Automatic Instrument Transformer Test Set: Features

The document describes an automatic instrument transformer test set that can test current and voltage transformers with a single instrument. It fully automatically measures current/voltage ratio errors, phase displacement, test current and voltage. It has a simple interface and high accuracy, and meets various international standards for testing instrument transformers.

Uploaded by

Dimitar Markov
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views

Automatic Instrument Transformer Test Set: Features

The document describes an automatic instrument transformer test set that can test current and voltage transformers with a single instrument. It fully automatically measures current/voltage ratio errors, phase displacement, test current and voltage. It has a simple interface and high accuracy, and meets various international standards for testing instrument transformers.

Uploaded by

Dimitar Markov
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

2763 / 2767 / 2769

Automatic Instrument Transformer Test Set

 The type 2767 automatic current and voltage FEATURES


transformer test set is a modern, fully automatic
instrument for fast, accurate measurement of  Current and voltage transformer measurements with a
instrument transformer errors. Increasingly severe single instrument
quality control requirements call for a higher degree of  Fully automatic measurement and digital display of
operating comfort and absolute reliability of the current/voltage ratio errors, phase displacement, test
measuring equipment employed. Based on the latest current and voltage
design technology, this instrument sets new standards
of quality, reliability, convenient operation and simple
 Measurements are possible on instrument
transformers of practically any primary and secondary
maintenance. current and voltage ratings
Its measurement ranges for current/voltage errors,  Test & standard transformers may have different ratios
phase displacement and current/ voltage excitation are  A cost-effective solution:
fully up to international standard requirements.  Different transformers can be tested using one
single standard transformer
This measuring instrument has been tested by PTB  Different standard and test transformer ratios
(Physical Technical Federal Authority) in Germany. It are matched without use of an external divider
fulfills all requirements according to the PTB test rules  Interactive parameter entry simplifies operation
for measuring instrument transformers and is approved
for calibration  Plain-language display of error messages on a 2 x 16
character dot-matrix
OPTIONS  Short measurement times, and dynamic averaging
 High accuracy, and low inherent burden
 For remote-controlled measurement - IEEE 488
interface
 Connection for external printer (RS 232 interface)
 Wide range of accessories (see order specification)  Specifications conform to the standards/
recommendations of IEC 60044-1, IEC 60044-2; IEC
60044-3; IEC 60044-7, ANSI/IEEE C57.13-1978 and
DESIGNED FOR USE IN: VDE 0414, part 2
 Including RS 232 interface for computer connection
 For remote-controlled measurement - IEEE 488
interface
 Laboratories COMPLETE MEASUREMENT SYSTEMS
 Manufacturing processes HAEFELY HIPOTRONICS also designs and supplies
 Quality control procedures computer controlled current and voltage transformer
 Official tetrology stations measurement facilities for specific customer requirements.
 Type 2767 combined test set for current and voltage
instrument transformers
 Series 4760 standard current transformer (current
comparator)
 Type 2763 is a test set for current instrument
transformers only
 Type 2769 is a test set for voltage instrument
transformers only
 Series 4820 standard voltage instrument transformer or
series 4860 electronic standard voltage divider with
high-voltage capacitive divider
 Type 3691 or 3695 programmable electronic burden or
series 3600 passive burdens
 In addition, TETTEX INSTRUMENTS can supply all
necessary peripherals (e.g. computer and printer) for
external control and data recovery.
 Series 5260 current supply
 Series 5270 voltage supply
 Series 8860 heavy-current connection cables

1/4
TECHNICAL SPECIFICATIONS

The type 2767 test set measures transformer ratio Permissible limits for k
errors by the differential method. A major advantage of
ISXR max. accuracy reduced accuracy
this is that balancing of winding turns at the differential
transformer (current comparator) and compensation 5A 0.5 ≤ k ≤ 1.6 –
via an additional winding enable fully accurate 2A 1.6 ≤ k ≤ 3 –
measurement although the test and standard 1A 3 ≤ k ≤ 10 10 < k  25
transformer have different ratios. 0.1 A 25 ≤ k ≤ 100 100 < k ≤ 500

Measurements are initiated simply by entering the Ratio matching factorof test and standard transformers
rated test and standard transformer data, for which the (correction)
built-in microprocessor has a particularly convenient
man-machine interface. Current or voltage errors,
phase displacement, test current or test voltage are
measured continuously and displayed in digital form.
All entered values for IPR and ISR are checked and the
A dynamic averaging facility is provided for optimum input parameters (NX, NN), are set by a
measurements at low current or voltage, which microprocessor.
ensures that accuracy and display stability are
maintained even at poor signal/noise ratios. Input limit values
 Rated primary current
Test circuit for current instrument: IPXR, IPNR 50 mA ... 1000 kA
 Rated secondary current
lSXR, ISNR 50 mA … 5 A
(continuously adjustable)

2. VOLTAGE TRANSFORMER MEASUREMENT PART


X and N-inputs
(test and standard transformers)
 Rated secondary voltage (max. rated range
values)
USXR, USNR 140, 300 V
additional with factors x 1/√3, x 1/3

 Max. operating range (USX, USN)


at USXR = 3... 140 V : 3 … 280 V
> 140 ... 300 V : 10 ... 400 V

 Inherent burden
at USXR, USNR = 100 V < 1 VA
140 V < 0.5 VA

Ratio matching factor


of test and standard transformers (correction)

1. CURRENT TRANSFORMER MEASUREMENT


PART
X-input (test transformer) Permissible limits for k
 Rated secondary currents  at max. accuracy 0.5  k  2
ISXR 0.1 - 1 - 2 - 5A  at reduced accuracy 2  k  10
 Max. operating range 1 … 210 % ISXR
 Inherent burden < 1 VA All entered values for UPR and USR are checked and the
(at rated current) optimum input parameters (NN, RX, RN) are set by a
microprocessor.
N-input (standard transformer) Input limit values
 Rated secondary current ISNR 5A  Rated primary voltage
 Max. operating range 1… 210 % ISNR UPXR, UPNR 3 V ... 10’000 kV
 Rated secondary voltage
 Inherent burden < 2.5 VA USXR, USNR 3 ... 300 V
(at rated current) (continuously adjustable)

2/4
DISPLAYS
Test circuit for voltage instrument transformer
6-digit LCD measured-value displays (height 18 mm) of:
RATIO ERROR (current / voltage error)
PHASE ANGLE (phase displacement)
EXCITATION (test current / voltage)
LCD dot-matrix, 2 x16 characters (height 7 mm) for
measurement frequency, entry instructions and error
messages

Mains supply 230 V or 115 V,


50/60 Hz
Power input approx. 35 VA
Temperature range + 5 ... + 40 C
Dimensions 500 x 310 x 470 mm
(W x H x D) (19.7 x 12.2 x 18.5 in)
Temperature Range +5 to +40°C
Humidity 5 to 80% r.h. non condensing

Weight 40 kg (88 Ib)


This instrument is designed in accordance with the safety
requirements of VDE 0411 /part 1 and IEC 348 (safety class
3. CURRENT AND VOLTAGE TRANSFORMER 1).
MEASUREMENT PART
Measurement ranges for
current/voltage errors (RATIO ERROR)
and Ratio Correction Factor (RCF)

Display of F [%] or RCF as required

Conversion

Measurement ranges for phase displacement (PHASE


ANGLE)

Display of [min] or [crad], as required.


Conversion 1 crad = 34.4 min

Current measurement ranges (EXITATION)


Display of test specimen current IPX or ISX as absolute
values in [A] or [%] of rated current.

Voltage measurement ranges (EXCITATION) Limits of error at current transformer measurements


Display of test specimen voltage UPX or USX as For operating range 1 ... 210 % of rated current
absolute values in [V] or [%] of rated voltage. Measurement frequency 50 or 60 Hz
Reference conditions as per IEC 359
Resolution
Current/voltage error 0.0001%
-6 Limits of error at voltage transformer measurements
= 1x10 (1ppm)
For operating range Usp = 3 ... 400 V
Phase angle  0.001 min
or 0.0001 crad Measurement frequency 50 or 60 Hz
Test current 0.001 A Reference conditions as per IEC 359
or 0.1 % ISNR
Test voltage 0.1 V Explanation of limit of errors specification
or 0.1 % USNR ... % rdg = % error of reading
... % fs = % error of value full-scale
Measurement frequency 0.1 Hz
The above limits of error also apply for test and standard
Measurement frequency ranges transformers of different ratios. Limits of error at rated
15…18 Hz/ 45 … 65 Hz operating conditions see specifications as per instruction
manual. Reference and rated operating conditions as per
Measurement times at 50 Hz IEC 359, rated range of use 1.
First measurement <3s
Subsequent measurements <1s

3/4
Example of a test certificate:

ORDER SPECIFICATIONS
STANDARD SUPPLY OTHER OPTIONAL SUPPLIES
Type 2767 automatic instrument current and voltage  Cable data-link for
transformer test set in a 19" case (including RS 232C RS 232C interface, 3 m type 5991
printer interface).
 Bus cable for
 Ground cable 2
16 mm , 10 m IEEE 488 interface, 4 m type 5993
 Power cable  Standard current transformers (current comparators),
current ratings as follows:
 Mains 230 or 115 V;
50/60 Hz  up to 1’000 A/1- 5A type 4761
 up to 5’000 A/1- 5 A type 4764
(please specify with order)
 up to 10’000 A/100 A *) type 4766
 Including RS 232C interface type 2767/2
 up to 100 kA/ 100 A *) series 4760
 Type 2763 is a test set for current
instrument transformers only *) In addition to type 4764
 Type 2769 is a test set for voltage  Standard voltage transformers
instrument transformers only up to 220 kV/100V series 4820
 Electronic standard voltage divider series 4860
OPTIONS FOR TYPE 2767/2763/2769  Programmable electronic
For remote control by external computer: current burden type 3691

 IEEE 488 interface type 2767/1  Programmable electronic


voltage burden type 3695
 Current and voltage passive burdens
(to VDE and ANSI/IEEE standards) series 3600
 Current supplies (up to 10 kA) series 5260
 High-voltage supplies series 5270
 Heavy-current connection cables series 8860
 Set of spare parts (type 2767) no. 016695-00

OFFICES:
Europe China North America
Haefely Test AG Haefely Test AG Representative Beijing Office Hipotronics, Inc.
Birsstrasse 300 8-1-602, Fortune Street 1650 Route 22 N
4052 Basel No. 67, Chaoyang Road, Chaoyang District Brewster, NY 10509
Switzerland Beijing, China 100025 United States

 + 41 61 373 4111  + 86 10 8578 8099  + 1 845 279 3644


 + 41 61 373 4912  + 86 10 8578 9908  + 1 845 279 2467
[email protected][email protected][email protected]

HAEFELY HIPOTRONICS has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.

4/4

You might also like