0% found this document useful (0 votes)
695 views32 pages

Control Equipment Limited Precept Fire Detection/Alarm Panel and Precept Repeater Installation & Commissioning Manual

The document provides installation and commissioning instructions for the Precepten Fire Detection/Alarm Panel and Precepten Repeater. It includes details on the panel's internal views, typical wiring schematics, circuit connection details, features of components like the motherboard and expansion boards, power supplies, installation, and commissioning procedures. The document contains lists of figures, tables, and contents to aid navigation.

Uploaded by

Dessouki Samak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
695 views32 pages

Control Equipment Limited Precept Fire Detection/Alarm Panel and Precept Repeater Installation & Commissioning Manual

The document provides installation and commissioning instructions for the Precepten Fire Detection/Alarm Panel and Precepten Repeater. It includes details on the panel's internal views, typical wiring schematics, circuit connection details, features of components like the motherboard and expansion boards, power supplies, installation, and commissioning procedures. The document contains lists of figures, tables, and contents to aid navigation.

Uploaded by

Dessouki Samak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Written by: RKP Checked by: AJC Approved by JBJ

Control Equipment Limited

Precepten Fire Detection/Alarm Panel

and Precepten Repeater

Installation & Commissioning Manual

Document Number: Prec en Inst Rev: 4 Page 1 of 32 22/12/09


Written by: RKP Checked by: AJC

List Of Contents

1. LIST OF FIGURES ..................................................... 3 13.1 USER INDICATIONS ..........................................21


2. LIST OF TABLES ....................................................... 3 13.2 USER CONTROLS ..............................................22
3. INTRODUCTION ........................................................ 4 14. OPERATING THE ENGINEER’S FUNCTIONS ..............23
4. OVERVIEW OF INSTALLATION AND COMMISSIONING 14.1 ENGINEER’S ZONE/OUTPUT CONFIGURATION
................................................................................ 4 PROCESS: .........................................................23
5. PRECEPTEN - INTERNAL PANEL VIEWS...................... 4 14.2 ZONE OR OUTPUT CONFIGURATION .................23
6. PRECEPTEN 16 ZONE - TYPICAL WIRING SCHEMATIC . 9 14.3 TO RESTORE THE FACTORY DEFAULT
7. CIRCUIT CONNECTION DETAILS ............................ 10 CONFIGURATION FOR ZONES & OUTPUTS: .......24
7.1 2-16 ZONE MOTHERBOARD TERMINATION 14.4 ENGINEER’S ZONE/OUTPUT CONFIGURATION
DETAILS .......................................................... 10 TIME-OUT WARNING: ......................................24
7.2 16 ZONE EXPANSION BOARD TERMINATION 14.5 INVALID CONFIGURATION CONDITIONS: ..........24
DETAILS .......................................................... 10 14.6 LIST OF CONFIGURATION DIL SWITCHES AND
8. PRECEPTEN C1627 MOTHERBOARD FEATURES ....... 11 THEIR FUNCTIONS ............................................. 24

9. PRECEPTEN C1632 16 ZONE EXPANSION BOARD 14.7 CONFIGURABLE OPTIONS VIA DIL SWITCH
FEATURES ............................................................. 12 SELECTION ON REPEATER INTERFACE BOARD: 26

10. POWER SUPPLIES ................................................... 12 14.8 CONFIGURING THE FIRE ROUTING, FIRE
PROTECTION AND FAULT ROUTING O/PS .........26
10.1 VISUAL INDICATIONS ....................................... 12
14.9 DISABLING THE EARTH FAULT MONITORING ....26
10.2 BATTERY DISCONNECT ................................... 12
15. OPTIONAL CLOCK MODULE - CONFIGURATION AND
10.3 32 ZONE PRECEPTEN POWER SUPPLY FEATURES
SETTING ................................................................. 26
AND CONNECTIONS ......................................... 13
15.1 STANDARD MODULE ENGINEER MODE:...........26
11. INSTALLATION ....................................................... 14
15.1.1 TO ZERO THE ALARM COUNTER: ................26
11.1 ELECTRICAL SAFETY ....................................... 14
15.1.2 TO ACCESS THE ENGINEER’S CLOCK
11.2 INSTALLATION INSTRUCTIONS ......................... 15
MODULE EDIT FUNCTIONS .........................26
11.2.1 PRECEPTEN PANEL INSTALLATION
15.2 CONFIGURING THE CLOCK MODULE. ...............28
INSTRUCTIONS ........................................... 15
15.3 C1651 CLOCK MODULE PCB FEATURES .........29
11.2.2 INSTALLATION AND CONNECTION OF THE
C1631 REPEATER INTERFACE .................... 16 15.4 CLOCK MODULE ERROR MESSAGES ................29
12. COMMISSIONING .................................................... 17 15.4.1 WP DIL SWITCH ERROR MESSAGE: ...........29
12.1 INTRODUCTION ................................................ 17 15.4.2 EEPROM ERROR MESSAGE: .....................29
12.2 COMMISSIONING CHECKLIST ........................... 17 15.4.3 ROM CHECKSUM ERROR MESSAGE:..........29
12.3 AN OVERVIEW OF THE COMMISSIONING 16. MECHANICAL, ELECTRICAL & ENVIRONMENTAL
PROCEDURE ..................................................... 17 SPECIFICATION ......................................................30
12.4 PRE-COMMISSIONING WIRING CHECK............. 17 17. CONSTRUCTION PRODUCTS DIRECTIVE..................32
12.5 POWERING UP .................................................. 18
12.6 CONFIGURATION. ............................................ 18
12.6.1 BASIC DEFAULT CONFIGURATION ............. 18
12.6.2 SITE-SPECIFIC CONFIGURATION................. 18
12.7 COMMISSIONING PROCEDURE.......................... 18
12.7.1 ALARM CIRCUITS ....................................... 18
12.7.2 COMMISSIONING ZONES ............................. 18
12.7.3 COMMISSIONING THE CLASS CHANGE INPUT
.................................................................. 19
12.7.4 COMMISSIONING THE FIRE AND FAULT
ROUTING OUTPUTS .................................... 19
12.7.5 COMMISSIONING THE FIRE PROTECTION
CONTROL SIGNAL ....................................... 19
12.7.6 COMMISSIONING ANCILLARY INPUTS ......... 20
12.7.7 COMMISSIONING ANCILLARY OUTPUTS ...... 20
12.7.8 COMMISSIONING REPEATERS ..................... 20
13. USER INDICATIONS ................................................ 21

Document Number: Prec en Inst Rev: 4 Page 2 of 32 22/12/09


Written by: RKP Checked by: AJC

1. List Of Figures 2. List of Tables


EN
FIGURE 1 - PRECEPT 2/4 ZONE INTERNAL VIEW .............4 TABLE 1 - MOTHERBOARD DELAY SWITCH SETTINGS... 25
FIGURE 2 - PRECEPTEN 8/16 INTERNAL VIEW .....................5 TABLE 2 - C1631 SETTING FOR QUANTITY OF REPEATERS
FIGURE 3 - PRECEPTEN 32 ZONE INTERNAL VIEW ..............5 .............................................................................. 26
FIGURE 4 - 2/4 ZONE PRECEPTEN PANEL - GENERAL TABLE 3 - C1631 SETTING FOR REPEATER ADDRESSES .. 26
ASSEMBLY [WITH OPTIONAL CLOCK/TIMER MODULE] TABLE 4 - C1651 CLOCK MODULE DIL SWITCH 1 AND
.................................................................................6 LINK 1 SETTINGS ................................................... 28
FIGURE 5 - 8/16 ZONE PRECEPTEN PANEL - GENERAL
ASSEMBLY [WITH OPTIONAL CLOCK/TIMER MODULE]
.................................................................................7
FIGURE 6 - 32 ZONE PRECEPTEN PANEL - GENERAL
ASSEMBLY [WITH OPTIONAL CLOCK/TIMER MODULE]
.................................................................................8
FIGURE 7 - TYPICAL WIRING DIAGRAM ...........................9
FIGURE 8 - C1627 FIELD TERMINATION .......................... 10
FIGURE 9 - C1632 16 ZONE EXPANSION BOARD FIELD
TERMINATION ........................................................ 10
FIGURE 10 - C1627 PRECEPTEN MOTHERBOARD LAYOUT 11
FIGURE 11 - C1632 16 ZONE EXPANSION BOARD ............ 12
FIGURE 12 - 32 ZONE PRECEPTEN POWER SUPPLY LAYOUT
............................................................................... 13
FIGURE 13 - REPEATER CONNECTION DIAGRAM ............. 16
FIGURE 14 - C1651 CLOCK MODULE PCB ..................... 29

Document Number: Prec en Inst Rev: 4 Page 3 of 32 22/12/09


Written by: RKP Checked by: AJC

3. Introduction 4. Overview of Installation and Commissioning


en This section lists the steps that are taken in
Thank you for purchasing the Precept en
en designing, installing and commissioning a Precept
conventional control panel. The Precept range of
system.
panels have been designed, manufactured and
tested to meet the requirements of BSEN 54 Parts 1. Install all field wiring and equipment
2 & 4 and will provide the user with many years of  Refer to the Installation Guidelines in section
reliable service. 11.2 below
 Refer to the field device installation manuals
This document contains all the information
necessary for the installation, commissioning and 2. Install the panel
en
maintenance of the Precept range of panels and  Refer to the installation instructions in section
repeaters. 11.2 below
NOTE: It is important to read this manual fully  Do not connect the field equipment at this
before commencing installation. stage.
The following supporting documentation is also 3. Connect any repeaters (if applicable)
available:
 Refer to the installation instructions in section
 Precept Sales Literature
en
11.2 below
 Precept
en
Panel Application Guide
4. Commission the panel
 Precept User Manual
en
 Refer to Commissioning in section 12.
 Wiring Recommendations

en
5. Precept - Internal Panel Views
See Figures below:

3 x Enclosure
fixing holes
Secondary earth bar Cable clip for
Removable chassis incoming mains cable
for cable screens Mains
warning /
primary
earth label
Mains terminal
block and primary
earth connection
Motherboard SW1

R0

C1631 repeater
1 2 3

CEL C1631

R1
ISSUE 0

R2

interface
[ optional]
Mains
transformer Removable chassis

1
2 DELAY/
4 MINUTES
8

Mains transformer

Batteries Motherboard

Batteries

en
Figure 1 - Precept 2/4 zone internal view

Document Number: Prec en Inst Rev: 4 Page 4 of 32 22/12/09


Written by: RKP Checked by: AJC

3 x Enclosure Mains
fixing holes warning/
Secondary earth bar Cable clip for
for cable screens primary
Removable chassis incoming
earth label Mains terminal
mains cable
block and primary
earth connection

C1631 repeater
ZONE ZONE ALARM AU interface

CHANG
INPUTS OUTPUTS REPEATER

ACTIV

RESE
X

CLAS

EVAC
CIRCUITS CIRCUITS

E
EVA
OUTPUTS

RST

BUZ
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.

N/T
S

DIS

SC
A
B
1 2 3 4

C
SIL

O
.

.
0

.
.
1 2 3 4 + - + - + - + - 24V
V

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21
[optional]
O/ C/ C/ O/ C/ O/ N/
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - +
P
FAULT - +
P
FIRE - +
P
FIRE -
P
RESEC
9 T
0 1 2ZONE 3 4 5 6 ROUTING ROUTING PROTECTION

CIRCUITS

EXPANSION
J1

J1
J1 J1 J1

7
J1 J1 J1

6 5 4
2 1 0
7

6
J

I/O
8 7
J J
Removable chassis

J2
0
SW
1 R

Motherboard

EXPANSION
1
0
R J2

CEL C1631

ZONE
2
1 0

ISSUE 0
R

3
2

~ ~
TB23
1
J
DISPLA

J
Y

Mains
1

SW SW
INHIBIT F/P ON 2 SILENCE BEFORE
1 1

1
NLZALARM SIL &
DELAY RESET
1
2

2
DELAYRESET
ON
2 DELA
3

3
Motherboard
AUTONON-LATCH
CONFIG MINUTE
Y/
L 4 S L
4

4
ZONES

transformer
1 CONFIG I/S 2
8
5

5
ZONESM/S
CONFIG ZONAL L
6

6
ZONES
CONFIG DELAY ALARMS
PULSE NON-ALARM 3
7

7
ZONES
CONFIG DELAY ZONES
SILENT ZONE L J18
8

8
O/PS TEST 4 B
2 STAGE BUZZER
9

9
DELAYON EVAC
ALARMS DISABLE
LATCHED TB11 TB13 L
ORIG
0
1

0
1
ONLY FAULTS FS 5
N1 BATTERY - BAT + THER
1 FUSE T M

Batteries

Batteries
en
Figure 2 - Precept 8/16 internal view

3 x Enclosure
fixing holes Cable clip for Mains warning/
Mains transformer incoming primary earth Mains terminal
Secondary earth bar label
mains cable block and primary
Removable chassis for cable screens
earth connection

C1631 repeater
ZONE ZONE ALARM AUX INPUTS OUTPUTS REPEATER ZONE CIRCUITS FI
interface
CHAN

+ 17 - + 18 - + 19 - + 20 - + 21 - + 22 - + 23 - + 24 -
ACTI

RES

[optional]
GE

CIRCUITS CIRCUITS
CLA

D1
EVA

VE

ET

OUTPUTS
SS

+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
D.C.
AC
EV

C.
RS

BU

A
B
SC

1 2 3 4
T.

Z.

N/
DI
S.

O
SI
L.

1 2 3 4 + - + - + - + - 24V 0V

TB TB TB TB TB TB TB TB
TB TB TB TB TB TB TB TB TB TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB2 TB2 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 0 2 4 5 6 7 8 9 0 1

Removable
O/ C C/ O/ C/ O/ N/ + 25 - + 26 - + 27 - + 28 - + 29 - + 30 - + 31 - + 32 -
+ - +1 - +1 - +1 - +1 - +1 - +1 - +1 - P
+ FAULT /- +
P
FIRE - +
P
FIRE -
P
RESC
9
I/O EXPANSION

0 1 2 ZONE 3 4 5 6 ROUTING ROUTING PROTECTION ET

CIRCUITS
J1
J1
J1 J1 J1
J1 J1 J1

7
6 5 4
2 1 0

7
8 7 6
J J J

J
1
chassis
ZONE EXPANSION J2
0

TO MOTHERBOARD

S
W1 R
1 2 3

0
R J2 J
CEL C1631
ISSUE 0

1
R 0 1
2

Motherboard
17 -32 zone
~ ~
1
J

TB2

expansion
3
DISPL

J
AY

S S
INHIBIT F/P SILENCE BEFORE

board
W1 W2
1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

ON NLZ
DELAY ALARM SIL RESET
1
DELAY& RESET
ON DEL
2 MINUT
AUTO
CONFIG NON- AY/
L 4 ES L
LATCH I/S
CONFIG ZONES
1 8 2
ZONESM/S
CONFIG ZONAL J1
L
ZONES
CONFIG DELAY ALARMS
PULSE NON- 8B
3

Mains
ZONES
CONFIG ALARM
SILENT ZONES
ZONE L
2DELAY
STAGEO/PS TEST
BUZZER 4
DELAY DISABLE TB1 TB1 L
ORI ALARMS ON LATCHED
0
1

0
1

FS 1 3 5
GN1 EVAC ONLY FAULTS BATTERY - BA + THE
1 FUSE TT RM

transformer 1-16 zone


Motherboard

Batteries

Batteries
en
Figure 3 - Precept 32 zone internal View

Document Number: Prec en Inst Rev: 4 Page 5 of 32 22/12/09


Written by: RKP Checked by: AJC

en
Figure 4 - 2/4 Zone Precept panel - General Assembly [with optional clock/timer module]

Document Number: Prec en Inst Rev: 4 Page 6 of 32 22/12/09


Written by: RKP Checked by: AJC

en
Figure 5 - 8/16 Zone Precept panel - General Assembly [with optional clock/timer module]

Document Number: Prec en Inst Rev: 4 Page 7 of 32 22/12/09


Written by: RKP Checked by: AJC

en
Figure 6 - 32 Zone Precept panel - General Assembly [with optional clock/timer module]

Document Number: Prec en Inst Rev: 4 Page 8 of 32 22/12/09


Typical Zone Wiring Typical Alarm Circuit Wiring Typical Input Circuit Wiring
22uF capacitor end-of-line device for Remote Silence, Evac, Reset &
-observe polarity Class Change,
-ve 3K9 resistor
end-of-line device [Normally open switch contacts]
6. Precept
en

+ 1A 2A -
Written by: RKP

Manual call point


Typical remote
with 680R resistor
output wiring
+ -
+ 1 2 -

+ - 2k2 0.5W
resistor
Typical zonal
output wiring Terminal identification

Document Number: Prec en Inst


notes:
+
Cl/C = Class Change.
+ -
B Act = Buzzer Active
Connect to - RST = Reset
24V DC Aux DC 24V
+ -
relay + Repeater Wiring - see
Detector base with Figure 9 - Repeater

Rev: 4
Schottky Diode connection diagram
16 zone - typical wiring schematic

1 2 3 4 1+ 1- 2+ 2- 3+ 3- 4+ 4- 5+ 5- 6+ 6- 7+ 7- 8+ 8- 1+ 1- 2+ 2- 3+ 3- 4+ 4 - 24V 0V Sil Evac RST Cl/C Dis Evac BAct A B Scn N/C
Lower terminal tier Zone O/Ps Zone Circuits Alarm Circuits Aux DC Inputs Outputs Repeater RST
Lower terminal tier
Checked by: AJC

Upper terminal tier Zone Circuits Aux DC Fault Routing Fire Routing Fire Protection RST Upper terminal tier
9+ 9 - 10 + 10 - 11 + 11 - 12 + 12 - 13 + 13 - 14 + 14 - 15 + 15 - 16 + 16 - 24V 0V O/+ P C/- C/+ P O/- C/+ P O/- P N/O

Fire Routing, Fault Routing & Fire Protection O/P configuration - Output specification: Fire and Fault Routing

Page 9 of 32
output wiring shown for the
When configured as monitored/powered outputs: When configured as volt-free changeover relays : monitored/powered

Figure 7 - Typical Wiring Diagram


configuration
For Fire Routing and Fire Protection O/Ps: For Fire Routing and Fire Protection O/Ps:
Quiescent: 5V DC Volt free relay contacts shown in quiescent [de-energised]
Relay local to fault Relay local to fire
Active [fire]: 24V nom] condition.
routing equipment routing equipment
equipment equipment
For Fault Routing O/P: For Fault Output:
Quiescent: 24V DC [nom] Volt free relay contacts shown in healthy [energised]
Active [fault]: 5V condition.
Field relay spec:
Connections: Coil resistance - 2.6K to 4.5K Ohms
Connections:
Connect to normally open or normally closed contact as Voltage 24V DC Nom
Observe correct polarity.
required.[P= Pole, C= Closed, O = Open] [min 18V, max 30V]
[+ = Positive, - = Negative]
Applied voltage must not exceed 30V DC. Fitted with suppression diode as shown.

22/12/09
Written by: RKP Checked by: AJC

7. Circuit Connection Details

7.1 2-16 Zone Motherboard Termination Details


Inputs: Outputs:
SIL = Silence alarms DIS = Disablement active
EVAC = Evacuate EVAC = Evacuation active
RST = Reset BUZ Active = Buzzer active
Precept Grey fill indicates I/O available on selected panel
2
4
8
16/32
Inputs Outputs Repeater

Class change
Aux

Reset N/C
Buz Active
Zone O/Ps Zone Circuits Alarm Circuits
DC

EVAC
1 2 3 4 5 6 7 8 1 2 3 4

EVAC

GND
RST

DIS
24V

SIL
0V
1 2 3 4 + - + - + - + - + - + - + - + - + - + - + - + - A B
Lower
terminal tier

Upper
terminal tier
+ - + - + - + - + - + - + - + -

O/+

C/+

C/+
24 V
0V

P
C/-

P
O/-

P
O/-

N/O
P
9 10 11 12 13 14 15 16
Zone Circuits Aux Fault Fire Fire Reset
Precept DC Routing Routing Protection
O/- = Normally Open or -ve
2 O/+ = Normally Open or +ve
4 P = Pole
C/+ = Normally Closed or +ve
8 C/- = Normally Closed or -ve
16/32
Grey fill indicates I/O available on selected panel

Figure 8 - C1627 field termination

7.2 16 Zone Expansion Board Termination Details

Zone Circuits
17 18 19 20 21 22 23 24
+ - + - + - + - + - + - + - + -

Lower terminal tier

Upper terminal tier

+ - + - + - + - + - + - + - + -
25 26 27 28 29 30 31 32
Zone Circuits

Figure 9 - C1632 16 zone expansion board field termination

Document Number: Prec en Inst Rev: 4 Page 10 of 32 22/12/09


Written by: RKP Checked by: AJC
en
8. Precept C1627 Motherboard Features
Figure 10 illustrates the motherboard features referred to elsewhere in the documentation.

Remote Inputs: Aux Outputs:


Silence Alarms DISablement active
Evacuate Fire EVACuate Active
Reset Routing BUZzer ACTIVE
Output

Aux DC Supply Fault Routing Fire


Zone Outputs
24V & 0V Output Protection
1-4 Alarm
Output Repeater
Circuits Terminals:
[Marked with Active A,B, GND
Polarity]

Zone Reset
Detection Relay
Inputs Output

J6,J7,J8
Fault Routing Connector
Output for C1632,
configuration J10,J11,J12 Zone
Fire Routing J14,J15,J16 Expansion
links
Output Fire Protection Output Board
configuration links configuration links

J1
Display C1631
Connector Repeater
Interface

Secondary
AC from
transformer

Configuration
mode enabled FS1
LED indicator Battery
Fuse J18
Power Supply LED Earth Fault
indicators: Monitoring
Battery OUTPUT OK
Terminals Link
Configuration Battery/Charger Fault
switches Configuration Charger Fault
SW1/1 to SW1/10 switches Battery Mains Fault
SW2/1 to Thermistor
SW2/10 Terminals

en
Figure 10 - C1627 Precept motherboard layout

Document Number: Prec en Inst Rev: 4 Page 11 of 32 22/12/09


Written by: RKP Checked by: AJC
en
9. Precept C1632 16 zone expansion board Features

Connector for Detection zone


motherboard terminals for
ribbon zones 17 - 32

Figure 11 - C1632 16 zone expansion board

10. Power Supplies  1Ω - 4-zone panels


en
The Precept 2, 4, 8 and 16 zone panels produce  1Ω - All repeaters
dc power regulation directly on the C1627
en
 0.6Ω - 8/16-zone panels
motherboard. The Precept 32 zone panel has an
 0.35Ω - 32-zone panels
off-board power supply via a dedicated PCB
(C1652) contained within the enclosure of the fire 3) A yellow „Charger Fault‟ LED („Internal Fault‟
alarm panel. LED on the C1652 PSU board) indicating any
of the following:
For all panels, the output voltage is adjustable from
a) A mains fault exists (see below)
25V to 28.2V via a small trimmer potentiometer on
the PCB. As the output voltage is factory set b) Switching regulator or charger circuitry is
however, this should not be necessary. malfunctioning
c) Battery Fuse is blown
10.1 Visual indications 4) A yellow „Mains Fault‟ LED. This indicates that
The following visual indications are provided: the mains voltage has failed or is less than the
required minimum for correct operation of the
1) A green „Output - OK‟ LED. This simply
power supply (80% of the rated voltage).
denotes that power is being supplied to the
panel Note: Fault indications do not become active for a
minimum of 10 seconds after the fault has
2) A yellow „Batt/Charge Fault‟ LED denoting any
occurred.
one of the following conditions:
a) Battery or associated wiring disconnected 10.2 Battery Disconnect
b) Battery fuse blown 1) The supply provides a battery disconnect
c) Low Battery voltage (15.7V ±0.4V) facility which disconnects the batteries when
d) Battery and interconnection resistance is the battery terminal voltage falls below 19.5V.
equal to or higher than:

Document Number: Prec en Inst Rev: 4 Page 12 of 32 22/12/09


Written by: RKP Checked by: AJC

en
10.3 32 zone Precept Power Supply Features and Connections
en
Figure 12 shows the layout of the 32 zone Precept panel power supply.

Secondary AC
Supply from
Transformer

28V, 0V DC
Power output

Mains
Fault
Output

Common
Fault
Output

4-way header for


connector to 32 zone
motherboard for DC
power, common fault
DC supply and mains fault
Battery output voltage
connections adjustment
potentiometer LED indicators for:
Battery [factory set]. Mains fault, Internal Fault,
Thermistor Battery/Charge Fault, Output O.K.
connections
FS1 Battery
Fuse [6.3A]

en
Figure 12 - 32 zone Precept power supply layout

Document Number: Prec en Inst Rev: 4 Page 13 of 32 22/12/09


Written by: RKP Checked by: AJC

11. Installation case of accidental skin or eye contact, flush the


affected area with plenty of clean, fresh water and
The control panel must be installed by suitably
seek immediate medical attention.
qualified engineers familiar with the installation of
fire detection systems. In addition, it is Valve Regulated Lead Acid (VRLA) batteries are
recommended to refer to the following information: “low maintenance”, requiring no electrolyte top-
up or measurement of specific gravity.
 Current edition of the IEE wiring regulations.
 Current edition of BS5839-1 or the installation WARNING: Only clean the battery case
standards for the relevant country. with a cloth that has been soaked or
dampened with distilled water. Do not use organic
 Any specific site requirements. solvents (such as petrol, paint thinner, benzene or
 Any field device installation instructions. mineral spirits) or other materials that can
 Any data sheet provided for the installation of substantially weaken the case. Do not use a dry
Intrinsically Safe devices. cloth as this will generate static electricity, which in
turn may lead to an explosion.
Notes:
The rating plate, containing essential electrical WARNING: Avoid operating temperatures
information is located inside the panel on the inside outside the range of -15C/5F to
face of the door. +50°C/122°F for float/standby applications.
The mains supply cable should be a minimum of The recommended normal operating temperature is
2
1mm copper protected by a 5A fuse. 20°C.
An appropriate lockable double pole disconnect HIGH TEMPERATURE will reduce battery service
device shall be provided as part of the building life. In extreme cases this can cause Thermal
installation. This device must have a minimum Runaway, resulting in high oxygen/hydrogen gas
contact gap of 3mm. production and battery swelling. Batteries are
irrecoverable from this condition and should be
replaced.
11.1 Electrical Safety
LOW TEMPERATURE will prolong battery life but
WARNING: Read this section completely before
reduce output capacity.
commencing installation.
Prior to commencing installation of the DANGER: Do not incinerate batteries. If
control panel, ensure that adequate placed in a fire, the batteries may rupture,
precautions are taken to prevent with the potential to release hazardous
damage to the sensitive electronic gases and electrolyte. VRLA batteries
components on the display board and the control contain substances harmful to the
board due to electrostatic discharge. You should environment.
discharge any static electricity you may have Exhausted batteries must be recycled.
accumulated by touching a convenient earthed Return them to the battery manufacturer or take
object such as an unpainted copper radiator pipe. them to your Council waste disposal site for
You should repeat the process at regular intervals appropriate disposal.
during the installation process, especially if you are ELECTRICAL SAFETY:
required to walk over carpets.
The volt-free relay contacts provided within the
The panel must be located in a clean, dry panel must not be used to directly switch any
position, which is not subject to shock or voltage that exceeds 50VAC or 75VDC. (Please
vibration and at least 2 metres away from pager also refer to relay rating data).
systems or any other radio transmitting
This equipment requires a 230VAC supply. All
equipment. The operating temperature range is
installation work should be carried out in
0ºC to 40ºC; maximum humidity is 95%.
accordance with the recommendations of
IMPORTANT NOTES ON BATTERIES: BS5839 Part 1 and the current edition of the IEE
regulations by suitably qualified and trained
DANGER: Batteries are electrically Live at
personnel.
all times, take great care never to short
circuit the battery terminals.
THIS PANEL MUST BE EARTHED
WARNING: Batteries are often heavy; take
great care when lifting and transporting
batteries. For weights above 24 kilos,
lifting aids should be used.
DANGER: Do NOT attempt to remove the
battery lid or tamper with the internal
workings of the battery. Electrolyte is a
highly corrosive substance, and presents significant
danger to you and to anything else it touches. In

Document Number: Prec en Inst Rev: 4 Page 14 of 32 22/12/09


Written by: RKP Checked by: AJC

11.2 Installation Instructions 8. Disconnect the flying leads from the


1. Carefully remove the control panel from the transformer to the mains terminal block and
packing and lie the panel on a flat surface. earth bar.
2. Open the door of the panel. 9. Remove the chassis from the enclosure and
place carefully to one side.
3. Locate the spares bag and check that the
following items are present: NOTE: The door and chassis both contain
en en PCBs with sensitive and fragile electronic
Precept Precept
Item components on them. You must place
2/4 8/16/32
these items in a location where they will not
T1AH250V T3.15AH250V be damaged. Choose an area that is clean,
Mains Fuse 20mm 20mm dry and dust-free. You can place the items
1 off 1 off inside the original packing carton but you
F5AL250V must ensure that sufficient soft packing is
F2AL250V
20mm [8/16] used to keep the door and chassis
Battery Fuse 20mm
F6.3AL250V separated.
1 off
20mm [32]
10. Identify the three indented holes in the backbox
EOL capacitors 22μF, 35V 22μF, 35V
that are used to mount the enclosure.
for normal zone axial. axial.
monitoring 2/4 off 8/16/32 off 11. Place the enclosure in the desired location and
EOL resistors for mark the position of the top indented hole.
3K9 0.25W 3K9 0.25W Remove the enclosure and fit a suitable fixing
alarm circuits
4/8 off 12/20/36 off to the wall. Hang the enclosure from the top
and I.S. zones.
Key Ref.: Key Ref.: fixing point and ensure that it is level. Mark the
Engineer‟s door locations of the other two mounting holes.
801 [Flat] 801 [Flat]
keys
1 off 1 off 12. Remove the enclosure from the wall and fit
Key Ref.: Key Ref.: suitable fixings to the two remaining mounting
Access Control points. Fix the enclosure to the wall using all
801 [Tubular] 801 [Tubular]
keys three mounting points.
1 off 1 off
Positive battery Red Red 13. Carefully remove the required knock-outs in the
lead 1 off 1 off panel enclosure and gland all field wiring in
Negative battery Black Black place ensuring that the cable conductors are of
lead 1 off 1 off sufficient length inside the enclosure. Ensure
Battery coupling Blue Blue that all conductors are clearly labelled. DO NOT
lead 1 off 1 off remove knock-outs from any unused cable
en
Battery terminal Precept 32 entries. Any unused cable entries which are
N/A
insulation boot only open must be sealed with a suitable plug
(available separately).
en
11.2.1 Precept Panel Installation Instructions 14. Connect the earth drain wires of the field
1. Disconnect the display ribbon cable from the cabling to the brass earth bar positioned at the
motherboard header. top of the backbox. Up to two drain wires may
be connected to each terminal.
2. Disconnect the earth strap connecting the door
and backbox via the spade terminal on the 15. Ensure that continuity of any cable shield is
door. maintained through to the last device on the
circuit. The shield must only be connected to
3. Unscrew the hinge pin at the bottom of the door enclosure earth in the panel by using the earth
whilst supporting the door. Swing the bottom of bars provided. [Different requirements apply for
the door clear of the backbox and pull the door the screen of data cable used for connecting
away from the top hinge pin. repeaters - see 11.2.2 below].
4. Place the door carefully to one side and replace 16. Connect the incoming protective earth
the bottom hinge pin in the backbox. conductor to the Earth terminal in the mains
5. Unscrew and remove the two lower chassis terminal block. This is the primary earth point
screws and only slacken the top two mounting
screws. and is labelled [also labelled E]. See
Section 5.
6. Carefully lift the chassis upward to align the
screw heads with the large holes in the chassis 17. Clear any dust and debris from inside the
keyholes. Lift the chassis clear of the upper enclosure.
screws and rest the chassis in the bottom of the 18. Connect the mains-in Live cable to the mains
enclosure. Take care not to strain the wires that terminal block [L terminal] as indicated in
remain connected to the backbox. section 5.
7. Disconnect the earth strap connecting the 20. Connect the mains-in Neutral cable to the
backbox and chassis at the earth bar. mains terminal block [N terminal] as indicated in
section 5.

Document Number: Prec en Inst Rev: 4 Page 15 of 32 22/12/09


Written by: RKP Checked by: AJC

21. Secure the mains-in cable to the cable clamp connector on the end of the red lead onto the
adjacent the mains terminal using the cable tie positive (red) terminal of the right-hand battery.
supplied. NOTE: The clamp should be over the 28. Connect the blue battery lead between the
outer cable insulation. positive (red) terminal of the left-hand battery
22. Reinstallation of the chassis is the reverse of and the negative (black) terminal of the right-
removal. Reconnect all wires and ensure none hand battery. Note that the batteries will not
are trapped between the chassis and backbox. power the panel until the mains supply is
Do not connect the field wiring at this stage. energised.
23. Refit the door. The refitting procedure is the
11.2.2 Installation And Connection Of The
reverse of removal. Ensure that the earth strap
C1631 Repeater Interface
and ribbon cable are reconnected correctly.
24. Place the left-hand battery into the bottom of Warning: Observe anti-static precautions
the enclosure. The terminals should be 1. Ensure that the panel and repeaters are
positioned towards the centre of the enclosure powered down and the main and standby
and the battery should be adjacent to the left supplies are disconnected.
side of the backbox, fixed by the raised indents
in the backbox, one above the battery and one 2. On the fire alarm panel and each repeater,
to the right. remove the jumper link at J22 (adjacent to J9)
and fit a C1631 repeater interface to connectors
25. Place the right-hand battery into the bottom of
J13 and J9 located immediately to the left of the
the panel. The terminals should be positioned
Zone Expansion ribbon connector on the right-
towards the centre of the enclosure and the
battery should be adjacent to the right side of hand side of the C1627 motherboard. The board
the backbox located by the raised indents in the should be held in place by the 12mm high plastic
spacer provided. See Figure 10.
back box above the battery and to the left.
26. Connect the black battery lead to the power 3. Connect the RS485 data cable as shown in
supply “Batt -” [battery negative] terminal and Figure 13.
connect the red battery lead to the power 4. If the repeater is powered from the panel then
supply “Batt +” [battery positive] positive connect the Aux 24V d.c. supply from the panel
terminal [situated on the motherboard for the to the repeater.
en
Precept 2/4, 8 and 16 panels and repeater
panel or on the separate power supply board in 5. Connect the repeater mains power supply (if
en
the Precept 32 panel]. The location of the required) to the L, N and E terminals as
motherboard battery terminals are shown in described above for the panel.
Figure 10 and Figure 12. Fit the connector on Note: Use only RS485 screened data cable.
the end of the black lead onto the negative
(black) terminal of the left-hand battery. Fit the
EARTH BAR EARTH BAR
Data Cable Screen

Power Supply connections not shown.

Repeater Repeater
GND

GND
A

B
A

[Top right hand corner of C1626 motherboard]


Repeater [max 5 off]
[Top right hand corner of C1627 motherboard]
Panel

Figure 13 - Repeater connection diagram

Document Number: Prec en Inst Rev: 4 Page 16 of 32 22/12/09


Written by: RKP Checked by: AJC

12. Commissioning with the site-specific requirements and carrying


out a functional check.
12.1 Introduction
iii) Functional testing of all circuits and field devices
The following equipment should be available where to check each circuit and function in turn to
possible to minimise commissioning time: ensure correct operation of the entire system.
i) VHF/UHF Portable Radio (for two engineers) In this way any faults may be located quickly and
ii) Multi-meter or equivalent accurately. The general procedures are as follows:
o Alarm circuits should be checked first. The
12.2 Commissioning Checklist correct operation of each sounder should be
1. Before commissioning, the engineer should checked for correct audibility as specified in
check the following: BS5839:1, using the Evacuate function.
i) All field wiring has been inspected and tested o Detection zones should be commissioned next.
in accordance with CEL wiring The purpose is to establish the correct
recommendations, current issues of functioning of each device and checking for
BS5839:1 and BS7671 IEE wiring correct indication at the control panel. The panel
regulations. responses as configured should be checked at
this time.
ii) All field cables are glanded into the control o All ancillary inputs and outputs should be
panel cabinet. commissioned and the functionality confirmed.
iii) Detector bases are terminated but detector o Fire protection signals should be tested.
heads are not fitted. Any devices with o Fire and fault routing signalling should be tested.
electronic components are not fitted.
Terminations to devices with electronic WARNING: Before testing, the engineer must be
components should be linked through to aware both of the operation of all devices fitted
maintain cable continuity. to the auxiliary circuits and of the
iv) Manual Call Points are not connected but consequences of their operation.
cable is linked through to maintain continuity.
12.4 Pre-Commissioning Wiring Check
v) No end-of-line devices (e.g. alarm circuit
NOTE: This pre-commissioning wiring check
EOL resistor) are fitted in the field. procedure should be followed to test all wiring
prior to specific commissioning of any
2. The following information should be available to detection, alarm and auxiliary circuits.
the commissioning team: 1. Ensure that no devices are connected to the
i) Detection layout drawings. detection zones and alarm circuits, but that the
cables are linked through at the device locations
ii) Wiring schematic diagram. to achieve a continuous circuit.
v) Control Panel installation manuals. 2. Ensure that the resistance of all cables to earth
vi) Installation manuals for all equipment and between cores is at least 2M.
connected to the system. Check the following:
vii) Site specific configuration details. i) Positive to earth resistance is 2M or
greater.
Experience has shown that tracing wiring faults on
ii) Negative to earth resistance is 2M or
long circuits that are routed through risers etc. can
greater.
be difficult without knowledge of the wiring route.
iii) Positive to negative resistance is 2M or
It is recommended that the electrical installer be greater.
made available until basic wiring continuity is
proven. A minimum of two persons (e.g. engineer 3. Connect a wire link as the end-of-line device on
and mate) is recommended for efficient each of the zones and alarm circuits. At the
commissioning. panel end, measure the resistance across the
positive & negative ends of the cables for each
of the circuits; ensuring the value does not
12.3 An Overview of the Commissioning exceed 20. Remember to remove the wire
Procedure links after the tests.
Commissioning is broken in to 3 sections:
Correct polarity throughout all circuits must be
i) Pre-commissioning wiring check. maintained. Rectify any faults.
ii) Powering the panel up with no field wiring All bells, detector heads and call points should
connected, configuring the panel in accordance now be connected and the correct end-of-line

Document Number: Prec en Inst Rev: 4 Page 17 of 32 22/12/09


Written by: RKP Checked by: AJC

devices fitted. Use the spare end-of-line devices 12.6 Configuration


supplied and leave the EOL devices in the panel
terminals at this stage. Remember to remove 12.6.1 Basic Default Configuration
any links fitted to detector bases. Be very careful When first powered up, the Precept
en
can be
to maintain correct polarity at each device. operated in the standard default mode without any
Warning: Intrinsically safe zone arrangement. additional configuration.
 End-of-line capacitors cannot be connected The basic default mode is:
to zones monitoring Intrinsically Safe  All zones latching fire, non-delay, standard [non-
detection devices in hazardous areas. To do intrinsically safe]
so will risk causing an explosion in the  Fire Routing, Fire Protection and Sounder
hazardous area. End-of-line resistors with a outputs not delayed.
value of 3K9 must be used, which comply
with the requirements laid down in the
12.6.2 Site-Specific Configuration
installation data sheets provided with the I.S.
barrier and the I.S. fire detection devices. It is possible to tailor the functionality of the
en
 In order for detector head removal Precept fire alarm panel in line with site-specific
monitoring to function correctly when requirements. Details of the site configurable
resistors are used as the end-of-line devices, options and the configuration process are provided
any diodes in the detector bases that are in in section 14.1. Charts are provided in the System
circuit when the detector head is removed Log Book for planning/recording the actual
must be disconnected. configuration. This configuration is not lost when
the panel is powered down.
 The panel must be configured to monitor
Intrinsically Safe zones.
 The first device on an Intrinsically Safe zone 12.7 Commissioning Procedure
must be an I.S. Zener Barrier or Galvanic After completion of the pre-commissioning wiring
Isolator. Detectors and Manual Call Points on check, power-up and configuration, commission the
the Safe side of the barrier are not permitted. circuits in line with the following guide.
 To comply with the requirements of BS5839,
all manual call points should be located in 12.7.1 Alarm Circuits
the zone cabling between the I.S. 1. Remove the resistor from the first alarm circuit
Barrier/Isolator and the first detector. Any terminal and connect the first alarm circuit wiring
manual call point or detector located on the to the terminals, observing correct polarity.
“end-of-line” side of a detector will be Check that any alarm fault indications clear after
rendered inoperative if the detector head is a few seconds.
removed. en
2. Use the Alarm Test facility [see Precept User
Manual] or press Evacuate to operate the
12.5 Powering up sounders. Check that all sounders connected to
1. Prior to powering up, the panel will have been the alarm circuit operate.
installed in accordance with the installation 3. Deselect the Alarms Test condition or if
instructions, all cabling will have been fully “Evacuate” was used, press silence alarms to
installed and tested, glanded into the panel stop the sounders operating.
enclosure but not connected to the panel
terminals. The mains supply should be isolated 4. Repeat steps 1 to 3 for the second and any
externally to the panel. subsequent alarm circuits.
2. Check the battery connections are correct.
12.7.2 Commissioning zones
3. Remove the mains supply fuse from the panel
mains terminal block. Once the permit to 1. Work logically and systematically through each
energise the mains supply is in place, energise zone.
the mains and check the voltage and polarity are 2. Zone fault conditions:
correct before replacing the panel fuse.
o Remove the end-of-line device from the zone 1
4. The panel will power up and if all the end of line terminals and connect the cables of the zone 1
devices are correctly terminated in the panel and circuit to the panel terminals, observing the
the battery is OK, the panel should be silent, correct polarity. Check that any zone 1 fault
displaying only the Power Supply On indication. indications clear after a few seconds.
5. Turn the Access Keyswitch to “1” and press the o Check the fault monitoring of the cable is
Test Display button. The panel should respond correct by applying an open circuit then a short
by lighting all indications and sounding the circuit at the end-of-line device (in the field).
buzzer. This will continue for a few seconds after Check that the fault condition is indicated on
the button is released. zone 1 on the fire panel.

Document Number: Prec en Inst Rev: 4 Page 18 of 32 22/12/09


Written by: RKP Checked by: AJC

o Remove the circuit faults, restoring the circuit  The fault relay operates.
to the healthy condition and confirm that the 5. Repeat steps 1 to 4, one zone at a time, until all
fault indication clears. the zones are commissioned.
3. Zone fire conditions 6. Any faults that are found must be traced and
o Starting with the device nearest the panel, rectified before proceeding.
operate each manual call point and detection
device on the zone in turn. 12.7.3 Commissioning the Class Change Input
o After operation of each device confirm:
1. Connect the Class Change switch to the class
 The fire indication is provided on the panel change input on the motherboard.
on the correct zone.
2. Operate the class change switch and observe:
 The fire alarm devices operate correctly in
i) The alarms sound for 5 seconds then stop.
line with the panel configuration.
ii) The internal buzzer on the panel does not
 The Fire Routing and Fire protection outputs operate.
operate correctly in line with the panel
configuration. iii) The internal buzzer on repeaters does not
operate.
o Press the Silence Alarms and the Reset
buttons after each device test and check the 3. De-activate the class change switch
alarm clears (Manual Call Points must be
manually reset before resetting the panel). 12.7.4 Commissioning the Fire and Fault
4. Detector removal operation. Routing Outputs
o Remove the 1st detector along the zone cable 1. Remove the resistor from the Fire Routing
[counting from the panel] on zone 1 and output circuit terminals and connect the field
observe the following: wiring to the terminals, observing correct
 The appropriate amber zone fault LED polarity. Check that any fault indications clear
illuminates after a few seconds.
 The internal buzzer sounds 2. To operate the output, initiate a fire condition on
a zone. Check that the fire signal is received at
 The fault relay operates the receiving station. Silence and reset the fire
o For non I.S. zone applications: alarm panel to clear the output.
 Operate a manual call point between the 3. Remove the resistor from the Fault Routing
detector that has been removed and the EOL output circuit terminals and connect the field
capacitor. Check that the panel reacts as wiring to the terminals, observing correct
described above for a fire condition. polarity. Check that any fault indications clear
 Refit the detector, reset the manual call point, after a few seconds.
press the “Silence Alarms” button and then 4. Initiate a fault condition on the fire alarm panel to
the “System Reset” button on the panel‟s signal a fault to the remote receiving station.
display board and check that the control 5. Confirm the receipt of the fault warning at the
panel returns to its normal state. receiving station.
 Repeat for all detectors on the zone. 6. Open-circuit the output wiring of each circuit in
o For I.S. zone applications: turn, confirm the fire alarm panel indicates Fire
Routing and Fault Routing faults appropriately.
 Remove the 1st detector in the zone cable
[counting from the panel] and operate a 7. Reconnect the cabling and confirm the faults
manual call point ensuring that the correct clear.
fire alarm condition is raised on the panel
(assuming the installation complies with 12.7.5 Commissioning the Fire Protection
BS5839). control signal
 Continue to check the operation of all other 1. Ensure any fire protection equipment to be
manual call points on the zone, resetting the controlled via the Fire Protection output is locked
manual call point and silencing/resetting the off/safe before attempting any connection,
panel at each stage. testing or commissioning.
 Refit the detector and check that the control 2. Remove the resistor from the Fire Protection
panel returns to its normal state. output circuit terminal and connect the field
 Continue to test each of the other detectors wiring to the terminals, observing correct
in turn, checking on each removal that: polarity. Check that any fault indications clear
 The appropriate amber zone fault LED after a few seconds.
illuminates 3. Initiate a fire condition on a zone to operate the
 The internal buzzer sounds. output. Check that the fire signal operates the

Document Number: Prec en Inst Rev: 4 Page 19 of 32 22/12/09


Written by: RKP Checked by: AJC

interface relay adjacent the fire protection the alarms operate and the internal buzzer
equipment. operates on all repeaters.
4. Open-circuit the field wiring and confirm that the 3. Press the “Silence” button on the fire alarm
fire alarm panel indicates Fire Protection output panel. Check that the alarm circuits silence and
fault. the internal buzzer silences on all repeaters.
5. Reconnect the cabling and confirm the faults 4. Repeat steps 2 and 3 for each repeater.
clear. 5. Operate a Manual Call Point on zone 1 and
6. Final testing and commissioning of the loop check for correct fire indication at each repeater.
through to the fire protection equipment, 6. Press the “Silence Alarms” button on a repeater
including test [simulated] activation of the and check that the alarms are silenced and the
equipment, should be carried out at the Zone 1 fire LED is constantly illuminated on all
appropriate time in conjunction with the engineer repeater panels.
responsible for the fire protection system.
7. Press the “Reset” button on a repeater and
check that the panel and repeaters return to the
12.7.6 Commissioning ancillary inputs quiescent state.
Remote Silence Alarms, Reset and Evacuate inputs 8. Repeat steps 5 to 7 for each zone and ensure
should each be tested by the activation of the “Silence Alarms” and “Reset” operate correctly
remote equipment. The response should be verified from each repeater.
for each signal. 9. Set the DIL switches on the C1631 Repeater
Interface card in the fire alarm panel OFF (No
12.7.7 Commissioning ancillary outputs Repeaters). Check that all repeaters indicate a
“Comms. Fault”.
The correct operation of equipment connected to
the Zone Outputs, Disablement Active, Evacuate 10. Set the C1631 Repeater Interface card DIL
Active and Buzzer Active outputs should be verified switches in the fire alarm panel back to their
in turn by initiating a fire condition on each of the previous settings and check that the repeaters
appropriate zones; disabling/enabling a zone; return to normal.
operating the Evacuate button on the panel‟s 11. Set the first repeater address to 0. Check that
display. the panel indicates a “Repeater fault” and any
additional repeaters display a steady “Comms
12.7.8 Commissioning repeaters fault” LED.
12. Set the first repeater address back to normal
1. Power-up the Panel and then the Repeaters. and check that the panel and repeaters return to
Only the “Power Supply On” LEDs should be normal.
illuminated on the Panel and Repeaters.
13. Repeat steps 11 and 12 for any other connected
2. At Repeater 1, turn the Access control switch to repeaters.
“1”, and press the “Evacuate” button. Check that

Document Number: Prec en Inst Rev: 4 Page 20 of 32 22/12/09


Written by: RKP Checked by: AJC

13. User Indications


This section gives an overview of the functions available to the end user.
13.1 User Indications
General Indicator Section
Indication
Indicator Description Operating Condition
Colour
Power Supply On Green Illuminates Steady for Mains or Standby power On.
Flashes on any new fire alarm condition, changing to a steady
Fire Red
indication on operation of Silence Alarms.
Fire Routing Active Red Illuminates Steady when the Fire Routing Output is active.
General Fault Yellow Flashes for any fault condition.
Power Supply Fault Yellow Flashes for mains or standby power supply/charge fault
Illuminates Steady to indicate Microcontroller or Memory Failure.
System Fault Yellow
Flashes to indicate Engineer‟s Configuration Mode active.
Earth Fault Yellow Flashes for any positive or negative power supply earth fault.
Fuse Fault Yellow Flashes for any auxiliary supply fuse failure
Repeater Fault Yellow Flashes for any Repeater fault or repeater communication fault,
Sounder Fault/Disabled Yellow Flashes for any sounder fault. Steady for sounders disabled.
Sounder Test Yellow Illuminates Steady while sounder walk test is active.
Fire Protection Flashes for a fault on the Fire Protection Output. Steady when Fire
Yellow
Fault/Disabled Protection Output is disabled.
Fire Routing Flashes for a fault on the Fire Routing Output. Steady when Fire
Yellow
Fault/Disabled Routing Output is disabled.
Fault Routing Flashes for a fault on the Fault Routing Output. Steady when Fault
Yellow
Fault/Disabled Routing Output is disabled.

POWER SUPPLY ON ZONE LOCATION ZONE LOCATION


1. 17.
FIRE EVACUATE TEST DISPLAY
2. 18.
FIRE ROUTING ACTIVE
3. 19.
SILENCE/
GENERAL FAULT RESOUND ENABLE 4. 20.
ALARMS
POWER SUPPLY FAULT 5. 21.

SYSTEM FAULT 6. 22.


RESET DISABLE
7. 23.
EARTH FAULT
8. 24.
FUSE FAILED
SILENCE 9. 25.
BUZZER TEST
REPEATER FAULT 10. 26.
SOUNDER FAULT/DISABLED 11. 27.
DELAY
ON/OFF/ 12. 28.
SOUNDER TEST
OVERRIDE
13. 29.
FIRE PROTECTION FAULT/DISABLED SELECT
14. 30.
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15. 31.
FAULT ROUTING FAULT/DISABLED 16. 32.

FIRE FAULT DISABLEMENT AND TEST


1. THE RED ZONE INDICATOR 1. DETERMINE THE CAUSE 1. PRESS SELECT ON/OFF.
0 1 WILL PULSE SHOWING THE OF THE FAULT. THE LED WILL ILLUMINATE.

2 1 : 18 : 05
LOCATION OF THE FIRE. 2. PRESS SILENCE BUZZER. 2. SELECT THE ZONE OR
2. CARRY OUT THE 3. CALL YOUR SERVICE OUTPUT USING  AND . THE
REQUIRED FIRE DRILL. ENGINEER. FAULT LED WILL PULSE.

D / N OFF
3. TO SILENCE ALARMS SYSTEM FAULT 3. PRESS DISABLE OR TEST.
PRESS SILENCE ALARMS. THE PANEL IS INOPERATIVE. 4. TO RE-ENABLE, SELECT
4. TO RESET FROM THE FIRE ARRANGE FOR THE ZONE OR OUTPUT AND
CONDITION PRESS RESET. ALTERNATIVE FIRE PRESS ENABLE.
DETECTION MEASURES.

Access Controls Keyswitch: Clock Module [Optional]:


Showing time and Day/Night off User Instructions
0 - Controls Locked
1 - Controls Unlocked Back light flashes for Clock Module fault.

Zone Location Indications


Indication
Indicator Description Operating Condition
Colour
User Generated Zone Flashes when zone is in a fire condition, turning to steady on
Red
Location Text operation of Silence Alarms.
User Generated Zone Flashes when zone is in a fault condition. Illuminates steady when
Yellow
Location Text zone is disabled or in test.

Document Number: Prec en Inst Rev: 4 Page 21 of 32 22/12/09


Written by: RKP Checked by: AJC

13.2 User Controls

POWER SUPPLY ON ZONE LOCATION ZONE LOCATION


1. 17.
FIRE EVACUATE TEST DISPLAY
2. 18.
FIRE ROUTING ACTIVE
3. 19.
SILENCE/
GENERAL FAULT RESOUND ENABLE 4. 20.
ALARMS
POWER SUPPLY FAULT 5. 21.

SYSTEM FAULT 6. 22.


RESET DISABLE
7. 23.
EARTH FAULT
8. 24.
FUSE FAILED
SILENCE 9. 25.
BUZZER TEST
REPEATER FAULT 10. 26.
SOUNDER FAULT/DISABLED 11. 27.
DELAY
ON/OFF/ 12. 28.
SOUNDER TEST
OVERRIDE
13. 29.
FIRE PROTECTION FAULT/DISABLED SELECT
14. 30.
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15. 31.
FAULT ROUTING FAULT/DISABLED 16. 32.

FIRE FAULT DISABLEMENT AND TEST


1. THE RED ZONE INDICATOR 1. DETERMINE THE CAUSE 1. PRESS SELECT ON/OFF.
0 1 WILL PULSE SHOWING THE OF THE FAULT. THE LED WILL ILLUMINATE.

2 1 : 18 : 05
LOCATION OF THE FIRE. 2. PRESS SILENCE BUZZER. 2. SELECT THE ZONE OR
2. CARRY OUT THE 3. CALL YOUR SERVICE OUTPUT USING  AND . THE
REQUIRED FIRE DRILL. ENGINEER. FAULT LED WILL PULSE.

D / N OFF
3. TO SILENCE ALARMS SYSTEM FAULT 3. PRESS DISABLE OR TEST.
PRESS SILENCE ALARMS. THE PANEL IS INOPERATIVE. 4. TO RE-ENABLE, SELECT
4. TO RESET FROM THE FIRE ARRANGE FOR THE ZONE OR OUTPUT AND
CONDITION PRESS RESET. ALTERNATIVE FIRE PRESS ENABLE.
DETECTION MEASURES.

Access Controls Keyswitch:


0 - Controls Locked
1 - Controls Unlocked
Switch
Functionality Button Availability
Description
Operates all sounders continuously and lights the Evacuated LED
Evacuate When controls are unlocked
adjacent the button until the silence button is operated
Following a fire alarm condition, 1st operation stops sounders. The
Silence/Resound
General Fire LED and the Zonal fire LED will change from flashing to When controls are unlocked
Alarms
steady. 2nd operation restarts the previously silenced sounders
When controls are unlocked and [if
Clears the panel display, resets the zones, outputs and operates the silence before reset is configured]
Reset
reset relay. alarms silence switch has been
operated.
1] Press to stop the buzzer sounding in fire or fault conditions. When controls are locked or
unlocked
Silence Buzzer 2] In 2 Stage Delay Mode, with stage 1 delay running, press to start When the panel is in the fire
stage 2 delay otherwise all delayed outputs operate when Stage 1 condition and the delay is running.
timer times out. Controls are locked or unlocked
1] Press once to Enable the delay mode, lighting the adjacent delay on 1] When controls are unlocked and
Delay LED. Press again to disable the delay mode and turn off the LED delay period is set to a value > 0.
On/Off/Override 2] Overrides the delay when delay is running. All delayed outputs will 2] When the panel is in the fire
operate immediately. condition and the delay is running.
Enables the User select feature [Select ↑ Select ↓] for selection of
Select On/Off zones or outputs for disablement/re-enablement also Day/Night On/Off When controls are unlocked
selection and setting current time on Clock Module when fitted.
Press to illuminate all LEDs on the display and operate the buzzer. All
When controls are locked or
Test Display indications remain active for approx 5 seconds after button release.
unlocked
Also displays alarm count on Clock Module [when fitted]
When controls are unlocked, the
Press to clear the disablement or test condition on a zone or output
Select switch has been operated
Enable
selected via the User Select feature. and a zone or output has been
selected.
Disable Press to disable a zone or output selected via the User Select feature. As above.
Press to initiate the One Man Test on sounders or zones as selected
Test As above.
via the User Select feature.
Used to scroll the cursor indication through the zone and output fault
When controls are unlocked and
LEDs on the display to select a zone or output for disablement, or test.
Select ↑ Select ↓ the Select switch has been
[LED illuminated when Select Mode is active]. Also scrolls through
operated.
Clock Module menu [when fitted].

Document Number: Prec en Inst Rev: 4 Page 22 of 32 22/12/09


Written by: RKP Checked by: AJC

14. Operating the Engineer‟s functions 2. Select a zone or output to be configured:


o On the panel display, press the Select On/Off
14.1 Engineer‟s Zone/Output Configuration switch to enable the Select Mode.
Process:
 The Select LED will become steady and the
Various programmable configuration options panel buzzer will silence.
associated with the zonal inputs and outputs can
 A pulsing indication [cursor] will appear either
be enabled/disabled by operating the appropriate
on the Zone 1 Fault/Disabled LED or the
DIL switch located within the panel enclosure.
Sounder Fault/Disabled LED/Test depending
These are:
upon which configuration DIL switch is
o Configure zones as delayed zones. selected.
o Configure zones for use with I.S. o Use the Select ↑ and Select↓ buttons to scroll
barriers/isolators. the cursor indication through the selectable
o Configure zones as latching/non-latching fire options:
indication.  For zonal configuration, through all zones
o Configure zones to short circuit fire mode. sequentially in forward [Select↓] or reverse
o Configure outputs to be delayed. [Select ↑] sequence starting at zone 1.
Note: Configure Machinery Space Zones feature  For Output Delay configuration, through
en
is not used on the Precept panels. Sounders, Fire Protection and Fire Routing
outputs in forward [Select↓] or reverse
14.2 Zone or Output Configuration [Select ↑] sequence starting at Sounders.
1. Select a programmable configuration mode: 3. To change the configuration of a selected
o Enable the controls on the display, by turning zone or output:
the Access Keyswitch on the panel display to With the cursor flashing on the selected zone or
the “1” position. output:
o If the panel is in the fire alarm condition,  Operation of the ENABLE button will apply the
silence the alarms and reset. configuration functionality to the selected
o Open the panel door and locate the zone/output causing the associated
appropriate DIL switch on the motherboard fault/disabled LED to provide a continuous
[Config Non-latch Zones; Config I.S. Zones; indication.
Config Delay Zones; Config Delay O/Ps] and  Operation of the DISABLE button will clear the
move the switch to the ON position. configuration from the selection and restore
 The CONFIG ENABLED LED on the normal operation. The fault/disabled LED will
motherboard will illuminate. clear.
 The Panel‟s System Fault LED will flash and By repeating steps 2 and 3, any number of
the buzzer will operate. zones [or outputs] can be configured.
 The Select LED on the front of the display 4. To quit the programmable configuration
will pulse. mode:
 Any standing fire or fault alarm indications o To return the panel to normal operating mode
and associated outputs will be inhibited. applying the updated configuration:
 If active, the indications for evacuation,  Open the panel door and return the selected
silence buzzer, delay on or disablement Config DIL switch on the motherboard to the
indications will clear. OFF position.
 The panel will indicate the current status of  The CONFIG ENABLED LED on the
the selected programmable configuration motherboard will clear, the panel buzzer will
mode on the yellow fault/disabled LEDs on silence and the flashing System Fault
the Zones, Sounders, Fire Routing and Fire indication and zone/output configuration
Protection outputs. status indications on the display will clear as
will the cursor and the Select indications. Any
A steady indication denotes that the current alarms, disablements, will be re-
zone/output is already configured to the indicated along with any active status
selected mode. indications [Delay on etc.].
No indication denotes that the zone/output o Close and lock the panel door.
has not been configured to the selected
mode. o Return the ACCESS Keyswitch to the “0”
position to disable the controls on the display.
o Close the panel door to allow access to the
buttons on the display. IMPORTANT NOTE: WHILE THE PANEL IS
IN THE ENGINEER‟S ZONAL/OUTPUT
CONFIGURATION MODE, ALL ZONAL
INPUTS ARE IN PERMANENT RESET AND

Document Number: Prec en Inst Rev: 4 Page 23 of 32 22/12/09


Written by: RKP Checked by: AJC

OUTPUTS ARE INHIBITED - THE PANEL 1/8] on the motherboard and ensure that only
WILL NOT RESPOND TO ANY FIRE ALARM. one is selected to ON.
 Invalid condition: Selecting any config mode
14.3 To Restore the Factory Default
switch [1/4, 1/5, 1/6, 1/7, 1/8] to the On position
Configuration for Zones & Outputs:
whilst the panel is in the fire condition.
 Open the panel door and locate the DIL
o The Config LED on the motherboard will flash.
switches SW1-4 to SW1-8 on the motherboard
[Config Non-latch Zones; Config I.S. Zones; o The System Fault and Select LEDs on the
Config M/S Zones; Config Delay Zones; Config display will flash.
Delay O/Ps] and move the switch actuator on o The panel buzzer will sound.
each switch to the On position. o The Cursor indication will clear.
o The Config Enabled LED on the motherboard o Configuration will be inhibited.
will flash.
 To clear the invalid condition, select the config
o The Panel‟s System Fault LED will flash and switch to OFF. Reset the fire alarm condition
the buzzer will operate. before attempting the configuration process
o Any standing fault or disablement indications again.
will clear.
o It will not be possible to enter the Select Mode. 14.6 List of configuration DIL switches and their
functions
 Press the Disable button on the panel‟s display.
 SW 1/1 - Inhibit F/P on NLZ:
 Return DIL switches 1-4 to 1-8 to the OFF
Selects Fire Protection relay to operate or not to
position.
operate for a fire condition on any zone
o The Config Enabled LED on the motherboard configured to non-latched mode.
will clear.
o OFF Fire Protection relay operates for a fire
o The Panel‟s System Fault LED will flash and condition on any zone configured to non-
the buzzer will clear. latched mode.
o The factory default configuration [all zones as o ON: Fire Protection relay does not operate for
latching fire, non-delay, standard [non- a fire condition on any zone configured to non-
intrinsically safe] will be restored and the Fire latched mode.
Routing, Fire Protection and Sounder outputs
o [Not EN54 compliant function].
will no longer be delayed

14.4 Engineer‟s Zone/Output Configuration  S/W 1/2 - Delay Alarm Sil & Rst:
Time-out Warning: o OFF: Silence and reset available as normal.
This feature is provided to prevent the panel being o ON: Prevents alarms being silenced or reset
left in the Zone/Output Configuration condition. for a period of 3 minutes after a fire alarm
 1 minute after the last button press: condition occurs.
o The panel buzzer will restart. [Not EN54 compliant function].
o The Select LED will flash.
o The System Fault LED will continue flashing.  SW 1/3 - Delay On Auto:
 Press the Select On/Off button to continue with o OFF: Automatically turn off the delay mode
the configuration process otherwise quit the once a day at the set time [the delay mode first
configuration process as described in 14.2 step being turned on manually].
4. o ON: Automatically turn the delay mode on
once a day and off once a day at the set times.
14.5 Invalid Configuration conditions:
Requires optional clock module.
 Invalid condition: If 2 or more configuration
switches on the motherboard are in the On
 SW 1/4 - Config Non-Latch Zones:
position at the same time:
o OFF: Configuration mode disabled.
o The Config LED on the motherboard will flash.
o ON: Enables selected zones to be configured
o The System Fault and Select LEDs on the
to non-latching fire mode via the Engineer‟s
display will flash.
Select feature.
o The fault relay will operate.
[Not EN54 compliant function].
o The panel buzzer will sound.
o The Cursor indication will clear.  SW 1/5 - Config I/S Zones:
o Configuration will be inhibited. o OFF: Configuration mode disabled.
 To clear the invalid condition check the zone o ON: Enables selected zones to be configured
and output config switches [1/4, 1/5, 1/6, 1/7, to Intrinsically Safe alarm thresholds and

Document Number: Prec en Inst Rev: 4 Page 24 of 32 22/12/09


Written by: RKP Checked by: AJC

passive end of line fault monitoring via the Table 1 - Motherboard Delay Switch Settings
Engineer‟s Select feature. [For use with Delay S/W S/W S/W S/W
appropriate I.S. barriers/Isolators, typically 330 Duration 2/2 2/3 2/4 2/5
Ohm zener barriers or galvanic isolators]. Delay disabled Off Off Off Off
Not EN54 compliant function. 1 min On Off Off Off
2 min Off On Off Off
 SW 1/6 - Config M/S Zones: 3 min On On Off Off
4 min Off Off On Off
o OFF: Configuration mode disabled.
5 min On Off On Off
o ON: Enables selected zones to be configured 6 min Off On On Off
to short circuit fire mode via the Engineer‟s 7 min On On On Off
Select feature. 8 min Off Off Off On
9 min On Off Off On
 SW 1/7 - Config Delay Zones: 10 min Off On Off On
o OFF: Configuration mode disabled. On On Off On
o ON: Enables selected zones to be configured Off Off On On
to Delay Mode via the Engineer‟s Select On Off On On
feature. Off On On On
On On On On
 SW 1/8 - Configure Delay O/Ps:  SW 2/6 - Enable Zonal Alarms:
o OFF: Configuration mode disabled. Select the type of sounder alarm response to a
o ON: Enables the selection of outputs, via the fire condition in conjunction with the Pulse Non
Engineer‟s Select feature, to which the panel Alarm Zones switch described below. [Not EN54
delay will apply. compliant function. Provided to meet existing
customer requirements]:
 SW 1/9 - 2 Stage Delay: o OFF: General Alarm Mode - all sounders
operate continuously until silenced.
o OFF: Single Stage Delay Mode.
o ON: Zonal Sounder Mode - Sounder groups for
o ON: Two Stage Delay Mode.
zones not in the alarm condition may be
selected, via the Pulse Non Alarm Zones
 SW 1/10 - Alarms on Evac Only: switch [SW 2/7], to pulse or not to operate.
o OFF: Sounders operate on any fire condition Note: Zonal alarms on the 2/4 zone panel affects
including evacuate. the standard sounder circuits on the motherboard.
o ON: Selects sounders to operate only when On the 8, 16 and 32 zone panels, it affects only
the panel is in the evacuate condition. the [future] expansion module sounder circuits.
Not EN54 complaint function.
 SW 2/7- Pulse Non Alarm Zones:
 SW 2/1 - Silence Before Reset: Select the type of zonal sounder alarm response
Select type of reset mode. [Not EN54 compliant to a fire condition in conjunction with the Zone
function. Provided to meet existing customer Alarms switch [SW 2/6] described above. [Not
requirements]: EN54 compliant function. Provided to meet
existing customer requirements]:
o OFF: Reset available when panel is in the [un-
silenced] fire or fault condition. With the Zone Alarms switch [SW 2/6] in the On
position [Zonal Sounder Mode]:
o ON: Fire Condition Reset available only when
panel is in Alarm Silenced condition. Fault o SW2/7 OFF: Zonal sounders for zone in the
reset available when panel is in the fault fire condition operate continuously until
condition. silenced. All others are silent.
o SW2/7 ON: Zonal sounders operate
 SW 2/2 to 2/5 - Delay/Minutes: continuously - all other sounders operate in
pulsed mode until silenced.
Sets the duration of the variable time delay element
[i.e. the single stage delay and stage 2 of the two
stage delay] in steps of 1 minute within the range 0-  SW 2/8 - Silent Zone Test:
9 minutes. See Table 1 - Motherboard Delay Switch Select sounder response in One Man [Detector]
Settings Test Mode:
o OFF: Sounders operate once on each test.
o ON: Sounders do not respond to a zone test.

Document Number: Prec en Inst Rev: 4 Page 25 of 32 22/12/09


Written by: RKP Checked by: AJC

 SW 2/9 - Buzzer Disable: To configure the Fire Protection Output to volt-free


Enable/disable panel fire/fault buzzer. relay contacts, remove links J14, J15 and J16.
[These links are combined in a single block].
o OFF: Buzzer is enabled.
To configure the Fault Routing Output to volt-free
o ON: Buzzer is disabled. General Disablement relay contacts, remove links J6, J7 and J8. [These
LED illuminated. links are combined in a single block].
Not EN54 compliant function. Provided for
commissioning purposes only. These links are located below the associated
output in the top right hand section of the
 SW 2/10 - Latched Faults: C1627 motherboard. See Figure 10.
When enabled, all fault conditions latch until the
Reset switch is operated. 14.9 Disabling the earth fault monitoring
o OFF: Non-latched faults. To disable the earth fault monitoring, remove
o ON: Latched faults. the link J18 located towards the bottom right
hand corner of the C1627 motherboard. See
14.7 Configurable Options via DIL switch Figure 10.
selection on Repeater Interface Board:
DIL switch SW1 on the C1631 Repeater 15. Optional Clock Module - configuration and
Interface PCB is used to set the quantity of setting
repeaters and the repeater addresses as
follows: 15.1 Standard Module Engineer Mode:
o To set the repeater quantity, set SW1 on the 15.1.1 To zero the Alarm counter:
C1631 fitted to the fire alarm panel in line with
Table 2. This is an ACCESS LEVEL 4 operation.
Open panel door and move the DIL switch 1, pole 2
Table 2 - C1631 setting for quantity of
on clock module PCB to the ON position. Return
repeaters
the DIL switch to the OFF position.
Repeater S/W S/W S/W
Quantity 1/1 1/2 1/3 15.1.2 To access the Engineer‟s Clock Module
0 Off Off Off Edit Functions
1 On Off Off
2 Off On Off Normal Time Display:
3 On On Off HH:MM:SS HH:MM:SS
or
4 Off Off On D/N ON D/N OFF
5 On Off On
Select Access Control key switch to position 1.
o To set the addresses of the individual repeater
panels, set SW1 on the C1631 fitted to each Press the SELECT ON/OFF switch.
repeater panel in line with Table 3. Note that Use the “Up/down” keys to scroll the cursor LED
each repeater must have a different address. indication through the selectable options on the
display LEDs until LCD backlight illuminates.
Table 3 - C1631 setting for repeater addresses
Normal Time Display:
Repeater S/W S/W S/W
HH:MM:SS HH:MM:SS
Address 1/1 1/2 1/3 or
0* Off Off Off D/N ON D/N OFF
1 On Off Off
2 Off On Off  To change the Day/Night Mode
3 On On Off
4 Off Off On
5 On Off On Press SELECT ON/OFF.
* Note: Address 0 = repeater disabled. Delay On/Off Set Display:
D/N ON D/N OFF
or
14.8 Configuring the Fire Routing, Fire Change? Change?
Protection and Fault routing O/Ps
To configure the Fire Routing Output to volt-free On the rear of the Clock Module PCB, move the
relay contacts, remove links J10, J11 and J12. DIL switch 1, pole 1 on to the ON position.
[These links are combined in a single block].

Pressing ENABLE (+) or DISABLE (-) toggles


setting between D/N ON and D/N OFF.

Document Number: Prec en Inst Rev: 4 Page 26 of 32 22/12/09


Written by: RKP Checked by: AJC

 To set current time  To set Day/Night Mode Off Time

Press SELECT ↓, to access current Time Set Press SELECT ↓, to access day/night OFF Time
display: Set display:
HH:MM:SS HH flashing HH:MM:SS HH flashing
Time Set OFF Time

Press ENABLE (+) or DISABLE (-) to change Press ENABLE (+) or DISABLE (-) to change
HH to desired value (00 to 23) HH to desired value (00 to 23)

Press SELECT ↓, Time Set display: Press SELECT ↓, OFF Time Set display:
HH:MM:SS MM flashing HH:MM:SS MM flashing
Time Set OFF Time

Press ENABLE (+) or DISABLE (-) to change Press ENABLE (+) or DISABLE (-) to change
MM to desired value (00 to 59) MM to desired value (00 to 59)

Press SELECT ↓, Time Set display: Press SELECT ↓, OFF Time Set display:
HH:MM:SS SS flashing HH:MM:SS SS flashing
Time Set OFF Time

Press ENABLE (+) or DISABLE (-) to reset the Press ENABLE (+) or DISABLE (-) to change SS
SS value to zero. to desired value (00 to 59)

 To set Day/Night Mode On Time Press SELECT ↓, to exit back to Delay On/Off
Set display:
Press SELECT ↓, to access day/night mode ON D/N ON D/N OFF
or
Time Set display: Change? Change?
HH:MM:SS HH flashing
ON Time Pressing SELECT ↓ repeats the cursor/display
changes as above.
Press ENABLE (+) or DISABLE (-) to change Pressing SELECT ↑ repeats the cursor/display
HH to desired value (00 to 23) changes as above in reverse.

Press SELECT ↓, ON Time Set display:  To exit Clock Module menu:


HH:MM:SS MM flashing Return WP DIL switch on TIMER MODULE to
OFF position.
ON Time

Press SELECT ON/OFF: Module switches off


Press ENABLE (+) or DISABLE (-) to change the LCD Backlight and exits configuration mode,
MM to desired value (00 to 59) Normal Time display:
HH:MM:SS HH:MM:SS
Press SELECT ↓, ON Time Set display: or
D/N ON D/N OFF
HH:MM:SS SS flashing
ON Time
On completion of editing, return the Access
Control Keyswitch to position 0.
Press ENABLE (+) or DISABLE (-) to change SS
to desired value (00 to 59)

Document Number: Prec en Inst Rev: 4 Page 27 of 32 22/12/09


Written by: RKP Checked by: AJC

15.2 Configuring the Clock Module Table 4 - C1651 Clock Module DIL Switch 1 and
The Clock Module is configured by setting Link 1 Link 1 Settings
and DIL switch 1, both located on the rear of the
C1651 Clock Module PCB [accessed by opening LINK 1
the panel door].
Position Function
NOTE: Link 1 & DIL switch 1 are only available Fitted
st
1 fire alarm time display mode
at ACCESS level 4, i.e. they can only be set by
Removed Day/Night mode
suitably trained and qualified personnel.

DIL Switch 1
Link 1 DIL
Position Function
Switch
1 Off Clock Module menu configuration disabled
Off
1 On Clock Module menu configuration enabled
1 Off No effect
On
1 On No effect
Off 2 Off Day/Night Mode and Fire Event Counter mode enabled
Day/Night Mode enabled, Fire Event Counter mode disabled.
Off 2 On
[To zero Fire Event Counter, select “On” momentarily then return to “Off.”].
st
On 2 Off 1 alarm fire time and Fire Event Counter mode enabled
st
1 alarm fire time enabled, Fire Event Counter mode disabled.
On 2 On
[To zero Fire Event Counter, select “On” momentarily then return to “Off.”].

Document Number: Prec en Inst Rev: 4 Page 28 of 32 22/12/09


Written by: RKP Checked by: AJC

15.3 C1651 Clock Module PCB Features


Figure 14 llustrates the PCB features referred to elsewhere in the documentation

LK1 - Select
operating mode

DIL switch S1 -
Select config mode,
reset/disable counter

Figure 14 - C1651 Clock Module PCB

15.4 Clock Module Error Messages


15.4.2 EEPROM Error Message:
15.4.1 WP DIL switch Error Message:
Data inconsistency detected in EEPROM0 or
WP DIL switch operated when timer is not in Timer EEPROM1:
Set Mode, Normal Time Display flashes with WP
EEPROM 0 EEPROM 1
DIL switch message: or
ERROR ERROR
HH:MM:SS HH:MM:SS
or
D/N ON D/N OFF Note: Both EEPROMs can be erased by the
following procedure:
Changes to (pulses every second):
1. Power the panel down
WP DILSW
2. Place the WP DIL switch in the ON position
IS ON
3. Power the panel back up.
The backlight remains OFF. The panel indicates a 4. Return the WP DIL switch to the OFF position
general fault and prevents the clock module from when the display is as described in 15.4.1
being accessed by the user/engineer. above.

15.4.3 ROM Checksum Error Message:


Internal ROM Checksum failed:
ROM FAIL
ERROR

Document Number: Prec en Inst Rev: 4 Page 29 of 32 22/12/09


Written by: RKP Checked by: AJC

16. Mechanical, Electrical & Environmental Specification


en
Mechanical Precept Panel Repeater
Specification 2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Size [mm]
Height: 370 370 370 441 370 370 441
Width: 325 325 325 400 325 325 400
Depth: 126 126 126 131 126 126 131
Weight excluding
6.65Kg 7.05Kg 7.05Kg 9.35Kg 6.65Kg 6.65Kg 7.6Kg
batteries:

en
Mains Input Precept Panel Repeater
Specification 2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Maximum Input
85W 165W 165W 240W 85W 85W 85W
Power:
Protection:
[Warning: Replace T1A T3.15A T3.15A T3.15A T1A T1A T1A
only with identical H250V H250V H250V H250V H250V H250V H250V
type & rating of [1A anti- [3.15A anti- [3.15A anti- [3.15A anti- [1A anti- [1A anti- [1A anti-
BEAB or VDE surge] surge] surge] surge] surge] surge] surge]
approved fuse]
Voltage: 230V AC +10%/-15%
Cable 2
Minimum of 1mm copper protected by a 5A fuse.
requirements:

en
Power Supply Precept Panel Repeater
Output
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Specification
Maximum Short
Term Current
1.5A 3A 3A 5A 1.5A 1.5A 1.5A
Output
(I max b)
Maximum Short
Term Current
1.5A 3A 3A 5A 1.5A 1.5A 1.5A
Output
(I max b)
Minimum Output N/A N/A
Current (PSU is integrated into the ZERO (PSU is integrated into the
(I min) motherboard) motherboard)
Voltage Output,
26.5 - 28.6V (27.3V nominal)
Mains On
Maximum Current
Output, Mains 1.5A 3A 3A 5A 1.5A 1.5A 1.5A
Failed
Voltage Output,
20.0* - 20.0* - 20.0* - 20.0* -
Mains Failed N/A
28.6V 28.6V 28.6V 28.6V
[* at full load]
Max Ripple
including switching
spikes[full
200 200 200 750 200
load/battery
disconnected]
(mV p-p)
Output Voltage Factory Set
adjustment
Output protection: Electronic current limiting
Common fault
N/A N/A N/A 25mA N/A N/A N/A
output:
Mains failed fault
N/A N/A N/A 25mA N/A N/A N/A
output:

Document Number: Prec en Inst Rev: 4 Page 30 of 32 22/12/09


Written by: RKP Checked by: AJC

en
Precept Panel Repeater
Battery Specification
2/4 zone 8 zone 16 zone 32 zone 2-8 zone 16 zone 32 zone
Battery charger output:
[Temperature
compensated float
charger] 1.5A 3A 3A 5A 1.5 A 1.5 A 1.5 A
28.6V 0.1V@-5C
26.5 V0.1V@ +40 C.
Maximum internal
resistance of battery &
charger circuit: 1 0.6 0.6 0.35 1 1 1
(Ri max)
(Ω)
Battery type:
POWERSONIC 2 off 2 off 2 off 2 off 2 off 2 off 2 off
[Warning: Replace PS1230 PS1270 PS12120 PS12170 PS1230 PS1230 PS1230
only with identical [12V 3.4Ah] [12V 7Ah] [12V 12Ah] [12V 17Ah] [12V 3.4Ah] [12V 3.4Ah] [12V 3.4Ah]
battery]
Battery size (mm):

W
L = 133 L = 151 L = 151 L = 181 L = 133 L = 133 L = 133
W = 67 W = 65 W = 98 W = 76 W = 67 W = 67 W = 67
H = 60 H = 94 H = 94 H = 167 H = 60 H = 60 H = 60
HT H
HT = 66 HT = 98 HT = 100 HT = 167 HT = 66 HT = 66 HT = 66
L

Battery circuit F6.15A


F2AL250V F5AL250V F5AL250V F2AL250V F2AL250V F2AL250V
protection: L250V
20mm fast 20mm fast 20mm fast 20mm fast 20mm fast 20mm fast
[Warning: Replace 20mm fast
blow glass blow glass blow glass blow glass blow glass blow glass
only with identical fuse fuse blow glass
fuse fuse fuse fuse
type & rating of fuse] fuse
Mains failed fault
45mA 45mA 45mA 55mA 40mA 40mA 40mA
battery current:
Mains failed alarm
80mA 80mA 80mA 90mA 75mA 75mA 75mA
battery current:

Environmental
All Panels
Specification
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%

Document Number: Prec en Inst Rev: 4 Page 31 of 32 22/12/09


Written by: RKP Checked by: AJC

17. Construction Products Directive

0086

Control Equipment Ltd


Hillcrest Business Park
Cinder Bank
Dudley
West Midlands
DY2 9AP
United Kingdom.

09
0086-CPD-555921

EN54-2
Control and indicating equipment for fire detection and fire alarm systems for buildings
Provided options:
 Outputs to fire alarm devices.
 Output to fire alarm routing equipment.
 Outputs to Fire Protection Equipment - Output type B
 Output to fault warning routing equipment.
 Test condition.
 Alarm Counter.
 Delays to Outputs

EN54-4
Power supply equipment for fire detection and fire alarm systems for buildings

Document Number: Prec en Inst Rev: 4 Page 32 of 32 22/12/09

You might also like