E-Line: Busbar Systems 630A... 6300A
E-Line: Busbar Systems 630A... 6300A
6300A
www.eaeelectric.com
E-LINECR
CONTENTS
E-LINE CR
Introduction 2-3
Distribution & Horizontal Applications 4
Riser & Vertical Applications 5
Technical Characteristics 6-9
Order Code System 10
Standard Straight Length 11
Elbows 12-14
Standard Components 15
Expansions 16
Standard Components 17
Panel / Transformer Connections 18-21
Panel Connection Dimensions 22
Transformer Connection 23
Joint Sets 24
Horizontal & Vertical Cast Resin Busbar Applications 25
Suspension Components 26-31
Measuring a Special Length / Cast Resin Installation Tools 32
Cast Resin Busbar Horizontal Application 33
Cast Resin Busbar Vertical Applications 34
Preparation of Joint Casting Material 35
Casting Vertical and Horizontal Installation 36
Declaration 37
Certificates 38
Product Overview 39
Project Design Form 40
Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
ELINECR
Introduction
1m
2
ELINECR
High IP Rating
PE L3 L2 L1 N
The body of the E-Line CR busbar is formed using
DURACOMP a composite material of epoxy resin and pure
silica, which gives protection against external elements as
listed above.
Effective Heat Dissipation
The cast resin body gives a very effective heat dissipation
characteristic (Diagram 1).
Diagram 1
EX - Protected
ATEX as per EN 60079-0:2009, EN 60079-18:2009, EN60079-31:2009
II 2G Ex mb IIC Gb
II 2D IIIC Db
DIN 4102-12
System Integrity Under Fire
E60 Standard
E120 External Protection Support
3
ELINECR
Distribution & Horizontal Applications
Component List
4
ELINECR
Riser & Vertical Applications
As each building’s structure is different, each of the E-Line CR projects has to be specially designed.
The details on this page briefly explain the information necessary for designing the vertical installation project.
PE L3 L2 L1 N PE L3 L2 L1 N
B A
50
100
2. Floor
h= ......
I3
a= ...... 1. Floor
h= ......
I2
I1
a= ...... 1.Basement
Feeder side,
h= ......
cable or busbar
2.Basement
Figure 1
Please refer to table on
Pre-Project Design and cost Analysis page 11 for “A” size.
Before design and cost analysis can be made, please submit the following information to Number of Conductors B
(mm)
our Design Department.
3 Conductors 82
Location and Dimensions of the floor penetration where the busbar line will be 4 Conductors 100
installed. 4 ½ Conductors 118
Floor height and Floor thickness (h=... a=...) 5 Conductors 118
Vertical line feeding method (by busbar or by cable) 136
6 Conductors
Busbar Code 06 08 10 12 16 20
Standards IEC 61439-6:2012 Ed.1 ; IEC 61439-1 Ed.2:2011, TS EN 61439-1: 2011
Rated Isolation Voltage Ui V 1000
Rated Operational Voltage Ue V 1000
Rated Frequency f Hz 50
Pollution Degree
Protection Degree IP68
External Mechanical Impacts (IK Code)* 50J, greater than IK10
Protection for Safety Basic Protection (HD 60364-4-41, Clause A1)
Rated Short-time Withstand Current (1s) Icw kA rms 20 28 40 55 70 70
Rated Peak Withstand Current Ipk kA 40 58,8 84 121 154 154
Rated Short-time Withstand Current for Neutral Conductor (1s) Icw kA 12 16,8 24 33 42 42
Rated Peak Withstand Current for Neutral Conductor Ipk kA 24 33,6 50,4 72,6 88,2 88,2
Rated Short-time Withstand Current for PE Conductor (1s) Icw kA 12 16,8 24 33 42 42
Rated Peak Withstand Current for PE Conductor Ipk kA 24 33,6 50,4 72,6 88,2 88,2
Rated Power Loss at 35 °C Watt 191,9 212,9 237,3 268,6 302,6 382,8
DC Resistance at a conductor temperature of 20 °C for Phases Rphdc mW/m 0,128 0,098 0,060 0,043 0,030 0,024
DC Resistance at a conductor temperature of 20 °C for Neutral RNdc mW/m 0,132 0,101 0,062 0,044 0,031 0,025
DC Resistance at a conductor temperature of 20 °C for PE RPEdc mW/m 0,132 0,101 0,062 0,045 0,031 0,025
SECTIONS
L1,L2,L3,N mm² 240 330 480 660 960 1200
PE (5 Conductors) mm² 240 330 480 660 960 1200
Conductor Cross Section mmxmm 6x40 6x55 6x80 6x110 6x160 6x200
Busbar Weight (5 Conductors) kg/m 28 33 40,4 49,9 64,9 77
25 23 30 33 36 40 50
L3 L2 L1 N PE L3 L2 L1 N
70 100 120 120 120 120 120 100 118 100 118
-3
0,020 0,022 0,016 0,015 0,012 0,010 0,008 DU= Ö3.L.I.(R1 .Cosj+X1.Sinj) 10 V
0,026 0,029 0,020 0,019 0,016 0,013 0,010
DU = Voltage Drop (V)
0,019 0,019 0,014 0,015 0,012 0,010 0,008
L = Line Length (m)
0,032 0,035 0,024 0,024 0,020 0,016 0,013
I = Line Current or Load (A)
0,027 0,029 0,021 0,021 0,017 0,014 0,012 = Resistance (mW/m)
R1
483,8 446,5 545,4 559,1 606,5 604,8 780,0 X1 = Reactance (mW/m)
0,020 0,025 0,018 0,016 0,014 0,012 0,012 Cosj = Power Factor
0,020 0,026 0,019 0,017 0,015 0,013 0,013
0,020 0,026 0,019 0,017 0,015 0,012 0,012
(2)
Fault-loop zero-sequences impedances have been
0,052 0,050 0,035 0,030 0,025 0,022 0,017
determined according to Annex CC of IEC 61439-6.
0,052 0,052 0,036 0,031 0,026 0,023 0,017
0,052 0,052 0,037 0,030 0,026 0,024 0,017 (3)
Fault-loop resistances and reactances have been
0,066 0,065 0,045 0,038 0,032 0,028 0,021 determined according to Annex DD of IEC 61439-6.
0,068 0,068 0,048 0,039 0,034 0,029 0,022
0,069 0,068 0,048 0,039 0,033 0,030 0,022 *IK10 corresponds to impact energy of 20J according
0,041 0,041 0,028 0,024 0,022 0,014 0,014 to IEC 62262.
0,059 0,057 0,040 0,037 0,033 0,028 0,023
**Cast Resin Busbars are produced with a minimum
0,059 0,056 0,040 0,037 0,032 0,028 0,024
of 3 conductors.
7
ELINECRC
Technical Characteristics
Copper Conductor (Cu)
Rated Current In A 800 1000 1250 1600 2000
Busbar Code 08 10 12 16 20
Standards IEC 61439-6:2012 Ed.1 ; IEC 61439-1 Ed.2:2011, TS EN 61439-1: 2011
Rated Isolation Voltage Ui V 1000
Rated Operational Voltage Ue V 1000
Rated Frequency f Hz 50
Pollution Degree
Protection Degree IP68
External Mechanical Impacts (IK Code)* 50J, greater than IK10
Protection for Safety Basic Protection (HD 60364-4-41, Clause A1)
Rated Short-time Withstand Current (1s) Icw kA rms 23 32 45 60 80
Rated Peak Withstand Current Ipk kA 48,3 67,2 94,5 132 176
Rated Short-time Withstand Current for Neutral Conductor (1s) Icw kA 13,8 19,2 27 36 48
Rated Peak Withstand Current for Neutral Conductor Ipk kA 27,6 38,4 56,7 75,6 100,8
Rated Short-time Withstand Current for PE Conductor (1s) Icw kA 13,8 19,2 27 36 48
Rated Peak Withstand Current for PE Conductor Ipk kA 27,6 38,4 56,7 75,6 100,8
MEAN PHASE CONDUCTOR CHARACTERISTICS AT RATED CURRENT In
Resistance at a conductor temperature of 20 °C R 20 mW/m 0,078 0,054 0,038 0,028 0,019
Resistance at an ambient air temperature of 35 °C R mW/m 0,100 0,070 0,048 0,035 0,023
Reactance (Independent from Temperature) X mW/m 0,069 0,056 0,045 0,033 0,028
Positive and negative sequence impedances at an ambient air temperature of 35 °C Z mW/m 0,121 0,090 0,066 0,048 0,036
Positive and negative sequence impedances at an ambient air temperature of 20 °C Z 20 mW/m 0,104 0,078 0,059 0,043 0,033
Rated Power Loss at 35 °C Watt 191,8 209,7 224,5 271,1 280,8
DC Resistance at a conductor temperature of 20 °C for Phases Rphdc mW/m 0,074 0,053 0,036 0,027 0,018
DC Resistance at a conductor temperature of 20 °C for Neutral RNdc mW/m 0,077 0,055 0,038 0,028 0,018
DC Resistance at a conductor temperature of 20 °C for PE RPEdc mW/m 0,077 0,055 0,037 0,027 0,019
SECTIONS
L1,L2,L3,N mm² 240 330 480 660 960
PE (5 Conductors) mm² 240 330 480 660 960
Conductor Cross Section mmxmm 6x40 6x55 6x80 6x110 6x160
Busbar Weight (5 Conductors) kg/m 35,6 43,4 55,6 70,3 95,3
MEAN FAULT-LOOP CHARACTERISTICS
Zero-sequence Impedance
Zero-sequence impedance at a conductor temperature of 20 °C Z(0)b20phN mW/m 0,500 0,391 0,315 0,220 0,167
Zero-sequence impedance at a conductor temperature of 20 °C Z(0)b20phPE mW/m 0,502 0,402 0,305 0,222 0,165
Zero-sequence impedance at an ambient temperature of 35 °C Z(0)bphN mW/m 0,576 0,448 0,353 0,247 0,184
Zero-sequence impedance at an ambient temperature of 35 °C Z(0)bphPE mW/m 0,578 0,461 0,341 0,250 0,183
Mean Resistances and Reactances
Resistance at a conductor temperature of 20 °C Rb20phph mW/m 0,156 0,115 0,080 0,057 0,039
Resistance at a conductor temperature of 20 °C Rb20phN mW/m 0,160 0,118 0,086 0,059 0,041
Resistance at a conductor temperature of 20 °C Rb20phPE mW/m 0,161 0,119 0,083 0,059 0,041
Resistance at an ambient air temperature of 35 °C Rbphph mW/m 0,201 0,148 0,102 0,073 0,049
Resistance at an ambient air temperature of 35 °C RbphN mW/m 0,205 0,153 0,110 0,076 0,051
Resistance at an ambient air temperature of 35 °C RbphPE mW/m 0,206 0,153 0,106 0,076 0,052
Reactance (Independent from temperature) Xbphph mW/m 0,133 0,109 0,082 0,064 0,050
Reactance (Independent from temperature) XbphN mW/m 0,175 0,144 0,119 0,091 0,071
Reactance (Independent from temperature) XbphPE mW/m 0,175 0,147 0,117 0,092 0,071
Attention! The standard mounting of the Cast Resin busbar is with the conductors on edge.
This allows for the easy application of the resin at the joint.
8
2500 3000 3200 3600 4000 5000 6300 L3 L2 L1 N PE L3 L2 L1 N
25 30 32 36 40 50 63
L3 L2 L1 N PE L3 L2 L1 N
80 120 120 120 120 120 120 100 118 100 118
-3
0,015 0,014 0,012 0,011 0,009 0,007 0,005 DU= Ö3.L.I.(R1 .Cosj+X1.Sinj) 10 V
0,019 0,018 0,016 0,014 0,012 0,009 0,006
DU = Voltage Drop (V)
0,022 0,019 0,017 0,016 0,014 0,012 0,009
L = Line Length (m)
0,029 0,026 0,023 0,021 0,018 0,015 0,011 = Line Current or Load (A)
I
0,026 0,023 0,021 0,019 0,017 0,014 0,010 = Resistance (mW/m)
R1
361,9 491,4 488,4 544,3 576,0 742,5 726,3 X1 = Reactance (mW/m)
0,014 0,016 0,013 0,012 0,010 0,008 0,006 Cosj = Power Factor
0,015 0,015 0,014 0,012 0,011 0,009 0,006
0,015 0,016 0,014 0,012 0,010 0,009 0,007
(2)
Fault-loop zero-sequences impedances have been
0,032 0,033 0,025 0,020 0,019 0,015 0,011
determined according to Annex CC of IEC 61439-6.
0,034 0,035 0,026 0,021 0,020 0,016 0,013
0,034 0,034 0,026 0,021 0,020 0,016 0,013 (3)
Fault-loop resistances and reactances have been
0,041 0,044 0,032 0,026 0,025 0,020 0,014 determined according to Annex DD of IEC 61439-6.
0,043 0,046 0,033 0,028 0,027 0,021 0,016
0,043 0,045 0,034 0,028 0,026 0,021 0,016 *IK10 corresponds to impact energy of 20J according
0,040 0,039 0,031 0,027 0,027 0,021 0,017 to IEC 62262.
9
ELINECR
BUSBAR
Order Code System CONDUCTOR MATERIAL
BUSBAR CODE
PROTECTION DEGREE
CONDUCTOR CONFIGURATION
UTILISATION TYPE / FEEDER
COMPONENT
CR C 16 8 04 B TR40
Busbar Type
Upwards Elbow U
Downwards Elbow D
CRA - Al CRC - Cu Conductor Left Elbow L
Cross
Conductor Conductor Section Right Elbow R
Rated Busbar Rated Busbar
Current Code Current Code Left Horizontal Offset LH
630 06 800 08 6x40 Right Horizontal Offset RH
800 08 1000 10 6x55 Upwards Horizontal Offset UV
1000 10 1250 12 6x80 Downwards Horizontal Offset DV
1250 12 1600 16 6x110 BUSBAR CODE Upwards Left Combined Offset KUL
1600 16 2000 20 6x160 Upwards Left Combined Offset KUR
2000 20 2500 25 6x200 Downwards Left Combined Offset KDL
2500 25 - - 6x250 Downwards Right Combined Offset KDR
2250 23 30 2(6x110) Left Upwards Combined Offset KLU
3000
2(6x125)
Right Upwards Combined Offset KRU
- - 3200 32
Left Downwards Combined Offset KLD
- - 3600 36 2(6x140)
Right Downwards Combined Offset KRD
3000 30 4000 40 2(6x160)
3200 33 - - 2(6x170)
End Closure S
3600 36 5000 50 2(6x200)
Reduction RD
4000 40 - - 2(6x250)
5000 50 6300 63 3(6x200)
Tee Module T
Component
Horizontal Expansion YDT
Vertical Expansion DDT
Phase Transposition Module FDM
PROTECTION DEGREE
IP 68 8 Panel Connection P10
Upwards Panel Connection PU20
Downwards Panel Connection PD20
Number of Conductor Configuration Right Panel Connection PR30
Code Left Panel Connection PL30
Conductors L1 L2 L3 N N
Clean ½
Panel Connection P40
Earth Clean Earth
10
ELINECR
Standard Straight Length
PE
L3
Application Areas: L2
L1
Between Transformer - N
Panel Applications 3000 mm
Between Panel to Panel Applications
Generator and Compensation
Panels Feeding
PE L3 L2 L1 N
By-pass feeding
Special Feeder -X
Straight Length Sample Order:
Special Straight
CRA 20806 - X - 147
Length in (mm)
2500 A, Copper, Feeder, IP 68,
5 Conductor, 1470 mm Special Length
PE
L3
Note: L2
L1
Minimum Special Length = 450 mm N
X
PE L3 L2 L1 N
Number of B
Conductors (mm)
B
3 Conductor 82
4 Conductor 100
A A
4 ½ Conductor 118
A
5 Conductor 118 A
6 Conductor 136
118 118 118
A (mm) 90 105 130 160 210 250 300 310 340 370 410 430 490 590 730
Attention ! The standard mounting of the Cast Resin busbar is with the conductors on edge This allows for the easy application of
the resin at the joint.
11
ELINECR
Elbows
PE
L3
L2
L1 B
N
A
The dimensions given above are minimum values. Please call us for non-standard components.
Rated Current
CRA - Al (A) 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Conductors Busbar Code 06 08 10 12 16 20 25 23 - - 30 33 36 40 50
Rated Current 3600
CRC - Cu (A) 800 1000 1250 1600 2000 2500 - 3000 3200 4000 - 5000 - 6300
Conductors Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
12
ELINECR
Elbows
Number of X Y H H
Conductors (mm) (mm) (max.)
3 Conductors 407 366 732
PE 4 Conductors 425 375 750
Y
L3 4 ½ Conductors 443 384 768 X
L2
L1 5 Conductors 443 384 768
N 6 Conductors 461 393 786
Right Left - RH A
Horizontal Offset B
- LH Sample Order:
CRC 32806 - RH60
X=600 mm, 3200 A, Copper
X Feeder, IP 68, 5 Conductor
(mm)
Note: C
C=min: 150 mm, Please see the table
for max dimensions.
PE *If there is no availability using two elbows,
L3 B
L2 then this offsets will be able to used. A
L1
N
Right Left
Horizontal Offset
Upwards Downwards
Vertical Offset
The dimensions given above are minimum values. Please call us for non-standard components.
Rated Current
CRA - Al (A) 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Conductors Busbar Code 06 08 10 12 16 20 25 23 - - 30 33 36 40 50
Rated Current 3600
CRC - Cu (A) 800 1000 1250 1600 2000 2500 - 3000 3200 4000 - 5000 - 6300
Conductors Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
A (min.) (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (min.) (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
C (max.) (mm) 740 755 780 810 860 900 950 960 990 1020 1060 1080 1140 1240 1380
13
ELINECR
Elbows
Number of X Y H
Conductors (mm) (mm) (max.)
3 Conductors 407 366 732 H
PE 4 Conductors 425 375 750
L3 4 ½ Conductors 443 384 768
L2
L1 5 Conductors 443 384 768 Y
N 6 Conductors 461 393 786 X
A
Downwards Left Downwards - KUR B
Right Combined Offset - KDL Sample Order:
- KLU CRC 32806 - B - KDL
- KRD 3300 A, Copper
Feeder, IP 68, 5 Conductor
H
X
(mm)
PE
L3 Y
L2 X
L1
N
The dimensions given above are minimum values. Please call us for non-standard components.
Rated Current
CRA - Al (A) 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Conductors Busbar Code 06 08 10 12 16 20 25 23 - - 30 33 36 40 50
Rated Current 3600
CRC - Cu (A) 800 1000 1250 1600 2000 2500 - 3000 3200 4000 - 5000 - 6300
Conductors Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
A (min.) (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (min.) (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
14
ELINECR
Standard Components
C
Tee Connection -T
Sample Order:
CRC 25806 - T
2500 A, Copper,
Feeder, IP 68, 5 Conductor
A
B
PE
L3
L2
L1
N
Reduction - RD Reduction
Is used to change busbar
cross section.
Sample Order:
CRC 20806 - RD17
2000A / 1600A, Copper
Feeder, IP 68, 5 Conductor 1000 mm
Note:
Decision and selection of reduction module and
protection on lower side is under the customer's responsibility.
PE
L3
L2
L1
N
Tee Connection
Reduction
The dimensions given above are minimum values. Please call us for non-standard components. For the rated current and busbar codes please check table.
Rated Current
CRA - Al (A) 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Conductors Busbar Code 06 08 10 12 16 20 25 23 - - 30 33 36 40 50
Rated Current 3600
CRC - Cu (A) 800 1000 1250 1600 2000 2500 - 3000 3200 4000 - 5000 - 6300
Conductors Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
C (mm) 740 754 780 810 860 900 950 960 990 1020 1060 1080 1140 1240 1380
15
ELINECR
Expansions
A
stage for our recommendations. Y (mm) 266 324 382 382 440
Attention! the total length of the module should be adjusted to
118 1500mm after installation.
Vertical Expansion
Horizontal Expansion
The dimensions given above are minimum values. Please call us for non-standard components
Note:1) Horizontal Expansion unit should be used when the busbar run crosses to an adjacent building or crosses a building
expansion joint.
2) This module is used on the long busbar line (75m) where line is ended by end closure and is not fixed on the support rigidly.
3) Horizontal Expansion Joint has sufficient movement span of 25mm max.
16
ELINECR
Standard Components
118
End Closer -S
Sample Order:
CRC 25806 - S
2500 A, Copper
Feeder, IP 68, 5 Conductor
End Closer
The dimensions given above are minimum values. Please call us for non-standard components.
17
ELINECR
Panel / Transformer Connections
Panel Connection
- P10 Sample Order: 125
- TR10 CRC 25806 - P10
2500 A, Copper,
Feeder, IP 68, 5 Conductors
For Panel Feeder 195
Flexibles -F
Sample Order:
CRC 0800 - F
*It will be produced according to details
Is used for between Transformer Bushings
and Busbar connections
Is used for between panel and busbar
B
connections. *
L
B=.....mm X
Z Y
X=.....mm
Y=.....mm
Z=.....mm
ø=.....mm
Panel Connection
The dimensions given above are minimum values. Please call us for non-standard components Distance between conductors can vary in +-5mm.
18
ELINECR
Panel / Transformer Connections
A-175
Feeder, IP 68, 5 Conductor
B-175
For Panel Feeder
N
150
L1 100 100 100 100
L2
L3
PE
Upwards
Downwards
Panel Connections
Upwards Downwards
Panel Connections
The dimensions given are minimum values. Please call us for non-standard components. Please refer to the following table for current grades and busbar codes.
Rated Current
CRA - Al (A) 630 800 1000 1250 1600 2000 2500 2250 2500 - 3000 3200 3600 4000 5000
Conductors Busbar Code 06 08 10 12 16 20 25 23 - - 30 33 36 40 50
Rated Current 3600
CRC - Cu (A) 800 1000 1250 1600 2000 2500 - 3000 3200 4000 - 5000 - 6300
Conductors Busbar Code 08 10 12 16 20 25 - 30 32 36 40 - 50 - 63
A (mm) 415 430 455 485 535 575 625 635 665 695 735 755 815 915 1055
B (mm) 370 377 390 405 430 450 475 480 495 510 530 540 570 620 690
19
ELINECR
Panel / Transformer Connections
Panel Connection
The dimensions given are minimum values. Please call us for non-standard components.
20
ELINECR
Panel / Transformer Connections
150
150
150
150
150
150
150
Ø14 Ø14 Ø14 Ø14 Ø14 Ø14 Ø14
23 40
23 40
23 40
23 40
23 40
23 40
23 40
PE L3 L2 L1 N
20 27,5 20 15 20 20 25
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 100 100 100 100
40 55 80 110 160 200 250
CRA 23 CRA 30
CRC 30 CRC 32 CRC 36 CRC 40
150
150
150
150
23 40
23 40
23 40
PE L3 L2 L1 N
30 25 20 20
40 40 40 4040 40 40 40 4040 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 100 100 100 100
260 290 320 360
150
150
23 40
23 40
PE L3 L2 L1 N
30 20 30
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 100 100 100 100
380 440 540
CRA 50
CRC 63
20
23
40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 X X X X
680
Please call us for non-standard components Distance between conductors can vary +-5mm. The dimensions given above are minimum values.
21
ELINECR
Panel Connection Dimensions
Flange PE
Earth
PE L3 L2 L1 N
Number of X Y
Conductors (mm) (mm)
3 Conductors 400 355
B
A
22
ELINECR
Transformer Connection
2500 A, Copper
Feeder, IP 68, 5 Conductor
N 150
L1 Please use the tables on page 21 for
250 290 670 670 250 113
connection measurements.
L2
L3
PE
PE
For between Transformer and Panel connection applications EAE Designing department can prepare your projects on request.
Transformer Connection
The dimensions given above are minimum values. Please call us for non-standard components
23
ELINECR
Joint sets
Edgewise Horizontal Line Joint set
Aluminium Copper Conductor
Rated 4 5 Rated 4 5 Cross
Current Conductor Conductor Current Conductor Conductor Section
630 3134311 3134317 800 3134428 3134434 6*40
800 3134320 3134326 1000 3134437 3134443 6*55
1000 3134329 3134335 1250 3134446 3134452 6*80
1250 3134338 3134344 1600 3134455 3134461 6*110
1600 3134347 3134353 2000 3134464 3134470 6*160
2000 3134356 3134362 2500 3134473 3134479 6*200
2500 3134374 3134380 - - - 6*250
2250 3134365 3134371 3000 3134482 3134488 2*6*110
2500
- - - 3200 3134491 3134497 2*6*125
- - - 3600 3134500 3134506 2*6*140
3000 3134383 3134389 4000 3134509 3134515 2*6*160
3200 3134392 3134398 - - - 2*6*170
3600 3134401 3134407 5000 3134518 3134524 2*6*200
4000 3134410 3134416 - - - 2*6*250
5000 3134419 3134425 6300 3134527 3134533 3*6*200
Description Code
Silis Sand Mixture 1021601
CR Hardener (B) 1006294
CR Resin (A) 1006292
Torque Wrench 5000048
CR Spoon Brush 5000311
CR Plastic Hammer 5000310
CR Mixer 5000132
24
ELINECR
Horizontal & Vertical Cast Resin Busbar Applications
FIGURE 1 - EDGEWISE APPLICATION FIGURE 5 - CROSSING UNDER A BEAM ON
FLATWISE APPLICATION
CEILING
CEILING
500
BEAM
100
200
WALL
PE
FIGURE 2 - EDGEWISE APPLICATION FIGURE 6 - SAMPLE WALL CROSSING WITH FIRE BARRIER
CEILING
WALL
500
HOLE
PE L3 L2 L1 N
200 BUSBAR-2 BUSBAR
WALL
200
500
350 (min.)
HOLE
200
BUSBAR
WALL
BUSBAR-1 BUSBAR-2
200
PE PE
CENTRE OF
L3 L3
JOINT POINT
L2 L2
L1 L1
N N
CEILING
Attention !
For correct installation, the dimension from the busbar to
BEAM
25
ELINECR
Suspension Components
64 4
L
5
64 4
*Horizontal mounting can be used only in special cases. Please call us for non-standard dimensions.
26
ELINECR
Suspension Components
64 4
64 4
*Horizontal mounting can be used only in special cases. Please call us for non-standard dimensions.
27
ELINECR
Suspension Components
4 47
4
47
47
L
5 50
4 47
4
47
47
L
5 50
*Horizontal mounting can be used only in special cases. Please call us for non-standard dimensions.
28
ELINECR
Suspension Components
Supports
Description L Order Code
24 (mm)
T Weight Order
Description (mm) (kg./pc.) Code
130
29
ELINECR
Suspension Components
Supports
UPY
Steel T
Dowel L
Threaded
Rod
65
UPY 43
Description T L Code
(mm) (mm)
UPY
30
ELINECR
Suspension Components
Supports
L
Description L Kodu
(mm)
50
5 50
Connection Units
Steel Nut
Washer
31
ELINECR
Measuring a Special Length
After installation of standard 3m busbar lengths, special lengths ( make up pieces ) shorter than 3m may be required.
The minimum length for these special pieces is 45cm
125 125
A
Implemented Additional
Total mixture weight of 1 Bucket is 15 kg
CRA - Al CRC - Cu Conductor Resin Value
Cross
Conductor Conductor Section 4 Conductor 5 Conductor
Rated Busbar Rated Busbar Section Kg. Kg.
Current Code Current Code
630 06 800 08 6x40 15 16
800 08 1000 10 6x55 16 17
1000 10 1250 12 6x80 18 19
1250 12 1600 16 6x110 20 21
1600 16 2000 20 6x160 23 25
2000
2500
20
25
2500
-
25
-
6x200
6x250
26
29
28
31
15 kg.
2250 23 3000 30 2(6x110) 32 34
- - 3200 32 2(6x125) 34 37
- - 3600 36 2(6x140) 36 39
3000 30 4000 40 2(6x160) 38 41
3200 33 - - 2(6x170) 40 43
3600 36 5000 50 2(6x200) 43 47
4000 40 - - 2(6x250) 53 57 The quantity must be determined according to
5000 50 6300 63 3(6x200) 60 65 number of joint in the project and ordered separately.
32
ELINECR
Cast Resin Busbar Horizontal Application
1 2
The exposed end parts of the busbar are to be cleaned with The second busbar length is introduced, slacken the joint
a clean piece of cloth. After the completion of the cleaning block to allow the conductors to slide into the block. Then
process install and fix the joint block. Tighten the joint bolt tighten the joint bolt.
enough to hold the joint block in place.
mm 4
3 250
m
7c
After checking the three parts for correct alignment and the Fix the casting mould plates to the joint area of the two
distance between the two busbar lengths is 25cm, tighten joined lengths. The casting mould plates should be fitted
the joint bolt to 82nm using a calibrated torque wrench. approximately 7cm from the end of the busbar.
5 6
The casting material should be poured from the same Please refer to the assembly manual for further instructions.
position as shown.
33
ELINECR
Cast Resin Busbar Vertical Applications
1 2
The exposed end parts of the busbar are to be cleaned with The second busbar length is introduced, slacken the joint
a clean piece of cloth. After the completion of the cleaning block to allow the conductors to slide into the block. Then
process install and fix the joint block. Tighten the joint bolt tighten the joint bolt.
enough to hold the joint block in place.
4
3
mm
250
After checking the three parts for correct alignment and the Fix the casting mould plates to the joint area of the two
distance between the two busbar lengths is 25cm, tighten joined lengths. The casting mould plates should be fitted
the joint bolt to 82nm using a calibrated torque wrench. approximately 7cm from the end of the busbar.
5 6
Only fit the gaskets at the bottom of the mould plates so Please refer to the assembly manual for further instructions.
that the resin can be poured through the gap at the top of
the plates.
34
ELINECR
Preparation of Joint Casting Material
Megger test must be done at joint and the result must be
higher than 1mOhm
< 5°C STOP
Resin (A), Hardener (B) and fillers; must be stored at least < 35°C STOP
one day over (> 20 °C ).
Ambient temperature of job side must be 5°C < T amb
MW
T(°C)
<40°C < 1MW OK
< 1MW NOT OK
350 mm
150 mm + 100 mm
1 2 3
A
A
B
Filler removed from the plastic bucket Resin and hardener are mixed in plastic bucket.
and fillers have to be absolutely dry
4 5
Mix resin and hardener thoroughly with stirrer at least 1 minute. Add fillers and mix until homogeneous; at least 5 minutes.
Then application must be done within 15 minutes.
35
ELINECR
Casting Vertical and Horizontal Installation
Horizontal Application
After all adjustments are made, the megger test and the slide electrical test are performed on the combined busbar
system to ensure that there is no leakage and the material prepared in the bucket is poured into the additional zone. It is
necessary to ensure that the poured material completely fills the joint block area. After finished vibrate the joint with a
small hammer to ensure that the joint is completely filled with the resin material.
The prepared cast resin mix can be poured in once the casting mould has been
fitted.
The cast resin mix requires a setting time of 7-8 h under normal ambient
conditions..
If one bucket of resin is not enough for the joint; the second one must be
prepared and applied immediately.
Note: Cast Resin Mix must be prepared for each joint separately
and the prepared Cast Resin Mix must be applied within 15 minutes.
Vertical Application
Note: In the vertical application the moulding plates should be
supported from the bottom to ensure that the plates are secure.
36
ELINECR
Declaration
CE DECLARATION OF CONFORMITY
Product Group E-Line CR Busbar Energy Distribution System
The objects of the declaration described below is in conformity with the relevant Union harmonisation
legislation. This declaration of conformity is issued under the sole responsibility of the manufacturer.
Standard :
EN 61439-6
Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking
systems
IEC 61439-6
Low-voltage switchgear and controlgear assemblies - Part 6: Busbar trunking
systems (busways)
CE - Directive
2014/35/EU “The Low Voltage Directive”
Emre GÜRLEYEN
37
ELINECR
Certificates
38
ELINECR
Product Overview
630A ... 6300A COMPACT BUSBAR
PRODUCT OVERVIEW (E-LINE CR)
1- Standards & Certification:
- Busbar trunking system shall be designed, type tested and, manufactured in accordance with the International standard IEC 61439-6. Type
test shall be documented by independent and internationally accredited testing and certification bodies. Short circuit type tests shall be
conducted by independent and accredited testing and certification bodies. Short circuit type tests and the following 3 main type tests shall be
conducted for each current rating of the busbar system and conformity to the standards certificates obtained.
2- General Structure Of The System
The busbar system should be low impedance in accordance with the following characteristics. The tin coated conductors are arranged as a
sandwich construction inside the resin body without any air gaps.
2.2- Housing
- The housing of the busbar system shall be manufactured with specially developed cast material.
- The structure of the busbar lengths shall have conductors tin plated along their complete length within the housing.
- Multi-path busbars should be combined in a single body so that they are not separated from each other.
- Up and down, right-left turn elements, "T" and offset elements, panel, transformer and cable connectors, termination, horizontal and vertical
expansion elements should be standard in the Busbar trunking system. Special modules and different lengths busbar ducts that may be
required during the application of the project must be manufactured in a short time in accordance with standard specifications and technology.
-If busbar runs pass through the building expansion joint a horizontal expansion element shall be used in the run. In addition horizontal
expansion elements should be used every 40 m along a horizontal run.
2.4- Insulation
-Busbars shall be insulated using a mixture of specially selected silica and calcite mixed with an electrical grade epoxy resin to make a
superior composite material.
This insulation material must have a high impact resistance against external impacts.
2.6- Protection
- Protection degree of the housing and joints shall be IP68.
After installation of the busbar systemthe installation should be checked for compliance with the manufacturer’s instructions and the
requirements of the project, an insulation test should be done.Insulation resistance between all conductors and body has to be bigger than 1
megaohm.
39
40
Component List
Company :
Project :
Project No :
Name :
Date :
Signature :
Prepared by
E L E K T R İ K
CABLE TRAYS
INDOOR SOLUTIONS
SUPPORT SYSTEMS
Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
IRAQ
OMAN
SUDAN
CHILE
PERU
KENYA
LEBANON
GHANA
SUDANCHILE
YEMEN CHILEALGERIA PERU
OMAN TURKMENISTAN TURKEY
INDIA MADAGASKAR
SRI LANKA LATVIA
ETHIOPIA
FRANCE TAIWAN
GHANA UKRAINE
JAN VIETNAM
KONGO
CAMEROON ESTONIA FINLAND KUWAIT
UM IRELAND
BANGLADESH KUWAIT
THAILAND QATAR
UZBEKISTAN SYRIA ALGERIA CHINA
AR SYRIA GHANA THAILAND QATAR CAMEROON DENMARK
ONIA TANZANIA MADAGASKAR
MOROCCO
KENYA
PAKISTAN ROMANIA QAT
BELGIUM AUSTRIA GERMANY KENYA
SINGAPORE TANZANIA
TAN CZECH REP. ETHIOPIA PERU
EQ. GUINEA TURKEY OMAN VIETNAM LATVIA MACE
MEN AUSTRIAIRAQ LIBYA
OMAN AZERBAIJAN
TANZANIA MACEDONIA MADAGASKAR TUNISIA AZER
PERU SYRIA NETHERLANDS SINGAPORE POLAND TURKMENISTAN
NIGERIA LUXEMBOURG RWANDA GREECE SYRIA CROATIA SOUTH KOREA SWI
MAURITIUS GREECE THAILAND SYRIA
ND TURKEY KAZAKHSTAN
TES MYANMAR SPAINIRELAND SERBIA OMAN
SLOVENIA
KOREA UZBE
EGYPT FRANCE ETHIOPIA VIETNAMCAMEROON PAKISTAN SPAIN EGYPT VIETNAM SUDANNETHERLANDS MADAGASKAR TURKEY NIGERIAITALY RUSSIA U.KINGDOM
TAIWAN
BAHRAIN
ULGARIA GHANATURKMENISTAN CYPRUSBELARUS AZERBAIJAN SWITZERLAND VIETNAM NORWAY SERBIA U. A. EMIRATES BULGARIA SOUTH AFRICA QATAR TURKEY GREECE
PAKISTAN
GREECE SRI LANKA
MYANMAR NIGERIARUSSIA NORWAY SPAIN FRANCE DENMARK
NIGERIA POLAND U. A. EMIRATES
NA VIETNAMSOUTH KOREA
ANDS
TURKEY
HUNGARY CAMEROON
ICELAND VIETNAM
YEMEN
SWITZERLAND TURKMENISTAN YEMEN SUDAN SWITZERLAND
U. A. EMIRATES CHILE LUXEMBOURG LITHUANIA MACEDONIA TANZANIAMADAGASKA
U. A. EMIRATES MALTA SU
MACEDON
ANMAR SAUDI ARABIA YEMEN BRASIL BELGIUM POLAND BELGIUM U.KINGDOM TURKMENISTAN CZECH REP. AZERBAIJAN DENMARK
RUSSIAYE
EAE Elektrik A.S.
Akcaburgaz Mahallesi,
3114. Sokak, No:10 34522
Esenyurt - Istanbul-TURKEY
Tel: +09 (212) 866 20 00
Fax: +09 (212) 886 24 20
Please visit our website for the updated version of our catalogues.
www.eaeelectric.com
MENTAL MAN
ON
ISO
IR
AG
Y A N D EN V
s
EMENT SYSTE
9001
IEC 61439-6 14001 T E
27001
IT
AL
E 344805
M
QU S