Electrical Abstract - (NBC NEC IE Rule CEA CPWD IS Code)
Electrical Abstract - (NBC NEC IE Rule CEA CPWD IS Code)
Circuits:
Topic Abstracts
Lighting
Per Circuit Not more than 10 Points of Lighting or Total 800Watt which is less
Circuit
Power
For Residential Per Circuit Less than 2 No of 5A/15A Plug Socket
Circuit
Power
For Non Residential Per Circuit Less than 1 No of 5A/15A Plug Socket
Circuit
Plug Socket In Residential wiring ,wiring of Socket outlet shall be done by copper Cable only
Min Size of
For Lighting Circuit Smallest size of conductor shall be 1.5 Sq.mm
Wire
Min Size of
For Power Circuit Smallest size of conductor shall be 4 Sq.mm
Wire
Plug Socket
5A/6A or 15A/16A Socket shall be installed at following heights: =For Non Resident
Plug Socket =For Kitchen 23cm above Platform.
=For Bathroom not Socket is provided in bathroom MCB/IC will be 2.1 mt from fixed appliance and at least 1 mt away from Sh
Operating
Operating Rod/Handle of Distribution Board at the height of min 2mt
Rod
D.B
Clear Distance in front of Switch Board/D.B shall be min 1 mt.
Clearance
D.B
If there may be bare connection at back of Switch Board than space behind S/W shall be either less than 20cm or more than
Clearance
D.B
No fuse Body shall be mounted within 2.5 com edge of D.B or Panel
Clearance
D.B
Clearance between 2.5 cm is maintained between opposite polarity
Clearance
Switch Box Switch Box or Regular Box shall be mounted normally 1.25 mt from floor level.
Fan Hook
Fan Hook For Fan Hook in concrete roof 12mm dia MS Rod in ‘U’ Shape, horizontally Leg at Top at least 19 cm on either side.
Safety If the distance with adjustment building is less than 3 mt and there is no any Road interval than GI pipe of suitable size shall b
Clearance mt.
Safety
If the distance with adjustment building is more than 3 mt and there is any Road interval than GI pipe of suitable size shall be
Clearance
Conduit
Metallic Shall be used for Industrial wiring, Heavy mechanical Stress, shall be ISI marked, The Thickness shall not be less than 1.6mm
Conduit conduit above 32mm Dia.
Metallic
No steel conduit less than 20 mm Diameter shall be used.
Conduit
Metallic
For rigid Conduit IS:2509/IS:3419 and For Flexible Conduit IS:6946.
Conduit
Metallic
All Metallic conduit accessories shall be threaded type (Not pin grip, clamp grip)
Accessories
Metallic
Saddle for surface conduit work on wall shall not less than 0.55mm(24 gauge) for conduit up to 25mm Dia not less than 0.9m
Accessories
Metallic Clear depth of Out less Box shall not be less than 60mm.
Outlets This will be increased as per mounting of Fan regulator
Bends in
Bending radius not less than 7.5 cm
Conduits
Fixating
Conduits on Conduits shall be fixed by saddles not less than 1mt interval but in case of coupler/Bends in either side of saddles, The saddl
Surface
Non Metallic
Normally grip Type.
Accessories
Non Metallic
Outlet(PVC PVC Box IS:5133(PartII) thickness not less than 2mm,Clear depth of PVC Boxes not less than 60mm.
Box)
Non Metallic
Surface Conduits shall be fixed by saddles not less than 60cm interval but in case of coupler/Bends in either side of saddles, The sad
Conduit
Junction Box
Junction Box Depth of Junction Box shall be min 65mm as per IS: 2667.
Fish Wire
Bus bar
Bus bar The Cross-section area of Bus bar shall be same as Phase Bus bar (Up to 200A) for higher Capacity Neutral Bus bar must be
Bus bar Bus bar shall be suitably installed with PVC sleeve/Tap.
Bus bar Bus bar Chamber shall be fabricated with MS angle for Frame work and sheet steel of thickness not less than 1.5mm.
Bus bar Minimum clearance between phase to earth shall be 26mm and phase to phase shall be 32mm.
Bus bar
Bus bar Trucking are generally used for interconnection between T/C over 500KVA/D.G set over 500KVA and their switch Bo
Trucking
Bus bar
Bus bar Trucking enclosure sheet steel of min 2mm thickness
Trucking
Earthing
Earthing Type of earthling are Pipe earthling/Plate earthling/Strip earthling.
Earthing Two copper strip, each size 50mmX5mm shall be provided as each bus bar in 11KV S/S or D.G generally.
Earthing The minimum Cross-section are of protective conductor (Not contained within cable or wire) 2mm Dia(14SWG) for Copper, 2.
Earthing Earthing Pit shall not be closer than 1.5mt from Building.
Earthing Top of Pipe earthling electrode shall not be less than 20cm below the ground
Earthing Plate electrode shall be buried in ground with face vertical and it’s Top not less than 3mt below ground level.
Earthing The strip of earthling electrode shall be buried in trench not less than 0.5m deep.
Earthing If strip electrode cannot be laid in straight length. It may be Zigzag with deviation up to 45 Degree from axis of strip.
Earthing In Plate Earthing Dia of water pipe shall not be less than 20mm and in Pipe earthling reducer of 40mmX20mm shall be used.
Earthing Thickness of MS cover of earthling pit shall be not less than 6mm and having locking arrangements.
Earthing Earthing resistance of each electrode shall be less than 5Ω and for Rocky Soil not less than 8Ω
Earthing Earthing conduit for earthling wire shall be Medium class 15mm Dia GI pipe and for Earthing Strip shall be medium class 40m
Conductor Clearance(min)
Cable
The horizontal and vertical distance between Power and Communication cable shall not be less than 60cm.
crossing
Railway
After taking approval of railway authority, Cable under railway track shall be min 1mt from bottom of sleeper under RCC or ca
crossing
Railway
Cable in parallel to Railway track shall be min 3mt far away from centre of nearest Track.
crossing
Cable Laying
For Single Conductor Shall be min 10cm Dia and more than Two Cable shall be min 15cm Dia.
in Pipe
Cable in
Road In Road Crossing Cable shall be laid min 1 mt below Road in Pipe.
Crossing
Cable trench
For single cable: For below 11Kv.Min length of Trench shall be 35cm and depth shall be min 75cm ( with sand cushioning of
Cable trench
Cable) and without Cushioning Depth shall be 75cm+25cm.
Cable trench For single cable: For above 11Kv.Min length of Trench shall be 35cm and depth shall be min 1.2mt ( with sand cushioning an
Cable trench For multi cable in horizontal level: Min distance between two cable shall be 20cm and min distance between cable and edge o
For multi cable in Vertical level: Min distance between two cable shall be 30cm.(min Sand cushioning at bottom of trench sha
Cable trench
covering/Sand cushioning of 17cm above Cable)
Cable trench For LV/MV cable cushioning is not required where there is no possibility of mechanical damages.
Cable trench Extra loop of cable at end shall be 3mt for cable termination/Joints.
Cable Route
Cable Route
Cable Route Marker shall be min 0.5mt away from cable trench at the interval not exceeding 100mt parallel.
Marker
Cable Route
Plate Type Cable Route Marker shall be made of 100mmX5mm GI/Aluminum Plate welded/Bolted on 35mmX35mmX6mm Iro
Marker
Cable Route
Cement Concrete(C.C) type marker shall be made in formation of 1:2:4.
Marker
Cable Tray Cable Tray may be fabricated by two angle irons of 50mmX50mmX6mm as two longitudinal members with cross bracing betw
(Perforated) MS sheet.
Overhead Line
Steel 1/6 length of Steel Tubular Pole + 30 cm from base shall be coated with Black Bituminous paint on both internally and externa
Tubular Pole The remaining portion of the pole shall be painted with Red oxide.
Struts The Pit for Struts shall be located not less than 1.8mt from pole side. The depth of Pit shall be at least 1.2mt
Danger
All Support carrying HV Line shall be fitted with Danger Board( IS:2551) at height of 3mt.
board
Anti Climbing
For HV Line(IS:278-1978) having 4Point Barbs 75mm+12mm apart weight 128/125 gm/mt shall be wrapped helically with pitc
Device
Insulator For LV/MV Overhead Line: Pin/Shackle Insulator and For 11KV Line Pin/Disc Insulator
D Clamp D clamp shall be made of MS Flat size of 50mmX6mm,height of 75mm Galvanized and only used for vertical configuration fo
Pole Top
Pole Top clamp made from Flat iron 50mmX8mm.
Clamp
Stay wire
Stay wire Rod shall not be less than 1.8 m Long and 19mm Dia.Ankor Plate shall not be less than 45mmX45mmX7.5mm.
Rod
For LV Line :
Overhead
AAC(All Alu.Cond) 7/1/2.21mm, ACSR 6/1/1/2.11mm, AAAC(All Alu.Alloy Cond) 7/2.09mm(20Sqmm)
Conductor
For 11KV/33KV Line :
(min)
AAC(All Alu.Cond) N/A, ACSR 6/1/1/2.11mm, AAAC(All Alu.Alloy Cond) 7/2.56mm(30Sqmm)
Binding Wire Binding Wire with insulator shall be with 2.6mm(12SWG) soft aluminum wire.
Earthing in
Earthing wire shall not be less than 4mm(8SWG) and min 3 earthling Pit per KM shall be required.
Overhead
If there is no Continuous wire for earthling in overhead line than each pole should be earthed.
Line
Same
For HV Line In Triangular Configuration for 11KV/33KV Line shall be min 1.5mt.
Support
Different
When Two conductor of different Voltage are erected on same support min clearance between LV/MV and 11KV shall be min
Voltage
Different
A Clearance not less than height of tallest support may be maintained between parallel overhead line on Different support.
Support
Different
When Two overhead line cross each other vertical clearance between LV/MV and 11KV shall not be less than 1.25mt and for
Support
Looping Box Looping Bus shall be fabricated from MS Sheet of 1.6mm(16SWG) thickness, Min Size 250mmX200mmX100mm for single c
Feeder Pillar
Feeder Pillar Feeder Pillar shall be fabricated min 2mm thick MS sheet and hinged type double door at front side. If width of Pillar shall be
Feeder Pillar Min height of Pedestal of Feeder Pillar shall be not less than 45cm and 1 to 2 mt height from Road Level.
Feeder Pillar Each Feeder Pillar shall be earthed with 2 no of Earthing electrode.
Substation
S/S TC Room Area Total S.S Area(T.C,HT/LT Panel, without DG) 2X500KVA 36 Sq
Sq.meter 3X500KVA 54 Sqmeter 172 Sq.meter
Area of S/S Sqmeter 135 Sq.meter 3X800KVA 58 Sqmeter 181
Sq.meter 2X1000KVA 39 Sqmeter 149 Sq.meter
Sqmeter 197 Sq.meter
Incandescent 15 to 500 to
12 to 20 Fair to good Very good
lamps 200 1000
Standard
fluorescent 20 to 80 55 to 65 5000 Fair to good Good
lamps
Compact
60 to Good to very
fluorescent lamps 5 to 40 7500 Good
70 good
(CFL)
Slim line
18 to 58 57 to 67 5000 Fair to good Good
fluorescent
High pressure
60 to 50 to Very low to
mercury vapor 5000 Federate
1000 65 fair
lamps
High pressure
50 to 90 to 10000 to
sodium vapor Fair to good Low to good
1000 125 15000
lamps
4 Sq.mm 22 To 30 A 20A
6 Sq.mm 39 To 39 A 30A
Plastic slabs (polymeric cover strips) depending on properties and has to be matched with
Fiber reinforced plastic the protective cushioning and cover
PVC conduit or PVC pipe or The pipe diameter should be such so that
stoneware pipe or Hume pipe the cable is able to easily slip down the pipe
The Trench : The trench shall be back filled to cover the cable initially by 200 mm of sand fill; and then a
plastic marker strip hall be put over the full length of cable in the trench.
The Marker Signs: The marker signs shall be provided where any cable enters or leaves a building. This will
identify that there is a cable located underground near the building.
The trench shall then be completely filled. If the cables rise above ground to enter a building or other structure,
a mechanical protection such as a GI pipe or PVC pipe for the cable from the trench depth to a height of 2.0 m
above ground shall be provided.
AREA REQUIRED FOR GENERATOR IN ELECTRIC SUBSTATION (As per
NBC)
Capacity kVA Area m2 Clear Height below the Soffit of the Beam m
25 56 3.6
48 56 3.6
100 65 3.6
150 72 3.6
Cables/wires, such as fiber optic cable, co-axial cable, etc. These shall be laid at least
at a distance of 300 mm from any power wire or cable. The distance may be reduced
only by using completely closed earthed metal trucking with metal separations for
various kind of cable. Special care shall be taken to ensure that the conduit runs and
Low Voltage wiring are laid properly for low voltage signal to flow through it.
Cable The power cable and the signal or data cable may run together under floor and near the
equipment. However, separation may be required from the insulation aspect, if the
signal cable is running close to an un-insulated conductor carrying power at high
voltage. All types of signal cables are required to have insulation level for withstanding 2
kV impulse voltages even if they are meant for service at low voltage.
Power conduit=Black
Security conduit=Blue
Conduit Color
Fire alarm conduit=Red
Scheme
Low voltage conduit=Brown
UPS conduit Green
If there is only one basement in a building, the substation/switch room shall not
be provided in the basement and the floor level of the substation shall not be
Substation Location
lowest point of the basement.
All door openings from substation, electrical rooms, etc, should open outwards
Vertical shutters (like rolling shutters) may also be acceptable provided they are
combined with a single leaf door opening outwards for exit in case of emergency
Substation For large substation room/electrical room having multiple equipment, two or
Door/Shutter more doors shall be provided which shall be remotely located from each other
No services or ventilation shafts shall open into substation or switch room unless
specific to substation or switch room
In case transformer and main MV/LV panel room are located at different floors or
are at a distance more than 20 m, MV/LV isolator shall be provided
at transformer end
In case of two transformers (dry type or transformers with oil quantity less
than 2 000 liter) located next to each other without intermittent wall, the
Transformer Location distance between the two shall be minimum 1 500 mm for 11 kV, minimum 2
000 mm for 22 kV and minimum 2 500 mm for 33 kV. Beyond 33 kV, two
transformers shall be separated by baffle wall of 4 h fire rating.
They shall not be located in any floor other than the ground floor or the first
basement of a utility building not be located below first basement slab of utility
building.
They shall have direct access from outside the building for operation and
maintenance of the equipment.
Oil Filled Equipment It shall be separated from the adjoining buildings including the main building by at
(Transformer / C.B) least 6 m clear distance to allow passage of fire tender between the
substation/utility building and adjoining building/main building.
Substation equipment having more than 2 000 liter of oil whether located indoors
in the utility building or outdoors shall have baffle walls of 4 h fire rating
between apparatus.
Provision of suitable oil soak-pit, and where use of more than 9 000 liter of oil in
any one oil tank, receptacle or chamber is involved, provision shall be made for
the draining away or removal of any oil which may leak or escape from the tank,
receptacle or chamber containing the same
In case of connected load of 100 kVA and above, the relative advantage of high
voltage three-phase supply should be considered.
Power Supply
Voltage In case of single point high voltage metering, energy meters
shall be installed in building premise,such a place which is readily accessible
to the owner/operator of the building and the Authority. The supplier or owner of
the installation shall provide at the point of commencement of supply a suitable
isolating device fixed in a conspicuous position at not more than 1.7 m above the
ground so as to completely isolate the supply to the building in case of
emergency
In case of cable trench in substation/HV switch room/MV switch room, the same
Trench Drain shall be adequately drained to ensure no water is stagnated at any time with live
cables.
Enclose any part of the substation which is open to the air, with a fence (earthed
Fence for Substation efficiently at both ends) or wall not less than 1800 mm (preferably not less than
2400 mm) in height
The power supply HV cables voltage shall not be more than 12 kV and a
separate dedicated and fire compartmented shaft should be provided for
HV Distribution in
carrying such high voltage cables to upper floors in a building. These shall not be
Building
mixed with any other shaft and suitable fire detection and suppression measures
shall be provided throughout the length of the cable on each floor.
1X160 14 90 9
11 KV 200 Kvar
22 KV 400 Kvar
33 KV 600 Kvar
Capacities of PVC conduits
25
16 mm 20 mm 32 mm
mm
Nominal conductor Size mm
1.0 6 5 19 30
1.5 5 4 15 24
2.5 3 3 11 17
4 2 2 8 13
6 2 – 6 10
10 – – 4 6
16 – – 3 4
25 – – 2 3
35 – – – 2
System Highest and Lower Voltage
11 kV 12 kV 10 kV
22 kV 24 kV 20 kV
33 kV 36 kV 30 kV
66 kV 72.5 kV 60 kV
66 kV 72.5 kV 60 kV
Number of Points for Dwelling Unit
No. Description
35 85 140
45 mm2 55 mm2
mm2 mm2 mm2
17
1 Light points 7 No 8 No 10 No 12 No
No
Recommended Schedule of Socket-Outlets
Number of Socket
Description
6A Socket 16A Socket
Bedroom 2 1
Living room 2 2
Kitchen 1 2
Dining room 2 1
Garage 1 1
For refrigerator – 1
Bathroom 1 1
Power requirements of the building
Laundry 5% 0.6
Lift Car Speed
No. of Floors
Occupancy Car Speed m/s
Served
Passenger lifts for low and medium lodging houses – 0.5 m/sec
Hospital bed lifts (Short travel lifts insmall hospitals) – 0.25 m/sec
Hospital bed lifts (Long travel lifts inGeneral hospitals) 0.6 to 1.5 m/sec
Capacitor Ratings at Rated Voltage
15 5 6 7 9 11 12
22.5 7 8 10 12 15 17
37 11 12.5 16 18 23 25
57 16 17 21 23 29 32
75 21 23 26 28 35 40
102 31 33 36 38 45 55
150 40 42 45 47 60 67
187 46 50 53 55 68 76
:Maximum Current Demand for Motor:
Single phaseor
Above 0.75 kW and up to 7.5 kW Three times the full load current
Three phase
Above 7.5 kW up to and up to11 kW Two times the full load current
Above 11 kW One and half times the full load current
Rated Basic Insulation Level (BIL)
33 KV 170
22 KV 125
11 KV 75
6.6 KV 60
3.3 KV 40
Illumination Level
Residence
Kitchen 200
Bathroom 100
Sewing 700
Workshop 200
Staircase 100
Garage 70
Office Building
Corridors 70
Stairs 100
Hospital Building
Toilet 70
Stairs 100
Radiology 100
Causality 150
Dispensaries 300
Laundry 200
Ironing 300
Kitchen 200
Platform 450
Corridors 70
Stairs 100
Cinema Halls
Foyers 150
Auditoria 50
Corridors 70
Stairs 100
Theatres
Foyers 150
Auditoria 70
Corridors 70
Stairs 100
Assembly Halls
General 150
Platform 300
Classes
Desktop 300
Libraries
Shelves 70 to 150
General
Office 300
Corridors 70
Stairs 100
Lamp’s Lumen Data
Incandescent Lamp
60 1000 870
Fluorescent Lamp
18 7000 1120
20 7000 1020
36 7000 2800
40 7000 2700
5 10000 220
7 7000 380
11 7000 560
13 7000 680
15 7000 810
18 7000 1050
23 7000 1500
26 7000 1800
32 7000 2400
50 15000 3400
70 15000 5600
35 16000 2250
50 24000 4000
70 24000 5800
50 15000 3400
70 15000 5600
:Duty Type of Motor:
Ref: IS-325
Duty Type
Duty Type Application
Symbol
Type of Distribution System
IT TT / TN (TN-S,TN-C,TN-C-S)
First Letter (the neutral point in relation to earth):T= directly earthed neutral (from the French word Terre)I
=unearthed or high impedance-earthed neutral (e.g. 2,000 Ω)
Second letter (Exposed conductive parts of the electrical installation in relation to earth):T =directly earthed
exposed conductive partsN =exposed conductive parts directly connected to the neutral conductor
11) Transformer:
Where transformer or transformers are used, suitable provision shall be made, either by connecting with earth a point of
the circuit at the lower voltage or otherwise, to guard against danger by reason of the said circuit becoming Accidentally
charged above its normal voltage by leakage from or contact with the circuit at the higher voltage
A sub-station or a switch station with apparatus having more than 2000 litres of oil shall not be located in the basement
where proper oil draining arrangement cannot be provided.
Where a sub-station or a switch station with apparatus having more than 2000 litres of oil is installed, whether indoor or
out-doors, the following measures shall be taken, namely: –
The baffle walls 4[of 4 hour fire rating] shall be provided between the apparatus in the following cases: –
(1) Single phase banks in the switch-yards of generating stations and substations;
(2) On the consumer premises;
(3) Where adequate clearance between the units is not available.
Provisions shall be made for suitable oil soakpit and where use of more than 9000 litres of oil in any one oil tank,
receptacle or chamber is involved, provision shall be made for the draining away or removal of any oil which may leak or
escape from the tanks receptacles or chambers containing the same.
The transformer shall be protected by an automatic high velocity water spray system or by carbon dioxide or BCF (Bromo
chlorodi feuromethane) or BTM (Bromo tri fluromethane) fixed installation system; and
Oil filled transformers installed indoors shall not be on any floor above the ground or below the first basement.
Isolators and the corresponding earthing switches shall be interlocked so that no earthing switch can be closed unless
and until the corresponding isolator is in open position.
When two or more transformers are operated in parallel, the system shall be so arranged as to trip the secondary breaker
of a transformer in case the primary breaker of that transformer trips.
Where two or more generators operate in parallel and neutral switching is adopted, inter-lock shall be provided to ensure
that generator breaker cannot be closed unless one of the neutrals is connected to the earthing system.
Gas pressure type protection to given alarm and tripping shall be provided on all transformers of ratings 1000 KVA and
above.
Transformers of capacity 10 MVA and above shall be protected against incipient faults by differential protection; and All
generators with rating of 100 KVA and above shall be protected against earth fault/leakage. All generators of rating
1000KVA and above shall be protected against faults within the generator winding using restricted earth fault protection
or differential protection or by both.
11) Connection with earth:
In case of the delta connected system the neutral point shall be obtained by the insertion of a grounding transformer and
current limiting resistance or impedance wherever considered necessary at the commencement of such a system.
Where the earthing lead and earth connection are used only in connection with earthing guards erected under high or
extra-high voltage overhead lines where they cross a telecommunication line or a railway line, and where such lines are
equipped with earth leakage relays of a type and setting approved by the Inspector, the resistance shall not exceed 25
ohms.
12) Clearance above ground of the lowest conductor
No conductor of an overhead line, including service lines, erected across a street shall at any part thereof be at a height
of less than:
For low and medium voltage lines 5.8 meters
For high voltage lines 6.1 metres
No conductor of an overhead line, including service lines, erected along any street shall at any part thereof be at a height
less than:
For low and medium voltage lines 5.5 metres
For high voltage lines 5.8 metres
No conductor of in overhead line including service lines, erected elsewhere than along or across any street shall be at a
height less than:
For low, medium and high voltages lines=4.6 meters.
For low, medium and high voltage=4.0 meters.
For high voltage lines above 11,000 volts=5.2 meters.
For extra-high voltage lines the clearance above ground shall not be less than 5.2 metres plus 0.3 meter for every 33,000
volts or part thereof by which the voltage of the line exceeds 33,000 volts.
Indian Standard Code-Abstract
(IS:1554/IS:15652/IS:1678/IS:1255/IS:694
SEPTEMBER 16, 2013 14 COMMENTS
Abstract of IS 1554
For cables having more than 5 cores, the core identification may be done by
numbers. In that case, the insulation of cores shall be of the same color and
numbered sequentially, starting with number 1 for the inner layer. The
numbers shall be printed in Hindu-Arabic numerals on the outer surface of
Arrangement of Marking the cores. All the numbers shall be of the same color which shall contrast
(up to 11 KV) with the color of the insulation. The numerals shall be legible.
When the number is a single numeral, a dash shall be placed underneath it.
If the number consists of two numerals, these shall be disposed one below
the other and a dash placed below the lower numeral. The spacing between
consecutive numbers shall not exceed 50 mm.
Where the calculated diameter below armoring does not exceed 13 mm, the
Type of Armor (up to 11
armor shall consist of galvanized round steel wires. Where the
KV)
calculateddiameter below armoring is greater than 13 mm, the armor shall
consist of either galvanized round steel wires or galvanized steel strips.
Class = AC (Rms)KV=DC(V)=Thickness(mm)
A=3.3=240= 2.0
Insulating Rubber Mat
B=11= 240=2.5 C=33=240=3.0
D =66= 240=3.5
Most of all classes hall be resistant to acid and oil and low temperagre and
shall be identified by the respective class symbol. However a category with
Insulating Rubber Mat
special property of resistance to extreme ‘low’ ternperature will be identified
by a subscript’s ‘to, the ‘respective “c” Class symbol
Roll of Mat shall be in multiple Length of of 5000mm and ion width of
Insulating Rubber Mat
1000mm.Standard Shape in length of 1000, 2000, 3000mm.
Insulating Rubber Mat Leakage current for all Class of Mat shall not be more than 10 Micro Amp.
Abstract of IS: 15652 for Insulating Mat
Most of all classes hall be resistant to acid and oil and low temperature and shall be
identified by the respective class symbol. However a category with special property of
Resistance
resistance to extreme ‘low’ ternperature will be identified by a subscript’S ‘to, the
‘respective “C” Class symbol.
Roll of Mat shall be in multiple Length of 5000mm and ion width of 1000mm.Standard
Length Shape in length of 1000, 2000, 3000mm.
Leakage current Leakage current for all Class of Mat shall not be more than 10 Micro Amp.
Abstract of IS: 1678 for Pole
Cable Route
Power cable route indicators should be provided at an interval not exceeding 200 M and also at turning p
Indicator (Up to
cable route wherever practicable
33KV)
Cable Corrosion Electrolytic corrosion: Where the possibility of electrolytic corrosion exists, for example, adjacent to dc tra
(Up to 33KV) potential gradient along the pipe-line and the cable sheath should be specified.
The neutral point is earthed in such a manner that during a line-to-earth fault the highest rms voltage to e
Neutral (Up to
phase(s) expressed as a percentage of the highest line-to-line voltage, does not exceed 80 percent, irres
33KV)
location,
Earthing The neutral point is not earthed but a device is installed which automatically and instantly cuts out any pa
(Up to 33KV) which becomes accidentally earthed,
In case of ac systems only, the neutral point is earthed through an arc suppression coil with arrangemen
Earthing
one hour for the non-radial field cables and within 8 hours for radial field cables, of occurrence of the fau
(Up to 33KV)
total of such periods in a year does not exceed 125 hours.
Cable Tensile
Strength (Up to PVC and XLPE insulated armored power cables P = 9 D2 ,P=Pulling Strength(N),D=Outer Dia of Cable(
33KV)
Cable Tensile
Strength (Up to PVC and XLPE insulated unarmored power cables P = 5 D2
33KV)
Cable Tensile
Strength (Up to Paper insulated armoured power cables P = 5 D3
33KV)
For Cables Pulled by Pulling Eye : If the cables are pulled by gripping the conductor directly with pulling
Cable Pulling permissible tensile stress depends on the material of the conductor and on their cross-section as given b
(Up to 33KV) conductors 30 N/mm2 and
For copper conductors 50 N/mm2
Cable Laying Direct This method involves digging a trench in the ground and laying cable(s) on a bedding of minimum 75 mm
in Ground at the bottom of the trench, and covering it with additional riddled soil or sand of minimum 75 mm and pr
(Up to 33KV) tiles, bricks
Depth : The desired minimum depth of laying from ground surface to the top of cable is as
Cable Laying Direct
follows: High vo
in Ground
11 kV rating =0.9 m
(Up to 33KV)
High voltage cables, 22 kV, 33 kV rating= 1.05 m
Low voltage and control cables = 0.75 m
Cables at road crossings = 1.00 m
Cables at railway level crossings (measured from bottom of sleepers to the top of pipe)=1.00m
Cable
The power cable should not be laid above the telecommunication cable, to avoid danger to life of the per
Clearance (Up
to the fault in the Telecommunication cable.
to 33KV)
Cables Laid Across Roads, Railway Tracks and Water Pipe Lines: Steel, cast iron, plastics, cement or ea
Crossing (Up to cable ducting blocks should be used where cables cross roads and railway tracks. Spare ducts for future
33KV) provided. Spare duct runs should be sealed off. Buried ducts or ducting blocks should project into footpa
of road, where there is no footpath, to permit smooth entry of cable without undue bending
Diameter of
The diameter of the cable conduit or pipe or duct should be at least 1.5 times the outer diameter of cable
Pipe (Up to
should be mechanically strong to withstand forces due to heavy traffic when they are laid across road/rai
33KV)
Bending
Radius (Up to The bending radius of steel or plastics ducts should not be less than 1.5 m.
33KV)
Cable Over Bridges : On bridges, the cables are generally supported on steel cable hooks or clamped on
regular intervals. While designing a cable layout on a bridge; expansion of bridge due to changes in atmo
Cable on Over
should be taken into account. On most of the rail-cum-road bridges, the cables are subjected to vibration
Bridge (Up to 33KV)
conditions, round wire armoured and lead alloy ‘B’ sheathed cables are preferred. Cables can be laid on
suspended from catenary wire at regular intervals
Cable on Railway Cables Below Railway Crossing : When the cables are laid under railway tracks the cables should be laid
Crossing (Up to concrete or cast iron or steel pipes at such depths as may be specified by the railway authorities but not
33KV) measured from the bottom of sleepers to the top of the pipe.
On long run ducts, it is desirable to apply lubrication to the lead or serving/outer sheath as it enters the d
Cable on Duct
graphite powder or a combination of both is effective for this purpose and through lubrication will reduce
(Up to 33KV)
about 40 percent.
Lying on Racks in Air-The vertical distance between the two racks should be minimum 0.3 m and the cle
Laying on Racks in
first cable and the wall (if racks are mounted on wall) should be 25 mm. The width of the rack should not
Air (Up to 33KV)
order to facilitate installation of cables.
Laying on Racks in Ungalvanized steel work of cable racking/trays should be painted with a coat of primer and thereafter fini
Air (Up to 33KV) anti-corrosive paint.
Laying on Racks in Only single-core cables laid on horizontal racks need be clamped at suitable intervals. Multi-core cables
Air (Up to 33KV) The distance between the vertical clamps should not be more than 2 m.
Laying Cables on Laying Cables on Racks Inside a Tunnel: Horizontal distance between Two cable is min Diameter of Cab
Racks Inside a distance between two cable row is 30cm.In cable tunnel, the head room should not be less than 2 m and
Tunnel(Up to 33KV) leave a free passage of at least 600 to 800 mm either from one side or in the middle.
Laying Cables on With temperatures below 3°C, the cables should be warmed before the laying out, since otherwise the be
Racks Inside a the insulation and protective coverings of cables. The cable laying must be carried out swiftly, so that the
Tunnel(Up to 33KV) down too much
Laying Cables on
Identification strips/tags of metal or plastics should be attached to the cables, particularly if several are la
Racks Inside a
m apart. Identification tags should also be attached at every entry point into the buildings and at the cabl
Tunnel(Up to 33KV)
Laying Cables on
Racks Inside a The spacing between three cables laid in one plane should be not less than the cable diameter.
Tunnel(Up to 33KV)
Laying Cables on
When the cable run is several kilometres long, the cables should be transposed at one-third and at two-t
Racks Inside a
lengths.
Tunnel(Up to 33KV)
Trefoil arrangement If several single-core cables are laid per phase, these should be arranged as follows to ensure balanced
in ducts (Up to Horizontal direction : R-Y-B-Distance-B-Y-R, (Distance=2 X Diameter of Cable) , vertical distance shall b
33KV) Cable
Abstract IS 694 (Cable)
The color of the sheath shall be black or any other color as agreed to
between the purchaser and the supplier. For weatherproof cables, the
color of sheath shall be black only.
Cable Sheath (Up to 1.1KV)
The difference between maximum and minimum measured values of
overall diameter of sheathed circular cables shall not exceed 15
percent of the maximum measured value at the same cross-section.
The cores which have passed the preliminary test given in 16.2.1 shall
be subsequently tested with a dc voltage of 1.2 kV in the same water-
bath at the same temperature. The conductors shall be connected to
the negative pole and water to the positive pole of dc supply by means
of a copper electrode.
Cable-Testing (Up to 1.1KV)
The core shall withstand this dc voltage test for 240 hours without
breakdown.