b084 Initialization selection 00: Disabling /01: Clearing the trip history / 02: Initializing the data /03: Clearing the trip history and initializing the data /04: Clearing the trip history and initializing the data and Drive Programming Increment key b130 Overvoltage LAD stop function 00: Disable /01: DC voltage kept constant / 02: Acceleration enabled Changes the set values, parameters and Commands b131 Overvoltage LAD stop function 200V class: 330. to 395. Decrement key level 400V class: 660. to 790.
Starts the operation. Forward / Reverse rotation
RUN key depends on the ‘F004’ setting.
STOP/RESET Stops the operation. Functions as the Reset key
key if an error occurs. D
Enter key Enters and stores the data.
Safety Precautions Precautions for Safe Use Maintenance Conformance to EC Directives · The Inverter consists of many parts, which must operate properly to Indications and Meanings of Safety Information Installation and Storage maximize its capabilities. Some electronic parts require maintenance · It is necessary to use optional EMC filter to comply with EMC directive In this user’s Manual, the following precautions and signal words Do not store or use the product in the following places. depending on their operating conditions. To ensure proper operation of (EN61800-3). · Locations subject to direct sunlight. the Inverter over a long period of time, be sure to perform periodic · For earthing, selection of cable, and any other conditions for EMC are used to provide information to ensure the safe use of the · Locations subject to ambient temperature exceeding the specifications. inspections and replace parts according to their service life. compliance, please refer to the manual for installation. 3G3MX2 Inverter. The information provided here is vital to safety. Strictly observe · Locations subject to relative humidity exceeding the specifications. (Excerpt from “Recommendations for Periodic Inspections of General- · Locations subject to condensation due to severe temperature fluctuations. purpose Inverters” issued by JEMA) OMRON Corporation the precautions provided. · Locations subject to corrosive or flammable gases. Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530, Japan Meanings of Signal Words · Locations subject to exposure to combustibles. Product Disposal · Locations subject to dust (especially iron dust) or salts. · Comply with the local ordinance and regulations when disposing of the Omron Europe B.V. Indicates an imminently hazardous situation which, · Locations subject to exposure to water, oil, or chemicals. if not avoided, will result in minor or moderate injury, product. Wegalaan 67-69, NL-2132 JD Hoofddorp, The Netherlands WARNING · Locations subject to shock or vibration. or may result in serious injury or death. Additionally there may be significant property damage. Transporting, Installation and Wiring UL Cautions Indicates a potentially hazardous situation which, · Do not drop or apply a strong impact on the product. The warnings and instructions in this section summarizes the procedures Safety Doing so may result in damaged parts or malfunction. CAUTION if not avoided, may result in minor or moderate necessary to ensure an inverter installation complies with Underwriters For use of the drive as a safety device, to meet the requirements of the · Do not hold by the front cover, but hold by the fins during transportation. injury or in property damage. Laboratories guidelines. ISO13849-1, please refer to user’s manual. · Do not connect an AC power supply voltage to the control input / output terminals. Doing so may result in damage to the product. · Use 60/75°C Cu wire only. Alert Symbols in this Document · Be sure to tighten the screws on the terminal block securely. Wiring work (For models:3G3MX2-A2001, -A2002, -A2004, -A2007, -AB015, -AB022, must be done after installing the unit body. -A4004, -A4007, -A4015, -A4022, and -A4030) For KC Marking Only WARNING · Do not connect any load other than a three-phase inductive motor to the U, V and W output terminals. · Use 75°C Cu wire only. (For models:3G3MX2-AB001, -AB002, -AB004, -AB007, -A2015, -A2022, ἽGὤὤஂ㛹ⱨ㟝Gⵝ㋕䋩㐔ὤ㣄㣠ஃ G Turn off the power supply and implement wiring correctly. 㢨Gὤὤ⏈G㛹ⱨ㟝OἽPG㤸㣄䑀㤵䚝ὤὤ⦐㉐G䑄⬘㣄G❄⏈G㇠㟝㣄⏈G㢨G · Take sufficient shielding measures when using the product in the -A2037, -A2055, -A2075, -A2110, -A2150, -A4040, -A4055,-A4075, 㥄㡸G㨰㢌䚌㐐ὤGⵈ⢰⮤SGᴴ㥉㞬㢌G㫴㜡㜄㉐G㇠㟝䚌⏈Gᶷ㡸G⯝㤵㡰⦐G Not doing so may result in a serious injury due to an electric shock. following locations. Not doing so may result in damage to the product. -A4110 and -A4150) 䚝⏼␘U Wiring work must be carried out only by qualified personnel. Not Locations subject to static electricity or other forms of noise. · Suitable for use on a circuit capable of delivering not more than 100,000 doing so may result in a serious injury due to an electric shock. Locations subject to strong magnetic fields. rms Symmetrical Amperes, 240 or 480 Volts Maximum. Be sure to ground the unit. Not doing so may result in a serious injury Locations close to power lines. · When Protected by CC, G, J, or R Class Fuses, or when Protected By A due to an electric shock or fire. · If a parameter is set incorrectly when starting up, adjusting, maintaining, Circuit Breaker Having An Interrupting Rating Not Less Than 100,000 (200V class:type-D grounding, 400V class:type-C grounding) or replacing, an unexpected operation may occur. Perform the operation rms Symmetrical Amperes, 240 or 480 Volts Maximum. Do not remove the front cover during the power supply and 10 minutes after enough confirmation. · Install device in pollution degree 2 environment. after the power shutoff. Doing so may result in a serious injury due to · When using DriveProgramming, confirm that the program data is · Maximum surrounding air temperature rating of 50°C an electric shock. downloaded normally before starting operation. · Solid State motor overload protection reacts with max. 150 % of FLA. Do not operate the Operator or switches with wet hands. · Integral solid state short circuit protection does not provide branch circuit Doing so may result in a serious injury due to an electric shock. Main Circuit Power Supply protection. Branch circuit protection must be provided in accordance with Inspection of the Inverter must be conducted after the power supply · Confirm that the rated input voltage of the Inverter is the same as AC the National Electric Code and any additional local codes. has been turned off. Not doing so may result in a serious injury due to power supply voltage. · Motor over temperature protection is not provided by the drive. an electric shock. The main power supply is not necessarily shut off even if the Operation and Adjustment AVERTISSEMENT: ne retirez pas le capot avant pendant l’alimentation emergency shut off function is activated. · Be sure to confirm the permissible range of motors and machines before et 10 minutes après l’arrêt de l’alimentation. Cela peut entraîner de Do not change wiring, slide switches, optional devices, or replace operation because the inverter speed can be changed easily from low to grave blessure due à un choc électrique. cooling fans while power is being supplied. high. Doing so may result in a serious injury due to an electric shock. · Provide a separate holding brake if necessary. · If the DriveProgramming stops during multi-function output, the output Fuse Size Do not touch the Inverter fins, braking resistors and the motor, which status is held. Take safety precautions such as stopping peripheral The Inverter shall be connected with a UL Listed Cartridge Nonrenewable become too hot during the power supply and for some time after the power shutoff. Doing so may result in a burn. devices. fuse, rated 600Vac with the current ratings as shown in the table below. · Even if the inverter power supply is turned off, the counter-electromotive Model No. Type Rating force occurs while the PM motor rotates, which may result in electric shock. 3G3MX2-AB001, -AB002, -AB004 Class J 10A, AIC 200kA SUITABILITY FOR USE 3G3MX2-AB007 20A, AIC 200kA CAUTION Do not remove the terminal block cover of the inverter until the PM motor stops. 3G3MX2-AB015 3G3MX2-AB022 30A, AIC 200kA 30A, AIC 200kA Omron Companies shall not be responsible for conformity Do not connect resistors to the terminals (PD/+1, P/+2, N/-) directly. 3G3MX2-A2001, -A2002, -A2004 10A, AIC 200kA with any standards, codes or regulations which apply to Doing so might result in a small-scale fire, heat generation or damage Maintenance and Inspection the combination of the product in the buyer’s application 3G3MX2-A2007, -A2015 15A, AIC 200kA to the unit. Install a stop motion device to ensure safety. Not doing so might result · Be sure to confirm safety before conducting maintenance, inspection or 3G3MX2-A2022 20A, AIC 200kA or use of the product. parts replacement. 3G3MX2-A2037 30A, AIC 200kA At buyer’s request, Omron will provide applicable third party certification in a minor injury. (A holding brake is not a stop motion device designed 3G3MX2-A2055, -A2075 60A, AIC 200kA · The life of the capacitor depends on the ambient temperatures. documents identifying ratings and limitations of use which apply to the product. to ensure safety.) 3G3MX2-A2110, -A2150 80A, AIC 200kA Refer to the product life curve shown in User’ s Manual. This information by itself is not sufficient for a complete determination of the Be sure to use a specified type of braking resistor / regenerative 3G3MX2-A4004, -A4007, -A4015, -A4022 10A, AIC 200kA When the capacitor stops operating at the end of its service life, the suitability of the product in combination with the end product, machine, system, braking unit. In case of a braking resistor, install a thermal relay that 3G3MX2-A4030, -A4040 15A, AIC 200kA or other application or use. Buyer shall be solely responsible for determining Inverter must be replaced. monitors the temperature of the resistor. Not doing so might result in a 3G3MX2-A4055, -A4075 30A, AIC 200kA appropriateness of the particular product with respect to Buyer’s application, moderate burn due to the heat generated in the braking resistor / 3G3MX2-A4110, -A4150 50A, AIC 200kA product or system. Buyer shall take application responsibility in all cases. regenerative braking unit. Configure a sequence that enables the Precautions for Correct Use NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS Inverter power to turn off when unusual overheating is detected in the Terminal symbols and Screw size RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT braking resistor / regenerative braking unit. Installation ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO · Mount the product vertically on a wall with the product’ s longer sides Model No. Screw Required Wire Range The Inverter has high voltage parts inside which, if short-circuited, ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY Size Torque(N-m) might cause damage to itself or other property. Place covers on the upright. RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL 3G3MX2-AB001, -AB002, -AB004 M3.5 1.0 AWG16 (1.3 mm2) openings or take other precautions to make sure that no metal objects The material of the wall has to be nonflammable such as a metal plate. EQUIPMENT OR SYSTEM. such as cutting bits or lead wire scraps go inside when installing and 3G3MX2-AB007 M4 1.4 AWG12 (3.3 mm2) wiring. Error Retry Function 3G3MX2-AB015, -AB022 M4 1.4 AWG10 (5.3 mm2) · Do not come close to the machine when using the error retry function Take safety precautions such as setting up a molded-case circut 3G3MX2-A2001, -A2002, -A2004, -A2007 M3.5 1.0 AWG16 (1.3 mm2) because the machine may abruptly start when stopped by an alarm. breaker(MCCB) that matches the Inverter capacity on the power · Be sure to confirm the RUN signal is turned off before resetting the alarm 3G3MX2-A2015 M4 1.4 AWG14 (2.1 mm2) OMRON Corporation Industrial Automation Company supply side. Not doing so might result in damage to property due to because the machine may abruptly start. 3G3MX2-A2022 AWG12 (3.3 mm2) Tokyo, JAPAN the short circuit of the load. M4 1.4 Do not dismantle, repair or modify the product. Non-Stop Function at Momentary Power Interruption 3G3MX2-A2037 M4 1.4 AWG10 (5.3 mm2) Contact: www.ia.omron.com Doing so may result in an injury. Regional Headquarters · Do not come close to the machine when selecting reset in the non-stop 3G3MX2-A2055, -A2075 M5 3.0 AWG6 (13 mm2) OMRON EUROPE B.V. OMRON ELECTRONICS LLC function at momentary power interruption selection (b050) because the 3G3MX2-A2110 Wegalaan 67-69, NL-2132 JD One Commerce Drive Schaumburg, M6 3.9 to 5.1 AWG4 (21 mm2) machine may abruptly start after the power is turned on. Hoofddorp IL 60173-5302 U.S.A. 3G3MX2-A2150 M8 5.9 to 8.8 AWG2 (34 mm2) The Netherlands Tel: (1) 847-843-7900 Tel: (31)2356-81-300 Fax: (1) 847-843-7787 Operation Stop Command 3G3MX2-A4004, -A4007, -A4015 M4 1.4 AWG16 (1.3 mm2) Fax: (31)2356-81-388 · Provide a separate emergency stop switch because the STOP Key on 3G3MX2-A4022, -A4030 M4 1.4 AWG14 (2.1 mm2) OMRON (CHINA) CO., LTD. the Operator is valid only when function settings are performed. OMRON ASIA PACIFIC PTE. LTD. Room 2211, Bank of China Tower, 3G3MX2-A4040 M4 1.4 AWG12 (3.3 mm2) No. 438A Alexandra Road # 05-05/08 200 Yin Cheng Zhong Road, · When checking a signal during the power supply and the voltage is (Lobby 2), Alexandra Technopark, Pu Dong New Area, Shanghai, 3G3MX2-A4055, -A4075 M5 3.0 AWG10 (5.3 mm2) erroneously applied to the control input terminals, the motor may start Singapore 119967 200120, China abruptly. Be sure to confirm safety before checking a signal. 3G3MX2-A4110, -A4150 M6 3.9 to 5.1 AWG6 (13 mm2) Tel: (65) 6835-3011 Tel: (86) 21-5037-2222 Fax: (65) 6835-2711 Fax: (86) 21-5037-2200
Note: Specifications subject to change without notice.