CMMS Presentation

This document describes a proposed computerized maintenance management system for an air conditioning system. The system will [1] monitor parameters of chilled water, chillers, air handlers, pumps, electric motors and [2] display abnormalities to recommend proper corrections while still allowing manual troubleshooting. Algorithms are provided to calculate cooling effects and power consumption of the various components. A relational database will also be created to identify troubles.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
491 views

CMMS Presentation

This document describes a proposed computerized maintenance management system for an air conditioning system. The system will [1] monitor parameters of chilled water, chillers, air handlers, pumps, electric motors and [2] display abnormalities to recommend proper corrections while still allowing manual troubleshooting. Algorithms are provided to calculate cooling effects and power consumption of the various components. A relational database will also be created to identify troubles.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPSX, PDF, TXT or read online on Scribd
You are on page 1/ 15

COMPUTERIZED MAINTENANCE

MANAGEMENT SYSTEM

By:
JOSEPH RUDENTE F. DAVID
PME 3561
BACKGROUND

Cost on Breakdown
Energy Consumption
Inconvenience
Overall Economic Effect
Purpose and Objective

Monitor the different parameters of the


different modules attributed to the chilled
water air conditioning system.
The computer program shall be in a passive
mode, i.e., it shall display and indicate the
trouble or abnormality experienced by the air
conditioning system and recommend the
proper correction of such trouble.
Trouble shooting will still be made manually.
Click to edit Master text styles
Second level
● Third level
● Fourth level
● Fifth level
General Algorithm
Chiller Algorithm

 Evaporator Heat Exchanger


chilled water flow rate
entering water temperature
leaving water temperature
entering water pressure
leaving water pressure
 Cooling q =qCH
Effect,
ch 500Q gpm ( t e − tl )
Chiller Algorithm

 Condenser Heat Exchanger


cooling water flow rate
entering water temperature
leaving water temperature
entering water pressure
leaving water pressure

condenser = 500Qgpm ( t e − t l )
qEffect,
 Cooling qCH
CHILLER Algorithm

 Chilled Water System


cooling water flow rate
entering water temperature
leaving water temperature
entering water pressure
leaving water pressure

condenser = 500Qgpm ( t e − t l )
qEffect,
 Cooling qCH
CHILLER Algorithm
Air Handler Algorithm

 Air System
air flow rate
entering air temperature
leaving air temperature
air differential pressure
entering air relative humidity

q AHU = 4.5Qcfm ( he − hl )
leaving air relative humidity
 Cooling Effect, qAHU
Airstyles
Click to edit Master text Handler Algorithm
Second level
● Third level

● Fourth level

● Fifth level
PUMP Algorithm
PUMP Algorithm

 Pump System
water flow rate
entering water pressure
leaving water pressure
 Pump Power, Ppump
Ppump = 19.25 ⋅ Qgpm ( pl − pe )
ELECTRIC
MOTORS
ELECTRIC MOTORS

 Monitoring Parameters
Voltage
Current on all phases
 Electric Power, Pmotor

VI 3
Pm = • 0.8
1000
Trouble Relational Database
Management System

A relational database management system


(RDMS) shall be created for trouble
identity. The algorithm for this shall be
provided by the system engineering
designer.