0% found this document useful (0 votes)
123 views

Power Tranducer LSMT2

This document provides information on the Power Transducer Series L-UNIT model LSMT2. It can convert power factors into 10 analog outputs or 1 pulse output using Modbus. It has a compact DIN rail design and allows free selection and assignment of measuring items to output channels. The LSMT2 has options for voltage input range, current input range, auxiliary power supply, and output types.

Uploaded by

dani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views

Power Tranducer LSMT2

This document provides information on the Power Transducer Series L-UNIT model LSMT2. It can convert power factors into 10 analog outputs or 1 pulse output using Modbus. It has a compact DIN rail design and allows free selection and assignment of measuring items to output channels. The LSMT2 has options for voltage input range, current input range, auxiliary power supply, and output types.

Uploaded by

dani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Power Transducer Series L-UNIT

MULTI POWER TRANSDUCER MODEL LSMT2


MODEL & SUFFIX CODE SELECTION
120 (4.72)

LSMT2–❑❑❑❑❑❑–❑
MODEL
CONFIGURATION 100
1 : 3-phase / 3-wire (See P. 5/10) (3.94)

2 : Single-phase / 2-wire (See P. 7/10)


3 : Single-phase / 3-wire (See P. 8/10) 128
4 : 3-phase / 4-wire (See P. 9/10) (5.04)
mm (inch)
VOLTAGE INPUT
0 : None Functions & Features
1 : 110V AC • Converting all major factors required for power
2 : 220V AC management into DC outputs • Compact design •
4 : 380V AC 10 analog outputs and 1 Wh pulse output or Modbus
A : 100V / 200V AC output • Saving wiring space • DIN rail mounting
CURRENT INPUT • Free selection of measuring items, assigned to any
0 : None output channel • Transducer input range is
1 : 1A AC selectable with Watt, Var, Power Factor or Fre-
5 : 5A AC quency • Linear output for bidirectional current for
ZERO-PHASE VOLTAGE INPUT Var and Power Factor • Output characteristics can
0 : None be changed according to Lag/Lead for Var and Power
1 : 110V AC Factor
2 : 190V AC Typical Applications
DC OUTPUT • Monitoring panels
Current Voltage
A : 4 – 20mA DC 4 : 0 – 10V DC GENERAL SPECIFICATIONS
G : 0 – 1mA DC 5 : 0 – 5V DC
Construction: stand-alone; terminal access at the front
6 : 1 – 5V DC
Connection
PULSE / NETWORK OUTPUT
Input and aux. supply: M4 screw terminals
0 : None (with zero-phase voltage input selected)
Output: M3.5 screw terminals
1 : Watthours
Screw terminals: nickel-plated brass (torque 0.8 N·m)
M : Modbus
Housing material: flame-resistant resin (black)
AUXILIARY POWER SUPPLY
Isolation: voltage input to current input to DC out-
AC Power DC Power
put or pulse (network) output to aux. sup-
M : 85 – 264V AC R : 24V DC
ply; negatives common to all outputs
V : 48V DC
Computation: digital processor
P : 110V DC
Output range: approx. 0 – 100% at 1 – 5V
ORDERING INFORMATION Zero/span adjustments: ±4% independently adjust-
See later pages of this data sheet for detailed infor- able for each measuring item
mation about availability of the functions for each in- Address setting: 0 – 249 selectable (front; default
put configuration. 001)
The unit is configured at the factory according to the Overrange output limit: high 101%, low -1%
user's specifications, however, measuring items can be (resettable)
freely selected and assigned to up to 10 output chan- Sampling rate: approx. 500 µsec.
nels via the front panel control switches, except V0 : (DO NOT connect directly to inverters.)
zero-phase voltage or MV0 : max. zero-phase voltage
which require specific hardware to be ordered.
The measuring items are listed below:
A = Line current V = Line voltage
W = Watt, active power var = var, reactive power
PF = Power factor Hz = Frequency
V0 = Zero-phase voltage
MV0 = Maximum zero-phase voltage
P. 1 / 10 ES-1954 Rev.6
LSMT2
MODBUS COMMUNICATION •Watt
OUT mA OUT V
Standard: Conforms to RS-485, EIA 20 10

Baud rate: 1200, 2400, 4800, 9600, 19.2k bps


12
selectable (front) 5
Communication: Half-duplex, asynchronous, no
4
procedure INP INP
0
Protocol: Modbus RTU 0
-1000
500
0
1000W
+1000W
0
-1000
500
0
1000W
+1000W
Transmission distance: 500 meters max.
Transmission media: shielded twisted-pair cable •Var
OUT mA OUT V
(CPEV-S 0.9 dia.) 20 10

Refer to the Modbus Protocol Reference Guide (EM-


12
5650) for supported functions. 5

4
INPUT & OUTPUT 1000 0
INP
1000var
0
1000 0
INP
1000var
■INPUT (LEAD) (LAG) (LEAD) (LAG)

•Voltage Input (must be balanced for 3-phase) •Var for Bidirectional Current
Operational range OUT mA
20
OUT V
10
Voltage & active/reactive power: 0 – 110% of rating
12
Power factor & frequency: 90 – 110% of rating 5

Overload capacity: 200% of rating for 10 sec., 4


INP INP
0
1000 0 1000 0 1000var 1000 0 1000 0 1000var
120% continuous (LEAD) (LAG) (LEAD) (LAG) (LEAD) (LAG) (LEAD) (LAG)
REVERSE FLOW DIRECT FLOW REVERSE FLOW DIRECT FLOW
Input burden: ≤0.2VA/phase for 110V AC
≤0.3VA/phase for 220V AC •Power Factor
OUT mA OUT V
≤0.5VA/phase for 380V AC 20 10

12
•Current Input (can be unbalanced for 3-phase) 5
Operational range
4
Current & active/reactive power: 0 – 120% of rating INP INP
0
Power factor: 20 – 120% of rating 0.5
(LEAD)
1 0.5
(LAG)
0.5
(LEAD)
1 0.5
(LAG)
Overload capacity: 4000% of rating for 1 sec., 2000% When the input voltage is zero or the current is the twentieth or less of
for 4 sec., 120% continuous the rating, the output is either equivalent to power factor 1 or
0% or less (selectable).
Input burden: ≤0.3VA/phase
•Power Factor for Bidirectional Current
OUT mA OUT V
20 10
■OUTPUT
•DC Current 12
5

Load resistance 4
INP 0 INP
4 – 20mA : 600 (Ω maximum) 0 1 0 1 0 0 1 0 1 0
(LEAD) (LAG) (LEAD) (LAG) (LEAD) (LAG) (LEAD) (LAG)
0 – 1mA : 10k REVERSE FLOW DIRECT FLOW REVERSE FLOW DIRECT FLOW
OUT mA OUT V
20 10

•DC Voltage 12
5
Load resistance
4
0 – 10V : 1000 (Ω minimum) INP 0 INP
0 0.5 1 0.5 0 0.5 1 0.5 0 0 0.5 1 0.5 0 0.5 1 0.5 0
0 – 5V : 1000 (LEAD) (LAG) (LEAD) (LAG)
REVERSE FLOW DIRECT FLOW
(LEAD) (LAG) (LEAD) (LAG)
REVERSE FLOW DIRECT FLOW
1 – 5V : 1000 When the input voltage is zero or the current is the twentieth or less of
the rating, the output is either equivalent to power factor 1 or
0% or less (selectable).
■I/O CHARACTERISTICS •Frequency
•Voltage •Current OUT mA OUT V
OUT mA OUT V 20 10
20 10

12
12 5
5
4
4 INP INP
0
INP 0 INP 45 55 65Hz 45 55 65Hz
0 150 300V 0 2.5 5A
When the input voltage is the fifth or less of the rating, the output
is equivalent to the input frequency – 2Hz.

Specifications subject to change without notice.


P. 2 / 10 ES-1954 Rev.6
FRONT PANEL CONFIGURATION •Assigning Output Channels
SW1 : ON (Set mode)
SELECT Rotary SW
SW6 : ON (Assign mode)
DATA Display Rotary SW : Choose the output channel.
Control buttons : Watching the DATA display show-
FUNCTION SW
ing measuring item No., press (+) or (–) for changing
1 2 3 4 5 6 7 8 9 10
data.

11 12 13
INSTALLATION

1
2
3
4
5
6
O
F
F
Auxiliary power supply
AC: operational voltage range: 85 – 264V,
14 16 18 20 22 24 26 28 30 32 A C 50/60 Hz, approx. 10VA
15 17 19 21 23 25 27 29 31 33 B DC: operational voltage range: rating ±10%, or
85 – 150V for 110V rating; ripple 10% p-p
Terminator
max.; approx. 10W (90mA at 110V)
Control Buttons Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 40 to 85% RH (non-condensing)
DATA display: green LED; 5 mm (.2 in) Mounting: surface or DIN rail
FUNCTION SW: Used to turn the unit into SET Dimensions: W125×H100×D128 mm (4.72"×3.94"×5.04")
mode and choose functions. Weight: 600 g (1.3 lbs)

SELECT rotary SW: Used to choose output channels,


programmable items, etc. in Set mode. PERFORMANCE in percentage of span
Accuracy
Control buttons: Used to increase (+) / decrease (–)
Voltage, current, watt, var, frequency: ±0.5%
the values, or move forward (+) / back (–) to other
Power factor: ±1.5%
items in Set mode.
Zero-phase voltage: ±1.0%
Continuously pressing the button increases incre-
Max. zero-phase voltage: ±1.0%
mental speed.
Watthours: ±2.0% (load current 5 – 100%, power factor 1.0)
OFF ON ±2.5% (load current 10 – 100%, power
SW1 Run mode Set mode factor 0.5, lag current)
SW2 Output Adj. mode Configure mode Temp. conditioning incl. in the accuray: 23 ±10°C
SW3 Zero adj. Span adj.
(73.4 ±18°F)
SW4 Measured value output Simulated rated value output
Freq. conditioning incl. in the accuracy: rating ±5%
SW5 — —
Response time (0 – 100% ±1%): ≤1 sec.
SW6 Run mode Assign mode
except for zero-phase voltage: ≤0.1 sec.
Terminator: For Modbus communication. Ripple: 1% p-p max.
Auxiliary supply voltage effect: half the accuracy
■PROGRAMMING PROCEDURE (example) over voltage range
•Zero/Span Adjustments Power failure protection: VT/CT ratios, watthours,
SW1 : ON (Set mode) max. zero-phase voltage are stored in the
SW2 : OFF (Output Adj. mode) non-volatile memory.
SW3 : OFF (zero) or ON (span) Insulation resistance: ≥50MΩ with 500V DC
Rotary SW : Choose the output channel. (voltage input to current input to DC
Control buttons : Watching the DATA display show- output to pulse (network) output to aux.
ing adjusted value, press (+) for increasing or (–) for supply to ground)
descreasing the value. Adjustable to ±5%. Dielectric strength: 2000V AC @1 minute
(circuit to ground; voltage input termi-
•Configuration Change (range, lag/lead, etc.) nals to output terminals; aux. supply to
SW1 : ON (Set mode) input or output terminals)
SW2 : ON (Configure mode) 1500V AC @1 minute
Rotary SW : Choose the item to be programmed. (output terminals to ground)
Control buttons : Watching the DATA display show- Surge withstand voltage: 1.2/50 µsec., ±6kV
ing data No., press (+) or (–) for changing data. (circuit to ground; voltage input termi-
nals to output terminals)

P. 3 / 10 ES-1954 Rev.6
LSMT2
CONNECTION DIAGRAM, OUTPUT & AUXILIARY SUPPLY
AUX SUPPLY

11 12 13
E U(+) V(–)

14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 A B C
+ – + – + – + – + – + – + – + – + – + – + – ■Pulse Output
1 2 3 4 5 6 7 8 9 10 11
OUTPUT + – ■Network Output
Output 1 through 10: Analog output
Output 11: Pulse or network output Shielded
Twisted-pair
Cable

To Other
RS-485 Devices

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENT mm (inch)


9.2 (.36) 13–M4 SCREW
4–5 (.2) dia. HOLE

DIN RAIL
1 2 3 4 5 6 7 8 9 10 35 mm wide

11 12 13

35.4 (1.39)
100 (3.94)
90 (3.54)
72 (2.83)

14 16 18 20 22 24 26 28 30 32 A C

15 17 19 21 23 25 27 29 31 33 B

23–M3.5 SCREW
64 (2.52) 7 (.28)
8.2 (.32)
120 (4.72) 128 (5.04) [3.3 (.13)]

MOUNTING REQUIREMENTS mm (inch)

64 (2.52) 4–M4
90 (3.54)

125 (4.92) min.

Specifications subject to change without notice.


P. 4 / 10 ES-1954 Rev.6
3-PHASE / 3-WIRE CONNECTION MODEL LSMT2-1
MODEL & SUFFIX CODE SELECTION INPUT RANGE
•Voltage •Current
LSMT2–1❑❑❑❑❑–❑
RATING RANGE RATING RANGE
MODEL
110V 0 – 150V 1A 0 – 1A
CONFIGURATION
220V 0 – 300V 5A 0 – 5A
1 : 3-phase / 3-wire
VOLTAGE INPUT •Active power
0 : None Input range and ± can be changed via the front panel.
1 : 110V AC RATING RANGE
2 : 220V AC 0 – 100W -100 – +100W
CURRENT INPUT *1 0 – 150W -150 – +150W
110V / 1A
0 : None 0 – 166.6W -166.6 – +166.6W
1 : 1A AC 0 – 200W -200 – +200W
5 : 5A AC 0 – 500W -500 – +500W
*1 : Alternative choice of V0 or current. 0 – 750W -750 – +750W
110V / 5A
ZERO-PHASE VOLTAGE INPUT (V0) *1 0 – 833W -833 – +833W
0 : None 0 – 1000W -1000 – +1000W
1 : 110V AC 0 – 200W -200 – +200W
2 : 190V AC 0 – 300W -200 – +200W
220V / 1A
DC OUTPUT 0 – 333.3W -333.3 – +333.3W
Current Voltage 0 – 400W -400 – +400W
0 – 1000W -1000 – +1000W
A : 4 – 20mA DC 4 : 0 – 10V DC
0 – 1500W -1500 – +1500W
G : 0 – 1mA DC 5 : 0 – 5V DC 220V / 5A
0 – 1666W -1666 – +1666W
6 : 1 – 5V DC
0 – 2000W -2000 – +2000W
PULSE / NETWORK OUTPUT
0 : None (with zero-phase voltage input selected) •Reactive power
1 : Watthours Input range and lag/lead can be changed via the front panel.
M : Modbus RATING RANGE
AUXILIARY POWER SUPPLY 0 – lag 100 var lead 100 – lag 100 var
AC Power DC Power 0 – lag 150 var lead 150 – lag 150 var
110V / 1A
M : 85 – 264V AC R : 24V DC 0 – lag 166.6 var lead 166.6 – lag 166.6 var
V : 48V DC 0 – lag 200 var lead 200 – lag 200 var
P : 110V DC 0 – lag 500 var lead 500 – lag 500 var
0 – lag 750 var lead 750 – lag 750 var
110V / 5A
ORDERING INFORMATION 0 – lag 833 var lead 833 – lag 833 var
0 – lag 1000 var lead 1000 – lag 1000 var
Specify code number and variables (e.g. LSMT2-
0 – lag 200 var lead 200 – lag 200 var
1150A1-M). Use Ordering Information Sheet (No.
0 – lag 300 var lead 200 – lag 200 var
ESU-1954-1). 220V / 1A
0 – lag 333.3 var lead 333.3 – lag 333.3 var
The unit is configured at the factory according to the
0 – lag 400 var lead 400 – lag 400 var
user's specifications, however, measuring items can be 0 – lag 1000 var lead 1000 – lag 1000 var
freely selected and assigned to up to 10 output chan- 0 – lag 1500 var lead 1500 – lag 1500 var
nels via the front panel control switches, except that 220V / 5A
0 – lag 1666 var lead 1666 – lag 1666 var
V0 : zero-phase voltage is available only when speci- 0 – lag 2000 var lead 2000 – lag 2000 var
fied in ordering.
The measuring items are listed below: •Zero-phase voltage
A = Line current V = Line voltage RATING RANGE
W = Watt, active power var = var, reactive power 110V 0 – 150V
PF = Power factor Hz = Frequency 190V 0 – 260V
V0 = Zero-phase voltage

P. 5 / 10 ES-1954 Rev.6
LSMT2
Power factor: lead 0.5 – 1 – lag 0.5
lag 0.5 – 1 – lead 0.5
lead 0 – 1 – lag 0
lag 0 – 1 – lead 0
Input range and lag/lead can be changed via the front panel.

Frequency: 45 – 55 Hz, 55 – 65 Hz, 45 – 65 Hz


Input range can be changed via the front panel.

Watthours
Ratio: 110V – 77kV at the VT primary
5 – 8000A at the CT primary
Pulse unit: 0.01, 0.1, 1, 10, 100, 1000 kWh/pulse

CONNECTION DIAGRAM, INPUT


•No Zero-phase Voltage Measuring

SOURCE A 1 K LOAD
1
V12 V31 A 2 k
2
V23 A3 K
3
k
V V CT CT
U U
VT
u v v u

1 2 3 4 5 6 7 8 9 10
P1 P2 P3 1S 1L 3S 3L

•With Zero-phase Voltage Measuring

SOURCE LOAD
1
V12 V31
2
V23
3
V V
U U GVT3
VT
u v v u

1 2 3 4 5 6 7 8 9 10
P1 P2 P3 G1 G4

Specifications subject to change without notice.


P. 6 / 10 ES-1954 Rev.6
SINGLE-PHASE / 2-WIRE CONNECTION MODEL LSMT2-2
MODEL & SUFFIX CODE SELECTION INPUT RANGE
•Voltage •Current
LSMT2–2❑❑0❑❑–❑
RATING RANGE RATING RANGE
MODEL
110V 0 – 150V 1A 0 – 1A
CONFIGURATION
220V 0 – 300V 5A 0 – 5A
2 : Single-phase / 2-wire
VOLTAGE INPUT •Active power
0 : None Input range and ± can be changed via the front panel.
1 : 110V AC
RATING RANGE
2 : 220V AC 0– 50W -50 – +50W
CURRENT INPUT 0– 75W -75 – +75W
0 : None 110V / 1A
0 – 83.3W -83.3 – +83.3W
1 : 1A AC 0 – 100W -100 – +100W
5 : 5A AC 0 – 250W -250 – +250W
ZERO-PHASE VOLTAGE INPUT (V0) 0 – 375W -375 – +375W
110V / 5A
0 : None 0 – 417W -417 – +417W
DC OUTPUT 0 – 500W -500 – +500W
Current Voltage 0 – 100W -100 – +100W
A : 4 – 20mA DC 4 : 0 – 10V DC 0 – 150W -150 – +150W
220V / 1A
G : 0 – 1mA DC 5 : 0 – 5V DC 0 – 166.6W -166.6 – +166.6W
6 : 1 – 5V DC 0 – 200W -200 – +200W
PULSE / NETWORK OUTPUT 0 – 500W -500 – +500W
1 : Watthours 0 – 750W -750 – +750W
220V / 5A
M : Modbus 0 – 833W -833 – +833W
AUXILIARY POWER SUPPLY 0 – 1000W -1000 – +1000W
AC Power DC Power
M : 85 – 264V AC R : 24V DC Power factor: lead 0.5 – 1 – lag 0.5
V : 48V DC lag 0.5 – 1 – lead 0.5
P : 110V DC lead 0 – 1 – lag 0
lag 0 – 1 – lead 0
ORDERING INFORMATION Input range and lag/lead can be changed via the front panel.

Specify code number and variables (e.g. LSMT2- Frequency: 45 – 55 Hz, 55 – 65 Hz, 45 – 65 Hz
2150A1-M). Use Ordering Information Sheet (No. Input range can be changed via the front panel.
ESU-1954-2).
The unit is configured at the factory according to the Watthours
user's specifications, however, measuring items can be Ratio: 110V – 77kV at the VT primary
freely selected and assigned to up to 10 output chan- 5 – 8000A at the CT primary
nels via the front panel control switches. Pulse unit: 0.01, 0.1, 1, 10, 100, 1000 kWh/pulse
The measuring items are listed below:
A = Line current V = Line voltage
W = Watt, active power
CONNECTION DIAGRAM, INPUT
PF = Power factor Hz = Frequency
SOURCE A K LOAD
1
V k
2

U V CT
VT
u v

1 2 3 4 5 6 7 8 9 10
P1 P2 1S 1L

P. 7 / 10 ES-1954 Rev.6
LSMT2

SINGLE-PHASE / 3-WIRE CONNECTION MODEL LSMT2-3


MODEL & SUFFIX CODE SELECTION INPUT RANGE
•Voltage •Current
LSMT2–3❑❑0❑❑–❑
RATING RANGE RATING RANGE
MODEL
100V 0 – 150V 1A 0 – 1A
CONFIGURATION
200V 0 – 300V 5A 0 – 5A
3 : Single-phase / 3-wire
VOLTAGE INPUT •Active power
0 : None Input range and ± can be changed via the front panel.
A : 100V / 200V AC
RATING RANGE
CURRENT INPUT 0 – 100W -100 – +100W
0 : None 0 – 150W -150 – +150W
1 : 1A AC 100/200V / 1A
0 – 166.6W -166.6 – +166.6W
5 : 5A AC 0 – 200W -200 – +200W
ZERO-PHASE VOLTAGE INPUT (V0) 0 – 500W -500 – +500W
0 : None 0 – 750W -750 – +750W
100/200V / 5A
DC OUTPUT 0 – 833W -833 – +833W
Current Voltage 0 – 1000W -1000 – +1000W
A : 4 – 20mA DC 4 : 0 – 10V DC
G : 0 – 1mA DC 5 : 0 – 5V DC Power factor: lead 0.5 – 1 – lag 0.5
6 : 1 – 5V DC lag 0.5 – 1 – lead 0.5
PULSE / NETWORK OUTPUT lead 0 – 1 – lag 0
1 : Watthours lag 0 – 1 – lead 0
M : Modbus Input range and lag/lead can be changed via the front panel.
AUXILIARY POWER SUPPLY
AC Power DC Power Frequency: 45 – 55 Hz, 55 – 65 Hz, 45 – 65 Hz
M : 85 – 264V AC R : 24V DC Input range can be changed via the front panel.
V : 48V DC
P : 110V DC Watthours
Ratio: 110V at the VT primary
ORDERING INFORMATION 5 – 8000A at the CT primary
Pulse unit: 0.01, 0.1, 1, 10, 100, 1000 kWh/pulse
Specify code number and variables (e.g. LSMT2-
3A50A1-M). Use Ordering Information Sheet (No.
ESU-1954-3). CONNECTION DIAGRAM, INPUT
The unit is configured at the factory according to the
SOURCE A 1 K LOAD
user's specifications, however, measuring items can be 1
k
V1N V12 A N
freely selected and assigned to up to 10 output chan- N
V2N A2 K
2
k
nels via the front panel control switches. U
V V
U CT CT
VT
The measuring items are listed below: u v v u

A = Line current V = Line voltage


1 2 3 4 5 6 7 8 9 10
W = Watt, active power
P1 P0 P2 1S 1L 2S 2L
PF = Power factor Hz = Frequency

Specifications subject to change without notice.


P. 8 / 10 ES-1954 Rev.6
3-PHASE / 4-WIRE CONNECTION MODEL LSMT2-4
MODEL & SUFFIX CODE SELECTION INPUT RANGE
•Voltage
LSMT2–4❑❑0❑❑–❑
RATING PHASE VOLTAGE LINE VOLTAGE
MODEL
110V 0 – 150V
CONFIGURATION 0 – 150V
√3 √3
4 : 3-phase / 4-wire
220V 0 – 300V
VOLTAGE INPUT 0 – 300V
√3 √3
0 : None
380V 0 – 450V
110V 0 – 450V
1 : / 110V AC √3 √3
√3
220V •Current
2 : / 220V AC
√3 RATING RANGE
380V 1A 0 – 1A
4 : / 380V AC
√3 5A 0 – 5A
CURRENT INPUT
0 : None •Active power
1 : 1A AC Input range and ± can be changed via the front panel.
5 : 5A AC RATING RANGE
ZERO-PHASE VOLTAGE INPUT (V0) 0 – 100W -100 – +100W
0 : None 110V 0 – 150W -150 – +150W
/ 1A
DC OUTPUT √3 0 – 166.6W -166.6 – +166.6W
Current Voltage 0 – 200W -200 – +200W
A : 4 – 20mA DC 4 : 0 – 10V DC 0 – 500W -500 – +500W
G : 0 – 1mA DC 5 : 0 – 5V DC 110V 0 – 750W -750 – +750W
/ 5A
6 : 1 – 5V DC √3 0 – 833W -833 – +833W
PULSE / NETWORK OUTPUT 0 – 1000W -1000 – +1000W
0 – 200W -200 – +200W
1 : Watthours
220V 0 – 300W -200 – +200W
M : Modbus / 1A
√3 0 – 333.3W -333.3 – +333.3W
AUXILIARY POWER SUPPLY
0 – 400W -400 – +400W
AC Power DC Power
0 – 1000W -1000 – +1000W
M : 85 – 264V AC R : 24V DC
220V 0 – 1500W -1500 – +1500W
V : 48V DC / 5A
√3 0 – 1666W -1666 – +1666W
P : 110V DC 0 – 2000W -2000 – +2000W
0 – 350W -350 – +350W
ORDERING INFORMATION 380V 0 – 525W -525 – +525W
/ 1A
Specify code number and variables (e.g. LSMT2- √3 0 – 583W -583 – +583W
4150A1-M). Use Ordering Information Sheet (No. 0 – 700W -700 – +700W
ESU-1954-4). 0 – 1750W -1750 – +1750W
The unit is configured at the factory according to the 380V 0 – 2625W -2625 – +2625W
/ 5A
user's specifications, however, measuring items can be √3 0 – 2917W -2917 – +2917W
freely selected and assigned to up to 10 output chan- 0 – 3500W -3500 – +3500W
nels via the front panel control switches.
The measuring items are listed below:
A = Line current V = Line voltage
W = Watt, active power var = var, reactive power
PF = Power factor Hz = Frequency

P. 9 / 10 ES-1954 Rev.6
LSMT2
•Reactive power
Input range and lag/lead can be changed via the front panel.
RATING RANGE
0 – lag 100 var lead 100 – lag 100 var
110V 0 – lag 150 var lead 150 – lag 150 var
/ 1A
√3 0 – lag 166.6 var lead 166.6 – lag 166.6 var
0 – lag 200 var lead 200 – lag 200 var
0 – lag 500 var lead 500 – lag 500 var
110V 0 – lag 750 var lead 750 – lag 750 var
/ 5A
√3 0 – lag 833 var lead 833 – lag 833 var
0 – lag 1000 var lead 1000 – lag 1000 var
0 – lag 200 var lead 200 – lag 200 var
220V 0 – lag 300 var lead 200 – lag 200 var
/ 1A
√3 0 – lag 333.3 var lead 333.3 – lag 333.3 var
0 – lag 400 var lead 400 – lag 400 var
0 – lag 1000 var lead 1000 – lag 1000 var
220V 0 – lag 1500 var lead 1500 – lag 1500 var
/ 5A
√3 0 – lag 1666 var lead 1666 – lag 1666 var
0 – lag 2000 var lead 2000 – lag 2000 var
0 – lag 350 var lead 350 – lag 350 var
380V 0 – lag 525 var lead 525 – lag 525 var
/ 1A
√3 0 – lag 583 var lead 583 – lag 583 var
0 – lag 700 var lead 700 – lag 700 var
0 – lag 1750 var lead 1750 – lag 1750 var
380V 0 – lag 2625 var lead 2625 – lag 2625 var
/ 5A
√3 0 – lag 2917 var lead 2917 – lag 2917 var
0 – lag 3500 var lead 3500 – lag 3500 var

Power factor: lead 0.5 – 1 – lag 0.5


lag 0.5 – 1 – lead 0.5
lead 0 – 1 – lag 0
lag 0 – 1 – lead 0
Input range and lag/lead can be changed via the front panel.

Frequency: 45 – 55 Hz, 55 – 65 Hz, 45 – 65 Hz


Input range can be changed via the front panel.

Watthours
Ratio: 110V – 77kV at the VT primary
5 – 8000A at the CT primary
Pulse unit: 0.01, 0.1, 1, 10, 100, 1000 kWh/pulse

CONNECTION DIAGRAM, INPUT


SOURCE A1 K LOAD
1
V1 V12 V31 A 2 k K
2
V2 V23 A3 k K
3
V3 k
N
V U CT CT CT
U V
VT
u v u v

1 2 3 4 5 6 7 8 9 10
P1 P3 P0 1S 1L 2S 2L 3S 3L

Specifications subject to change without notice.


P. 10 / 10 ES-1954 Rev.6