Catalogo de Controles CO2
Catalogo de Controles CO2
7000+
CO2 systems built
with Danfoss
products
www.danfoss.us/aftermarket
Why choose Danfoss for CO2?
Danfoss has pioneered CO2 technologies for both transcritical and
subcritical systems for more than ten years and has gained valuable
experience from thousands of installations across six continents.
We offer the widest range of field tested CO2 controls available today.
AKS 11 GD/DGS
AK-PC 781
AKS 2050
AKS 11
Oil
Separator
AKS 21
NRV NRV
CCMT
(ICMTS)
DMT AKS 2050
AKS 2050
GBC CCM GBC
FC 103
AKS 11
AKS 2050
NRV
AK-SM 8XX/
AKVH AK-SM 350/
AK-SM 720/
AKS 2050 AKA 245
NRV
GBC
DCR AK-CC 550A AKS 11
GBC
AKS 11
AKS 2050
FC 103
NRV
AKVH
AKS 11
AKS 32R NRV
AK-CC 550A AKS 2050
GBC AKS 11
R64-2105.11
Danfoss
GBC
R64-2106.11
Danfoss
FC 103
AK-PC 783
AKS 32R
AKS 11
FC 103
DCR
AKS 11 AKS 11
AK-CC 450
AKS 2050
AKS 11
AKS 11
Pump
EVRH
SGN
FC 103
AKS 32 R AK-CC 550 A
DCR
AKS 11
GD/DGS AKS 32R
AKVH
AKS 11
HP vapour refrigerant
HP Liquid refrigerant
LP vapour refrigerant
Filter Driers............................................................................................................................................ 6
DCR Filter Driers............................................................................................................................................................................................ 6
DCR Cores & Gaskets................................................................................................................................................................................... 6
Pressure Switches.................................................................................................................................. 7
Type KP............................................................................................................................................................................................................. 7
Check Valves.......................................................................................................................................... 7
Type NRV......................................................................................................................................................................................................... 7
Solenoid Valves...................................................................................................................................... 8
EVR Valves....................................................................................................................................................................................................... 8
EVRH Valves.................................................................................................................................................................................................... 8
Temperature Transducers................................................................................................................... 14
Type AKS........................................................................................................................................................................................................14
AKS Spare Parts and Accessories..........................................................................................................................................................14
Filter Driers, type DCR, DCR filter driers with replaceable solid cores are used in liquid and/or suction lines in refrigeration and
and Cores, type DM air conditioning systems. The shells featured below have been designed for high pressure refrigerants.
DM cores contain 100% molecular sieve. They provide high moisture adsorption and protect against
system impurities.
KP Pressure Switches
Danfoss Danfoss Pressure Weight Reset Regulation Range Range Differential Max. Working
Type Code No. Connection Type (oz.) Function (psig) (°F) (psi) Pressure (psig)
KP 6W 060-519066 Flare – ¼, male 11 Auto 116 – 610 −15° to 150° 58 – 145 675
KP 6B 060-519166 Flare – ¼, male 10 Man. 116 – 610 −15° to 150° 58 675
Check Valves, NRV check valves can be used in liquid, suction, and hot gas lines in refrigeration and air conditioning
type NRV applications. They ensure that refrigerant flows in the correct direction. A built-in damping piston
makes the valve suitable for installation in lines where pulsation can occur, such as in the discharge line
from the compressor. The NRV 10s H is specifically designed with a high maximum working pressure to
permit use in CO2 applications.
EVR Valves
Danfoss Danfoss Inlet Type Inlet Size Outlet Type Outlet Size Cv Value Weight w/o Coil
Type Code No. (in.) (in.) (gpm) (oz.)
EVR 2 (NC) 032F7100 solder, ODF 1
⁄4 solder, ODF 1
⁄4 0.18 6
EVR 3 (NC) 032F7105 solder, ODF 1
⁄4 solder, ODF 1
⁄4 0.31 6
EVR 3 (NC) 032F1157 solder, ODF 3
⁄8 solder, ODF 3
⁄8 0.31 6
EVR 4 (NC) 032F7110 solder, ODF 3
⁄8 solder, ODF 3
⁄8 0.70 6 1⁄2
EVR 4 (NC) 032F7111 solder, ODF 1
⁄2 solder, ODF 1
⁄2 0.70 6
EVR 6 (NC) 032F7115 solder, ODF 3
⁄8 solder, ODF 3
⁄8 0.92 6 1⁄2
EVR 6 (NC) 032F1162 solder, ODF 1
⁄2 solder, ODF 1
⁄2 0.92 6 1⁄2
EVR 6 (NC) 032F7117 solder, ODF 5
⁄8 solder, ODF 5
⁄8 0.92 7
EVR 8 (NC) 032F7121 solder, ODF 1
⁄2 solder, ODF 1
⁄2 1.30 11 1⁄2
EVR 8 (NC) 032F7122 solder, ODF 5
⁄8 solder, ODF 5
⁄8 1.30 8 1⁄2
EVR 6 (NO) 032F1164 solder, ODF 3
⁄8 solder, ODF 3
⁄8 0.92 8
EVRH Valves
Danfoss Danfoss Inlet Type Inlet Size Outlet Type Outlet Size Cv Value Weight w/o Coil
Type Code No. (in.) (in.) (gpm) (oz.)
EVRH 10 (NC) 032G1077 solder, ODF 1
⁄2 solder, ODF 1
⁄2 2.20 13 1⁄2
EVRH 15 (NC) 032G1078 solder, ODF 5
⁄8 solder, ODF 5
⁄8 3.01 22 1⁄2
EVRH 20 (NC) 032G1079 solder, ODF 7
⁄8 solder, ODF 7
⁄8 5.80 46
Type DGS
Danfoss Danfoss Refrigerant Temperature Range Supply Voltage Alarm Set Point
Type Code No. (°F) (V) (ppm)
DGS CO2 Low Temp 080Z2996 CO2 (R744) −40° to 120° 12 – 24 5000
DGS CO2 Standard Temp 080Z2995 CO2 (R744) −4° to 120° 12 – 24 5000
Flash Gas Bypass Valve, The CCM is an electrically operated valve designed specifically for operation in CO2 systems and is
type CCM capable of functioning both as an expansion valve and as a gas bypass valve with back-pressure
regulation in subcritical applications. Additional features include: precise positioning for optimal
control of intermediate pressure in transcritical CO2 systems or liquid injection in heat exchangers,
combined stainless steel butt weld and solder connections for installation in copper piped systems
and a standard M12 connector for simple and flexible connection to the motor driver.
CCM Valves
Danfoss Danfoss Connection Solder Weld Cv Value MWP
Type Code No. Standard Connection Size Connection Size (gpm) (psig)
(in.) (in.)
CCM 10 027H7188 EN10220 5
⁄8 1
⁄2 0.81 1305
CCM 20 027H7187 EN10220 7
⁄8 3
⁄4 2.14 1305
CCM 30 027H7186 EN10220 1 ⁄8 1
1 3.22 1305
CCM 40 027H7185 EN10220 1 1 ⁄8 1 5.55 1305
AKVH Valves
Danfoss Danfoss Inlet Type Inlet Size Outlet Type Outlet Size Rated Capacity Orifice Kit MWP
Type Code No. (in.) (in.) (TR) (psi)
AKVH 10-1 068F4079 solder, ODF 3
⁄8 solder, ODF 1
⁄2 0.37 Kit 0 – 3 1305
AKVH 10-2 068F4080 solder, ODF 3
⁄8 solder, ODF 1
⁄2 0.60 Kit 0 – 3 1305
AKVH 10-3 068F4081 solder, ODF 3
⁄8 solder, ODF 1
⁄2 0.97 Kit 0 – 3 1305
AKVH 10-4 068F4082 solder, ODF 3
⁄8 solder, ODF 1
⁄2 1.51 Kit 4 – 6 1305
AKVH 10-5 068F4083 solder, ODF 3
⁄8 solder, ODF 1
⁄2 2.36 Kit 4 – 6 1305
AKVH 10-6 068F4084 solder, ODF 3
⁄8 solder, ODF 1
⁄2 3.75 Kit 4 – 6 1305
AKVH Orifices
Danfoss Type Danfoss Code No.
Orifice Kit #0-#3 068F5283
Orifice Kit #4-#6 068F5284
CCMT Valves
Danfoss Danfoss Temperature Range Connection Solder Weld Cv Value Diff. Range
Type Code No. (°F) Standard Connection Size Connection Size (gpm) (psi)
(in.) (in.)
CCMT 2 027H7200 −40° to 40° EN10220 5
⁄8 1
⁄2 0.19 1305
CCMT 4 027H7201 −40° to 40° EN10220 5
⁄8 1
⁄2 0.52 1305
CCMT 8 027H7202 −40° to 40° EN10220 5
⁄8 1
⁄2 0.92 1305
CCMT 16 027H7231 −40° to 40° EN10220 1 1 ⁄8 1 1.85 1305
CCMT 24 027H7232 −40° to 40° EN10220 1 ⁄8 1
1 2.77 1305
CCMT 30 027H7233 −40° to 40° EN10220 1 1 ⁄8 1 3.70 1305
CCMT 42 027H7234 −40° to 40° EN10220 1 ⁄8 1
1 5.32 1305
ICMTS Valves
Danfoss Danfoss Connection Inlet Type Inlet Size Outlet Type Outlet Size Cv Value
Type Code No. Standard (in.) (in.) (gpm)
AK-PC Controllers
Danfoss Danfoss Function Supply Voltage Communication No. of Compressors
Type Code No. (V) Types (max.)
medium-large transcritical
AK-PC 781 080Z0186 24 LON RS485 8
(single suction)
medium-large transcritical
AK-PC 781 A 080Z0191 24 LON RS485 10
(single suction)
AK-PC 783 080Z0196 cascade system (dual suction) 24 LON RS485 4×4
AK-PC 772 080Z0200 small transcritical (dual-suction) 24 LON RS485 3×2
AK-CC Controllers
Danfoss Danfoss Supply Voltage Communication
Type Code No. (V) Types
AK-CC 550A 084B8036 115 LON RS485, Modbus
AK-CC 550A 084B8030 230 LON RS485, Modbus
AK-SM Controllers
Danfoss Danfoss Function Frequency Communication
Type Code No. (HZ) Types
AK-SM 850 080Z4001 refrigeration 50/60 LON RS485, Modbus
AK-SM 880 080Z4008 refrigeration & HVAC 50/60 LON RS485, Modbus
AK-SM 880 080Z4009 refrigeration & HVAC 50/60 LON TP78, Modbus
Electronic Controllers, The EKC 326A controller, when paired with an ICMTS valve, can be used in transcritical and CO2 systems
type EKC to regulate gas cooler (condenser) pressure and ensure that the system achieves optimal efficiency.
EKC Controllers
Danfoss Danfoss Function Supply Voltage Communication No. of Compressors
Type Code No. (V) Types (max.)
EKC 326A 084B7252 gas cooler for CO2 24 EKA 174 8
Temperature Sensors, AKS PT1000 temperature sensors utilize a platinum element to ensure optimal accuracy.
type AKS
Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.