125ERESC Spec Sheet
125ERESC Spec Sheet
208--480 V Gas
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source.
The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited
running time and continuous ratings, consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves
the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATING: Altitude: Derate 1.3% per 100 m (328 ft.) elevation
above 200 m (656 ft.) up to a maximum elevation of 3000 m (9842 ft.). Temperature: Derate 2.0% per 10_C (18_F) temperature above 25_C (77_F) up to 50_C (122_F). For units having enclosures
with enclosed silencers, add 5_C (9_F) to the ambient temperature. For dual fuel engines, use the LPG ratings for both the primary and secondary fuels.
G4-223 (125ERESC) 10/13d
Alternator Specifications
Specifications Alternator D NEMA MG1, IEEE, and ANSI standards compliance for
Manufacturer Kohler
temperature rise and motor starting.
Type 4-Pole, Rotating-Field D Sustained short-circuit current of up to 300% of the rated
Exciter type Brushless, Rare-Earth current for up to 10 seconds.
Permanent- Magnet
Leads: quantity, type D Sustained short-circuit current enabling downstream circuit
4RX 12, Reconnectable breakers to trip without collapsing the alternator field.
4TX 4, 120/240
D Self-ventilated and dripproof construction.
Voltage regulator Solid State, Volts/Hz
Insulation: NEMA MG1 D Vacuum-impregnated windings with fungus-resistant epoxy
Material Class H varnish for dependability and long life.
Temperature rise 130_C, Standby
Bearing: quantity, type 1, Sealed D Superior voltage waveform from a two-thirds pitch stator and
Coupling Flexible Disc skewed rotor.
Amortisseur windings Full D Total harmonic distortion (THD) from no load to full load with
Voltage regulation, no-load to full-load ±0.5% a linear load is less than 3.3%.
Unbalanced load capability 100% of Rated Standby
Current
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
480 V 4R12X (12 lead) 448 (60 Hz)
480 V 4R13X (12 lead) 540 (60 Hz)
240 V 4T13X (4 lead) 440 (60 Hz)
Application Data
Engine Engine Electrical
Engine Specifications Engine Electrical System
Manufacturer PSI Ignition system Individual Coil
Engine: model, type Industrial 8.8 L, 4-Cycle, Near Plug Ignition
Turbocharged Battery charging alternator:
Cylinder arrangement V-8 Ground (negative/positive) Negative
Displacement, L (cu. in.) 8.8 (537) Volts (DC) 12
Bore and stroke, mm (in.) 110 x 114 (4.35 x 4.5) Ampere rating 70
Compression ratio 10.1:1 Starter motor rated voltage (DC) 12
Piston speed, m/min. (ft./min.) 411 (1350)
Battery, recommended cold cranking
Main bearings: quantity, type 5, Bi-Metal Steel and amps (CCA):
Aluminum
Qty., rating for --18_C (0F) One, 630
Rated rpm 1800
Max. power at rated rpm, NG, kW (HP) 142 (190) Battery voltage (DC) 12
Max. power at rated rpm, LPG, kW (HP) 121 (162)
Cylinder head material Cast Iron
Fuel
Piston type and material Flat Top, Hypereutectic Fuel System
Cast Alum. Fuel type Natural Gas, LPG, or
Crankshaft material Forged Steel, Induction Dual Fuel
Hardened, Tangential Fillet Fuel supply line inlet 1.5 NPTF
Valve (exhaust) material Int.-A193 Exh. Inconel Natural gas fuel supply pressure, kPa
Governor type Electronic (in. H2O) 1.74--2.74 (7-11)
Frequency regulation, no-load to full-load Isochronous LPG vapor withdrawal fuel supply
Frequency regulation, steady state 0.5% pressure, kPa (in. H2O) 1.24--2.74 (5-11)
Frequency Fixed Dual fuel engine, LP vapor withdrawal
Air cleaner type, all models Dry fuel supply pressure, kPa (in. H2O) 1.24 (5)
Fuel Composition Limits * Nat. Gas LPG
Exhaust
Methane, % by volume 90 min. 1.2 max.
Exhaust System Ethane, % by volume 4.0 max. 10 max
Exhaust manifold type Dry Propane, % by volume 1.0 max. 96 max.
Exhaust flow at rated kW, m3/min. (cfm) 21.1 (745) Propene, % by volume 0.1 max. 3 max.
Exhaust temperature at rated kW, dry C4 and higher, % by volume 0.3 max. 3 max.
exhaust, _C (_F) 649 (1200) Sulfur, ppm mass 25 max. 25 max.
Maximum allowable back pressure, Lower heating value,
kPa (in. Hg) 10.2 (3.0) MJ/m3 (Btu/ft3), min. 33.2 (890) 78.8 (2116)
Exhaust outlet size at engine hookup See ADV drawing
* Fuels with other compositions may be acceptable. If your fuel is
outside the listed specifications, contact your local distributor for
further analysis and advice.
Cooling
Decision-Makerr 3000 Controller
Radiator System
Ambient temperature, _C (_F) 45 (113) Provides advanced control, system monitoring, and system diagnostics for
Engine jacket water capacity, L (gal.) 13.4 (3.54) optimum performance and compatibility.
Radiator system capacity, including
engine, L (gal.) 27.6 (7.3) D Digital display and menu control provide easy local data access
Engine jacket water flow, Lpm (gpm) 125 (33) D Measurements are selectable in metric or English units
Heat rejected to cooling water at rated
D Remote communication through a PC via network or serial
kW, dry exhaust, kW (Btu/min.) 73.5 (4184) configuration
Heat rejected to engine oil at rated kW,
kW (Btu/min.) 1.2 (67.5) D Integrated hybrid voltage regulator with 0.5% regulation
Water pump type Centrifugal D Built-in alternator thermal overload protection
Fan diameter, including blades, mm (in.) 660 (26) Refer to G6-100 for additional controller features and accessories.
Fan, kWm (HP) 8.9 (12.0)
Max. restriction of cooling air, intake and
discharge side of radiator, kPa (in. H2O) 0.125 (0.5)
Sound Enclosure
Operation Requirements
Air Requirements
Radiator-cooled cooling air,
m3/min. (scfm)[ 306 (10800)
Combustion air, m3/min. (cfm) 6.9 (244)
Heat rejected to ambient air:
Engine, kW (Btu/min.) 21.6 (1230)
Alternator, kW (Btu/min.) 15.7 (893)
[ Air density = 1.20 kg/m3 (0.075 lbm/ft3)
D Sound level (8 point logarithmic average) at 7 m (23 ft.) with full load:
Fuel Consumption] Standby Rating 73 dB(A).
Natural Gas, m3/hr. (cfh) at % load D Sound level compared to competitor ratings with no load: 70 dB(A).*
100% 42.8 (1511) D Sound attenuating enclosure uses acoustic insulation that meets
75% 34.1 (1204) UL 94 HF1 flammability classification and repels moisture absorption.
50% 25.2 (890) D Vertical air inlet and outlet discharge with 90 degree bends to redirect
25% 16.5 (583) air and reduce noise.
0% 6.8 (240) D Internal-mounted critical silencer and flexible exhaust connector.
LPG, m3/hr. (cfh) at % load D Skid-mounted, steel (standard) or aluminum (optional) construction
100% 17.7 (626) with hinged doors.
75% 13.4 (473) D Fade-, scratch-, and corrosion-resistant Kohlerr Cashmere Power
50% 9.5 (334) Armort textured e-coat paint.
25% 5.9 (209)
0% 2.7 (95) D Lockable, flush-mounted door latches.
D Certified to withstand 241 kph (150 mph) wind load rating (aluminum
] Nominal fuel rating: Natural gas, 37 MJ/m3
(1000 Btu/ft3)
enclosures only).
LPG, 93 MJ/m3 (2500 Btu/ft3)
* Lowest of 8 points measured around the generator. Sound levels at
LPG conversion factors: other points around generator may be higher depending on installation
8.58 ft.3 = 1 lb. parameters.
0.535 m3 = 1 kg.
36.39 ft.3 = 1 gal.
NOTE: This drawing is provided for reference only and should not be
used for planning installation. Contact your local distributor for more
detailed information.