
DISABLED XXX OF XXX ◄ZONE

4.9 Other Conditions


The two remaining conditions are:
System
 This event is not printed or displayed on the LCD
 The event will be logged
 All outputs configured to operate under this condition will operate
Transparent
 This event is not logged, printed or displayed on the LCD
 All outputs configured to operate under this condition will operate

15
ODYSSEY OPERATION & ONSITE PROGRAMMING
5. Test Functions
The FACP provides a set of diagnostic test functions that can be run on various inputs & outputs
(like loops, loop devices, LED indicators, LCD display, Sounders etc) to verify whether they operate
as they are intended.
The diagnostic test functions are;
Loop test
Lamp test
Walk test
Device Locator
5.1 Loop Test
Access level 2

Loop Test is available via the Menu - - Control - - Panel - - Loop. - - Test.
Invoking the Loop Test will drive the loop firstly from side A followed by side B and count all detected
devices on each side of the loop. These counts will be displayed upon completion of the test
prompting the user to press CANCEL to end.
The loop test also monitors for
 Over current and short circuit in single-ended mode
 Over current, short circuit and open circuit conditions in redundant mode.
If there were any latching loop faults prior to commencement of the test these will be re-tested and
cleared if no longer present.
Once the Loop Test is complete the loop is re-initialised.
5.2 Lamp Test
Access level 1 or 2
The Lamp Test is initiated by pressing and holding the LAMP TEST key and will include any add-on
indicator cards.

Note: The test will not start if there is a genuine alarm condition is present.
The lamp test performs the following two tests while beeping the panel’s internal buzzer until the
completion of the test.
 LED test – all front panel LED's shall be illuminated simultaneously. A Lamp test command
will be sent to the add-on modules to instigate their individually controlled lamp test
functionality.
 LCD display –all the pixels of the LCD and backlight are activated simultaneously.
The following will also apply:
 The lamp test is run while the LAMP TEST key is held.
 The test will not start if there is a genuine alarm condition present.
 A fire event is recognised during the test, in which case the test will be aborted and the fire
condition will be displayed.
If the results do not match those described above, the operator is required to note it and report it to
the Eurotech Service Centre.

16
ODYSSEY OPERATION & ONSITE PROGRAMMING
5.3 Walk Test
Access level 2
Walk Test and Silent Walk Test is available via the

Menu - Control - - Zone. - Select Zone - Silent Walk Test or - Walk Test
The purpose of the walk test is to verify the detectors, MCP's and optionally the alarm devices
(sounders) are functioning as required. Once a zone has been placed in walk test, the maintenance
personnel can manually activate each detector (or MCP) and check the local indicator is illuminated
and the alarm devices (sounders) operate if selected.
Details of walk test are as follows:
 Individual or multiple zones can be placed under test
 Zones placed under test can be removed from the test condition via the Zone Control menu
at access level 2 or 3
 Selecting “SILENT WALK TEST” performs the test without sounding programmed sounders
 Selecting “WALK TEST” performs the test activating associated sounders as programmed
 If “WALK TEST” or “SILENT WALK TEST” is invoked the control will toggle to display the
“REMOVE TEST” control
 The test indicator is illuminated if one or more zones are placed under test and will remain
illuminated for the duration of the test
 When a zone is placed under test the LCD displays a zone status of “WALK TEST”,
“SILENT WALK TEST”, or “C&E WALK TEST” depending on the type of active test
 If a fire is registered from within a zone under test the zone status will be displayed as
“WALK TEST FIRE” and sounders will sound if selected. The associated zone fire LED (if
fitted) will also be illuminated
 The common fire indicator will not be illuminated if a fire is detected from a zone under test
 The “WALK TEST FIRE” condition will not operate the designated Fire Output/s
 The “WALK TEST FIRE” condition will be logged and printed
 A fire detected from within a zone will be automatically reset every 5 seconds after it is
detected and associated sounders will be activated if selected for that duration. If the device
within the zone remains in fire the zone will re-enter the “WALK TEST FIRE” state, otherwise
the zone will be reverted to the active walk test status and the associated zone fire LED (if
fitted) is extinguish
 The test condition can be cleared by selecting “REMOVE TEST” from within the Zone
Control menu for individual zones
 Pressing the RESET key also removes all zones placed under test
 The walk test may alternatively be initiated as a System Effect in Cause and Effects. The
test will be performed on the zone designated by the Cause and Effect and the programmed
Sounders activated by default. The test will end when this System Effect is de-activated in
the Cause and Effect

Note: The test is not available if a fire condition existed at the panel prior to the test being
invoked

17
ODYSSEY OPERATION & ONSITE PROGRAMMING
5.4 Device Locator
Access level 2
The Device Locator test is available via

Menu - - Control - - Device - Select Device - Alarm led ON


Device locator allows maintenance personnel to locate a particular device by forcing the device
alarm LED ON. Only devices with physical alarm LED's support this test.
This is a low priority test and can only be performed on one device at a time. Once invoked the user
is prompted that the alarm LED has been forced on and to press CANCEL to end.
The Alarm LED of the device will remain on throughout the duration of the test.

18
ODYSSEY OPERATION & ONSITE PROGRAMMING
6. Menu Structure
6.1 Menu Layout and Navigation
The main menu for the system is as shown below. The accessibility of this menu for the three access
levels is as described previously and summarized below.
Access Level 1: Menu not accessible
Access Level 2: Menu partially accessible.
The menu system is accessible except for the disablement of individual sounder devices, SETUP (*)
and PROGRAMMING (*) menus, which are displayed with the suffix “(*)”. Selecting these menu
options at this access level, will prompt the user for a password, to allow entry into access level 3.
Access Level 3: Menu fully accessible.
“(*) “suffix on SETUP and PROGRAMMING will not be displayed indicating full access. All menu
options are accessible with respect to panel configuration.
The block arrow cursor “►” resides beside the selected menu item. The user can navigate around
the menu items using the arrow keys and to enter a selected menu item press the MENU ENTER
key. Alternatively the number beside each menu item can be selected using the numeric keypad this
will select and enter the respective menu item directly.

Note: In all menu’s if the Number selection is followed by a | symbol it is selectable by typing
the number or using the arrow keys. If the Number selection is followed by a ":" symbol it is only
selectable by typing the number.

MAIN MENU
1►DISPLAY 4|TOOLS
2|CONTROL 5|SETUP(*)
3|EVENTS 6|PROGRAMMING(*)

The items available in this menu are as described below & in more detail in the following sections.
DISPLAY – This menu allows the user to view all the events that are currently active within the
system. This consists of Fire, Fault, Pre-Alarm, Emergency, Security, User and Disable type of
events. There is also an ABOUT screen which displays software version information.
CONTROL – This menu allows the user to view and control the various inputs & outputs from the
panel, loops, add-ons and zones. Disablement, Manual I/O control, Testing and Printing can be done
from this menu.
EVENTS – This menu allows the user to view, print or erase the event logs that are logged in the
system
TOOLS – This menu allows the user to conduct specific Dirty Devices and Loop diagnostics tests.
SETUP – This menu allows the user to setup the system settings such as date and time, day/night,
etc.
PROGRAMMING – This menu allows the user to modify the configuration of the various inputs &
outputs of the panel, loops, add-ons and zones within the panel. It also provides the various Learn
options such as Auto Learn.

MAIN MENU
1►DISPLAY 4|TOOLS
2|CONTROL 5|SETUP(*)
3|EVENTS 6|PROGRAMMING(*)

Or - Move cursor up or down

Or - Move cursor Left or right

- Enter currently selected menu item

To - Select and enter menu item by corresponding number

- Return to previous menu


19
ODYSSEY OPERATION & ONSITE PROGRAMMING
6.1.1 Generic Point Selection Screens
Within the menu system there are several instances in which points are required to be selected in
order to proceed further and display and/or manipulate the selected points. Points include Zones,
Loops, Devices, Device Sub-Addresses, Panel Inputs, Panel Outputs and Add-Ons.
6.1.2 Zone Point Selection
Zones 1 up to 999 can be selected.

SELECT ZONE: XXX


<selected zone descriptor>
►Z1 Z2 Z3 Z4 Z5
Z6 Z7 Z8 Z9 Z10

Zone Address Prefixes:


 Z - Zone configured
 X - Zone not configured
Zone Address Suffixes:
 *- Zone Disabled
 S - Zone Sounders Disabled
6.1.3 Loop Point Selection
Loop 1 or 2 can be selected.

SELECT LOOP: X
<selected loop descriptor>
►L1 L2

This screen will be skipped if there is only one loop configured in the system except for in the
programming menu where the prefix “L” next to the loop number will be replaced with an “X” if the
loop is not configured and it can be selected to configure the loop. The loop number suffix “*”
indicates that the loop has been disabled.
6.1.4 Loop Device Point Selection
Apollo device addresses 1 to 126 can be selected.

SELECT DEVICE: XXX <device type>


<selected device descriptor>
►D1 D2 D3 D4 D5
D6 D7 D8 D9 D10

Device Address Prefixes:


 D - Device configured and fitted
 M - Missing device configured and not fitted
 T - Type mismatch configured and fitted with incorrect type
 E - Extra device not configured but fitted
 X - Device not configured and not fitted
Device Address Suffix:
 - Device Disabled
6.1.5 Sub-Address Point Selection
Apollo loop device sub-address inputs
1-3 and outputs 1-3 can be selected.

SELECT SUB ADDRESS: X


<selected sub address descriptor>
1►I/P1 2:I/P2 3:I/P3 4:O/P1 5:O/P2
6:O/P3

Sub-Address Prefixes:
 I/P – Sub-Address Input
 O/P – Sub-Address Output
20
ODYSSEY OPERATION & ONSITE PROGRAMMING
Sub-Address Suffix:
 - Sub-Address Disabled
6.1.6 Add-On Point Selection
Add-On module addresses 1 up to 30 can be selected, depending on type.

SELECT ADD-ON: XX <add-on type>


<selected add-on descriptor>
►A1 A2 A3 A4 A5
A6 A7 A8 A9 A10

Add-On Address Prefixes:


 A – Add-On configured
 X – Add-On not configured
Add-On Address Suffix:
* - Add-On Disabled
6.1.7 Panel Input Point Selection
Panel digital inputs 1 to 4 can be selected.

SELECT INPUT: X <input type>


<input descriptor>
►I/P1 I/P2 I/P3 I/P4

Panel Input Prefix:


 I/P – Panel Input
Panel Input Suffix:
 - Panel Input Disabled
6.1.8 Panel Output Point Selection
4 panel Supervised Outputs, 3 Relay Outputs, 2 Open Collector Outputs and 2 Auxiliary Outputs can
be selected.

SELECT OUTPUT: X <output type>


<output descriptor>
►O/P1 O/P2 O/P3 O/P4

Panel Output Prefix:


 O/P – Panel Output
Panel Output Suffix:
 - Panel Output Disabled
6.1.9 Password User ID Selection
User IDs 1 and 2 can be selected at the panel.

SELECT USER ID: X


►ID1 ID2

21
ODYSSEY OPERATION & ONSITE PROGRAMMING
7. MENU STRUCTURE & NAVIGATION
 The following should be read in conjunction with the complete “Menu Structure”.
The primary components of the Menu Structure are;
DISPLAY CONTROL EVENTS TOOLS SETUP PROGRAMMING
The sections below have been broken down by primary component for ease of explanation
7.1 Menu > Display
Access level 2
1
DISPLAY
1 2 3 4 5 6 7 8 9
1 FIRE FAULT PRE-ALARM EMERGENCY SECURITY USER DISABLE TEST ABOUT

 Pressing
1
opens the “Display” menu. Here the operator can view any of the above
facilities, 1 to 8 by following the screen prompts, (up), (down), to move through the
menu. To view its status on the LCD press the number associated with that facility, for example
3
press DEF to view any “Pre-alarms” that may be present on the system. This process of
navigation and following the screen prompts forms the basis for accessing, viewing and / or
programming.
In the DISPLAY menu, the menu items consist of all the displayable system conditions.

DISPLAY MENU
1►FIRE 4|EMERGENCY 7|DISABLE
2|FAULT 5|SECURITY 8|TEST
3|PRE-ALARM 6|USER 9|ABOUT

When a display condition is selected, the status screen of the condition to be shown is displayed at
the zone level initially:

Zzzz <status>
<zone descriptor>
<date> <time> CONTROL*
ZONE <action type> XXX OF XXX DEVICE►

Pressing the “DEVICE►” forward button will allow the panel to display the individual devices or
inputs with the associated condition.

<point location> <status>


<point descriptor> <type>
<date> <time> CONTROL*
<action type> XXX OF XXX ◄ZONE

Note: If there are no Zones with the selected condition and there are devices with the selected
condition, the zone screen will be bypassed and the device screen will be displayed immediately.
7.1.1 Menu->Display->About
If ABOUT is selected the following screen is presented:

<custom banner 1>


<custom banner 2>
<system status>
◄BACK APP:VMM.mm.bb.ccccccc CB:XXX

22
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.2 Menu > Control
Access Level 2 – to access this level the operator should use the “Controls Normal – Enable”
keyswitch or enter the Password.
NOTE:
2
ABC
CONTROL 1: At Access Level 1, the entire menu is not accessible.
1 2
2 2: At Access Level 2, individual sounder disablement,
1 ZONE ABC DEVICE SET-UP and PROGRAMMING menu items
are not accessible, user can access level 3 via the
3 4 correct password entry.
DEF
3 PANEL 4
GHI GLOBAL CONTROL 3: At access level 3, every option is available

2
Pressing ABC
opens the “Control” menu from which the operator can select one of the “Control”
functions shown above by pressing (up), (down), to move through the menu. To view its
control options on the LCD press the number associated with that facility on the alpha numeric key

pad or press to go directly to it.

CONTROL MENU
1►ZONE 3|PANEL
2|DEVICE 4|GLOBAL CONTROL

7.2.1 Menu > Control > Zone


2
ABC CONTROL
1
1
ZONE
1 2 3 4
DISABLE INPUTS DISABLE SOUNDERS SILENT WALK TEST WALK TEST DEVICE
1 2 3 4
DISABLE SUB ADDR / REM I/O PRINT ALARM LED ON
NON 1 2 3
SOUNDER
DISABLE ON PRINT
1 2 3 4
SOUNDER
DISABLE ALERT EVAC PRINT

1
Once in the “Control” menu press to open the “Zone” menu. By following the screen prompts
select the type of control, 1 to 4. Once selected simply step through the menu again to implement.
Selecting the Zone Control menu prompts the user to select the zone number using the generic zone
point selection screen followed by the corresponding zone control menu:

Zzzz <status>
<zone descriptor>
1:DISABLE INPUTS 2:DISABLE SOUNDERS
3:SILENT WALK TEST 4:WALK TEST DEVICE►

Actions are all context sensitive


Disable inputs becomes enable inputs
Disable sounders becomes enable sounders
Walk test will start walk test and toggle to remove test
Silent walk test will start silent walk test and toggle to remove test
Pressing ► will display device (or input) within the zone; these are scrollable using ▲▼
Device screens:

Zzzz Ppp Lll Dddd.s <status>


<device descriptor>
◄BACK:DISABLE 2:SUB ADDR 3:PRINT
4:ALARM LED ON MORE►

23
ODYSSEY OPERATION & ONSITE PROGRAMMING
ACTION:<action type> <dev type>
AVALUE:XXX I:000 O:000 DRIFT:YYY%MODE:X
◄BACK:DISABLE 2:SUB ADDR 3:PRINT
4:ALARM LED ON

Note: Option 2 shall be SUB ADDR (Sub-Address) or REM O/P (Remote Output) depending on
the type of device being displayed.
Input Screens:
Pressing DEVICE ► will also reveal the panel Input Control.
Use the ▼▲ arrows to display the available panel inputs

<point location> <status>


<point descriptor>
ACTION:<action type>
◄BACK 1:DISABLE 2:ON 3:PRINT

7.2.2 Menu > Control > Device


2
ABC CONTROL
1 2 2
ABC
ZONE DEVICE
1 2
NOTE: SUB ADDR AND REM O/P DEPEND
L1 L2 ON THE SELECTED DEVICE
1 2 3 4
DISABLE SUB ADDR / REM I/O PRINT ALARM LED ON
NON 1 2 3
SOUNDER
DISABLE ON PRINT
1 2 3 4
SOUNDER
DISABLE ALERT EVAC PRINT

Selecting DEVICE from the control menu; the user shall be prompted to select loop and device
address via generic point selection screens. The following device control menu shall be presented
next:

Zzzz Ppp Lll Dddd.s <status>


<device descriptor>
◄BACK 1:DISABLE 2:SUB ADDR 3:PRINT
4:ALARM LED ON MORE►

On the 4x40 LCD the Device control menu is split into two screens and the user can navigate
between these screens by selecting MORE► and ◄BACK.

ACTION:<action type> <dev type>


AVALUE:XXX I:000 O:000 DRIFT:YYY MODE:X
◄BACK 1:DISABLE 2:SUB ADDR 3:PRINT
4:ALARM LED ON

Selecting “2: SUB ADDR” will display the generic sub address selection screen if configured. Also
“2: SUB ADDR” will be replaced with “2: REM O/P” if the context displayed is a detector.
Input Screens:

<input location> <status>


<input descriptor>
ACTION:<action type> <dev type>
◄BACK 1:DISABLE 2:ON 3:PRINT

24
ODYSSEY OPERATION & ONSITE PROGRAMMING
Non-Sounder Output Screens:

<output location> <status>


<output descriptor>
<assigned output type> <dev type>
◄BACK 1:DISABLE 2:ON 3:PRINT

Sounder Output Screens:

<output location> <status>


<output descriptor>
<assigned output type> <dev type>
◄BACK 1:DISABLE 2:ALERT 3:EVAC 4:PRINT

7.2.3 Menu >Control > Panel


CONTROL
1 2
2 ZONE DEVICE
ABC

3 4
3
DEF PANEL GLOBAL CONTROL
1 2
INPUT OUTPUT
1 2 3 4
SUPERVISED O/P RELAY O/P OPEN COLLECTOR O/P AUXILIARY O/P
NON 1 2 3
SOUNDER
DISABLE ON PRINT
1 2 3 4
SOUNDER
DISABLE ALERT EVAC PRINT

1 DISABLE 2 ON 3 PRINT

3
ADD-ON
1 2 3 4 5 6
8 WAY RELAY 8 WAY SOUNDER SMART TERMINAL 32 INDICATOR SWITCH & INDICATOR 8Z CONVENTIONAL

1 2 3
DISABLE I/O PRINT
NON 1 2 3
SOUNDER
DISABLE ON PRINT
4 1 2 3 4
SOUNDER
LOOP DISABLE ALERT EVAC PRINT
1 2 3 4
DISABLE TEST PRNT ALL PRNT TYPES

5 6 7
NOTE: DELAY MODE (7) MENU IS ONLY AVAILABLE
PRINTER POWER DELAY MODE IF INVESTIGATION DELAYS ARE CONFIGURED
1 2 1
FIRE MODE
ON-LINE EVENT MODE ON / OFF

7.2.3.1 Menu->Control->Panel->Input

CONTROL PANEL MENU


1►INPUT 4|LOOP 6|POWER
2|OUTPUT 5|PRINTER 7|DELAY MODE
3|ADD-ON

Use the ▼▲ arrows to display the 4 available panel inputs

Ppp Ii Zzzz <status>


<input descriptor> <type>
ACTION:<action type>
◄BACK 1:DISABLE 2:ON 3:PRINT

25
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.2.3.2 Menu->Control->Panel->Output

CONTROL PANEL OUTPUT MENU


1►SUPERVISED O/P 3|OPEN COLLECTOR O/P
2|RELAY O/P 4|AUXILIARY O/P

7.2.3.2.1 Menu->Control->Panel->Output->Supervised O/P


Use the ▼▲ arrows to display the 4 available panel supervised outputs
Non-Sounder Outputs:

Zzzz Ppp SUP:Oo <status>


<output descriptor> <type>
<assigned output type>
◄BACK 1:DISABLE 2:ON 3:PRINT

Sounder Outputs:

Zzzz Ppp SUP:Oo <status>


<output descriptor> <type>
<assigned output type>
◄BACK 1:DISABLE 2:ALERT 3:EVAC 3:PRINT

7.2.3.2.2 Menu->Control->Panel->Output->Relay O/P


Use the ▼▲ arrows to display the 3 available panel relay outputs

Zzzz Ppp RLY:Oo <status>


<output descriptor> <type>
<assigned output type>
◄BACK 1:DISABLE 2:ON 3:PRINT

7.2.3.2.3 Menu->Control->Panel->Output->Open Collector O/P


Use the ▼▲ arrows to display the 2 available panel open collector outputs

Zzzz Ppp OC:Oo <status>


<output descriptor> <type>
<assigned output type>
◄BACK 1:DISABLE 2:ON 3:PRINT

7.2.3.2.4 Menu->Control->Panel->Output->Auxiliary O/P


Use the ▼▲ arrows to display the 2 available panel open collector outputs

Zzzz Ppp AUX:Ooo <status>


<output descriptor> <type>
<assigned output type>
◄BACK 1:DISABLE 2:ON 3:PRINT

7.2.3.3 Menu->Control->Panel->Add-On

SELECT ADD-ON TYPE: 8-WAY RELAY


CHANGE▼
◄BACK NEXT►

After the type of Add-On is selected the generic Add-On point selection screen is presented allowing
the Add-On address to be selected. The Add-On control menu is then presented:

26
ODYSSEY OPERATION & ONSITE PROGRAMMING
<add-on location> <status>
<add-on descriptor>
<add-on type> <add-on version>
◄BACK 1:DISABLE 2:I/O 3:PRINT

Selecting “2:I/O” will display the individual inputs and/or outputs of the add-ons
Use the ▼▲ arrows to display the available inputs and outputs
Non-Sounder Outputs:

<add-on location> <status>


<output descriptor> <type>
<assigned output type> <add-on type>
◄BACK 1:DISABLE 2:ON 3:PRINT

Sounder Outputs:

<add-on location> <status>


<output descriptor> <type>
<assigned output type> <add-on type>
◄BACK 1:DISABLE 2:ALERT 3:EVAC 4:PRINT

7.2.3.4 Menu->Control->Panel->Loop
Use the ▼▲ arrows to display the available loops

Pppp Lll <status>


<loop descriptor>
<loop configuration> <loop current>
1:DISABLE 2:TEST 3:PRNT ALL 4:PRNT

7.2.3.5 Menu->Control->Panel->Printer

PANEL PRINTER <on-line status>


<fire/event mode>

◄BACK 1:ON-LINE 2:FIRE MODE

7.2.3.6 Menu->Control->Panel->Power

PANEL POWER
AC:xxxxxxxxx VBATT:xx.xDC TEMP:xxxC
BATTERY:xxxxxxxxx
◄BACK

AC statuses include:
 NORMAL
 FAIL
 CHGR HIGH
 CHGR LOW
 CHGR FLT
BATTERY statuses include:
 NORMAL
 DAMAGED
 MISSING
 CABLE FLT
 LOW

27
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.2.3.7 Menu->Control->Panel->Delay Mode
This menu is only accessible if investigation delays have been configured and the panel is in the day
or night modes in which delays are configured.

INVESTIGATION DELAY MODE: ON

◄BACK 1:OFF

7.2.4 Menu ->Control > Global Control


2
ABC
CONTROL
1 2
ZONE DEVICE

3 4
PANEL GLOBAL CONTROL 4
GHI

1 2 3 4 5
DISABLE SOUNDERS ENABLE SOUNDERS GLOBAL ENABLE REMOVE MANUAL I/O REMOVE WALK TEST

GLOBAL CONTROL MENU


1►DISABLE SOUNDERS 4|REMOVE MANUAL I/O
2|ENABLE SOUNDERS 5|REMOVE WALK TESTS
3|GLOBAL ENABLE

7.3 Menu.> Events


3
DEF EVENTS
1 2 3 4 5 6 7 8 9
ALL FIRE FAULT PRE-ALARM EMERGENCY SECURITY USER SYSTEM DISABLE
1 2 3
PRINT DELETE GOTO
1 2 3 4 1 2 3
CURRENT ENTRY ALL RANGE BY DATE RANGE BY ENTRY No MOST RECENT BY DATE BY ENTRY

EVENTS MENU
1►ALL 4|PRE-ALARM 7|USER
2|FIRE 5|EMERGENCY 8|SYSTEM
3|FAULT 6|SECURITY 9|DISABLE

The user can select to view any individual event type or all event types; revealing the following event
screen:

<event type> xxx/yyy <date>


<time>
<location> <status>
<descriptor> <user id>

7.3.1 Menu->Events->Print

PRINT <event type> EVENTS


1►CURRENT ENTRY 3|RANGE BY DATE
2|ALL 4|RANGE BY ENTRY

7.3.2 Menu->Events->Delete

DELETE <event type> EVENTS


1►CURRENT ENTRY 3|RANGE BY DATE
2|ALL 4|RANGE BY ENTRY

28
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.3.3 Menu->Events->Goto

GOTO <event type> EVENTS


1►MOST RECENT
2|BY DATE
3|BY ENTRY

7.4 Menu > Tools


4
GHI
TOOLS
1 2
DIRTY DEVICES LOOP STATISTICS
1 2 3 1 2
LOW% MED% HIGH% L1 L2
1
RESET COUNT

TOOLS MENU
1►DIRTY DEVICES
2|LOOP STATISTICS

7.4.1 Menu->Tools->Dirty Devices


The compensation threshold level can be set to the default Low, Medium or High percentage. The
selected default Low, Medium or High compensation threshold is displayed, and an asterisk shall
appear next to the current selection where the medium threshold is the default.
Only those devices which have a drift percentage higher than the threshold will be displayed.
If there are no dirty devices on the system found at the selected drift threshold the following screen is
presented:

NO DIRTY DEVICES FOUND


AT SELECTED DRIFT THRESHOLD

◄BACK 1:005% 2*040% 3:080%

If devices are found with drift percentage values higher than the selected drift percentage threshold
then the following screen is displayed:

Zzzz Ppp Lll Dddd.s <status>


DRIFT LEVEL: XXX
DIRTY DEVICES XXX OF XXX CONTROL*
◄BACK 1:005% 2*040% 3:080%

Use the ▼▲ arrows to display the available dirty devices. The control menu hotkey can also be
invoked by pressing the * key allowing direct access into the control menu for the current device
being displayed.
7.4.2 Menu->Tools->Loop Statistics
If there is more than one loop available, selecting LOOP STATISTICS shall allow the user to select
which loop they would like to view using the generic loop selection screen. This is followed by the
loop statistics menu screen:

BAD POLLS:xxxxxxxx (xx.xx%) <loop no.>


SINCE DD/MM/YYYY HH:MM:SS
LOOP NOISE LEVEL:xxmA - <noise status>
◄BACK 1:RESET COUNT

This screen shows the number of bad polls and a percentage of bad/good polls from the date and
time. “1: RESET COUNT” will reset the bad poll count and establish a new datum.
Noise level is the average level of noise on the loop. The noise status displayed shall be GOOD,
FAIR or BAD based on the preset thresholds.

29
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.5 Menu > Setup
5
JKL SETUP
1
DATE AND TIME
1 2 3 4 5
DATE FORMAT DAYLIGHT SAVE ON/OFF TIME FORMAT

2 3
DAY/NIGHT EARTH MON
1 2 3 4 5 6 7 6 7
SUNDAY MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SET ALL DISABLE

4
PASSWORDS
1 2
ID1 ID2

SETUP MENU
1►DATE AND TIME 3|EARTH MONITORING
2|DAY/NIGHT 4|PASSWORDS

This menu is only accessible at access level 3. If the active access level is less than 3 the user will
be prompted to enter password before allowing access to this menu.
7.5.1 Menu->Setup->Date and Time

DATE AND TIME MENU


1►DATE :01/01/2008 4|TIME :10:05:33
2|FORMAT:DD/MM/YYYY 5|FORMAT:24 HOUR
3|DAYLIGHT SAVE ON

The date format can be changed by selecting 2, the time format can be changed by selecting 5 and
the daylight savings mode can be tuned on or off by selecting 3.
7.5.1.1 Menu->Setup->Date and Time->Date

FORMAT: DD/MM/YYYY
CURRENT: 01/01/2008
NEW: _
▲DEL APPLY►

7.5.1.2 Menu->Setup->Date and Time->Time

CURRENT: 10:05:34
NEW: _

▲DEL APPLY►

7.5.2 Menu->Setup->Day/Night

DAY/NIGHT MENU <disabled status>


1►SUNDAY 4|WEDNESDAY 7|SATURDAY
2|MONDAY 5|THURSDAY 8|SET ALL
3|TUESDAY 6|FRIDAY 9|DISABLE

Day/Night mode can be enabled or disabled by selecting 9. The <disabled status> shall toggle
accordingly as this is selected.

30
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.5.2.1 Menu->Setup->Day/Night->Day

DAY/NIGHT SETTINGS - SUNDAY


CURRENT - DAY: HH:MM NIGHT: HH:MM
NEW - DAY: _ NIGHT: DEL▲
◄BACK APPLY▼ NEXT►

Back will return to day/night menu or previous day if not on first day selected.
Next will proceed to the day/night settings for each of the remaining six days in sequence after which
it will return to the day/night menu.
Pressing APPLY will set the CURRENT day/night settings to the new value and clear the new values
to allow re-editing.
Cancel returns to the day/night menu on any day.
Selecting “8|SET ALL" from the Day/Night menu shall present the user with a screen similar to that
above. The settings applied on this screen will be applied to all days of the week.
7.5.3 Menu->Setup->Earth Monitoring

EARTH MONITORING: ENABLED


ENSURE EARTH MONITORING LINK ISFITTED
CHANGE▼
◄BACK APPLY

Press CHANGE▼ to toggle between enabled and disabled


7.5.4 Menu->Setup->Passwords
Selecting the password menu shall reveal the generic password user ID selection screen followed by
the following:

ADD/EDIT PASSWORD
ID ►: 01
ACCESS LEVEL : 2 DEL▲
PASSWORD : 2222 SAVE►

Use ▼arrow to move edit point.


Only password IDs 1 and 2 are editable at the panel. All other IDs need to be configured using the
PC configuration tool.

31
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.6 Menu > Programming
6
MNO

PROGRAMMING (*)
1
ENTER PASSWORD ZONE

2
DEVICE
1 2 2
ADD DELETE EDIT

3
PANEL
1 2 3 4
INPUT OUTPUT LOOP DESCRIPTOR
1 2
L1 L2
1 2 3 4
SUPERVISED O/P RELAY O/P OPEN COLLECTOR O/P AUXILIARY O/P

4
SOUNDERS
1 2
GLOBAL ZONE
ACTIVATION ACTIVATION

5
LEARN OPTIONS
1 2 3 4
AUTO LEARN EXTRA DEVICES MISMATCHED DEVICES MISSING DEVICES
1 1 2 1 2 1 2
YES LEARN LEARN ALL RESOLVE RESOLVE ALL DELETE DELETE ALL

6
VERSION

This menu is only accessible at access level 3. If the active access level is less than 3 the user will
be prompted to enter password before allowing access to this menu.

PROGRAMMING MENU
1►ZONE 4|SOUNDERS
2|DEVICE 5|LEARN OPTIONS
3|PANEL 6|VERSION

The programming menu is divided into a series of programming wizards. Each individual
programmable attribute will be displayed on each screen of the wizard and navigation and editing
options are displayed.
If any changes to the configuration are made during the course of the programming wizard a DO
YOU WANT TO SAVE screen is displayed:

CHANGES MADE
DO YOU WANT TO SAVE?

◄BACK 1:YES

If no changes were made a NO CHANGES MADE splash screen will be displayed for a short period
before returning to the menu.
7.6.1 Menu->Programming->Zone
When this is selected the user is presented with the generic zone number selection screen followed
by the EDIT DESCRIPTION screen.

EDIT DESCRIPTOR
<descriptor>_
#CLEAR DEL▲
◄BACK NEXT►

32
ODYSSEY OPERATION & ONSITE PROGRAMMING
Use the alpha-numeric keys to key in descriptor characters. Pressing next (or enter) will update the
programming.

DAY MODE
ZONE CONFIGURATION: INVESTIGATION
CHANGE▼
◄BACK NEXT►

For day and night mode, choices are:


 NORMAL (No Timeout)
 INVESTIGATE (Timeout 1 / 2, MCP Override, Inhibit Sounders, Inhibit Fire Outputs
 DEPENDANCY A (Timeout 1)
 DEPENDANCY B (Timeout 1)
 DEPENDANCY C (Inhibit Sounders, Inhibit Fire Outputs)
Pressing next (or enter) will update the programming and prompt for respective timeout 1 setting.

DAY MODE <zone configuration>


EDIT ZONE TIMEOUT 1: 60 (1-180 SECS)
#CLEAR
◄BACK NEXT►

Pressing next (or enter) will update the programming and prompt for respective timeout 2 setting.

DAY MODE <zone configuration>


EDIT ZONE TIMEOUT 2: 300 (1-420 SECS)
#CLEAR
◄BACK NEXT►

Pressing next (or enter) will update the programming and prompt for MCP override setting.

DAY MODE <zone configuration>


MCP OVERRIDE: ENABLED
CHANGE▼
◄BACK NEXT►

Pressing next (or enter) will update the programming and prompt for Inhibit sounders setting.

DAY MODE <zone configuration>


INHIBIT SOUNDERS: ENABLED
CHANGE▼
◄BACK NEXT►

Pressing next (or enter) will update the programming and prompt for Inhibit fire outputs setting.

DAY MODE <zone configuration>


INHIBIT FIRE OUTPUTS: ENABLED
CHANGE▼
◄BACK NEXT►

The screens are then repeated for night mode. Then the user will be prompted to save changes if
required.
7.6.2 Menu->Programming->Device

DEVICE MENU
1►ADD
2|DELETE
3|EDIT

The user may choose to Add, Edit or Delete devices. Once selected, the user will be prompted to
select the loop and device to which to perform the selected action using the generic point selection
screens.

33
ODYSSEY OPERATION & ONSITE PROGRAMMING
SELECT DEVICE TYPE: <device type>

CHANGE▼
◄BACK NEXT►

7.6.2.1 Menu->Programming->Device->Add
In this wizard the user can scroll through the desired device type to be added. The user is also
prompted to save changes if required.
7.6.2.2 Menu->Programming->Device->Delete

Zzzz Ppp Lll Dddd.s <device type>

◄BACK DELETE►

Once selected the device location and type shall be displayed:


The user shall then be prompted to save changes if required.
7.6.2.3 Menu->Programming->Device->Edit

SELECT DEVICE TYPE: <device type>

CHANGE▼
◄BACK NEXT►

Once the device is selected firstly the device type can be changed:
If the device type is changed the following confirmation screen is presented:

WARNING: SETTINGS WILL BE DEFAULT


EXCEPT ZONE NUMBER AND DESCRIPTOR
PROCEED WITH CHANGE
◄BACK 1:YES

Confirming this will change the device type. As each device type has a different set of configurable
attributes only the device descriptor and zone number are common hence all other configurable
attributes for the given device are set to their default value when the device type is changed.

EDIT DESCRIPTOR
<descriptor>_
#CLEAR DEL▲
◄BACK NEXT►

Edit the descriptor using the alphanumeric keys. Press NEXT► to go to the next field.

ENTER ZONE NUMBER: X

#CLEAR DEL▲
◄BACK NEXT►

The zone number may then be changed:

EDIT ACTION TYPE: FIRE

CHANGE▼
◄BACK NEXT►

Press CHANGE▼ to browse through the available action types. Press NEXT► to go to the next
field.

INPUT TYPE: NON-LATCHING

CHANGE▼
◄BACK NEXT►

34
ODYSSEY OPERATION & ONSITE PROGRAMMING
Press CHANGE▼ to browse through the available latching state options. Press NEXT► to go to the
next field.

EDIT PRE-DELAY: 0 (0-90 seconds)

#CLEAR DEL▲
◄BACK NEXT►

Key-in the new pre-delay value for the selected field. Press NEXT► to go to the next field.

DAY SENSITIVITY: 100 (80-120%)

#CLEAR DEL▲
◄BACK NEXT►

Press NEXT► to enter the sensitivity mode of the device. For XP95 devices the following screens
are presented:

NIGHT SENSITIVITY: 100 (80-120%)

#CLEAR DEL▲
◄BACK NEXT►

The fixed alarm and pre-alarm thresholds of the XP95 device will be multiplied by this sensitivity
percentage for day and night; hence allowing increased(<100%) or reduced(>100%) sensitivity.

DAY SENSITIVITY MODE: 3

#CLEAR DEL▲
◄BACK NEXT►

For Discovery devices the Sensitivity mode setting adjust the analogue value within the detector.
Day mode displayed. Press NEXT► for Night mode.

DAY MODE: <detector mode>

#CLEAR DEL▲
◄BACK NEXT►

For Multi sensor detectors this Day mode screen format is used. Press NEXT► for Night mode.

INDICATE PRE-ALARM: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to select if the device should indicate a pre-alarm status at the panel.
The user is then prompted to save any changes if they have been made.
7.6.2.4 Menu->Programming->Device->Edit – Sub Input

EDIT DEVICE TYPE: <device type>

CHANGE▼
◄BACK NEXT►

Once the device is selected firstly the device type can be changed:

WARNING: SETTINGS WILL BE DEFAULT


EXCEPT ZONE NUMBER AND DESCRIPTOR
PROCEED WITH CHANGE
◄BACK 1:YES

If the device type is changed this confirmation screen is displayed:

35
ODYSSEY OPERATION & ONSITE PROGRAMMING
TYPE: <device type>
1 DEVICE
2►SUB ADDRESS
NEXT►

If the device type has sub-address inputs or outputs this screen is displayed next:

SELECT SUB ADDRESS: 1


<selected sub address descriptor>
1►I/P1 2:I/P2 3:I/P3 4:O/P1 5:O/P2
6:O/P3

Select 2 SUB ADDRESS and pressing NEXT► displays the generic sub-address selection screen:

EDIT DESCRIPTOR
LOOP 1 DEVICE 1 INPUT 1_
#CLEAR DEL▲
◄BACK NEXT►

Select one of the sub inputs and press enter to edit the input configuration.

ENTER ZONE NUMBER: 1_

◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT ACTION TYPE: FIRE

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

INPUT TYPE: NON-LATCHING

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT CONTACT STATE: NORMALLY OPEN

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

SUPERVISED: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT PRE-DELAY: 0 (0-90 seconds)

#CLEAR DEL▲
◄BACK NEXT►

Press NEXT► to go to the next field.


The user is then prompted to save any changes that may have been made.
7.6.2.5 Menu->Programming->Device->Edit – Sub Output
36
ODYSSEY OPERATION & ONSITE PROGRAMMING
EDIT DEVICE TYPE: <device type>

CHANGE▼
◄BACK NEXT►

Once the device is selected firstly the device type can be changed:

WARNING: SETTINGS WILL BE DEFAULT


EXCEPT ZONE NUMBER AND DESCRIPTOR
PROCEED WITH CHANGE
◄BACK 1:YES

If the device type is changed this confirmation screen is displayed:

TYPE: <device type>


1 DEVICE
2►SUB ADDRESS

If the device type has sub-address inputs or outputs the following screen is displayed next:

SELECT SUB ADDRESS: 4


<selected sub address descriptor>
1:I/P1 2:I/P2 3:I/P3 4►O/P1 5:O/P2
6:O/P3

Select 2 SUB ADDRESS and pressing NEXT► displays the generic sub-address selection screen:

EDIT DESCRIPTOR
LOOP 1 DEVICE 1 OUTPUT 1_
#CLEAR DEL▲
◄BACK NEXT►

Select one of the sub outputs and press enter to edit the output configuration.

ENTER ZONE NUMBER: 1_

◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT ACTION TYPE: NONE

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

GLOBAL ACTION: <action type>


ENABLED
CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

ZONE ACTION: <action type>


ENABLED
CHANGE▼
◄BACK NEXT►

Press CHANGE▼ to enable or disable the displayed global action. Press NEXT► to go to the next
global action setting.

37
ODYSSEY OPERATION & ONSITE PROGRAMMING
NORMALLY ENERGISED: DISABLED

CHANGE▼
◄BACK NEXT►

Press CHANGE▼ to enable or disable the displayed zone action. Press NEXT► to go to the next
zone action setting.

RESPOND TO ALERT/EVAC: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

RESPOND TO CLASS CHANGE: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT POST-DELAY: 0 (0-999 seconds)

#CLEAR
◄BACK NEXT►

Press NEXT► to go to the next field.


The user is then prompted to save any changes if they have been made.
7.6.3 Menu->Programming->Panel

PANEL MENU
1►INPUT 3|LOOP
2|OUTPUT 4|DESCRIPTOR

Panel Inputs, Outputs, Loops and normal screen descriptors can be programmed from this menu.
7.6.3.1 Menu->Programming->Panel->Input

SELECT INPUT: 1 PANEL INPUT


<input descriptor>
►I/P1 I/P2 I/P3 I/P4

The user may select 1 of 4 panel inputs.

EDIT DESCRIPTOR
DIGITAL INPUT 1_
#CLEAR DEL▲
◄BACK NEXT►

Select desired input and press enter to edit it configuration settings.

ENTER ZONE NUMBER: 1_

#CLEAR DEL▲
◄BACK NEXT►

Press NEXT► to go to the next field.

38
ODYSSEY OPERATION & ONSITE PROGRAMMING
EDIT ACTION TYPE: FIRE

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

INPUT TYPE: NON-LATCHING

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT CONTACT STATE: NORMALLY OPEN

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

SUPERVISED: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

EDIT PRE-DELAY: 0 (0-90 seconds)

#CLEAR DEL▲
◄BACK NEXT►

Press NEXT► to go to the next field.


The user shall then be prompted to save any changes if they have been made.
7.6.3.2 Menu->Programming->Panel->Output

PANEL OUTPUT MENU


1►SUPERVISED O/P 3|OPEN COLLECTOR O/P
2|RELAY O/P 4|AUXILIARY O/P

The user may select between the four types of panel outputs.

SELECT OUTPUT: X <output type>


<output descriptor>
►O/P1 O/P2 O/P3 O/P4

There are 4 Supervised Outputs, 3 Relay Outputs, 2 Open Collector Outputs and 2 Auxiliary Outputs
to choose from.
Depending on the output type selected, the number of available outputs shall be displayed on the
generic output point selection this screen

EDIT DESCRIPTOR
<output descriptor>_
#CLEAR DEL▲
◄BACK NEXT►

Press enter to edit the selected output configuration settings.

39
ODYSSEY OPERATION & ONSITE PROGRAMMING
ENTER ZONE NUMBER: 1_

#CLEAR DEL▲
◄BACK NEXT►

Press NEXT► to go to the next field.

FIXED ACTIVATION: NONE

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

OUTPUT TYPE: SOUNDER

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

GLOBAL ACTION: <action type>


ENABLED
CHANGE▼
◄BACK NEXT►

Press CHANGE▼ to enable or disable the displayed global action.


Press NEXT► to go to the next field.

ZONE ACTION: <action type>


ENABLED
CHANGE▼
◄BACK NEXT►

Press CHANGE▼ to enable or disable the displayed zone action.


Press NEXT► to go to the next zone action setting.

NORMALLY ENERGISED: DISABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

SILENCEABLE: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

RESPOND TO ALERT/EVAC: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.

RESPOND TO CLASS CHANGE: ENABLED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.


40
ODYSSEY OPERATION & ONSITE PROGRAMMING
EDIT POST-DELAY: 0 (0-999 seconds)

#CLEAR
◄BACK NEXT►

Press NEXT► to go to the next field.


The user is then prompted to save any changes that may have been made.
7.6.3.3 Menu->Programming->Panel->Loop

SELECT LOOP: X
<selected loop descriptor>
►L1 L2

If there is more then one loop the user is prompted to select the loop using the generic loop selection
screen.

EDIT DESCRIPTOR
LOOP 1_
#CLEAR DEL▲
◄BACK NEXT►

Press enter to edit the selected Loop configuration settings.

LOOP X TERMINATION: SINGLE-ENDED

CHANGE▼
◄BACK NEXT►

Press NEXT► to go to the next field.


The user is then prompted to save any changes that may have been made.
7.6.3.4 Menu->Programming->Panel->Descriptor

EDIT CUSTOM BANNER 1


EUROTECH TECHNOLOGIES PTY. LTD._
#CLEAR DEL▲
◄BACK NEXT►

The user may modify the two descriptors displayed on the normal screen

EDIT CUSTOM BANNER 2


ODYSSEY (C) 2008_
#CLEAR DEL▲
◄BACK NEXT►

Press NEXT► to go to the next descriptor.


The user is then prompted to save any changes that may have been made.
7.6.4 Menu->Programming->Sounders

SOUNDER MENU
1►GLOBAL ACTIVATION
2|ZONE ACTIVATION

This menu allows programming of the Zone and Global activation settings for sounders.
7.6.4.1 Menu->Programming->Sounders->Global Activation

GLOBAL <action type>


ACTIVATION MODE: EVACUATE
CHANGE▼
◄BACK NEXT►

The activation mode for each Global action type can be selected.
41
ODYSSEY OPERATION & ONSITE PROGRAMMING
The activation mode choices are:
 EVACUATE
 ALERT
 ALERT TIMEOUT EVACUATE
 DELAYED

GLOBAL <action type>


ACTIVATION DELAY: 30 (0-999 Sec)
#CLEAR
◄BACK NEXT►

The activation mode screens are repeated for all action types in which the delays can be edited
The user is then prompted to save any changes that may have been made.
7.6.4.2 Menu->Programming->Sounders->Zone Activation

SELECT ZONE: XXX


<selected zone descriptor>
►Z1 Z2 Z3 Z4 Z5
Z6 Z7 Z8 Z9 Z10

The user is first prompted to select the Zone number to be configured.


Press enter to continue.

ZONE <action type>


ACTIVATION MODE: EVACUATE
CHANGE▼
◄BACK NEXT►

The activation mode for each Zone action type can then be selected.
The activation mode choices are:
 EVACUATE
 ALERT
 ALERT TIMEOUT EVACUATE
 DELAYED

ZONE <action type>


ACTIVATION DELAY: 30 (0-999 SEC )
#CLEAR
◄BACK NEXT►

The activation mode screens are repeated for all action types in which the delays can be edited.
The user is then prompted to save any changes that may have been made.
7.6.5 Menu->Programming->Learn Options

LEARN OPTIONS MENU


1►AUTO LEARN 3|MISMATCHED DEVICES
2|EXTRA DEVICES 4|MISSING DEVICES

 Auto Learn can be used to learn all Loops, Loop Devices, Panel Inputs and outputs
connected to the system and store the default configuration for all these points
 Mismatched Devices is used to resolve any detected loop devices that do not match the
configuration
 Extra Devices is used to learn any newly detected loop devices that do not exist in the
configuration
 Missing Devices is used to remove any device that exist in the configuration but are
removed from physical connection to the loop
7.6.5.1 Menu->Programming->Learn Options->Auto Learn
Selecting Auto Learn firstly prompts for confirmation.

42
ODYSSEY OPERATION & ONSITE PROGRAMMING
AUTO LEARN
CONFIGURATION WILL BE CHANGED
ARE YOU SURE?
◄BACK 1:YES

Select 1 to confirm.

AUTO LEARN
INITIALISING PLEASE WAIT

◄BACK NEXT►

While the Auto Learn sequence is initialising all system functions cease, and the panel is prepared
for Auto Learn.

AUTO LEARN IN PROGRESS


<----->

◄BACK

The Auto Learn in Progress screen is displayed while all devices have been learnt.
Upon completion the panel will restart with the newly learnt configuration.

 Note: If an Auto Learn is executed the Auto-Learn Defaults for devices is outlined in section 8
Compatible Devices
7.6.5.2 Menu->Programming->Learn Options->Extra Devices

Zzzz Ppp Lll Dddd.s <status>


TYPE: <detected type>
EXTRA DEVICES XXX OF XXX
◄BACK 1:LEARN 2:LEARN ALL

If extra devices are detected on the system, the following screen is displayed.
Here the user may select to learn the individual extra device currently being displayed or all extra
devices detected.

NO EXTRA DEVICES DETECTED

If no extra devices were detected the following screen is displayed for a short period before returning
to the previous menu.
7.6.5.3 Menu->Programming->Learn Options->Mismatched Devices
If mismatched devices are detected on the system, the following screen is displayed.

Zzzz Ppp Lll Dddd.s <detected type>


CONFIGURED TYPE: <device type>
MISMATCHED DEVICES XXX OF XXX
◄BACK 1:RESOLVE 2:RESOLVE ALL

Here the user may select to resolve the individual device mismatch currently being displayed or all
mismatched devices detected.

NO MISMATCHED DEVICES DETECTED

If no mismatched devices were detected the following screen is displayed for a short period before
returning to the previous menu.
7.6.5.4 Menu->Programming->Learn Options->Missing Devices
43
ODYSSEY OPERATION & ONSITE PROGRAMMING
If devices in the system are missing, the following screen is displayed.
Here the user may select to delete the individual device from the configuration currently being
displayed or all missing devices.

Zzzz Ppp Ll Dddd.s <status>


CONFIGURED TYPE: <device type>
MISSING DEVICES XXX OF XXX
◄BACK 1:DELETE 2:DELETE ALL

If no missing devices were detected the following screen is displayed for a short period before
returning to the previous menu.

NO MISSING DEVICES DETECTED

7.6.6 Menu->Programming->Version
The date and time is updated by the PC configuration tool upon alteration of the configuration
information when saving and is also updated at the panel when configuration changes are made via
programming.
The Configuration Major Version is incremented by the PC upon alteration of the configuration
information when saving. When this occurs the Configuration Minor Version shall be cleared to zero.
If the Major or Minor version reaches 65535 it shall remain at this value unless reset by user
intervention using the PC tool. The Configuration Minor Version shall be incremented upon alteration
of the configuration at the panel via programming. Also, the major version shall default to 1 and
minor version default to 0 upon auto learn at the panel

SITE CONFIGURATION DATA


LAST MODIFIED: <date> <time>
VERSION: <major>.<minor>
◄BACK

44
ODYSSEY OPERATION & ONSITE PROGRAMMING
7.7 Event Logging
Events are logged into one of eight event type categories. Individual storage is pre-allocated for each
event type amounting to a total of 1000 events:
Event Type Maximum Capacity
Fire 100
Fault 200
Disable 100
Pre-Alarm 100
Emergency 100
Security 100
User 100
System 200
If an event exceeds the maximum capacity for that type the oldest event will be discarded allowing
the most recent event to be stored.
Events that are logged may contain the following attributes:
 Event Type
 Event Status
 Date/Time of occurrence
 Event Origin
 Active Password ID (stored with event origin)
 Checksum
The system event log contains system input action type events as well as the following system
events:
 Loop Test with password ID
 Walk Test with password ID
 Lamp Test with password ID
 Override key press with password ID
 Silence/Resound key press with password ID
 Reset key press with password ID
 Evacuate key press with password ID
 Access Level change with password ID
The fault event log contains input action type fault events as well as all reported faults within the
FACP. The disable event log contains all reported system disables. All other event types are only
logged according to their assigned input action type events.

Note: The Transparent action type is not logged.


The events are viewed by individual type or collectively. The events can be printed or erased by
individual entry, range by date/time, range by entry number, and all by entry number. Each event
type can also be disabled or enabled.
All events can be uploaded using the PC configuration software which will format the event record to
be viewable using Microsoft Excel or a standard text editor.

45
ODYSSEY OPERATION & ONSITE PROGRAMMING
8. Compatible Devices
Note: If an Auto Learn is executed the Auto-Learn Defaults are also listed below
Auto
EUROTECH Type
Learn Device Type Displayed Type (19 chars)
Type Code Desc
Default

Optical
05h  XP95 Optical XP95 PHOTO PHOTO
05h XP95 Optical with base sounder XP95 PHOTO + SNDR PHOTO
05h XPander Optical XPANDER PHOTO PHOTO
05h S90 Optical S90 PHOTO PHOTO
05h Xplorer Optical XPLORER PHOTO PHOTO
05h Xplorer Optical with base sounder XPLR PHOTO + SNDR PHOTO
05h XP95 Beam XP95 BEAM PHOTO
0Dh  XP95 Reflective beam XP95 REFLECT BEAM BEAM
105h  Discovery Optical DISC PHOTO PHOTO
105h Discovery Optical with base sounder DISC PHOTO + SNDR PHOTO
11Dh  Discovery Multisensor DISC MULTISENSOR MULTI
11Dh Discovery Multisensor with base sounder DISC MULTI + SNDR MULTI
15h  XP95 Flame XP95 FLAME FLAME
1Dh  XP95 Multisensor XP95 MULTISENSOR MULTI
1Dh XP95 Multisensor with base sounder XP95 MULTI + SNDR MULTI
1Dh XPander Multisensor XPANDER MULTI MULTI
31Dh  Enhanced Discovery Multisensor EDSC MULTISENSOR MULTI
31Dh Enhanced Discovery Multi + base sounder EDSC MULTI + SNDR MULTI

Heat Detectors
06h  XP95 Heat XP95 HEAT HEAT
06h XP95 Heat with base sounder XP95 HEAT + SNDR HEAT
06h XPander Heat XPANDER HEAT HEAT
06h S90 Heat S90 HEAT HEAT
06h Xplorer Heat XPLORER HEAT HEAT
06h Xplorer Heat with base sounder XPLR HEAT + SNDR HEAT
0Eh  XP95 Hi temp XP95 HI HEAT HHEAT
0Eh XP95 Hi temp with base sounder XP95 HI HEAT + SNDR HHEAT
0Eh XPander Hi temp XPANDER HI HEAT HHEAT
0Eh Xplorer Hi temp XPLORER HI HEAT HHEAT
0Eh Xplorer Hi temp with base sounder XPLR HI HEAT + SNDR HHEAT
106h  Discovery Heat DISC HEAT HEAT
106h Discovery Heat with base sounder DISC HEAT + SNDR HEAT

Ionisation
03h  XP95 Ion XP95 ION ION
03h XP95 Ion with base sounder XP95 ION + SNDR ION
03h S90 Ion S90 ION ION
103h  Discovery Ion DISC ION ION
103h Discovery Ion with base sounder DISC ION + SNDR ION
10Bh  Discovery Carbon Monoxide DISC CO CO
10Bh Discovery Carbon Monoxide with base DISC CO + SNDR CO
46
ODYSSEY OPERATION & ONSITE PROGRAMMING
sndr

Manual Call Points


07h  S90 MCP S90 MCP MCP
11Fh  Discovery MCP DISC MCP MCP
1Fh  XP95 MCP XP95 MCP MCP
1Fh XPander MCP XPANDER MCP MCP
1Fh XP95 Mini switch monitor with interrupt XP95 MINI SW + INT MCP
1Fh Xplorer MCP XPLORER MCP MCP

Sounders
01h  XP95 sounder / sounder control unit XP95 SOUNDER SNDR
01h XPander sounder XPANDER SOUNDER SNDR
01h XP95 integrated base sounder XP95 INTGR BSE SNDR SNDR
01h XP95 Intelligent base sounder XP95 INTEL BSE SNDR SNDR
01h XP95 sounder beacon base XP95 SND BEACN BSE SNDR
01h XP95 loop powered beacon XP95 LOOP PWR BEACN SNDR
01h S90 sounder control unit S90 SCU SNDR
Discovery sounder beacon base/open
111h  DISC SOUNDER BEACN SNDR
area

I/O Units
02h  XP95 input / output module XP95 I/O I/O
02h XPander I/O (Relay) Unit XPANDER I/O I/O
02h XP95 three channel input / output module XP95 3I/O I/O
02h XP95 output module XP95 OUTPUT I/O
XP95 mains switching input / output
02h XP95 MAINS I/O I/O
module
02h S90 single channel I/O unit S90 SINGLE I/O I/O
02h S90 3 channel I/O unit S90 3I/O I/O
02h S90 3 channel analogue I/O unit S90 3I/O + ANALOGUE I/O
02h S90 switch monitor unit S90 SWITCH I/O
02h Xplorer output module XPLORER OUTPUT I/O

Zone Monitors
04h  XP95 zone monitor XP95 ZONE MONITOR CONV
04h XPander Loop Interface XPANDER INTERFACE RADIO
04h S90 zone monitor S90 ZONE MONITOR CONV

0Ch  XP95 switch monitor XP95 SWITCH SWITCH


0Ch XP95 mini switch monitor XP95 MINI SWITCH SWITCH
0Ch XP95 switch monitor plus XP95 SWITCH PLUS SWITCH

1Ch  FastSense XP95 APIC XP95 FASTSENSE FSENSE

User Defined
10h  XP95 AAF XP95 AAF AAF

47
1
DISPLAY
1 2 3 4 5 6 7 8 9
FIRE FAULT PRE-ALARM EMERGENCY SECURITY USER DISABLE TEST ABOUT
2
CONTROL
1 2
ZONE DEVICE
ODYSSEY

1 2 3 4 1 2
NOTE: SUB ADDR AND REM O/P DEPEND
DISABLE INPUTS DISABLE SOUNDERS SILENT WALK TEST WALK TEST DEVICE> INPUT
L1 L2 ON THE SELECTED DEVICE
*1 *2 1 2 3 1 2 3 4
DISABLE ALL INPUTS DISABLE NON-MCP's DISABLE ON PRINT DISABLE SUB ADDR / REM O/P PRINT ALARM LED ON
DEVICE
*Note: Only If MCP's Present 1 2 3 4 NON 1 2 3
SOUNDER
DISABLE SUB ADDR / REM O/P PRINT ALARM LED ON DISABLE ON PRINT
NOTE: SUB ADDR AND REM O/P DEPEND 1 2 3 1 2 3 4
ON THE SELECTED DEVICE SOUNDER
DISABLE ON PRINT DISABLE ALERT EVAC PRINT

3 NOTE: DELAY MODE (7) MENU IS ONLY ACCESSIBLE IF 4


PANEL INVESTIGATION DELAYS ARE CONFIGURED GLOBAL CONTROL
1 2 3 4 5 6 7
INPUT OUTPUT ADD-ON LOOP PRINTER POWER DELAY MODE
1 2 3 4 1 2 3 4 1 2 1
SELECT ON-LINE / FIRE MODE /
SUPERVISED O/P RELAY O/P OPEN COLLECTOR O/P AUXILIARY O/P ADD-ON TYPE DISABLE TEST PRNT ALL PRNT TYPES OFF-LINE EVENT MODE ON / OFF
9. Complete Menu Structure

NON 1 2 3 1 2 3 1 2 3 4 5
SOUNDER
DISABLE ON PRINT DISABLE I/O PRINT DISABLE SOUNDERS ENABLE SOUNDERS GLOBAL ENABLE REMOVE MANUAL I/O REMOVE WALK TESTS
1 2 3 4 NON 1 2 3
SOUNDER SOUNDER
DISABLE ALERT EVAC PRINT DISABLE ON PRINT
1 2 3 1 2 3 4
SOUNDER
DISABLE ON PRINT DISABLE ALERT EVAC PRINT
3

48
EVENTS
1 2 3 4 5 6 7 8 9
ALL FIRE FAULT PRE-ALARM EMERGENCY SECURITY USER SYSTEM DISABLE
LOOPSENSE MENU TREE
1 2 3
PRINT DELETE GOTO NOTE:
1: At Access Level 1, the entire menu is not accessible.
1 2 3 4 1 2 3 2: At Access Level 2, the DISPLAY, CONTROL, EVENTS and TOOLS menus are accessible.
CURRENT ENTRY ALL RANGE BY DATE RANGE BY ENTRY No MOST RECENT BY DATE BY ENTRY SETUP(*) and PROGRAMMING(*) are not accessible. Also, indivdual Sounder Disablements
4 via the control menu are not accessible at Access Level 2. The user shall be presented with the
TOOLS ENTER PASSWORD screen when trying to access a higher level function..
1 2 3: At access level 3, all options are available
DIRTY DEVICES LOOP STATISTICS
1 2 3 1 2 = ACCESS LEVEL 2
LOW% MED% HIGH% L1 L2
= ACCESS LEVEL 3
1
RESET COUNT
5
SETUP (*)
OPERATION & ONSITE PROGRAMMING

1 2 3 4
DATE AND TIME DAY/NIGHT EARTH MON PASSWORDS
1 2 3 4 5 1 2 3 4 5 6 7 6 7 1 2
DAYLIGHT SAVE
DATE DATE FORMAT ON / OFF TIME TIME FORMAT SUNDAY MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SET ALL DISABLE/ENABLE ID1 ID2
6
PROGRAMMING (*)
1 2 3 4 5 6
ZONE DEVICE PANEL SOUNDERS LEARN OPTIONS VERSION
1 2 2 1 2 3 4 1 2 1 2 3 4
GLOBAL ZONE
ADD DELETE EDIT INPUT OUTPUT LOOP DESCRIPTOR ACTIVATION ACTIVATION AUTO LEARN EXTRA DEVICES MISMATCHED DEVICES MISSING DEVICES
1 2 1 1 2 1 2 1 2
L1 L2 YES LEARN LEARN ALL RESOLVE RESOLVE ALL DELETE DELETE ALL
1 2 3 4
SUPERVISED O/P RELAY O/P OPEN COLLECTOR O/P AUXILIARY O/P
0832

Ampac Technologies Ltd


7 Ledgar Road Balcatta, Western Australia, 6021

09
0832-CPD-1288

EN54-2 & 4 1997 including amendments 1 & 2

Control and Indicating equipment and Power Supply equipment for fire detection and
fire alarm systems for buildings

8281-0105 1 Loop 32 Zone analogue addressable control and


indicating equipment
8281-0205 1 Loop 32 Zone analogue addressable control and
indicating equipment

Provided options:
Output to fire alarm devices
Output to fire alarm routing equipment
Alarm confirmation input from fire alarm routing equipment
Delay to outputs
Dependencies on more than one alarm signal – Type A
Dependencies on more than one alarm signal – Type B
Dependencies on more than one alarm signal – Type C
Fault signal from point
Output to fault warning routing equipment
Disablement of each addressable point
Test condition

UNCONTROLLED DOCUMENT
NOTE: Due to our commitment to continuous improvement specifications may change without notice.

You might also like