0% found this document useful (0 votes)
165 views1 page

Chilled Water Fan Coil UnitPart-4

This document provides specifications for three ceiling cassette compact air conditioner models from FWMJCC-A. The models are the FWMJCC2BV1, FWMJCC4BV1, and FWMJCC5BV1. Key specs include nominal cooling and heating capacities, power requirements, air flow rates, dimensions, weights and installation details. Features include a slim front panel, 4-way air discharge, compact design, wireless control, and built-in drain pump.

Uploaded by

Enak Cenir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
165 views1 page

Chilled Water Fan Coil UnitPart-4

This document provides specifications for three ceiling cassette compact air conditioner models from FWMJCC-A. The models are the FWMJCC2BV1, FWMJCC4BV1, and FWMJCC5BV1. Key specs include nominal cooling and heating capacities, power requirements, air flow rates, dimensions, weights and installation details. Features include a slim front panel, 4-way air discharge, compact design, wireless control, and built-in drain pump.

Uploaded by

Enak Cenir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Ceiling Cassette Compact Type (600x600) Specification for Ceiling Cassette Compact Type

*
MODEL FWMJCC2BV1 FWMJCC4BV1 FWMJCC5BV1
AL BL
Btu/h 8500 14000 15500
NOMINAL COOLING CAPACITY
* Optional Item W 2490 4100 4540
Btu/h 6500 10000 11500
NOMINAL SENSIBLE COOLING CAPACITY
W 1910 2930 3370

NOMINAL HEATING CAPACITY Btu/h 12000 16000 18000


(ENTERING WATER TEMP. = 50°C) W 3520 4690 5280
NOMINAL TOTAL INPUT POWER W 63 64 79
NOMINAL RUNNING CURRENT A 0.28 0.28 0.35
POWER SOURCE V/Ph/Hz 220-240 / 1 / 50
REFRIGERANT TYPE N/A
AIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
BRC52A62 BRC51A62 CONTROL
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
HIGH CFM 380 400 440
FWMJCC-A
AIR FLOW MEDIUM CFM 290 310 330
LOW CFM 230 220 280
› Aesthetically attractive and slim front panel › Built in high pressure head drain pump USGPM 2.03 3.43 3.57
› 4 Way air discharge for better air distribution › Washable saranet air filter NOMINAL WATER FLOW RATE
litres/min 7.68 12.98 13.51
› Compact design › Easy-to-use wireless handset
HEAD LOSS (COOLING) kPa 19.3 26.9 28.8
› Easy installation and maintenance › Wired handset available (optional)
HEAD LOSS (HEATING) : 50°C kPa 16.8 23.9 26.5
MAX. WORKING PRESSURE kPa 1608
SURFACE AIR VELOCITY m/s 0.75 0.76 0.83
SOUND PRESSURE LEVEL (H/M/L) dBA 42 / 35 / 29 45 / 38 / 30 48 / 40 / 36
UNIT DIMENSION - ( ) WITH PANEL HXWXD mm 250 X 570 X 570 (295 X 640 X 640)
PACKING DIMENSION - ( ) PANEL HXWXD mm 316 X 630 X 630 (126 X 700 X 726)
UNIT WEIGHT (UNIT + PANEL) kg 15 + 3 17 + 3 17 + 3
CONDENSATE DRAIN SIZE mm 19.05
PIPE CONNECTION mm 19.05
TYPE TURBO FAN
DRIVE DIRECT
FAN HIGH RPM 725 810 900
FAN SPEED MEDIUM RPM 565 630 700

INDOOR UNIT
LOW RPM 460 480 610
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP20
INSULATION GRADE B
HIGH W 63 64 79
RATED
INPUT POWER MEDIUM W 51 58 73
LOW W 46 52 69
FAN MOTOR
HIGH A 0.28 0.28 0.35
RATED
RUNNING MEDIUM A 0.23 0.25 0.32
CURRENT LOW A 0.21 0.24 0.31
STARTING CURRENT A 0.32 0.30 0.47
MOTOR OUTPUT W 17 23 28
POLES 6
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
MATERIAL ALUMINIUM
COIL
FIN FACE AREA m² 0.24 0.25 0.25
ROW 1 2 2
WATER VOLUME litre 0.43 0.83 0.83
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
CASING COLOUR LIGHT GREY

MODE COOLING HEATING


ENTERING AIR TEMPERATURE 27˚C DB / 19˚C WB 20˚C DB
ENTERING WATER TEMPERATURE 7˚C 50°C (2 Pipes System)
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE 12˚C 45°C (2 Pipes System)
60°C (4 Pipes System)

ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.