Control Equipment Limited Precept Fire Detection/Alarm Panel and Precept Repeater Installation & Commissioning Manual
Control Equipment Limited Precept Fire Detection/Alarm Panel and Precept Repeater Installation & Commissioning Manual
List Of Contents
9. PRECEPTEN C1632 16 ZONE EXPANSION BOARD 14.7 CONFIGURABLE OPTIONS VIA DIL SWITCH
FEATURES ............................................................. 12 SELECTION ON REPEATER INTERFACE BOARD: 26
10. POWER SUPPLIES ................................................... 12 14.8 CONFIGURING THE FIRE ROUTING, FIRE
PROTECTION AND FAULT ROUTING O/PS .........26
10.1 VISUAL INDICATIONS ....................................... 12
14.9 DISABLING THE EARTH FAULT MONITORING ....26
10.2 BATTERY DISCONNECT ................................... 12
15. OPTIONAL CLOCK MODULE - CONFIGURATION AND
10.3 32 ZONE PRECEPTEN POWER SUPPLY FEATURES
SETTING ................................................................. 26
AND CONNECTIONS ......................................... 13
15.1 STANDARD MODULE ENGINEER MODE:...........26
11. INSTALLATION ....................................................... 14
15.1.1 TO ZERO THE ALARM COUNTER: ................26
11.1 ELECTRICAL SAFETY ....................................... 14
15.1.2 TO ACCESS THE ENGINEER’S CLOCK
11.2 INSTALLATION INSTRUCTIONS ......................... 15
MODULE EDIT FUNCTIONS .........................26
11.2.1 PRECEPTEN PANEL INSTALLATION
15.2 CONFIGURING THE CLOCK MODULE. ...............28
INSTRUCTIONS ........................................... 15
15.3 C1651 CLOCK MODULE PCB FEATURES .........29
11.2.2 INSTALLATION AND CONNECTION OF THE
C1631 REPEATER INTERFACE .................... 16 15.4 CLOCK MODULE ERROR MESSAGES ................29
12. COMMISSIONING .................................................... 17 15.4.1 WP DIL SWITCH ERROR MESSAGE: ...........29
12.1 INTRODUCTION ................................................ 17 15.4.2 EEPROM ERROR MESSAGE: .....................29
12.2 COMMISSIONING CHECKLIST ........................... 17 15.4.3 ROM CHECKSUM ERROR MESSAGE:..........29
12.3 AN OVERVIEW OF THE COMMISSIONING 16. MECHANICAL, ELECTRICAL & ENVIRONMENTAL
PROCEDURE ..................................................... 17 SPECIFICATION ......................................................30
12.4 PRE-COMMISSIONING WIRING CHECK............. 17 17. CONSTRUCTION PRODUCTS DIRECTIVE..................32
12.5 POWERING UP .................................................. 18
12.6 CONFIGURATION. ............................................ 18
12.6.1 BASIC DEFAULT CONFIGURATION ............. 18
12.6.2 SITE-SPECIFIC CONFIGURATION................. 18
12.7 COMMISSIONING PROCEDURE.......................... 18
12.7.1 ALARM CIRCUITS ....................................... 18
12.7.2 COMMISSIONING ZONES ............................. 18
12.7.3 COMMISSIONING THE CLASS CHANGE INPUT
.................................................................. 19
12.7.4 COMMISSIONING THE FIRE AND FAULT
ROUTING OUTPUTS .................................... 19
12.7.5 COMMISSIONING THE FIRE PROTECTION
CONTROL SIGNAL ....................................... 19
12.7.6 COMMISSIONING ANCILLARY INPUTS ......... 20
12.7.7 COMMISSIONING ANCILLARY OUTPUTS ...... 20
12.7.8 COMMISSIONING REPEATERS ..................... 20
13. USER INDICATIONS ................................................ 21
en
5. Precept - Internal Panel Views
See Figures below:
3 x Enclosure
fixing holes
Secondary earth bar Cable clip for
Removable chassis incoming mains cable
for cable screens Mains
warning /
primary
earth label
Mains terminal
block and primary
earth connection
Motherboard SW1
R0
C1631 repeater
1 2 3
CEL C1631
R1
ISSUE 0
R2
interface
[ optional]
Mains
transformer Removable chassis
1
2 DELAY/
4 MINUTES
8
Mains transformer
Batteries Motherboard
Batteries
en
Figure 1 - Precept 2/4 zone internal view
3 x Enclosure Mains
fixing holes warning/
Secondary earth bar Cable clip for
for cable screens primary
Removable chassis incoming
earth label Mains terminal
mains cable
block and primary
earth connection
C1631 repeater
ZONE ZONE ALARM AU interface
CHANG
INPUTS OUTPUTS REPEATER
ACTIV
RESE
X
CLAS
EVAC
CIRCUITS CIRCUITS
E
EVA
OUTPUTS
RST
BUZ
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
N/T
S
DIS
SC
A
B
1 2 3 4
C
SIL
O
.
.
0
.
.
1 2 3 4 + - + - + - + - 24V
V
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21
[optional]
O/ C/ C/ O/ C/ O/ N/
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - +
P
FAULT - +
P
FIRE - +
P
FIRE -
P
RESEC
9 T
0 1 2ZONE 3 4 5 6 ROUTING ROUTING PROTECTION
CIRCUITS
EXPANSION
J1
J1
J1 J1 J1
7
J1 J1 J1
6 5 4
2 1 0
7
6
J
I/O
8 7
J J
Removable chassis
J2
0
SW
1 R
Motherboard
EXPANSION
1
0
R J2
CEL C1631
ZONE
2
1 0
ISSUE 0
R
3
2
~ ~
TB23
1
J
DISPLA
J
Y
Mains
1
SW SW
INHIBIT F/P ON 2 SILENCE BEFORE
1 1
1
NLZALARM SIL &
DELAY RESET
1
2
2
DELAYRESET
ON
2 DELA
3
3
Motherboard
AUTONON-LATCH
CONFIG MINUTE
Y/
L 4 S L
4
4
ZONES
transformer
1 CONFIG I/S 2
8
5
5
ZONESM/S
CONFIG ZONAL L
6
6
ZONES
CONFIG DELAY ALARMS
PULSE NON-ALARM 3
7
7
ZONES
CONFIG DELAY ZONES
SILENT ZONE L J18
8
8
O/PS TEST 4 B
2 STAGE BUZZER
9
9
DELAYON EVAC
ALARMS DISABLE
LATCHED TB11 TB13 L
ORIG
0
1
0
1
ONLY FAULTS FS 5
N1 BATTERY - BAT + THER
1 FUSE T M
Batteries
Batteries
en
Figure 2 - Precept 8/16 internal view
3 x Enclosure
fixing holes Cable clip for Mains warning/
Mains transformer incoming primary earth Mains terminal
Secondary earth bar label
mains cable block and primary
Removable chassis for cable screens
earth connection
C1631 repeater
ZONE ZONE ALARM AUX INPUTS OUTPUTS REPEATER ZONE CIRCUITS FI
interface
CHAN
+ 17 - + 18 - + 19 - + 20 - + 21 - + 22 - + 23 - + 24 -
ACTI
RES
[optional]
GE
CIRCUITS CIRCUITS
CLA
D1
EVA
VE
ET
OUTPUTS
SS
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
AC
EV
C.
RS
BU
A
B
SC
1 2 3 4
T.
Z.
N/
DI
S.
O
SI
L.
1 2 3 4 + - + - + - + - 24V 0V
TB TB TB TB TB TB TB TB
TB TB TB TB TB TB TB TB TB TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB2 TB2 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 0 2 4 5 6 7 8 9 0 1
Removable
O/ C C/ O/ C/ O/ N/ + 25 - + 26 - + 27 - + 28 - + 29 - + 30 - + 31 - + 32 -
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - P
+ FAULT /- +
P
FIRE - +
P
FIRE -
P
RESC
9
I/O EXPANSION
CIRCUITS
J1
J1
J1 J1 J1
J1 J1 J1
7
6 5 4
2 1 0
7
8 7 6
J J J
J
1
chassis
ZONE EXPANSION J2
0
TO MOTHERBOARD
S
W1 R
1 2 3
0
R J2 J
CEL C1631
ISSUE 0
1
R 0 1
2
Motherboard
17 -32 zone
~ ~
1
J
TB2
expansion
3
DISPL
J
AY
S S
INHIBIT F/P SILENCE BEFORE
board
W1 W2
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
ON NLZ
DELAY ALARM SIL RESET
1
DELAY& RESET
ON DEL
2 MINUT
AUTO
CONFIG NON- AY/
L 4 ES L
LATCH I/S
CONFIG ZONES
1 8 2
ZONESM/S
CONFIG ZONAL J1
L
ZONES
CONFIG DELAY ALARMS
PULSE NON- 8B
3
Mains
ZONES
CONFIG ALARM
SILENT ZONES
ZONE L
2DELAY
STAGEO/PS TEST
BUZZER 4
DELAY DISABLE TB1 TB1 L
ORI ALARMS ON LATCHED
0
1
0
1
FS 1 3 5
GN1 EVAC ONLY FAULTS BATTERY - BA + THE
1 FUSE TT RM
Batteries
Batteries
en
Figure 3 - Precept 32 zone internal View
en
Figure 4 - 2/4 Zone Precept panel - General Assembly [with optional clock/timer module]
en
Figure 5 - 8/16 Zone Precept panel - General Assembly [with optional clock/timer module]
en
Figure 6 - 32 Zone Precept panel - General Assembly [with optional clock/timer module]
+ 1A 2A -
Written by: RKP
+ - 2k2 0.5W
resistor
Typical zonal
output wiring Terminal identification
Rev: 4
Schottky Diode connection diagram
16 zone - typical wiring schematic
1 2 3 4 1+ 1- 2+ 2- 3+ 3- 4+ 4- 5+ 5- 6+ 6- 7+ 7- 8+ 8- 1+ 1- 2+ 2- 3+ 3- 4+ 4 - 24V 0V Sil Evac RST Cl/C Dis Evac BAct A B Scn N/C
Lower terminal tier Zone O/Ps Zone Circuits Alarm Circuits Aux DC Inputs Outputs Repeater RST
Lower terminal tier
Checked by: AJC
Upper terminal tier Zone Circuits Aux DC Fault Routing Fire Routing Fire Protection RST Upper terminal tier
9+ 9 - 10 + 10 - 11 + 11 - 12 + 12 - 13 + 13 - 14 + 14 - 15 + 15 - 16 + 16 - 24V 0V O/+ P C/- C/+ P O/- C/+ P O/- P N/O
Fire Routing, Fault Routing & Fire Protection O/P configuration - Output specification: Fire and Fault Routing
Page 9 of 32
output wiring shown for the
When configured as monitored/powered outputs: When configured as volt-free changeover relays : monitored/powered
22/12/09
Written by: RKP Checked by: AJC
Class change
Aux
Reset N/C
Buz Active
Zone O/Ps Zone Circuits Alarm Circuits
DC
EVAC
1 2 3 4 5 6 7 8 1 2 3 4
EVAC
GND
RST
DIS
24V
SIL
0V
1 2 3 4 + - + - + - + - + - + - + - + - + - + - + - + - A B
Lower
terminal tier
Upper
terminal tier
+ - + - + - + - + - + - + - + -
O/+
C/+
C/+
24 V
0V
P
C/-
P
O/-
P
O/-
N/O
P
9 10 11 12 13 14 15 16
Zone Circuits Aux Fault Fire Fire Reset
Precept DC Routing Routing Protection
O/- = Normally Open or -ve
2 O/+ = Normally Open or +ve
4 P = Pole
C/+ = Normally Closed or +ve
8 C/- = Normally Closed or -ve
16/32
Grey fill indicates I/O available on selected panel
Zone Circuits
17 18 19 20 21 22 23 24
+ - + - + - + - + - + - + - + -
+ - + - + - + - + - + - + - + -
25 26 27 28 29 30 31 32
Zone Circuits
Zone Reset
Detection Relay
Inputs Output
J6,J7,J8
Fault Routing Connector
Output for C1632,
configuration J10,J11,J12 Zone
Fire Routing J14,J15,J16 Expansion
links
Output Fire Protection Output Board
configuration links configuration links
J1
Display C1631
Connector Repeater
Interface
Secondary
AC from
transformer
Configuration
mode enabled FS1
LED indicator Battery
Fuse J18
Power Supply LED Earth Fault
indicators: Monitoring
Battery OUTPUT OK
Terminals Link
Configuration Battery/Charger Fault
switches Configuration Charger Fault
SW1/1 to SW1/10 switches Battery Mains Fault
SW2/1 to Thermistor
SW2/10 Terminals
en
Figure 10 - C1627 Precept motherboard layout
en
10.3 32 zone Precept Power Supply Features and Connections
en
Figure 12 shows the layout of the 32 zone Precept panel power supply.
Secondary AC
Supply from
Transformer
28V, 0V DC
Power output
Mains
Fault
Output
Common
Fault
Output
en
Figure 12 - 32 zone Precept power supply layout
21. Secure the mains-in cable to the cable clamp connector on the end of the red lead onto the
adjacent the mains terminal using the cable tie positive (red) terminal of the right-hand battery.
supplied. NOTE: The clamp should be over the 28. Connect the blue battery lead between the
outer cable insulation. positive (red) terminal of the left-hand battery
22. Reinstallation of the chassis is the reverse of and the negative (black) terminal of the right-
removal. Reconnect all wires and ensure none hand battery. Note that the batteries will not
are trapped between the chassis and backbox. power the panel until the mains supply is
Do not connect the field wiring at this stage. energised.
23. Refit the door. The refitting procedure is the
11.2.2 Installation And Connection Of The
reverse of removal. Ensure that the earth strap
C1631 Repeater Interface
and ribbon cable are reconnected correctly.
24. Place the left-hand battery into the bottom of Warning: Observe anti-static precautions
the enclosure. The terminals should be 1. Ensure that the panel and repeaters are
positioned towards the centre of the enclosure powered down and the main and standby
and the battery should be adjacent to the left supplies are disconnected.
side of the backbox, fixed by the raised indents
in the backbox, one above the battery and one 2. On the fire alarm panel and each repeater,
to the right. remove the jumper link at J22 (adjacent to J9)
and fit a C1631 repeater interface to connectors
25. Place the right-hand battery into the bottom of
J13 and J9 located immediately to the left of the
the panel. The terminals should be positioned
Zone Expansion ribbon connector on the right-
towards the centre of the enclosure and the
battery should be adjacent to the right side of hand side of the C1627 motherboard. The board
the backbox located by the raised indents in the should be held in place by the 12mm high plastic
spacer provided. See Figure 10.
back box above the battery and to the left.
26. Connect the black battery lead to the power 3. Connect the RS485 data cable as shown in
supply “Batt -” [battery negative] terminal and Figure 13.
connect the red battery lead to the power 4. If the repeater is powered from the panel then
supply “Batt +” [battery positive] positive connect the Aux 24V d.c. supply from the panel
terminal [situated on the motherboard for the to the repeater.
en
Precept 2/4, 8 and 16 panels and repeater
panel or on the separate power supply board in 5. Connect the repeater mains power supply (if
en
the Precept 32 panel]. The location of the required) to the L, N and E terminals as
motherboard battery terminals are shown in described above for the panel.
Figure 10 and Figure 12. Fit the connector on Note: Use only RS485 screened data cable.
the end of the black lead onto the negative
(black) terminal of the left-hand battery. Fit the
EARTH BAR EARTH BAR
Data Cable Screen
Repeater Repeater
GND
GND
A
B
A
o Remove the circuit faults, restoring the circuit The fault relay operates.
to the healthy condition and confirm that the 5. Repeat steps 1 to 4, one zone at a time, until all
fault indication clears. the zones are commissioned.
3. Zone fire conditions 6. Any faults that are found must be traced and
o Starting with the device nearest the panel, rectified before proceeding.
operate each manual call point and detection
device on the zone in turn. 12.7.3 Commissioning the Class Change Input
o After operation of each device confirm:
1. Connect the Class Change switch to the class
The fire indication is provided on the panel change input on the motherboard.
on the correct zone.
2. Operate the class change switch and observe:
The fire alarm devices operate correctly in
i) The alarms sound for 5 seconds then stop.
line with the panel configuration.
ii) The internal buzzer on the panel does not
The Fire Routing and Fire protection outputs operate.
operate correctly in line with the panel
configuration. iii) The internal buzzer on repeaters does not
operate.
o Press the Silence Alarms and the Reset
buttons after each device test and check the 3. De-activate the class change switch
alarm clears (Manual Call Points must be
manually reset before resetting the panel). 12.7.4 Commissioning the Fire and Fault
4. Detector removal operation. Routing Outputs
o Remove the 1st detector along the zone cable 1. Remove the resistor from the Fire Routing
[counting from the panel] on zone 1 and output circuit terminals and connect the field
observe the following: wiring to the terminals, observing correct
The appropriate amber zone fault LED polarity. Check that any fault indications clear
illuminates after a few seconds.
The internal buzzer sounds 2. To operate the output, initiate a fire condition on
a zone. Check that the fire signal is received at
The fault relay operates the receiving station. Silence and reset the fire
o For non I.S. zone applications: alarm panel to clear the output.
Operate a manual call point between the 3. Remove the resistor from the Fault Routing
detector that has been removed and the EOL output circuit terminals and connect the field
capacitor. Check that the panel reacts as wiring to the terminals, observing correct
described above for a fire condition. polarity. Check that any fault indications clear
Refit the detector, reset the manual call point, after a few seconds.
press the “Silence Alarms” button and then 4. Initiate a fault condition on the fire alarm panel to
the “System Reset” button on the panel‟s signal a fault to the remote receiving station.
display board and check that the control 5. Confirm the receipt of the fault warning at the
panel returns to its normal state. receiving station.
Repeat for all detectors on the zone. 6. Open-circuit the output wiring of each circuit in
o For I.S. zone applications: turn, confirm the fire alarm panel indicates Fire
Routing and Fault Routing faults appropriately.
Remove the 1st detector in the zone cable
[counting from the panel] and operate a 7. Reconnect the cabling and confirm the faults
manual call point ensuring that the correct clear.
fire alarm condition is raised on the panel
(assuming the installation complies with 12.7.5 Commissioning the Fire Protection
BS5839). control signal
Continue to check the operation of all other 1. Ensure any fire protection equipment to be
manual call points on the zone, resetting the controlled via the Fire Protection output is locked
manual call point and silencing/resetting the off/safe before attempting any connection,
panel at each stage. testing or commissioning.
Refit the detector and check that the control 2. Remove the resistor from the Fire Protection
panel returns to its normal state. output circuit terminal and connect the field
Continue to test each of the other detectors wiring to the terminals, observing correct
in turn, checking on each removal that: polarity. Check that any fault indications clear
The appropriate amber zone fault LED after a few seconds.
illuminates 3. Initiate a fire condition on a zone to operate the
The internal buzzer sounds. output. Check that the fire signal operates the
interface relay adjacent the fire protection the alarms operate and the internal buzzer
equipment. operates on all repeaters.
4. Open-circuit the field wiring and confirm that the 3. Press the “Silence” button on the fire alarm
fire alarm panel indicates Fire Protection output panel. Check that the alarm circuits silence and
fault. the internal buzzer silences on all repeaters.
5. Reconnect the cabling and confirm the faults 4. Repeat steps 2 and 3 for each repeater.
clear. 5. Operate a Manual Call Point on zone 1 and
6. Final testing and commissioning of the loop check for correct fire indication at each repeater.
through to the fire protection equipment, 6. Press the “Silence Alarms” button on a repeater
including test [simulated] activation of the and check that the alarms are silenced and the
equipment, should be carried out at the Zone 1 fire LED is constantly illuminated on all
appropriate time in conjunction with the engineer repeater panels.
responsible for the fire protection system.
7. Press the “Reset” button on a repeater and
check that the panel and repeaters return to the
12.7.6 Commissioning ancillary inputs quiescent state.
Remote Silence Alarms, Reset and Evacuate inputs 8. Repeat steps 5 to 7 for each zone and ensure
should each be tested by the activation of the “Silence Alarms” and “Reset” operate correctly
remote equipment. The response should be verified from each repeater.
for each signal. 9. Set the DIL switches on the C1631 Repeater
Interface card in the fire alarm panel OFF (No
12.7.7 Commissioning ancillary outputs Repeaters). Check that all repeaters indicate a
“Comms. Fault”.
The correct operation of equipment connected to
the Zone Outputs, Disablement Active, Evacuate 10. Set the C1631 Repeater Interface card DIL
Active and Buzzer Active outputs should be verified switches in the fire alarm panel back to their
in turn by initiating a fire condition on each of the previous settings and check that the repeaters
appropriate zones; disabling/enabling a zone; return to normal.
operating the Evacuate button on the panel‟s 11. Set the first repeater address to 0. Check that
display. the panel indicates a “Repeater fault” and any
additional repeaters display a steady “Comms
12.7.8 Commissioning repeaters fault” LED.
12. Set the first repeater address back to normal
1. Power-up the Panel and then the Repeaters. and check that the panel and repeaters return to
Only the “Power Supply On” LEDs should be normal.
illuminated on the Panel and Repeaters.
13. Repeat steps 11 and 12 for any other connected
2. At Repeater 1, turn the Access control switch to repeaters.
“1”, and press the “Evacuate” button. Check that
2 1 : 18 : 05
LOCATION OF THE FIRE. 2. PRESS SILENCE BUZZER. 2. SELECT THE ZONE OR
2. CARRY OUT THE 3. CALL YOUR SERVICE OUTPUT USING AND . THE
REQUIRED FIRE DRILL. ENGINEER. FAULT LED WILL PULSE.
D / N OFF
3. TO SILENCE ALARMS SYSTEM FAULT 3. PRESS DISABLE OR TEST.
PRESS SILENCE ALARMS. THE PANEL IS INOPERATIVE. 4. TO RE-ENABLE, SELECT
4. TO RESET FROM THE FIRE ARRANGE FOR THE ZONE OR OUTPUT AND
CONDITION PRESS RESET. ALTERNATIVE FIRE PRESS ENABLE.
DETECTION MEASURES.
2 1 : 18 : 05
LOCATION OF THE FIRE. 2. PRESS SILENCE BUZZER. 2. SELECT THE ZONE OR
2. CARRY OUT THE 3. CALL YOUR SERVICE OUTPUT USING AND . THE
REQUIRED FIRE DRILL. ENGINEER. FAULT LED WILL PULSE.
D / N OFF
3. TO SILENCE ALARMS SYSTEM FAULT 3. PRESS DISABLE OR TEST.
PRESS SILENCE ALARMS. THE PANEL IS INOPERATIVE. 4. TO RE-ENABLE, SELECT
4. TO RESET FROM THE FIRE ARRANGE FOR THE ZONE OR OUTPUT AND
CONDITION PRESS RESET. ALTERNATIVE FIRE PRESS ENABLE.
DETECTION MEASURES.
OUTPUTS ARE INHIBITED - THE PANEL 1/8] on the motherboard and ensure that only
WILL NOT RESPOND TO ANY FIRE ALARM. one is selected to ON.
Invalid condition: Selecting any config mode
14.3 To Restore the Factory Default
switch [1/4, 1/5, 1/6, 1/7, 1/8] to the On position
Configuration for Zones & Outputs:
whilst the panel is in the fire condition.
Open the panel door and locate the DIL
o The Config LED on the motherboard will flash.
switches SW1-4 to SW1-8 on the motherboard
[Config Non-latch Zones; Config I.S. Zones; o The System Fault and Select LEDs on the
Config M/S Zones; Config Delay Zones; Config display will flash.
Delay O/Ps] and move the switch actuator on o The panel buzzer will sound.
each switch to the On position. o The Cursor indication will clear.
o The Config Enabled LED on the motherboard o Configuration will be inhibited.
will flash.
To clear the invalid condition, select the config
o The Panel‟s System Fault LED will flash and switch to OFF. Reset the fire alarm condition
the buzzer will operate. before attempting the configuration process
o Any standing fault or disablement indications again.
will clear.
o It will not be possible to enter the Select Mode. 14.6 List of configuration DIL switches and their
functions
Press the Disable button on the panel‟s display.
SW 1/1 - Inhibit F/P on NLZ:
Return DIL switches 1-4 to 1-8 to the OFF
Selects Fire Protection relay to operate or not to
position.
operate for a fire condition on any zone
o The Config Enabled LED on the motherboard configured to non-latched mode.
will clear.
o OFF Fire Protection relay operates for a fire
o The Panel‟s System Fault LED will flash and condition on any zone configured to non-
the buzzer will clear. latched mode.
o The factory default configuration [all zones as o ON: Fire Protection relay does not operate for
latching fire, non-delay, standard [non- a fire condition on any zone configured to non-
intrinsically safe] will be restored and the Fire latched mode.
Routing, Fire Protection and Sounder outputs
o [Not EN54 compliant function].
will no longer be delayed
14.4 Engineer‟s Zone/Output Configuration S/W 1/2 - Delay Alarm Sil & Rst:
Time-out Warning: o OFF: Silence and reset available as normal.
This feature is provided to prevent the panel being o ON: Prevents alarms being silenced or reset
left in the Zone/Output Configuration condition. for a period of 3 minutes after a fire alarm
1 minute after the last button press: condition occurs.
o The panel buzzer will restart. [Not EN54 compliant function].
o The Select LED will flash.
o The System Fault LED will continue flashing. SW 1/3 - Delay On Auto:
Press the Select On/Off button to continue with o OFF: Automatically turn off the delay mode
the configuration process otherwise quit the once a day at the set time [the delay mode first
configuration process as described in 14.2 step being turned on manually].
4. o ON: Automatically turn the delay mode on
once a day and off once a day at the set times.
14.5 Invalid Configuration conditions:
Requires optional clock module.
Invalid condition: If 2 or more configuration
switches on the motherboard are in the On
SW 1/4 - Config Non-Latch Zones:
position at the same time:
o OFF: Configuration mode disabled.
o The Config LED on the motherboard will flash.
o ON: Enables selected zones to be configured
o The System Fault and Select LEDs on the
to non-latching fire mode via the Engineer‟s
display will flash.
Select feature.
o The fault relay will operate.
[Not EN54 compliant function].
o The panel buzzer will sound.
o The Cursor indication will clear. SW 1/5 - Config I/S Zones:
o Configuration will be inhibited. o OFF: Configuration mode disabled.
To clear the invalid condition check the zone o ON: Enables selected zones to be configured
and output config switches [1/4, 1/5, 1/6, 1/7, to Intrinsically Safe alarm thresholds and
passive end of line fault monitoring via the Table 1 - Motherboard Delay Switch Settings
Engineer‟s Select feature. [For use with Delay S/W S/W S/W S/W
appropriate I.S. barriers/Isolators, typically 330 Duration 2/2 2/3 2/4 2/5
Ohm zener barriers or galvanic isolators]. Delay disabled Off Off Off Off
Not EN54 compliant function. 1 min On Off Off Off
2 min Off On Off Off
SW 1/6 - Config M/S Zones: 3 min On On Off Off
4 min Off Off On Off
o OFF: Configuration mode disabled.
5 min On Off On Off
o ON: Enables selected zones to be configured 6 min Off On On Off
to short circuit fire mode via the Engineer‟s 7 min On On On Off
Select feature. 8 min Off Off Off On
9 min On Off Off On
SW 1/7 - Config Delay Zones: 10 min Off On Off On
o OFF: Configuration mode disabled. On On Off On
o ON: Enables selected zones to be configured Off Off On On
to Delay Mode via the Engineer‟s Select On Off On On
feature. Off On On On
On On On On
SW 1/8 - Configure Delay O/Ps: SW 2/6 - Enable Zonal Alarms:
o OFF: Configuration mode disabled. Select the type of sounder alarm response to a
o ON: Enables the selection of outputs, via the fire condition in conjunction with the Pulse Non
Engineer‟s Select feature, to which the panel Alarm Zones switch described below. [Not EN54
delay will apply. compliant function. Provided to meet existing
customer requirements]:
SW 1/9 - 2 Stage Delay: o OFF: General Alarm Mode - all sounders
operate continuously until silenced.
o OFF: Single Stage Delay Mode.
o ON: Zonal Sounder Mode - Sounder groups for
o ON: Two Stage Delay Mode.
zones not in the alarm condition may be
selected, via the Pulse Non Alarm Zones
SW 1/10 - Alarms on Evac Only: switch [SW 2/7], to pulse or not to operate.
o OFF: Sounders operate on any fire condition Note: Zonal alarms on the 2/4 zone panel affects
including evacuate. the standard sounder circuits on the motherboard.
o ON: Selects sounders to operate only when On the 8, 16 and 32 zone panels, it affects only
the panel is in the evacuate condition. the [future] expansion module sounder circuits.
Not EN54 complaint function.
SW 2/7- Pulse Non Alarm Zones:
SW 2/1 - Silence Before Reset: Select the type of zonal sounder alarm response
Select type of reset mode. [Not EN54 compliant to a fire condition in conjunction with the Zone
function. Provided to meet existing customer Alarms switch [SW 2/6] described above. [Not
requirements]: EN54 compliant function. Provided to meet
existing customer requirements]:
o OFF: Reset available when panel is in the [un-
silenced] fire or fault condition. With the Zone Alarms switch [SW 2/6] in the On
position [Zonal Sounder Mode]:
o ON: Fire Condition Reset available only when
panel is in Alarm Silenced condition. Fault o SW2/7 OFF: Zonal sounders for zone in the
reset available when panel is in the fault fire condition operate continuously until
condition. silenced. All others are silent.
o SW2/7 ON: Zonal sounders operate
SW 2/2 to 2/5 - Delay/Minutes: continuously - all other sounders operate in
pulsed mode until silenced.
Sets the duration of the variable time delay element
[i.e. the single stage delay and stage 2 of the two
stage delay] in steps of 1 minute within the range 0- SW 2/8 - Silent Zone Test:
9 minutes. See Table 1 - Motherboard Delay Switch Select sounder response in One Man [Detector]
Settings Test Mode:
o OFF: Sounders operate once on each test.
o ON: Sounders do not respond to a zone test.
Press SELECT ↓, to access current Time Set Press SELECT ↓, to access day/night OFF Time
display: Set display:
HH:MM:SS HH flashing HH:MM:SS HH flashing
Time Set OFF Time
Press ENABLE (+) or DISABLE (-) to change Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23) HH to desired value (00 to 23)
Press SELECT ↓, Time Set display: Press SELECT ↓, OFF Time Set display:
HH:MM:SS MM flashing HH:MM:SS MM flashing
Time Set OFF Time
Press ENABLE (+) or DISABLE (-) to change Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59) MM to desired value (00 to 59)
Press SELECT ↓, Time Set display: Press SELECT ↓, OFF Time Set display:
HH:MM:SS SS flashing HH:MM:SS SS flashing
Time Set OFF Time
Press ENABLE (+) or DISABLE (-) to reset the Press ENABLE (+) or DISABLE (-) to change SS
SS value to zero. to desired value (00 to 59)
To set Day/Night Mode On Time Press SELECT ↓, to exit back to Delay On/Off
Set display:
Press SELECT ↓, to access day/night mode ON D/N ON D/N OFF
or
Time Set display: Change? Change?
HH:MM:SS HH flashing
ON Time Pressing SELECT ↓ repeats the cursor/display
changes as above.
Press ENABLE (+) or DISABLE (-) to change Pressing SELECT ↑ repeats the cursor/display
HH to desired value (00 to 23) changes as above in reverse.
15.2 Configuring the Clock Module Table 4 - C1651 Clock Module DIL Switch 1 and
The Clock Module is configured by setting Link 1 Link 1 Settings
and DIL switch 1, both located on the rear of the
C1651 Clock Module PCB [accessed by opening LINK 1
the panel door].
Position Function
NOTE: Link 1 & DIL switch 1 are only available Fitted
st
1 fire alarm time display mode
at ACCESS level 4, i.e. they can only be set by
Removed Day/Night mode
suitably trained and qualified personnel.
DIL Switch 1
Link 1 DIL
Position Function
Switch
1 Off Clock Module menu configuration disabled
Off
1 On Clock Module menu configuration enabled
1 Off No effect
On
1 On No effect
Off 2 Off Day/Night Mode and Fire Event Counter mode enabled
Day/Night Mode enabled, Fire Event Counter mode disabled.
Off 2 On
[To zero Fire Event Counter, select “On” momentarily then return to “Off.”].
st
On 2 Off 1 alarm fire time and Fire Event Counter mode enabled
st
1 alarm fire time enabled, Fire Event Counter mode disabled.
On 2 On
[To zero Fire Event Counter, select “On” momentarily then return to “Off.”].
LK1 - Select
operating mode
DIL switch S1 -
Select config mode,
reset/disable counter
en
Mains Input Precept Panel Repeater
Specification 2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Maximum Input
85W 165W 165W 240W 85W 85W 85W
Power:
Protection:
[Warning: Replace T1A T3.15A T3.15A T3.15A T1A T1A T1A
only with identical H250V H250V H250V H250V H250V H250V H250V
type & rating of [1A anti- [3.15A anti- [3.15A anti- [3.15A anti- [1A anti- [1A anti- [1A anti-
BEAB or VDE surge] surge] surge] surge] surge] surge] surge]
approved fuse]
Voltage: 230V AC +10%/-15%
Cable 2
Minimum of 1mm copper protected by a 5A fuse.
requirements:
en
Power Supply Precept Panel Repeater
Output
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Specification
Maximum Short
Term Current
1.5A 3A 3A 5A 1.5A 1.5A 1.5A
Output
(I max b)
Maximum Short
Term Current
1.5A 3A 3A 5A 1.5A 1.5A 1.5A
Output
(I max b)
Minimum Output N/A N/A
Current (PSU is integrated into the ZERO (PSU is integrated into the
(I min) motherboard) motherboard)
Voltage Output,
26.5 - 28.6V (27.3V nominal)
Mains On
Maximum Current
Output, Mains 1.5A 3A 3A 5A 1.5A 1.5A 1.5A
Failed
Voltage Output,
20.0* - 20.0* - 20.0* - 20.0* -
Mains Failed N/A
28.6V 28.6V 28.6V 28.6V
[* at full load]
Max Ripple
including switching
spikes[full
200 200 200 750 200
load/battery
disconnected]
(mV p-p)
Output Voltage Factory Set
adjustment
Output protection: Electronic current limiting
Common fault
N/A N/A N/A 25mA N/A N/A N/A
output:
Mains failed fault
N/A N/A N/A 25mA N/A N/A N/A
output:
en
Precept Panel Repeater
Battery Specification
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Battery charger output:
[Temperature
compensated float
charger] 1.5A 3A 3A 5A 1.5 A 1.5 A 1.5 A
28.6V 0.1V@-5C
26.5 V0.1V@ +40 C.
Maximum internal
resistance of battery &
charger circuit: 1 0.6 0.6 0.35 1 1 1
(Ri max)
(Ω)
Battery type:
POWERSONIC 2 off 2 off 2 off 2 off 2 off 2 off 2 off
[Warning: Replace PS1230 PS1270 PS12120 PS12170 PS1230 PS1230 PS1230
only with identical [12V 3.4Ah] [12V 7Ah] [12V 12Ah] [12V 17Ah] [12V 3.4Ah] [12V 3.4Ah] [12V 3.4Ah]
battery]
Battery size (mm):
W
L = 133 L = 151 L = 151 L = 181 L = 133 L = 133 L = 133
W = 67 W = 65 W = 98 W = 76 W = 67 W = 67 W = 67
H = 60 H = 94 H = 94 H = 167 H = 60 H = 60 H = 60
HT H
HT = 66 HT = 98 HT = 100 HT = 167 HT = 66 HT = 66 HT = 66
L
Environmental
All Panels
Specification
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%
0086
09
0086-CPD-555921
EN54-2
Control and indicating equipment for fire detection and fire alarm systems for buildings
Provided options:
Outputs to fire alarm devices.
Output to fire alarm routing equipment.
Outputs to Fire Protection Equipment - Output type B
Output to fault warning routing equipment.
Test condition.
Alarm Counter.
Delays to Outputs
EN54-4
Power supply equipment for fire detection and fire alarm systems for buildings