3G3MX2- W W1 H H1 D Parameter Function name Monitor or data range Parameter Function Monitor or data range

No. No. name


AB001-E, AB002-E 109
A2001-E, A2002-E d001 Output frequency monitor 0.00 to 400.0 C001 Multi-function 00:FW(forward RUN/Stop) /01:RV(reverse RUN/Stop) /02:CF1(Multi-
to C007 input 1 to 7 speed Select, Bit0(LSB)) / 03:CF2(Multi-speed Select, Bit1) /04: CF3
3G3MX2-…-E AB004-E
A2004-E
68 56 128 118
122.5
d002
d003
Output current monitor
Rotation direction monitor
0.0 to 655.3
F: forward /o: stop /r: reverse
selection (Multi-speed Select, Bit2) /05:CF4(Multi-speed Select, Bit3(MSB)) /
06:JG(jogging) /07:DB(External DC braking) /08:SET(Set (select) 2nd
Multi-function Compact Inverter A2007-E 145.5 d004 PID feedback value monitor 0.00 to 9999. Motor Data) /09:2CH(2-stage Acceleration and Deceleration) /11:FRS
(Freerun Stop) /12:EXT(External Trip) /13:USP(Unattended Start
A4004-E 143.5 d007 Output frequency monitor 0.00 to 9999. Protection) /14:CS(Commercial power source switchover) /15:SFT

INSTRUCTION MANUAL AB007-E, AB015-E, AB022-E


A2015-E, A2022-E, A4007-E
108 96 128 118
170.5 d008
(after conversion)
Real frequency monitor -400. to 400.
(Software Lock) /16:AT(Analog Input Voltage/Current Select) /18:RS
(Reset Inverter) /19:PTC(PTC thermistor Thermal Protection(C005
only)) /20:STA(Start(3-wire interface)) /21:STP(Stop(3-wire interface)) /
A4015-E, A4022-E, A4030-E d009 Torque reference monitor -200. to +200.
22:F/R(FWD, REV(3-wire interface) /23:PID(PID Disable) /24:PIDC
Thank you for purchasing 3G3MX2 Inverter. A2037-E d010 Torque bias monitor -200. to +200. (PID Reset) /27:UP(UP/DWN function accelerated) /28:DWN(UP/DWN
To ensure the safe operation, please be sure to read the safety 140 128 128 118 170.5 d012 Output torque monitor -200. to +200. function decelerated) /29:UDC(Remote Control Data Clearing) /
A4040-E
d013 Output voltage monitor 0. to 600. 31:OPE(Operator Control) /32:SF1(Multi-speed Selection, Bit operation
precautions provided in this document along with all of the user A2055-E, A2075-E Bit1) /33:SF2(Multi-speed Selection, Bit operation Bit2) /34:SF3
140 122 260 248 155 d014 Input power monitor 0.0 to 100.0
manuals for the inverter. Please be sure you are using the most A4055-E, A4075-E (Multi-speed Selection, Bit operation Bit3) /35:SF4(Multi-speed
A2110-E d015 Integrated power monitor 0.0 to 9999. Selection, Bit operation Bit4) /36:SF5(Multi-speed Selection, Bit
recent versions of the user manuals. Keep this instruction manual 180 160 296 284 175 d016 Total RUN time 0.0 to 9999. operation Bit5) /37:SF6(Multi-speed Selection, Bit operation Bit6) /
A4110-E, A4150-E
and all of the manuals in a safe location and be sure that they are d017 Power ON time 0.0 to 9999.
38:SF7(Multi-speed Selection, Bit operation Bit7) /39:OLR(Overload
A2150-E 220 192 350 336 175 Restriction Source Changeover) /40:TL(Torque Limit Selection) /
readily available to the final user of the products. [mm] d018 Fin temperature monitor -20.0 to 150.0 41:TRQ1(Torque limit switch1) /42:TRQ2(Torque limit switch2) /
d029 Position command monitor -268435455 to 268435455 44:BOK(Brake confirmation) /46:LAC(LAD cancellation) /47:PCLR
„Standard Connection Diagram (Displays MSB 4 digits including) (Pulse counter clear) /50:ADD(ADD frequency enable) /51:F-TM
Manual Name Cat.No. ELB (Force Terminal Mode) /52:ATR(Enable torque command Input) /
MC d030 Current position monitor -268435455 to 268435455 53:KHC(Clearance of cumulative power data) /56:MI1(General
MX2 Series User’ s Manual I570-E2 Single-phase/ R/L1(L1) (Displays MSB 4 digits including) purpose input1) /57:MI2(General purpose input2) /58:MI3(General
U/T1
3-phase S/L2
power supply T/L3(N) V/T2 M d080 Fault counter 0. to 9999. purpose input3) /59:MI4(General purpose input4) /60:MI5(General
3~ d081 Fault monitor1 (latest) Error code (condition of occurrence) purpose input5) /61:MI6(General purpose input6) /62:MI7(General
P24 W/T3
Motor to d086 ~ Fault monitor6 ĺ2XWSXWIUHTXHQF\ĺ2XWSXWFXUUHQW purpose input7) /65:AHD(Analog command hold) /66:CP1(Multistage-
Short-circuit PLC Short-circuit bar
bar ĺ,QWHUQDO'&YROWDJHĺ581WLPHĺ21WLPH position switch1) /67:CP2(Multistage-position switch2) /68:CP3
L DCL To connect the DC (Multistage-position switch3) /69:ORL(Limit signal of homing) /
OMRON Corporation Multi-function input
7/EB
PD/+1
reactor (DCL), remove
d090 Warning monitor Warning code 70:ORG(Trigger signal of homing) /73:SPD(Speed/position
changeover) /77:GS1(GS1 input(C003 only)) /78:GS2(GS2 input
(7 contacts) the short-circuit bar. d102 DC voltage monitor 0.0 to 999.9
©OMRON Corporation 2012 All Rights Reserved. 2272699-9B NT321XC-EN In case two or more 6 P/+
(C004 only)) /81:485(Start EzCOM) /82:PRG(Executing Drive
d103 Regenerative braking load 0.0 to 100.0
inverters are connected 5/PTC RB Programming) /83:HLD(Retain output frequency) /84:ROK(Permission
rate monitor
Names of Parts to common I/O wiring,
special care to be taken
4/GS2
N/-
Braking resistor
d104 Electronic thermal monitor 0.0 to 100.0
of Run command) /85:EB(Rotation direction detection(C007 only)) /
86:DISP(Display limitation) /91:PSET(Preset)
to avoid closed loop 3/GS1
AL0 F001 Output frequency setting Starting frequency to max. frequency C011 Multi-function 00: NO
circuit. Please refer to 2
USB connector (mini-B) user’ s manual. F002 Acceleration time1 0.01 to 3600. to C017 input terminal 01: NC
1 AL1 Multi-function contact output
F003 Deceleration time1 0.01 to 3600. operation
AL2 selection
10V DC power supply F004 Operator rotation direction 00: forward
Connector for NŸPLQ (7 mA max.)
H selection 01: reverse C021 Multi-function
00:RUN(RUN Signal)) /01:FA1(Frequency Arrival Type 1-Constant
Digital Operator (RJ45) Analog voltage input 12 to C022 output 11-12 Speed) /02:FA2(Frequency Arrival Type 2-Over frequency) /03:OL
A001 Frequency reference 00: Digital Operator(volume)
0 to 10 V (10 bits)
O Multi-function output selection (Overload Adovance Notice Signal1) /04:OD(Output Deviation for PID
11/EDM selection (Enable when 3G3AX-OP01 is used) /
Safety function selector switch Analog current input (2 terminals) Control) /05:AL(Alarm Signal) /06:FA3(Frequency Arrival Type 3-Set
01: Terminal /02: Digital Operator(F001) /
EDM function 4 to 20 mA (10 bits)
OI CM2 frequency) /07:OTQ(Over/under Torque Signal) /09:UV(Undervoltage) /
03: Modbus communication /04: Option /
Disable Ù Enable selector switch Pulse input 10:TRQ(Torque Limited Signal) /11:RNT(RUN Time Expired) /12:ONT
06: Pusle train frequency /07: Drive
5 to 24 V DC (Power On time Expired) /13:THM(Thermal Warning) /19:BRK(Brake
Disable Ù Enable (32 kHz max.) Programming /10: Frequency operation result
Modbus-RTU Termination resistor SP Serial communications port Release Signal) /20:BER(Brake Error Signal) /21:ZS(Zero Hz Speed
EA
selector switch Analog voltage output
(RS485/Modbus-RTU) A002 RUN command selection 01: Terminal /02: Digital Operator / Detection Signal) /22:DSE(Speed Deviation Excessive) /23:POK
0 to 10 V (10 bits) SN 03: Modbus communication /04: Option (Positioning Completion) /24:FA4(Frequency Arrival Type 4-Over
Off Ù On AM
Pulse output A003 Base frequency 30.0 to max. frequency frequency) /25:FA5(Frequency Arrival Type 5-Set frequency) /26:OL2
0 to 10 V (32 kHz max.) (Overload Advance Notice Signal2) /27:ODc(Analog Voltage Input
Connector for E0 A004 Maximum frequency Base frequency to 400. Disconnect Detection) /28:OIDc(Analog Current Output Disconnect
Control circuit Detection) /31:FBV(PID Second Stage Output) /32:NDc(Network
optional board A005 O/OI selection 00:Switch between O and OI terminals
terminal block A L 02:Switch between O terminal and keypad C026 Relay output Disconnect Detection) /33:LOG1(Logic Output Function1) /34:LOG2
potentiometer /03:Switch between OI terminal function (Logic Output Function2) /35:LOG3(Logic Output Function3) /39:WAC
Control circuit and keypad potentiometer selection (Capacitor Life Warning Signal) /40:WAF(Cooling Fan Warning Signal) /
terminal block B Type-D (200V class) 41:FR(Starting Contact Signal) /42:OHF(Heat Sink Overheat Warning) /
Multi-function contact Type-C (400V class) A019 Multi-step speed selection 00: Binary(16-step selection with 4 terminals)
01: bit (8-step selection with 7 terminals) 43:LOC(Low load detection) /44:MO1(General Output1) /45:MO2
terminal block
(General Output2) /46:MO3(General Output3) /50:IRDY(Inverter Ready
Main circuit ÚConnect a single-phase 200V AC input to terminals R/L1 and T/L3(N). A020 Multi-step speed reference 0 0.00, /Starting frequency to max. frequency Signal) /51:FWR(Forward Rotation) /52:RVR(Reverse Rotation) /
terminal block ÚFactory default settings for relay output are NC contact for AL1 and NO A021 Multi-step speed reference 1 to 15 0.00, /Starting frequency to max. frequency 53:MJA(Major Failure Signal) /54:WCO(Window Comparator for Analog
CHARGE indicator
contact for AL2. to A035 Voltage Input) /55:WCOI(Window Comparator for Analog Current
Input) /58:FREF(Frequency Command Source) /59:REF(Run
A038 Jogging frequency Starting frequency to 9.99 Command Source) /60:SETM(2nd Motor Selection) /62:EDM(STO
Keys A039 Jogging stop selection 00: Free running on jogging stop, Disabled in
operation /01: Deceleration stop on jogging
(Safe Torque Off) Performance Monitor(C021 only)) /63:OPO(Option
card output)
stop, Disabled in operation /02: DC injection
Installation and Wiring Name Description braking on jogging stop, Disabled in operation/
03: Free running on jogging stop, Enabled in
C031 to Multi-function 00:NO contact at 11, 12, AL2, NC contact at AL1
C032, C036 Relay output 01:NC contact at 11, 12, AL2, NO contact at AL1
Switches the function code group to next when operation /04: Deceleration stop on jogging H003 Motor 0.1 / 0.2 / 0.4 / 0.55 / 0.75 / 1.1 / 1.5 / 2.2 / 3.0 / 3.7 / 4.0 / 5.5 / 7.5 /
„Dimensions function code is displayed. stop, Enabled in operation /05: DC injection Capacity 11.0 / 15.0 / 18.5 [kW]
Switches to function code without data settings when braking on jogging stop, Enabled in operation H004 Motor pole 2 /4 /6 /8 /10 /12 /14 /16 /18 /20 /22 /24 /26 /28 /30 /32 /34 /36 /38 /
W data is displayed. A045 Output voltage gain 20. to 100. number 40 /42 /44 /46 /48 [pole]
W1 „Status transition A097/A098 Acceleration / Deceleration 00: Linear /01: S-shape curve /02: U-shape
pattern selection curve /03: Inverted U-shape curve /
04: EL-S-shape curve
b001 Retry selection 00: Alarm /01: 0Hz start /02: Frequency
Mode key matching start /03: Trip after frequency
matching deceleration stop /04: Active
Frequency matching
b002 Allowable momentary power 0.3 to 25.0
interruption time
H1
H

b083 Carrier frequency 2.0 to 15.0 / 10.0


b084 Initialization selection 00: Disabling /01: Clearing the trip history /
02: Initializing the data /03: Clearing the trip
history and initializing the data /04: Clearing
the trip history and initializing the data and
Drive Programming
Increment key b130 Overvoltage LAD stop function 00: Disable /01: DC voltage kept constant /
02: Acceleration enabled
Changes the set values, parameters and Commands
b131 Overvoltage LAD stop function 200V class: 330. to 395.
Decrement key level 400V class: 660. to 790.

Starts the operation. Forward / Reverse rotation


RUN key
depends on the ‘F004’ setting.

STOP/RESET Stops the operation. Functions as the Reset key


key if an error occurs.
D

Enter key Enters and stores the data.


Safety Precautions Precautions for Safe Use „Maintenance Conformance to EC Directives
· The Inverter consists of many parts, which must operate properly to
„Indications and Meanings of Safety Information „Installation and Storage maximize its capabilities. Some electronic parts require maintenance · It is necessary to use optional EMC filter to comply with EMC directive
In this user’s Manual, the following precautions and signal words Do not store or use the product in the following places. depending on their operating conditions. To ensure proper operation of (EN61800-3).
· Locations subject to direct sunlight. the Inverter over a long period of time, be sure to perform periodic · For earthing, selection of cable, and any other conditions for EMC
are used to provide information to ensure the safe use of the
· Locations subject to ambient temperature exceeding the specifications. inspections and replace parts according to their service life. compliance, please refer to the manual for installation.
3G3MX2 Inverter.
The information provided here is vital to safety. Strictly observe · Locations subject to relative humidity exceeding the specifications. (Excerpt from “Recommendations for Periodic Inspections of General-
· Locations subject to condensation due to severe temperature fluctuations. purpose Inverters” issued by JEMA)
„OMRON Corporation
the precautions provided. · Locations subject to corrosive or flammable gases. Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530, Japan
„Meanings of Signal Words · Locations subject to exposure to combustibles. „Product Disposal
· Locations subject to dust (especially iron dust) or salts. · Comply with the local ordinance and regulations when disposing of the „Omron Europe B.V.
Indicates an imminently hazardous situation which, · Locations subject to exposure to water, oil, or chemicals.
if not avoided, will result in minor or moderate injury, product. Wegalaan 67-69, NL-2132 JD Hoofddorp, The Netherlands
WARNING · Locations subject to shock or vibration.
or may result in serious injury or death. Additionally
there may be significant property damage. „Transporting, Installation and Wiring UL Cautions
Indicates a potentially hazardous situation which,
· Do not drop or apply a strong impact on the product.
The warnings and instructions in this section summarizes the procedures
Safety
Doing so may result in damaged parts or malfunction.
CAUTION if not avoided, may result in minor or moderate necessary to ensure an inverter installation complies with Underwriters For use of the drive as a safety device, to meet the requirements of the
· Do not hold by the front cover, but hold by the fins during transportation.
injury or in property damage. Laboratories guidelines. ISO13849-1, please refer to user’s manual.
· Do not connect an AC power supply voltage to the control input / output
terminals. Doing so may result in damage to the product. · Use 60/75°C Cu wire only.
„Alert Symbols in this Document · Be sure to tighten the screws on the terminal block securely. Wiring work (For models:3G3MX2-A2001, -A2002, -A2004, -A2007, -AB015, -AB022,
must be done after installing the unit body. -A4004, -A4007, -A4015, -A4022, and -A4030) For KC Marking Only
WARNING · Do not connect any load other than a three-phase inductive motor to the
U, V and W output terminals.
· Use 75°C Cu wire only.
(For models:3G3MX2-AB001, -AB002, -AB004, -AB007, -A2015, -A2022,
஛ἽGὤὤஂ㛹ⱨ㟝Gⵝ㋕䋩㐔ὤ㣄㣠ஃ G
Turn off the power supply and implement wiring correctly. 㢨Gὤὤ⏈G㛹ⱨ㟝O஛ἽPG㤸㣄䑀㤵䚝ὤὤ⦐㉐G䑄⬘㣄G❄⏈G㇠㟝㣄⏈G㢨G
· Take sufficient shielding measures when using the product in the -A2037, -A2055, -A2075, -A2110, -A2150, -A4040, -A4055,-A4075, 㥄㡸G㨰㢌䚌㐐ὤGⵈ⢰⮤SGᴴ㥉㞬㢌G㫴㜡㜄㉐G㇠㟝䚌⏈Gᶷ㡸G⯝㤵㡰⦐G
Not doing so may result in a serious injury due to an electric shock.
following locations. Not doing so may result in damage to the product. -A4110 and -A4150) 䚝⏼␘U
Wiring work must be carried out only by qualified personnel. Not Locations subject to static electricity or other forms of noise. · Suitable for use on a circuit capable of delivering not more than 100,000
doing so may result in a serious injury due to an electric shock. Locations subject to strong magnetic fields. rms Symmetrical Amperes, 240 or 480 Volts Maximum.
Be sure to ground the unit. Not doing so may result in a serious injury Locations close to power lines. · When Protected by CC, G, J, or R Class Fuses, or when Protected By A
due to an electric shock or fire. · If a parameter is set incorrectly when starting up, adjusting, maintaining, Circuit Breaker Having An Interrupting Rating Not Less Than 100,000
(200V class:type-D grounding, 400V class:type-C grounding) or replacing, an unexpected operation may occur. Perform the operation rms Symmetrical Amperes, 240 or 480 Volts Maximum.
Do not remove the front cover during the power supply and 10 minutes after enough confirmation. · Install device in pollution degree 2 environment.
after the power shutoff. Doing so may result in a serious injury due to · When using DriveProgramming, confirm that the program data is · Maximum surrounding air temperature rating of 50°C
an electric shock. downloaded normally before starting operation. · Solid State motor overload protection reacts with max. 150 % of FLA.
Do not operate the Operator or switches with wet hands. · Integral solid state short circuit protection does not provide branch circuit
Doing so may result in a serious injury due to an electric shock. „Main Circuit Power Supply protection. Branch circuit protection must be provided in accordance with
Inspection of the Inverter must be conducted after the power supply · Confirm that the rated input voltage of the Inverter is the same as AC the National Electric Code and any additional local codes.
has been turned off. Not doing so may result in a serious injury due to power supply voltage. · Motor over temperature protection is not provided by the drive.
an electric shock.
The main power supply is not necessarily shut off even if the „Operation and Adjustment AVERTISSEMENT: ne retirez pas le capot avant pendant l’alimentation
emergency shut off function is activated. · Be sure to confirm the permissible range of motors and machines before et 10 minutes après l’arrêt de l’alimentation. Cela peut entraîner de
Do not change wiring, slide switches, optional devices, or replace operation because the inverter speed can be changed easily from low to grave blessure due à un choc électrique.
cooling fans while power is being supplied. high.
Doing so may result in a serious injury due to an electric shock. · Provide a separate holding brake if necessary.
· If the DriveProgramming stops during multi-function output, the output „Fuse Size
Do not touch the Inverter fins, braking resistors and the motor, which
status is held. Take safety precautions such as stopping peripheral The Inverter shall be connected with a UL Listed Cartridge Nonrenewable
become too hot during the power supply and for some time after the
power shutoff. Doing so may result in a burn. devices. fuse, rated 600Vac with the current ratings as shown in the table below.
· Even if the inverter power supply is turned off, the counter-electromotive Model No. Type Rating
force occurs while the PM motor rotates, which may result in electric
shock.
3G3MX2-AB001, -AB002, -AB004 Class J 10A, AIC 200kA SUITABILITY FOR USE
3G3MX2-AB007 20A, AIC 200kA
CAUTION Do not remove the terminal block cover of the inverter until the PM motor
stops.
3G3MX2-AB015
3G3MX2-AB022
30A, AIC 200kA
30A, AIC 200kA
Omron Companies shall not be responsible for conformity
Do not connect resistors to the terminals (PD/+1, P/+2, N/-) directly.
3G3MX2-A2001, -A2002, -A2004 10A, AIC 200kA
with any standards, codes or regulations which apply to
Doing so might result in a small-scale fire, heat generation or damage „Maintenance and Inspection the combination of the product in the buyer’s application
3G3MX2-A2007, -A2015 15A, AIC 200kA
to the unit.
Install a stop motion device to ensure safety. Not doing so might result
· Be sure to confirm safety before conducting maintenance, inspection or 3G3MX2-A2022 20A, AIC 200kA or use of the product.
parts replacement. 3G3MX2-A2037 30A, AIC 200kA
At buyer’s request, Omron will provide applicable third party certification
in a minor injury. (A holding brake is not a stop motion device designed 3G3MX2-A2055, -A2075 60A, AIC 200kA
· The life of the capacitor depends on the ambient temperatures. documents identifying ratings and limitations of use which apply to the product.
to ensure safety.) 3G3MX2-A2110, -A2150 80A, AIC 200kA
Refer to the product life curve shown in User’ s Manual. This information by itself is not sufficient for a complete determination of the
Be sure to use a specified type of braking resistor / regenerative 3G3MX2-A4004, -A4007, -A4015, -A4022 10A, AIC 200kA
When the capacitor stops operating at the end of its service life, the suitability of the product in combination with the end product, machine, system,
braking unit. In case of a braking resistor, install a thermal relay that 3G3MX2-A4030, -A4040 15A, AIC 200kA or other application or use. Buyer shall be solely responsible for determining
Inverter must be replaced.
monitors the temperature of the resistor. Not doing so might result in a 3G3MX2-A4055, -A4075 30A, AIC 200kA appropriateness of the particular product with respect to Buyer’s application,
moderate burn due to the heat generated in the braking resistor / 3G3MX2-A4110, -A4150 50A, AIC 200kA product or system. Buyer shall take application responsibility in all cases.
regenerative braking unit. Configure a sequence that enables the Precautions for Correct Use NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
Inverter power to turn off when unusual overheating is detected in the „Terminal symbols and Screw size RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
braking resistor / regenerative braking unit. „Installation ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
· Mount the product vertically on a wall with the product’ s longer sides Model No. Screw Required Wire Range
The Inverter has high voltage parts inside which, if short-circuited, ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY
Size Torque(N-m)
might cause damage to itself or other property. Place covers on the upright. RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
3G3MX2-AB001, -AB002, -AB004 M3.5 1.0 AWG16 (1.3 mm2)
openings or take other precautions to make sure that no metal objects The material of the wall has to be nonflammable such as a metal plate. EQUIPMENT OR SYSTEM.
such as cutting bits or lead wire scraps go inside when installing and 3G3MX2-AB007 M4 1.4 AWG12 (3.3 mm2)
wiring. „Error Retry Function 3G3MX2-AB015, -AB022 M4 1.4 AWG10 (5.3 mm2)
· Do not come close to the machine when using the error retry function
Take safety precautions such as setting up a molded-case circut 3G3MX2-A2001, -A2002, -A2004, -A2007 M3.5 1.0 AWG16 (1.3 mm2)
because the machine may abruptly start when stopped by an alarm.
breaker(MCCB) that matches the Inverter capacity on the power
· Be sure to confirm the RUN signal is turned off before resetting the alarm 3G3MX2-A2015 M4 1.4 AWG14 (2.1 mm2) OMRON Corporation Industrial Automation Company
supply side. Not doing so might result in damage to property due to
because the machine may abruptly start. 3G3MX2-A2022 AWG12 (3.3 mm2)
Tokyo, JAPAN
the short circuit of the load. M4 1.4
Do not dismantle, repair or modify the product. „Non-Stop Function at Momentary Power Interruption 3G3MX2-A2037 M4 1.4 AWG10 (5.3 mm2)
Contact: www.ia.omron.com
Doing so may result in an injury. Regional Headquarters
· Do not come close to the machine when selecting reset in the non-stop 3G3MX2-A2055, -A2075 M5 3.0 AWG6 (13 mm2) OMRON EUROPE B.V. OMRON ELECTRONICS LLC
function at momentary power interruption selection (b050) because the 3G3MX2-A2110 Wegalaan 67-69, NL-2132 JD One Commerce Drive Schaumburg,
M6 3.9 to 5.1 AWG4 (21 mm2)
machine may abruptly start after the power is turned on. Hoofddorp IL 60173-5302 U.S.A.
3G3MX2-A2150 M8 5.9 to 8.8 AWG2 (34 mm2) The Netherlands Tel: (1) 847-843-7900
Tel: (31)2356-81-300 Fax: (1) 847-843-7787
„Operation Stop Command 3G3MX2-A4004, -A4007, -A4015 M4 1.4 AWG16 (1.3 mm2) Fax: (31)2356-81-388
· Provide a separate emergency stop switch because the STOP Key on 3G3MX2-A4022, -A4030 M4 1.4 AWG14 (2.1 mm2) OMRON (CHINA) CO., LTD.
the Operator is valid only when function settings are performed. OMRON ASIA PACIFIC PTE. LTD. Room 2211, Bank of China Tower,
3G3MX2-A4040 M4 1.4 AWG12 (3.3 mm2) No. 438A Alexandra Road # 05-05/08 200 Yin Cheng Zhong Road,
· When checking a signal during the power supply and the voltage is (Lobby 2), Alexandra Technopark, Pu Dong New Area, Shanghai,
3G3MX2-A4055, -A4075 M5 3.0 AWG10 (5.3 mm2)
erroneously applied to the control input terminals, the motor may start Singapore 119967 200120, China
abruptly. Be sure to confirm safety before checking a signal. 3G3MX2-A4110, -A4150 M6 3.9 to 5.1 AWG6 (13 mm2) Tel: (65) 6835-3011 Tel: (86) 21-5037-2222
Fax: (65) 6835-2711 Fax: (86) 21-5037-2200

Note: Specifications subject to change without notice.


2272699-9B NT321XC-EN