Electromechanical Sensors For Pressure Control OsiSense XM - Schneider

The document is a catalogue for OsiSense XM electromechanical pressure and vacuum sensors. It describes different types of sensors for controlling pressure in control circuits or power circuits. Sensors can detect or regulate pressure thresholds for various fluids like air, water, oils, and corrosive fluids at pressures from 1 bar to 500 bar and temperatures from -30°C to 160°C, depending on the model. The catalogue provides specifications, dimensions, and reference information for different sensor models.

Uploaded by

Iman Faisal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
262 views102 pages

Electromechanical Sensors For Pressure Control OsiSense XM - Schneider

The document is a catalogue for OsiSense XM electromechanical pressure and vacuum sensors. It describes different types of sensors for controlling pressure in control circuits or power circuits. Sensors can detect or regulate pressure thresholds for various fluids like air, water, oils, and corrosive fluids at pressures from 1 bar to 500 bar and temperatures from -30°C to 160°C, depending on the model. The catalogue provides specifications, dimensions, and reference information for different sensor models.

Uploaded by

Iman Faisal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 102

Electromechanical sensors

for pressure control OsiSense XM

Catalogue

Simply easy!
TM
Contents Electromechanical pressure and
vacuum switches OsiSense XM

Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 2 to 5

bb General............................................................................................ pages 6 to 11


bb Operating curves.......................................................................... pages 12 to 15

Electromechanical pressure and vacuum switches


for control circuits
For controlling the pressure of air, water, hydraulic oils, corrosive fluids
and viscous products
bb Presentation and setting......................................................................... page 16
bb Characteristics........................................................................................ page 17
bb References
vv Pressure and vacuum switches XMLA, B, C and D......................... pages 18 to 67
vv Accessories and replacement parts........................................................... page 68
vv Dimensions..................................................................................... pages 69 to 71
vv Components materials of units in contact with fluid...................... pages 72 and 73

For controlling the pressure of air, water, hydraulic oils and corrosive fluids
bb Presentation and setting......................................................................... page 74
bb Characteristics........................................................................................ page 75
bb References
vv OsiSense ACW, sizes from: 0.7 to 131 bar................................... pages 76 and 77
vv OsiSense ADW, sizes from: 69 to 340 bar ................................... pages 78 and 79
vv Dimensions.................................................................................. pages 80 and 81

For controlling the pressure of air and water


bb Presentation and setting......................................................................... page 82
bb Characteristics........................................................................................ page 83
bb References
vv OsiSense XMX and XMA, sizes from: 6 to 25 bar........................ pages 84 and 85
vv Accessories and replacement parts........................................................... page 86
vv Dimensions................................................................................................ page 87

Electromechanical pressure switches for power circuits


For controlling the pressure of water
bb Presentation and setting......................................................................... page 88
bb Characteristics........................................................................................ page 89
bb References
vv OsiSense FGT, FSG and FYG ....................................................... pages 90 to 92
vv Dimensions................................................................................................ page 93

For controlling the pressure of air and water


bb Presentation............................................................................................. page 94
bb Characteristics........................................................................................ page 95
bb References
vv OsiSense XMP, IP 54, sizes from: 6 to 25 bar ............................... pages 96 to 101
vv OsiSense XMP, IP 65, sizes from: 6 to 25 bar .......................... pages 102 and 103
vv Accessories and replacement parts......................................................... page 104
vv Dimensions.............................................................................................. page 105

bb Product reference index........................................................ pages 106 and 107

1
Selection guide Electromechanical sensors
for pressure control
OsiSense XM

Applications Type of installation Control circuits Control circuits

Fluids controlled Air, water, hydraulic oils, corrosive fluids, viscous products Air, water, hydraulic oils, corrosive fluids, Air, hydraulic oils, corrosive fluids
viscous products

Type of operation Detection of a single Regulation between 2 thresholds (adjustable differential) Dual stage switches Regulation between 2 thresholds (adjustable differential)
threshold Detection at each threshold (fixed differential)
(fixed differential)

Fluid characteristics Air, fresh water, corrosive fluids, viscous products, up to 160°C Air, fresh water, corrosive fluids, viscous products, Air, oils and other non corrosive fluids Oils and other fluids (- 25…+ 120 °C)
Sea water, up to 30 °C, depending on model up to 160°C (- 73…+ 125°C)
Sea water, up to 30 °C, depending on model Only oils, including synthetic oils,
(- 30…+ 125 °C), depending on model

Sizes - 1 bar…500 bar (- 14.5 psi…7250 psi) - 1 bar…500 bar (- 14.5 psi…7250 psi) 0.7 bar…131 bar (10.15 psi…1900 psi) 69 bar…340 bar (1000 psi…4930 psi)

Dimensions of case (mm) Width x height x depth 35 x 68 x 75 46 x 68 x 85 45 x 68 x 85 88 x 88 x 68

Type of contacts 1 CO single-pole, snap action 2 CO single-pole, simultaneous, 2 CO single-pole, staggered, snap action 1 CO or 2 CO single-pole, snap action
snap action

Degree of protection IP 66: switches with terminal connections IP 66: switches with terminal IIP 66: switches with terminal connections IP 65
IP 65: switches with connector connections

Electrical connection Connector : Connector : Screw terminals:


bb EN 175301-803-A (ex-DIN 43650A), 4-pin male. bb EN 175301-803-A (ex-DIN 43650A), 4-pin male. bb 1 tapped entry M20 x 1.5 mm for ISO cable gland or
b 1 tapped entry for n° 13 cable gland, depending on model
Screw terminals: Screw terminals:
bb 1 tapped entry M20 x 1.5 mm for ISO cable gland or bb 1 tapped entry M20 x 1.5 mm for ISO cable gland
bb 1 tapped entry 1/2”-14 NPT for cable gland, depending on model. or
bb 1 tapped entry 1/2”-14 NPT for cable gland,
depending on model.

Fluid connection G 1/4 (female) G 1/4 (female) G 1/4 (femelle) G 3/8 (female)
1/4” - 18 NPTF (female) 1/4” - 18 NPTF (female)
G 1¼” (female) for viscous products G 1¼” (female) for viscous products

Type reference XMLA XMLB XMLC XMLD ACW ADW

Pages 18 to 67 18 to 67 76 and 77 78 and 79

Other versions Electromechanical pressure and vacuum switches with alternative tapped cable entries and/
or fluid entries: NPT etc. Please consult our Customer Care Centre.

2 3
Selection guide (continued) Electromechanical sensors
for pressure control
OsiSense XM

Applications Type of installation Control circuits Power circuits

Fluids controlled Air, water Water Air, water

Type of operation Regulation between 2 thresholds (adjustable differential) Detection of a single Regulation between 2 thresholds (adjustable differential)
threshold (fixed differential)

Fluid characteristics Air, fresh water, sea water (0…+ 70°C) Fresh water, sea water (0…+ 70°C) Air, fresh water, sea water
(0…+ 70°C)

Sizes 6 bar, 12 bar and 25 bar (87 psi, 174 psi and 362.5 psi) 4.6 bar (66.7 psi) 7 bar (101.5 psi) 10.5 bar (152.3 psi) 6 bar, 12 bar and 25 bar
(87 psi, 174 psi and 362.5 psi)

Dimensions of case (mm) Width x height x depth 57 x 78 x 97.5 73 x 73 x 102 72 x 77 x 106 72 x 73 x 102 57 x 78 x 97.5

Setting of switching points Internal screws External screws Internal screws

Type of contacts 1 CO single-pole, snap action 2 NC snap action 2 NC or 3 NC snap action

Degree of protection IP 54 IP 20/IP 65 IP 54 or IP 65, depending


on model

Electrical connection Screw terminals: Screw terminals: Screw terminals:


b 2 entries tapped for n° 13 cable gland, b 2 cable entries with grommet or b 2 entries incorporating n° 13
b one fitted with n° 13 cable gland, b 2 cable entries with n° 13 cable gland cable gland or without cable
b one fitted with blanking plug. gland, depending on model

Fluid connection G 1/4 or 4 x G 1/4 (female), depending on model G 1/4 or R 1/4 (female or male) G 1/4, G 3/8 or 4 x G 1/4
(female), depending on model

Type reference XMX XMA FTGp, FTGpNE FSGp, FSGpNE FYG22, FYG22NE FYG32, FYG32NE XMP

Pages 84 85 90 to 92 96 to 103

Other versions Electromechanical pressure switches with alternative tapped cable entries and/or fluid entries:
ISO, NPT, etc. Please consult our Customer Care Centre.

4 5
General Electromechanical pressure
and vacuum switches
OsiSense XM

Function
The function of pressure and vacuum switches is the control or regulation of
pressure or vacuum levels in hydraulic or pneumatic systems.
They transform the pressure change into a digital electrical signal when the preset
switching points are reached.

Switches for power circuits


Switches with power electrical contacts, either 2-pole or 3-pole, designed for direct
switching of single-phase or 3-phase motors (pumps, compressors, etc.).

Switches for control circuits


Switches with standard electrical contacts, designed for control of contactors, relays,
power valves, PLC inputs, etc.

Pressure switch operating principle


Detection of a single threshold
The switches for detection of a single threshold (fixed differential) have a single
adjustable setting point (PH). The differential between the high and low points
(PH - PB) depends upon the natural characteristics of the switch. It is not adjustable.
Pressure Example: contact
PH schematics of XMLA
Fixed

13

11

13

11
differential
PB

14

12

14

12
Time 1 2
1 2 1 2

–– Adjustable value PH = High point


--- Non adjustable value PB = Low point
Regulation between 2 thresholds
The switches for regulation between 2 thresholds (adjustable differential) have
both a high point setting (PH) and a low point setting (PB). Both of these points can
be independently adjusted.
Pressure
Example: contact
PH schematics of XMLB
6 Adjustable
13

11

13

11
differential

PB
14

12

14

12
Time 1 2
1 2 1 2

–– Adjustable value PH = High point


PB = Low point
Detection of 2 thresholds
The dual stage switches, for detection at each threshold, have an adjustable high point
setting for each stage (PH1 and PH2). Both of these points can be independently adjusted.
For both stages, the differential between the high point and the low point (PH1 - PB1 and
PH2 - PB2) depends upon the natural characteristics of the switch. It is not adjustable.
Pressure Example: contact
PH2 schematics of XMLD
Fixed
differ- Adjustable
13

11

23

21

PB2 spread
ential
1
PH1
Fixed
14

12

24

22

PB1 differential
13

11

23

21

Time
2
1 2 3 4 1 2 3 4
14

12

24

22

–– Adjustable value PH = High point


13

11

23

21

--- Non adjustable value PB = Low point 3


14

12

24

22
13

11

23

21

4
14

12

24

22

6
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM

Vacuum switch operating principle


Detection of a single threshold
The switches for detection of a single threshold (fixed differential) have a single
adjustable setting point (PH). The differential between the high and low points
(PH - PB) depends upon the natural characteristics of the switch. It is not adjustable.

Time Example: contact


schematics of XMLA

13

11
13

11

14

12
14

12
PH
Fixed
differential 1 2
PB
1 2 1 2

Vacuum

–– Adjustable value PH = High point


--- Non adjustable value PB = Low point

Regulation between 2 thresholds


The switches for regulation between 2 thresholds (adjustable differential) have
both a high point setting (PH) and a low point setting (PB). Both of these points can
be independently adjusted.
Time Example: contact
schematics of XMLB

13

11
13

11
PH

14

12
14

12
Adjustable
differential
1 2
PB
1 2 1 2

Vacuum

–– Adjustable value PH = High point 6


PB = Low point

Detection of 2 thresholds
The dual stage switches, for detection at each threshold, have an adjustable high
point setting for each stage (PH1 and PH2). Both of these points can be
independently adjusted.
For both stages, the differential between the high point and the low point (PH1 - PB1
and PH2 - PB2) depends upon the natural characteristics of the switch. It is not
adjustable.
Time Example: contact
schematics of XMLD
PH1
13

11

23

21

Fixed
PB1 differ- Adjustable 1
ential spread
14

12

24

22

PH2
Fixed
13

11

23

21

differential
PB2 2
1 2 3 4 1 2 3 4
14

12

24

22

Vacuum

–– Adjustable value PH = High point


13

11

23

21

--- Non adjustable value PB = Low point 3


14

12

24

22
13

11

23

21

4
14

12

24

22

7
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM

Terminology
Operating range
The difference between the minimum low point (PB) and the maximum high point
(PH) setting values.

Size
Pressure switches and vacuum-pressure switches (vacu-pressure switches)
Maximum value of the operating range.

Vacuum switches
Minimum value of the operating range.

Switching point on rising pressure (PH)


Pressure switches
The upper pressure setting at which the pressure switch will actuate the contacts
on rising pressure.

Vacuum switches
The lower vacuum setting at which the vacuum switch will reset the contacts on
rising pressure.

Switching point on falling pressure (PB)


The pressure at which the switch output changes state on falling pressure.

Switches with fixed differential


The lower point (PB) is not adjustable and is entirely dependent on the high point
setting (PH) and the natural differential of the switch.

Switches with adjustable differential


The adjustable differential enables the independent setting of the lower point (PB).

Differential
The difference between the switching point on rising pressure (PH) and the switching
point on falling pressure (PB).

Spread
6 For dual stage switches, the spread indicates the difference between the 2 switching
points on rising pressure (PH2 and PH1) and, for vacuum switches, the difference
between the 2 switching points on falling pressure (PB2 and PB1).

Accuracy (switches with setting scale)


+ The tolerance between the point at which the
Setting point switch actuates its contacts and the value
indicated on the setting scale. Where very high
– setting accuracy is required (initial installation
of the product), it is recommended to use
separate measuring equipment (pressure
gauge, etc.).

8
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM

Terminology (continued)
Repeat accuracy (R)
The tolerance between two consecutive
switching operations.
R

Drift (F)
The tolerance of the switching point
throughout the entire service life
F of the switch.

Accidental overpressure
bar This is an accidental pressure surge of
300 very short duration (a few milliseconds).

200 If accidental overpressures occur and their


duration is less than 50 milliseconds, the
100 pressure damping device incorporated in
the XML switches (sizes 10 bar and
0 greater) will diminish the effect.
0 50 100 150
ms

Example 1: with destructive


pressure level.
bar
100

50

0
6
0 50 100 150
ms

Example 2: with destructive pressure level


and destructive pressure oscillations.
Without damping device
With damping device

Maximum permissible pressure per cycle (Ps)


A pressure switch can withstand this pressure, without detrimental effect, on each
cycle throughout its service life.

Its minimum value is at least equal to 1.25 times the switch size.

Maximum permissible accidental pressure


The maximum accidental pressure is at least equal to 2.25 times the switch size.

Destruction pressure
The maximum guaranteed pressure that the switch will withstand before its destruction,
i.e. bursting, rupturing, component failure, etc.

Its value is at least equal to 4.5 times the switch size.

9
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM

Application range of pressure and vacuum switches XML, XMA and XMX, for control circuits
On standard loads
Continuous duty, frequent switching.
Insulation voltage limit
V
500

240 3

200

150

4
120

100

60
Inductive loads

Heating limit (lth)


48

24

20

1
15

6 2

10

5 I
1 mA 2 mA 3 mA 6 mA 10 mA 1A 1,5 A 2A 3A 6A 10 A

1 Standard PLC input, type 1 Pressure Application range


2 Standard PLC input, type 2 switches
3 Switching capacity conforming XMLA
to IEC 60947-5-1, XMLB
utilisation category AC-15, DC-13 XMLC
B300 240 V 1.5 A XMLD
R300 250 V 0.1 A XMX, XMA
4 Switching capacity conforming XMLG
to IEC 60947-5-1, XMLK
utilisation category AC-15, DC-13
B300 120 V 3A
R300 125 V 0.22 A
PLC: Programmable Logic Controller
On small loads
The use of electromechanical pressure and vacuum switches with programmable
logic controllers is becoming more predominant.
On small loads, the reliability of the switches maintain a failure rate of less than 1 for
100 million operating cycles.

10
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM

Selection of switch size


After establishing the type of switch required for the application (single threshold
detection or regulation between 2 thresholds), the selection of its size will depend
on the following criteria:
v the differential: difference between the high point (PH) and the low point (PB),
v the maximum pressure permissible per cycle,
v repeat accuracy, precision and minimum drift.

Examples of a fixed differential pressure switch selection, for detection of a


single threshold
Main criterion: minimum differential
Example: for a selected high point (PH) of 7 bar
10 bar 20 bar 35 bar

7 6.5

7 6
7
5
0.6 1 1.5
XMLA010ppppp XMLA020ppppp XMLA035ppppp
Differential = 0.5 bar Differential = 1 bar Differential = 2 bar
Select an XMLA010ppppp (the lowest size)

Main criterion: tolerance to overpressures


Example: for a selected high point (PH) of 12 bar
45 bar 80 bar

25 45
20
35

12

12
1
1.5

XMLA020ppppp XMLA035ppppp
Permissible accidental Permissible accidental
overpressure = 45 bar overpressure = 80 bar
Select an XMLA035ppppp (the highest size) 6
Main criterion: repeat accuracy, precision and minimum drift
Example: for a selected high point (PH) of 18 bar
20 bar 35 bar As a general rule, working
18 at the upper or lower limits
of the operating range
18
should be avoided.

1 1.5

XMLA020ppppp XMLA035ppppp
Adjustable from 1 to 20 bar Adjustable from 1.5 to 35 bar
Select an XMLA035ppppp

Units of pressure conversion table


psi kg/cm2 bar atm mm Hg mm H2O Pa
(Torr)
1 psi = 1 0.07031 0.06895 0.06805 51.71 703.7 6895
1 kg/cm2 = 14.22 1 0.98066 0.96784 735.55 10 000 98 066
1 bar = 14.50 1.0197 1 0.98695 750.06 10 197 105
1 atm = 14.70 1.0333 1.0132 1 760.0 10 333 101 325
1 mm Hg = 0.01934 1.360 x 10-3 1.333 x 10-3 1.316 x 10-3 1 13.59 133.3
(Torr)
1 mm H2O = 1.421 x 10-3 10-4 a 10-4 a 10-4 0.07361 1 a 9.80

1 Pa = 1.45 x 10-4 1.0197 x 10-5 10-5 9.8695 x 10-6 7.5 x 10-3 0.10197 1

Example: 1 bar = 14.50 psi = 105 Pa

11
Operating curves Electromechanical pressure
and vacuum switches
Fixed differential switches, for detection
of a single threshold

Rising pressure
Adjustment
range of the Defined by the difference between the
1 high point
+
Maxi
minimum and maximum high point (PH)
setting values.

switching point (PH)


Adjustable range of
For a high set point (PH), the lower
point (PB) is fixed and cannot be
adjusted.
For a low set point (PB1 or PB2), the

2 Mini
higher point (PH1 or PH2) is fixed and
cannot be adjusted.
– 0
0 Low point (PB) Falling
range pressure

Switching Rising pressure

point on The upper pressure setting at which the

3 rising +
PH
pressure or vacuum switch will actuate
the contacts on rising pressure.
pressure
(PH) Adjustable throughout the range on
rising pressure.

4
– 0
0 Falling pressure

Switching Rising pressure

point on The pressure at which the switch


+ contact changes state on falling
5 falling
pressure
PH pressure.

(PB) The lower point (PB) is not adjustable


and is entirely dependent on the high
point setting (PH) and the natural
PB differential of the switch.

6 – 0
0 PB
Falling pressure

Differential Rising pressure


PH - PB = natural differential
+ The difference between the switching
7 PH point on rising pressure (PH) and the
switching point on falling pressure (PB).
PH – PB
This point is not adjustable and therefore,
the value of the differential is fixed.
PB It is the natural differential of the switch
(contact differential, friction, etc.).
8 – 0
0 PB
Falling pressure

Example Rising pressure


b Consider a switching point on rising
bar 60 pressure (PH) of 40 bar (set value at

9 which the contact will change state on


rising pressure).
PH 40 b It can be seen that the switching
point on falling pressure (PB) is 28 bar
(fixed value at which the contact will
20 return to its original state).
Conclusion:

10 0
v the differential will be 40 - 28 = 12 bar.

03 20 28 40 60 bar
PB Falling pressure

12
Operating curves Electromechanical pressure
and vacuum switches
Adjustable differential switches, for regulation
between 2 thresholds

Rising pressure
Adjustment
range of the Defined by the difference between the
+
high point Maxi
minimum and maximum high point (PH)
setting values. 1

switching point (PH)


Adjustable range of
1 2

Mini
2
– 0
0 Low point (PB) Falling
range pressure

Switching Rising pressure

point on The upper pressure setting at which the


rising
+ pressure or vacuum switch will actuate
the contacts on rising pressure. 3
pressure PH 1 2
(PH) Adjustable throughout the range on rising
pressure.

4
– 0
0 Falling pressure

Switching Rising pressure

point on The pressure at which the switch


+ contact changes state on falling
falling
pressure PH 1 2
pressure. 5
(PB) The adjustable differential enables
the independent setting of the lower
PB" point (PB).
PB'

– 0
6
0 PB' PB"
Falling pressure

Differential Rising pressure

Low point < High point


+ PH - PB' = natural differential

PH 1 2
PH - PB" = minimum differential
7
The difference between the switching
PH – PB" point on rising pressure (PH) and the
PH – PB'
PB" switching point on falling pressure (PB).
PB'
Note: the low point can be set at any value

– 0
between PB' and PB".
8
0 PB' PB"
Falling pressure

Example Rising pressure


bar b Consider a switching point on rising
30 pressure (PH) of 22 bar (set value at

9
which the contact will change state on
PH 22 1 2 rising pressure).
20 b It can be seen that the switching
point on falling pressure (PB) can be
between 4 and 19 bar inclusive
10 (set value at which the contact will
return to its original state).

10
Conclusion:
1 Maximum differential 0 v the maximum differential will be:
0 4 10 19 20 30 bar
2 Minimum differential PB' PB" 22 - 4 = 18 bar,
Falling pressure v the minimum differential will be:
22 - 19 = 3 bar.

13
Operating curves Electromechanical pressure
(switching points on rising and vacuum switches
pressure) Dual stage, fixed differential switches,
for detection at each threshold

Rising pressure
Adjustment
ranges of the Defined by the difference between the
1
+ minimum and maximum high point
switching setting values of each stage (PH1 and
points PH1

Adjustment range of
1 2 PH2).

high point (PH2)


and PH2
on rising
pressure

2
– 0
0 Adjustment range Falling
of high point PH1 pressure

Switching Rising pressure

point PH2 The upper pressure setting at which the


+
3
pressure or vacuum switch will actuate
on rising the contacts on rising pressure.
pressure PH2 1 2
Adjustable throughout the range on rising
pressure.

4 – 0
0
Falling pressure

Switching Rising pressure

point PH1 The upper pressure setting at which the


+ pressure or vacuum switch will actuate
on rising
5 pressure PH2 1 2
contact 1 on rising pressure.

PH1"
PH1'

6 – 0
0 PH1' PH1"
Falling pressure

Spread Rising pressure


PH1 < PH2
+ PH2 - PH1' = maximum spread
PH2 - PH1" = minimum spread
7 PH2 1 2
The difference between switching points
PH2 – PH1" PH2 and PH1 on rising pressure.
PH2 – PH1'
PH1"
PH1' Note: switching point PH1 can be set at any
value between PH1' and PH1".

8 – 0
0 PH1' PH1"
Falling pressure

Example: Rising pressure

Determining bar b Consider a 2nd stage switching point


30 on rising pressure (PH2) of 20 bar (set
switching value at which contact 2 will change
9 points on
rising PH2 20
1 2 state on rising pressure).
b It can be seen that the 1st stage
pressure for switching point (PH1) can be set
between 4.5 and 17 bar on rising
the 2 stages 10 pressure.
Conclusion:
v the maximum spread will be:
10 1 Maximum spread
2 Minimum spread
0
0 4,5
PH1'
10 17 20
PH1"
30 bar
20 - 4.5 = 15.5 bar,
v the minimum spread will be:
Falling pressure 20 - 17 = 3 bar.

14
Operating curves Electromechanical pressure
(switching points on falling and vacuum switches
pressure) Dual stage, fixed differential switches,
for detection at each threshold

Adjustment Rising pressure

range of Defined by the difference between the


high point
+
Maxi
minimum and maximum high point
(PH1 or PH2) setting values for each 1
(PH1 or PH2) stage.

of switching point
Adjustable range
For a high set point (PH), the lower
point (PB) is fixed and cannot be
adjusted.
Mini
For a low set point (PB1 or PB2), the
higher point (PH1 or PH2) is fixed and 2
– 0 cannot be adjusted.
0 Low point (PB) Falling
range pressure

Switching Rising pressure

point on The upper pressure setting at which the


+ pressure or vacuum switch will actuate
rising
pressure
PH the contact, for each stage, on rising
pressure.
3
(PH1 or PH2)
Adjustable throughout the range on
rising pressure.

– 0
4
0 Falling pressure

Switching Rising pressure

point on The pressure at which the switch


+ contact changes state, for each stage,
falling on falling pressure.
5
PH
pressure
(PB1 or PB2) The lower point (PB) is not adjustable
and is entirely dependent on the high
point setting (PH) and the natural
PB differential of the switch.

– 0
0 PB
6
Falling pressure
Differential Rising pressure
PH - PB = natural differential
+ The difference between the switching
PH point on rising pressure (PH) and the

PH – PB
switching point on falling pressure (PB),
for each stage. 7
This point is not adjustable and therefore,
PB the value of the differential is fixed.
It is the natural differential of the switch
(contact differential, friction, etc.),

8
– 0 for each of its 2 stages.
0 PB
Falling pressure

Example: Rising pressure

stage 1 = bar H For stage 2 (segment GH):


30 b Consider a switching point on rising
segment EF F
pressure (PH2) of 20 bar (set value at
stage 2 = which contact 2 will change state on
segment GH PH 20 rising pressure).
b It can be seen that the switching
9
point on falling pressure (PB2) is 14 bar
10 (fixed value at which contact 2 will
G return to its original state).
E Conclusion:
0 for stage 2, the differential will be:
1 Maximum spread
10
03 10 14 20 30 bar
2 Minimum spread PB 20 - 14 = 6 bar.
Falling pressure
Repeat the same procedure for stage 1
(segment EF).

15
Presentation Electromechanical pressure
and vacuum switches
OsiSense XM
OsiSense XML for control circuits

Presentation
OsiSense XML pressure and vacuum switches are designed for use in control
circuits.
They are used to control the pressure of hydraulic oils, fresh water, sea water, air,
steam, corrosive fluids or viscous products, up to 500 bar.

OsiSense XMLA pressure and vacuum switches have a fixed differential and are
used for detection of a single threshold. They incorporate 1 CO single-pole contact.
OsiSense XMLB pressure and vacuum switches have an adjustable differential and
are used for regulation between 2 thresholds. They incorporate 1 CO single-pole
contact.
OsiSense XMLC pressure and vacuum switches have an adjustable differential and
are used for regulation between 2 thresholds. They incorporate 2 CO single-pole
contacts.
OsiSense XMLD pressure and vacuum switches are dual stage switches, each
stage with a fixed differential, and are used for detection at each threshold. They
incorporate 2 CO single-pole contacts (one per stage).

Setting
When setting OsiSense XML pressure and vacuum switches, adjust the switching
point on rising pressure (PH) first and then the switching point on falling pressure
(PB).

OsiSense XMLA pressure and vacuum switches with fixed differential


1 Switching point on rising pressure
The switching point on rising pressure (PH) is set by adjusting the red screw 1.

Switching point on falling pressure


The switching point on falling pressure (PB) is not adjustable.
The difference between the tripping and resetting points of the contact is the natural
differential of the switch (contact differential, friction, etc.).

OsiSense XMLB and XMLC pressure and vacuum switches with adjustable
differential
1 2 Switching point on rising pressure
The switching point on rising pressure (PH) is set by adjusting the red screw 1.

Switching point on falling pressure


The switching point on falling pressure (PB) is set by adjusting the green screw 2.

OsiSense XMLD dual stage pressure and vacuum switches with fixed
differential for each threshold
1 2 Switching point on rising pressure of stage 1 and stage 2
The first stage switching point on rising pressure (PH1) is set by adjusting the red
screw 1.
The second stage switching point on rising pressure (PH2) is set by adjusting the
blue screw 2.

Switching point on falling pressure


The switching points on falling pressure (PB1 and PB2) are not adjustable.
The difference between the tripping and resetting points of each contact is the
natural differential of the switch (contact differential, friction, etc.).

16
Characteristics Electromechanical pressure
and vacuum switches
OsiSense XM
OsiSense XML for control circuits

Environment characteristics
Conformity to standards e, IEC/EN 60947-5-1, UL 508, CSA C22-2 no. 14
Product certifications All products: UL, CSA, EAC
XMLA and XMLB: CCC, BV, LROS
Protective treatment Standard version “TC”. Special version “TH”
Ambient air temperature °C For operation: -25…+70. For storage: -40…+70
Fluids or products controlled Hydraulic oils, air, fresh water, sea water
Steam, corrosive fluids, viscous products, depending on model
Materials Case: zinc alloy
Component materials in contact with fluid: see pages 72 and 73
Operating position All positions
Vibration resistance 4 gn (30...500 Hz) conforming to IEC 60068-2-6 except XMLpL35ppppp,
XMLp001ppppp and XMLBM03ppppp: 2 gn
Shock resistance 50 gn conforming to IEC 60068-2-27 except XMLpL35ppppp, XMLp001ppppp
and XMLBM03ppppp: 30 gn
Electric shock protection Class I conforming to IEC 1140, IEC 536 and NF C 20-030
Degree of protection Screw terminal models: IP 66 conforming to IEC/EN 60529
Connector models: IP 65 conforming to IEC/EN 60529
Operating rate Op. Piston version switches: y 60 (for temperatures > 0 °C)
cycles/ Diaphragm version switches: y 120 (for temperatures > 0 °C)
min
Repeat accuracy < 2%
Fluid connection G 1/4 (BSP female) conforming to NF E 03-005, ISO 228 or 1/4”-18 NPTF
For sizes u 300 bar, use the gasket supplied with the product.
This gasket is also available as a separate part, reference XMLZL010.

Electrical connection Screw terminal models: ISO M20 x 1.5 or 1/2” NPT tapped entry
For an entry tapped for no.13 (DIN Pg 13.5) cable gland, replace the last number of
the reference with 1 (for example, XMLA010A2S12 becomes XMLA010A2S11)
Connector models: EN 175301-803-A (ex-DIN 43650) connector

Contact block characteristics


Rated operational characteristics a AC-15, B300 (Ue = 240 V, Ie = 1.5 A; Ue = 120 V, Ie = 3 A)
c DC-13; R300 (Ue = 250 V, Ie = 0.1 A), conforming to IEC 60947-5-1 Appendix A,
EN 60947-5-1
Rated insulation voltage Ui = 500 V conforming to IEC/EN 60947-1
Ui = 300 V conforming to UL 508, CSA C22-2 no. 14
Rated impulse withstand voltage U imp = 6 kV conforming to IEC/EN 60947-1
Type of contacts Silver tipped contacts
XMLA and XMLB: 1 CO single-pole contact (4 terminals), snap action
XMLC: 2 CO single-pole contacts (8 terminals), simultaneous, snap action
XMLD: 2 CO single-pole contacts (8 terminals), staggered, snap action
Resistance across terminals mW < 25 conforming to NF C 93-050 method A or IEC 255-7 category 3
Terminal referencing Conforming to CENELEC EN 50013
Short-circuit protection 10 A cartridge fuse type gG (gl)
Connection Screw clamp terminals.
Minimum clamping capacity: 1 x 0.5 mm2/ AWG 20
Maximum clamping capacity: 2 x 2.5 mm2/AWG 14
Electrical durability XMLA and XMLB XMLC and XMLD
Conforming to IEC/EN 60947-5-1 Appendix C AC supply a 50/60 Hz AC supply a 50/60 Hz
Utilisation categories AC-15 and DC-13 o Inductive circuit, lthe = 10 A o Inductive circuit, lthe = 10 A

Operating rate: 3600 operating cycles/hour 7 5


Ithe 4 Ithe
Load factor: 0.5 5
4 3
12/24 V
Millions of operating cycles

Millions of operating cycles

3 2
2
48 V 230 V 48 V
1
1

0,5
0,5
230 V 110 V

0,2

0,1
110 V
0,1
0,3 0,5 1 2 5 10 20 0,5 1 2 3 4 5 10
Current in A Current in A

DC supply c DC supply c
Power broken in W Power broken in W for 5 million operating
for 1 million operating cycles cycles
Voltage V 24 48 120 Voltage V 24 48 120
o W 31 29 26 o W 10 7 4

17
References, Electromechanical vacuum switches
characteristics OsiSense XML
Size - 1 bar (- 14.5 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA vacuum switches With setting scale

Adjustable range of switching point (PB) - 0.28…- 1 bar (- 4.06…- 14.5 psi)
(Falling pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLAM01V2C11 XMLAM01V2S12 XMLAM01V2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLAM01T2C11 XMLAM01T2S12 –
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 0.685 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.24 bar (3.48 psi)
(add to PB At high setting (3) 0.24 bar (3.48 psi)
to give PH)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLAM01V2S12
becomes XMLAM01V2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.05 bar (± 0.72 psi).
Operating curves Connection
Terminal model
Rising pressure
13

11

-1 -0.76 -0.6 -0.4 -0.2 -0.04


bar 0 Time
14

12

-0.2
-0.28

-0.4 Connector model


PH
Vacuum switch connector pin view
-0.6
PB
Falling pressure

1 → 11 and 13
-0.8 Vacuum 2 → 12
1 2
3 3 → 14
-1
bar

–– Adjustable value
--- Non adjustable value
Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

18
References, Electromechanical vacuum switches
characteristics OsiSense XM, OsiSense XML
Size - 1 bar (- 14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB vacuum switches With setting scale

Adjustable range of switching point (PB) - 0.14…- 1 bar (- 2.03…- 14.5 psi)
(Falling pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLBM02V2C11 XMLBM02V2S12 XMLBM02V2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLBM02T2C11 XMLBM02T2S12 XMLBM02T2S13
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 1.015 1.030 1.030
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.13 bar (1.88 psi)
(add to PB Min. at high setting (3) 0.13 bar (1.88 psi)
to give PH)
Max. at high setting 0.8 bar (11.6 psi)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBM02V2S12
becomes XMLBM02V2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves Connection
Terminal model
Rising pressure
13

11

-1 -0.87 -0.6 -0.4 -0.2 -0.01 Time


bar 0
14

12

-0.14
-0.2
PH
-0.4 Connector model
2 Vacuum switch connector pin view
-0.6 PB
1 → 11 and 13
Falling pressure

Vacuum 2 → 12
1 1 2 3 → 14
-0.8
3

-1
bar

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.

19
References, Electromechanical vacuum switches
characteristics (continued) OsiSense XML
Size - 1 bar (- 14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC vacuum switches With setting scale

Adjustable range of switching point (PB) - 0.14…- 1 bar (- 2.03…- 14.5 psi)
(Falling pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLCM02V2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLCM02T2S12
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 1.015
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.13 bar (1.89 psi)
(add to PB Min. at high setting (3) 0.14 bar (2.03 psi)
to give PH)
Max. at high setting 0.8 bar (11.6 psi)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLCM02V2S12
becomes XMLCM02V2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves Connection
Terminal model
Rising pressure Time
-0.86 -0.6 -0.4 -0.14 0
13

11

23

21

bar -0.01
14

12

24

22

-0.2
PH

-0.4

2 PB
-0.6
Vacuum
Falling pressure

-0.8

bar

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

20
References, Electromechanical vacuum switches
characteristics OsiSense XML
Size - 1 bar (- 14.5 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD vacuum switches Without setting scale

Adjustable range of each 2nd stage switching point (PB2) - 0.12…- 1 bar (- 1.74…- 14.5 psi)
switching point 1st stage switching point (PB1) - 0.10…- 0.98 bar (- 1.45…- 14.21 psi)
(Falling pressure)
Spread between 2 stages (PB2 - PB1) 0.02…0.88 bar (0.29…12.76 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLDM02V1S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLDM02T1S12
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 1.015
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.1 bar (1.45 psi)
(add to PB1/PB2 At high setting (4) 0.1 bar (1.45 psi)
to give PH1/PH2)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLDM02V1S12
becomes XMLDM02V1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.035 bar (± 0.51 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2

PH1 setting (falling pressure) Rising pressure


-0.98 -0.8 -0.6 -0.4 -0.12 0 -1 -0.88 -0.6 -0.4 -0.2 -0.02 Time
bar 0 bar 0
-0.12
E
-0.12
-0.2 G-0.2
PH1
PH2 setting (falling pressure)

-0.4
PB1
-0.4

2 PH2
-0.6 -0.6 PB2
Falling pressure

Vacuum
1
-0.8 -0.8 –– Adjustable value
F --- Non adjustable value
-0.98 -0.98
bar H bar Connection
Terminal model
Contact 1 Contact 2
(stage 1) (stage 2)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.

21
References, Electromechanical vacuum switches
characteristics OsiSense XML
Size - 200 mbar (- 2.9 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB vacuum switches With setting scale

Adjustable range of switching point (PB) - 20…- 200 mbar (- 0.29…- 2.9 psi)
(Falling pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLBM03R2S12 XMLBM03R2S13
(2) up to + 160 °C
Weight (kg) 3.310 3.310
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 18 mbar (0.26 psi)
(add to PB Min. at high setting (3) 18 mbar (0.26 psi)
to give PH)
Max. at high setting 180 mbar (2.6 psi)
Maximum permissible Per cycle 1 bar (14.5 psi)
pressure Accidental 2 bar (29 psi)
Destruction pressure 3.5 bar (50.75 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBM03R2S12
becomes XMLBM03R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 2 mbar (± 0.29 psi).
Operating curves Connection
Terminal model
Rising pressure Time
13

11

-182 -160 -120 -80 -40 -20 -2


mbar 0
14

12

-20
-40
PH

-80

2 PB
-120
Vacuum
Falling pressure

-160
1

-200
mbar

1 Maximum differential –– Adjustable value


2 Minimum differential

Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

22
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 50 mbar (0.72 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 2.6…50 mbar (0.038…0,72 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLBL05R2S12
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLBL05S2S12
up to + 160 °C
Weight (kg) 2.420
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1.4 mbar (0.02 psi)
(subtract from PH Min. at high setting (4) 4 mbar (0.06 psi)
to give PB)
Max. at high setting 40 mbar (0.58 psi)
Maximum permissible Per cycle 62.5 mbar (0.90 psi)
pressure Accidental 112.5 mbar (1.63 psi)
Destruction pressure 225 mbar (3.26 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBL05R2S12
becomes XMLBL05R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 0.8 mbar, + 1.1 mbar (- 0.01 psi, + 0.02 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 1.4 mbar, (+ 0.02 psi).
Operating curves Connection
Terminal model
Pressure
mbar
50 PH
Rising pressure

13

11

1
40
14

12

PB
30

2
20
Time

10

2.6
0
1.2 10 20 30 40 46 mbar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential

Other versions For pressure switches with EN 175301-803-A (ex-DIN 43650A) connector or with alternative
tapped cable entries, such as NPT, etc. please consult our Customer Care Centre.

23
References, Electromechanical vacu-pressure
characteristics switches
OsiSense XML. Size 5 bar (72.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB vacu-pressure switches With setting scale

Adjustable range of switching point (PH) - 0.5…5 bar (- 7.25…72.5 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLBM05A2C11 XMLBM05A2S12 XMLBM05A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLBM05B2C11 XMLBM05B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLBM05C2C11 XMLBM05C2S12 –
Viscous products, up to + 160 °C XMLBM05P2C11 XMLBM05P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.5 bar (7.25 psi)
(subtract from PH Min. at high setting (3) 0.5 bar (7.25 psi)
to give PB)
Max. at high setting 6 bar (87 psi)
Maximum permissible Per cycle 6.25 bar (90.62 psi)
pressure Accidental 11.25 bar (163.12 psi)
Destruction pressure 23 bar (333.5 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Vacu-pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBM05A2S12
becomes XMLBM05A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.05 bar (± 0.72 psi).
Operating curves Connection
Terminal model
Pressure
13

11

bar PH1
5
Rising pressure

14

12

PB1
1
4

3 PH2
0 Connector model
1 Time
2 PB2 Vacu-pressure switch pin view
2 2
1 3
PH3
0.5 1 2 1 → 11 and 13
0 3
PB3 2 → 12
-0.5
Vacuum 3 → 14
-1
-1 0 1 2 3 4 4.5 5 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For vacu-pressure switches with alternative tapped cable entries, such as NPT, etc. please
consult our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

24
References, Electromechanical vacu-pressure
characteristics switches
OsiSense XML. Size 5 bar (72.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC vacu-pressure switches With setting scale

Adjustable range of switching point (PH) - 0.55…5 bar (- 7.97…72.5 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLCM05B2S12
(2) up to + 160 °C
Corrosive fluids, XMLCM05C2S12
up to + 160 °C
Weight (kg) 0.685
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.45 bar (6.52 psi)
(subtract from PH Min. at high setting (3) 0.45 bar (6.52 psi)
to give PB)
Max. at high setting 6 bar (87 psi)
Maximum permissible Per cycle 6.25 bar (90.62 psi)
pressure Accidental 11.25 bar (163.12 psi)
Destruction pressure 23 bar (333.5 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Vacu-pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLCM05B2S12
becomes XMLCM05B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.1 bar (± 1.45 psi).
Operating curves Connection
Terminal model
bar Pressure
13

11

23

21

5
Rising pressure

PH1

PB1
14

12

24

22

4
1
3
PH2
2
1
0
2 Time Connector model
PB2
1
2 Vacu-pressure switch pin view
0.5
3 1 → 11 and 13
0 PH3
-0.55 1 2 2 → 12
PB3 3
-1 3 → 14
-1 0 1 2 3 4 4.55 5 bar Vacuum
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential

Other versions For vacu-pressure switches with alternative tapped cable entries, such as NPT, etc. please
consult our Customer Care Centre.

25
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 350 mbar (5.07 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 45…350 mbar (0.65…5.07 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLBL35R2C11 XMLBL35R2S12 XMLBL35R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLBL35S2C11 XMLBL35S2S12 –
up to + 160 °C
Viscous products, up to + 160 °C XMLBL35P2C11 XMLBL35P2S12 –
(G 1¼" fluid connection)
Weight (kg) 2.590 2.575 2.575
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 42 mbar (0.60 psi)
(subtract from PH Min. at high setting (4) 50 mbar (0.72 psi)
to give PB)
Max. at high setting 300 mbar (4.35 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 million operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBL35R2S12
becomes XMLBL35R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 8 mbar, + 3 mbar (- 0.12 psi, + 0.04 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 8 mbar (± 0.11 psi).
Operating curves Connection
Terminal model
mbar Pressure
13

11

350
PH
Rising pressure

14

12

300
1

PB
Connector model
200 2 Pressure switch connector pin view

100 Time
1 2 1 → 11 and 13
3 2 → 12
45
3 → 14
0
–– Adjustable value
3 50 100 200 300 mbar
Falling pressure

1 Maximum differential
2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

26
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 350 mbar (5.07 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches 30 bar (435 psi) overpressure


With setting scale

Adjustable range of switching point (PH) 42…330 mbar (0.61…4.78 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLBS35R2S12
(2) up to + 160 °C
Weight (kg) 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 33 mbar (0.48 psi)
(subtract from PH Min. at high setting (4) 58 mbar (0.84 psi)
to give PB)
Max. at high setting 250 mbar (3.62 psi)
Maximum permissible Per cycle 30 bar (435 psi)
pressure Accidental 37.5 bar (543.75 psi)
Destruction pressure 67.5 bar (978.75 psi)
Mechanical life 2 million operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Connector type for connector models EN 175301-803-A (ex-DIN 43650A), 4-pin male connector. For suitable female connector,
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBS35R1S12
becomes XMLBS35R1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 8 mbar, + 3 mbar (- 0.12 psi, + 0.04 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 8 mbar (± 0.11 psi).
Operating curves Connection
Terminal model
13

11

mbar Pressure
350
Rising pressure

PH
14

12

300
1

PB
Connector model
200 2 Pressure switch connector pin view

100 1 2 1 → 11 and 13
Time 3 2 → 12
45 3 → 14

0
3 50 100 200 300 mbar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

27
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 350 mbar (5.07 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale 30 bar (435 psi) overpressure
With setting scale

Adjustable range of switching point (PH) 45…350 mbar (0.65…5.07 psi) 42…330 mbar (0.61…4.78 psi)
(Rising pressure)
Electrical connection Terminals Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLCL35R2S12 – XMLCS35R2S12 XMLCS35R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLCL35S2S12 XMLCL35S2S13 – –
up to + 160 °C
Weight (kg) 2.575 2.575 3.500 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 20 mbar (0.29 psi) 40 mbar (0.58 psi)
(subtract from PH Min. at high setting (3) 35 mbar (0.51 psi) 88 mbar (1.27 psi)
to give PB)
Max. at high setting 300 mbar (4.35 psi) 230 mbar (3.33 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi) 30 bar (435 psi)
pressure Accidental 2.25 bar (32.62 psi) 37.5 bar (543.75 psi)
Destruction pressure 4.5 bar (65.25 psi) 67.5 bar (978.75 psi)
Mechanical life 4 million operating cycles 2 million operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x 1 entry tapped
1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable 1/2”-14 NPT for cable
gland, clamping gland, clamping gland, clamping gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLCL35R2S12
becomes XMLCL35R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 20 mbar (± 0.29 psi).
Operating curves Connection
Terminal model
Pressure
13

11

23

21

mbar
350
PH
Rising pressure

1
14

12

24

22

300

PB
200
2

Time
100

45

0
0 25 50 100 200 315 mbar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

28
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 350 mbar (5.07 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 58…350 mbar (0.84…5.07 psi)
switching point 1st stage switching point (PH1) 33…325 mbar (0.48…4.71 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 25…310 mbar (0.36…4.50 psi)
Electrical connection Terminals
Fluid connection G 1/4 (female)
References (1)
Fluids controlled Hydraulic oils, air, XMLDL35R1S12
(2) up to + 160 °C
Weight (kg) 2.575
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 30 mbar (0.44 psi)
(subtract from PH1/PH2 At high setting (4) 30 mbar (0.44 psi)
to give PB1/PB2)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 million operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLDL35R1S12
becomes XMLDL35R1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 10 mbar (± 0.15 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 8 mbar (± 0.11 psi).
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
mbar mbar PH2
350 350 H
PH2 setting (falling pressure)

343
Falling pressure

1 325 F PB2
300 300
PH1
PB1

200 200
2
Time
100 100
G –– Adjustable value
58 58
33 --- Non adjustable value
E
0 0 Connection
0 33 100 200 300 325mbar 3 28 100 200 295 320 mbar
PH1 setting (falling pressure) Rising pressure Terminal model
Contact 1 Contact 2
(stage 1) (stage 2)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

29
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 1 bar (14.5 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 0.03…1 bar (0.435…14.5 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLA001R2C11 XMLA001R2S12 –
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLA001S2C11 XMLA001S2S12 XMLA001S2S13
up to + 160 °C
Weight (kg) 2.570 2.555 2.555
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.02 bar (0.29 psi)
(subtract from PH At high setting (3) 0.04 bar (0.58 psi)
to give PB)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA001R2S12
becomes XMLA001R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.01 bar (± 0.14 psi)
Operating curves Connection
Terminal model
Pressure
13

11

bar
1 PH
Rising pressure

14

12

0.8 PB

Connector model
0.6
Pressure switch connector pin view

0.4
Time
1 2 1 → 11 and 13
3
0.2 2 → 12
3 → 14
0.03
0
0.01 0.2 0.4 0.6 0.8 0.96
bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

30
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 1 bar (14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 0.05…1 bar (0.72…14.5 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLB001R2C11 XMLB001R2S12 XMLB001R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLB001S2C11 XMLB001S2S12 XMLB001S2S13
up to + 160 °C
Viscous products, up to + 160 °C – XMLB001P2S12 –
(G 1¼" fluid connection)
Weight (kg) 2.590 2.575 2.575
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.04 bar (0.58 psi)
(subtract from PH Min. at high setting (4) 0.06 bar (0.87 psi)
to give PB)
Max. at high setting 0.75 bar (10.87 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB001R2S12
becomes XMLB001R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 10 mbar (± 0.14 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 20 mbar (± 0.29 psi).
Operating curves Connection
Terminal model
Pressure
13

11

bar
1 PH
Rising pressure

14

12

0.8
1
PB
0.6
Connector model
Pressure switch connector pin view
2
0.4
Time
1 2 1 → 11 and 13
3
0.2 2 → 12
3 → 14
0.05
0
0.01 0.25 0.4 0.6 0.8 0.94
bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

31
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 1 bar (14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale

Adjustable range of switching point (PH) 0.05…1 bar (0.725…14.5 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, air, XMLC001R2S12 XMLC001R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLC001S2S12 XMLC001S2S13
up to + 160 °C
Weight (kg) 2.555 2.555
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.03 bar (0.43 psi)
(subtract from PH Min. at high setting (4) 0.04 bar (0.58 psi)
to give PB)
Max. at high setting 0.8 bar (11.6 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC001R2S12
becomes XMLC001R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.01 bar (± 0.14 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.03 bar (± 0.43 psi)
Operating curves Connection
Terminal model
Pressure
13

11

23

21

bar
1 PH
Rising pressure

14

12

24

22

PB
0.6
2
0.4
Time

0.2

0.05
0
0.02 0.2 0.4 0.6 0.8 0.96 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

32
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 2.5 bar (36.25 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 0.15…2.5 bar (2.17…36.25 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA002A2C11 XMLA002A2S12 XMLA002A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA002B2C11 XMLA002B2S12 –
up to + 160 °C
Corrosive fluids, XMLA002C2C11 XMLA002C2S12 –
up to + 160 °C
Weight (kg) 1.010 0.995 0.995
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.13 bar (1.88 psi)
(subtract from PH At high setting (3) 0.13 bar (1.88 psi)
to give PB)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 8 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA002A2S12
becomes XMLA002A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.03 bar (± 0.43 psi).
Operating curves Connection
Terminal model
Pressure
13

11

bar
2.5 PH
Rising pressure

14

12

2 PB

Connector model
Pressure switch connector pin view

1
Time 1 2 1 → 11 and 13
3
2 → 12
3 → 14
0.15
0
0.02 1 2 2.37 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

33
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 2.5 bar (36.25 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 0.3…2.5 bar (4.35…36.25 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB002A2C11 XMLB002A2S12 XMLB002A2S13 –
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB002B2C11 XMLB002B2S12 – XMLBS02B2S12
up to + 160 °C
Corrosive fluids, XMLB002C2C11 XMLB002C2S12 – –
up to + 160 °C
Weight (kg) 1.030 1.015 1.015 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.16 bar (2.32 psi) 0.1 bar (1.45 psi)
(subtract from PH Min. at high setting (3) 0.21 bar (3.04 psi) 0.22 bar (3.19 psi)
to give PB)
Max. at high setting 1.75 bar (25.37 psi) 1.45 bar (21 psi)
Maximum permissible Per cycle 5 bar (72.5 psi) 30 bar (435 psi)
pressure Accidental 9 bar (130.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 18 bar (261 psi) 67.5 bar (978.75 psi)
Mechanical life 8 x 106 operating cycles 2 x 106 operating
cycles
Connection EN 175301-803-A 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x
(ex-DIN 43650A), 1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable
4-pin male connector. gland, clamping gland, clamping gland, clamping
For suitable female capacity 7 to 13 mm capacity 7 to 13 mmcapacity 7 to 13 mm
connector, see page
68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB002A2S12
becomes XMLB002A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
- 0.03 bar, + 0.05 bar (- 0.43 psi, + 0.72 psi).
Operating curves Connection
bar
Pressure Terminal model
2.5 PH
Rising pressure

13

11

2
14

12

1 PB
Connector model
Pressure switch connector pin view
2
1
Time
1 2 1 → 11 and 13
3
0.3 2 → 12
3 → 14
0
0.14 0.75 1 2 2.29 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

34
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 2.5 bar (36.25 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale 30 bar (435 psi) overpressure
With setting scale

Adjustable range of switching point (PH) 0.3…2.5 bar (4.35…36.25 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 1/4”-18 NPTF G 1/4 1/4”-18 NPTF


(female) (female) (female) (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLC002B2S12 XMLC002B2S13 XMLCS02B2S12 XMLCS02B2S13
(2) up to + 160 °C
Weight (kg) 0.995 0.995 3.500 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.13 bar (1.89 psi) 0.1 bar (1.45 psi)
(subtract from PH Min. at high setting (4) 0.17 bar (2.47 psi) 0.18 bar (2.61 psi)
to give PB)
Max. at high setting 2 bar (29 psi) 1.25 bar (18.12 psi)
Maximum permissible Per cycle 5 bar (72.5 psi) 30 bar (435 psi)
pressure Accidental 9 bar (130.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 18 bar (261 psi) 67.5 bar (978.75 psi)
Mechanical life 8 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x 1 entry tapped
1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable 1/2”-14 NPT for cable
gland, clamping gland, clamping gland, clamping gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC002B2S12
becomes XMLC002B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.02 bar (± 0.29 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.03 bar (± 0.43 psi)
Operating curves Connection
Terminal model
Pressure
13

11

23

21

bar
2.5 PH
Rising pressure

14

12

24

22

1
2

PB

2
1
Time

0.3

0
0.17 0.5 1 2 2.33 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

35
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 0.4…4 bar (5.8…58 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA004A2C11 XMLA004A2S12 XMLA004A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA004B2C11 XMLA004B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA004C2C11 XMLA004C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA004P2C11 XMLA004P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.35 bar (5.07 psi)
(subtract from PH
to give PB) At high setting (3) 0.35 bar (5.07 psi)

Maximum permissible Per cycle 5 bar (72.5 psi)


pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 8 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA004A2S12
becomes XMLA004A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.03 bar (± 0.43 psi)
Operating curves Connection
Terminal model
Pressure
13

11

bar
4 PH
Rising pressure

14

12

PB
3

Connector model
2 Pressure switch connector pin view

Time
1 1 2 1 → 11 and 13
3
2 → 12
0.4 3 → 14
0
0.05 1 2 3 3.65 4 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

36
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 0.25…4 bar (3.62…58 psi)


(Rising pressure)
Electrical connection DIN connector Terminals
Fluid connection G 1/4 G 1/4 1/4”-18 NPTF G 1/4
(female) (female) (female) (female)
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB004A2C11 XMLB004A2S12 XMLB004A2S13 –
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB004B2C11 XMLB004B2S12 – XMLBS04B2S12
up to + 160 °C
Corrosive fluids, XMLB004C2C11 XMLB004C2S12 – –
up to + 160 °C
Weight (kg) 1.030 1.015 1.015 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.2 bar (2.9 psi) 0.15 bar (2.18 psi)
(subtract from PH Min. at high setting (4) 0.25 bar (3.62 psi) 0.34 bar (4.93 psi)
to give PB)
Max. at high setting 2.4 bar (34.8 psi) 2.46 bar (35.67 psi)
Maximum permissible Per cycle 5 bar (72.5 psi) 30 bar (435 psi)
pressure Accidental 9 bar (130.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 18 bar (261 psi) 67.5 bar (978.75 psi)
Mechanical life 8 x 106 operating cycles 2 x 106 operating
cycles
Connection EN 175301-803-A 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x
(ex-DIN 43650A), 1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable
4-pin male connector. gland, clamping gland, clamping gland, clamping
For suitable female capacity 7 to 13 mm capacity 7 to 13 mmcapacity 7 to 13 mm
connector, see page
68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB004A2S12
becomes XMLB004A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.01 bar (± 0.14 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 0.03 bar, + 0.05 bar (- 0.43 psi, + 0.72 psi).
Operating curves Connection
bar
Pressure Terminal model
4
PH
Rising pressure

13

11
14

12

3
PB
1 2 Connector model
2 Pressure switch connector pin view

Time 1 → 11 and 13
1
1 2 2 → 12
3
3 → 14
0.25
0
0.05 1 1.6 2 3 3.75 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

37
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 0.3…4 bar (4.35…58 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLC004B2S12 XMLC004B2S13 XMLCS04B2S12
(2) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC004C2S12 XMLC004C2S13 –

Weight (kg) 0.685 0.685 3.500


Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.15 bar (2.18 psi) 0.1 bar (1.45 psi)
(subtract from PH Min. at high setting (3) 0.17 bar (2.47 psi) 0.25 bar (3.62 psi)
to give PB)
Max. at high setting 2.5 bar (36.25 psi) 2.20 bar (31.9 psi)
Maximum permissible Per cycle 5 bar (72.5 psi) 30 bar (435 psi)
pressure Accidental 9 bar (130.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 18 bar (261 psi) 67.5 bar (978.75 psi)
Mechanical life 8 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT 1 entry tapped M20 x 1.5 mm
for ISO cable gland, clamping for cable gland, clamping for ISO cable gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC004B2S12
becomes XMLC004B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves Connection
Terminal model
Pressure
13

11

23

21

bar
4 PH
Rising pressure

14

12

24

22

3
1
PB

2 2

Time
1

0.3
0
0.15 1 1.5 2 3 3.83 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

38
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 0.40…4 bar (5.8…58 psi)
switching point 1st stage switching point (PH1) 0.19…3.79 bar (2.76…54.96 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 0.21…2.18 bar (3.05…31.61 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLD004B1S12
(2) up to + 160 °C
Weight (kg) 1.015
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.15 bar (2.18 psi)
(subtract from PH1/PH2 At high setting (3) 0.19 bar (2.76 psi)
to give PB1/PB2)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 8 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD004B1S12
becomes XMLD004B1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.03 bar (± 0.43 psi).
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar bar H PH2
4 4
PH2 setting (rising pressure)

Rising pressure

3.79
F PB2

PH1
3
1
3 PB1

2.35
2 2 2

Time

1 1
–– Adjustable value
0.4 0.40 G --- Non adjustable value
0.19
0 0 E Connection
0.19 1 1.82 2 3 3.79 bar 0.04 1 2 3 3.6 3.81 bar
PH1 setting (rising pressure) Falling pressure Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

39
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 10 bar (145 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 0.6…10 bar (8.7…145 psi)


(Rising pressure)
Electrical connection DIN connector Terminals Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA010A2C11 XMLA010A2S12 XMLA010A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA010B2C11 XMLA010B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA010C2C11 XMLA010C2S12 XMLA010C2S13
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA010P2C11 XMLA010P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.5 bar (7.25 psi)
(subtract from PH At high setting (3) 0.5 bar (7.25 psi)
to give PB)
Maximum permissible Per cycle 12.5 bar (181.25 psi)
pressure Accidental 22.5 bar (326.25 psi)
Destruction pressure 45 bar (652.5 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA010A2S12
becomes XMLA010A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size: ± 0.05
bar (± 0.72 psi)
Operating curves Connection
Terminal model
Pressure
13

11

bar
10 PH
Rising pressure

14

12

8 PB

6
Connector model
Pressure switch connector pin view
4
Time
2 1 2 1 → 11 and 13
1 3
2 → 12
0.6
0 3 → 14
0.1 2 4 6 8 9.5 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

40
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 10 bar (145 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 0.7…10 bar (10.15…145 psi)


(Rising pressure)
Electrical connection DIN connector Terminals Terminals Terminals

Fluid connection G 1/4 G 1/4 1/4”-18 NPTF G 1/4


(female) (female) (female) (female)
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB010A2C11 XMLB010A2S12 XMLB010A2S13 XMLBS10A2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB010B2C11 XMLB010B2S12 XMLB010B2S13 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLB010C2C11 XMLB010C2S12 XMLB010C2S13 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLB010P2C11 XMLB010P2S12 – –
(G 1¼" fluid connection)
Weight (kg) 0.735 0.705 0.705 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.57 bar (8.26 psi) 0.45 bar (6.52 psi)
(subtract from PH Min. at high setting (4) 0.85 bar (12.32 psi) 0.85 bar (12.32 psi)
to give PB)
Max. at high setting 7.5 bar (108.75 psi) 6.25 bar (90.62 psi)
Maximum permissible Per cycle 12.5 bar (181.25 psi) 30 bar (435 psi)
pressure Accidental 22.5 bar (326.25 psi) 37.5 bar (543.75 psi)
Destruction pressure 45 bar (652.5 psi) 67.5 bar (978.75 psi)
Mechanical life 5 x 106 operating cycles 2 x 106 operating
cycles
Connection EN 175301-803-A 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x
(ex-DIN 43650A), 1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable
4-pin male connector. gland, clamping gland, clamping gland, clamping
For suitable female capacity 7 to 13 mm capacity 7 to 13 mm
capacity 7 to 13 mm
connector, see page
68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB010A2S12
becomes XMLB010A2S11.
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.05 bar (± 0.72 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 0.1 bar, + 0.15 bar (- 1.45 psi, + 2.17 psi).
Operating curves Connection
bar Pressure Terminal model
10
PH
Rising pressure

13

11

8
14

12

1
PB
6 Connector model
2
Pressure switch connector pin view
4

Time 1 → 11 and 13
2 1 2 2 → 12
3
3 → 14
0.7
0
0.13 2.5 4 6 8 9.15
bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential

41
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 10 bar (145 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 0.7…10 bar (10.15…145 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, – – XMLCS10A2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLC010B2S12 XMLC010B2S13 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC010C2S12 XMLC010C2S13 –
Sea water, up to + 30 °C
Weight (kg) 0.685 0.685 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.45 bar (6.53 psi) 0.25 bar (3.62 psi)
(subtract from PH Min. at high setting (4) 0.70 bar (10.15 psi) 0.65 bar (9.42 psi)
to give PB)
Max. at high setting 8 bar (116 psi) 5.6 bar (81.2 psi)
Maximum permissible Per cycle 12.5 bar (181.25 psi) 30 bar (435 psi)
pressure Accidental 22.5 bar (326.25 psi) 37.5 bar (543.75 psi)
Destruction pressure 45 bar (652.5 psi) 67.5 bar (978.75 psi)
Mechanical life 5 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT 1 entry tapped M20 x 1.5 mm
for ISO cable gland, clamping for cable gland, clamping for ISO cable gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC010B2S12
becomes XMLC010B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.05 bar (± 0.72 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.01 bar (± 1.45 psi)
Operating curves Connection
Terminal model
bar Pressure
13

11

23

21

10
PH
Rising pressure

1
14

12

24

22

PB
6

2
4

Time
2

0.7
0
0.25 2 4 6 8 9.3 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

42
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 10 bar (145 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 1.2…10 bar (17.4…145 psi)
switching point 1st stage switching point (PH1) 0.52…9.32 bar (7.54…135.14 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 0.68…5.8 bar (9.86…84.1 psi)
Fluid connection G 1/4 (female)

Electrical connection Terminals

References
Fluids controlled Hydraulic oils, fresh water, air, XMLD010B1S11 XMLD010B1S12
(1) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLD010C1S11 –
Sea water, up to + 30 °C
Weight (kg) 0.705 0.705
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (2) 0.45 bar (6.53 psi)
(subtract from PH1/PH2 At high setting (3) 0.6 bar (8.7 psi)
to give PB1/PB2)
Maximum permissible Per cycle 12.5 bar (181.25 psi)
pressure Accidental 22.5 bar (326.25 psi)
Destruction pressure 45 bar (652.5 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped for no. 13 cable gland 1 entry tapped M20 x 1.5 mm for ISO cable
gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For component materials of units in contact with the fluid, see pages 72 and 73.
(2) Deviation of the differential at low setting point for switches of the same size:
± 0.05 bar (± 0.72 psi)
(3) Deviation of the differential at high setting point for switches of the same size:
± 0.1 bar (± 1.45 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
bar Pressure
bar H
10 10
Rising pressure
PH2 setting (rising pressure)

PH2
9.32 F PB2
8 8
1 PH1
6.34 PB1
6 6

2
4 4
Time

2 2
–– Adjustable value
1.2 1.2 G
0.52
--- Non adjustable value
0 0 E Connection
0.52 2 4.2 6 8 9.32 bar 0.07 0.75 2 4 6 8.72 9.4 bar
PH1 setting (rising pressure) Falling pressure Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

43
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 1…20 bar (14.5…290 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA020A2C11 XMLA020A2S12 XMLA020A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA020B2C11 XMLA020B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA020C2C11 XMLA020C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA020P2C11 XMLA020P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.4 bar (5.8 psi)
(subtract from PH At high setting (3) 1 bar (14.5 psi)
to give PB)
Maximum permissible Per cycle 25 bar (362.5 psi)
pressure Accidental 45 bar (652.5 psi)
Destruction pressure 90 bar (1305 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA020A2S12
becomes XMLA020A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at high setting point for switches of the same size:
± 0.1 bar (± 1.45 psi)
Deviation of the differential at low setting point: ± 0.2 bar (± 2.9 psi)

Operating curves Connection


Terminal model
bar Pressure
13

11

20
PH
Rising pressure

14

12

15 PB

10 Connector model
Pressure switch connector pin view

5 Time

1 2 1 → 11 and 13
3
1 2 → 12
0 3 → 14
0.6 5 10 15 19 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

44
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 1.3…20 bar (18.9…290 psi)


(Rising pressure)
Electrical connection DIN connector Terminals
Fluid connection G 1/4 G 1/4 1/4”-18 NPTF G 1/4
(female) (female) (female) (female)
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB020A2C11 XMLB020A2S12 XMLB020A2S13 XMLBS20A2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB020B2C11 XMLB020B2S12 XMLB020B2S13 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLB020C2C11 XMLB020C2S12 – –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLB020P2C11 XMLB020P2S12 – –
(G 1¼" fluid connection)
Weight (kg) 0.735 0.705 0.705 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1 bar (14.5 psi) 0.95 bar (13.78 psi)
(subtract from PH Min. at high setting (3) 1.6 bar (23.20 psi) 1.45 bar (21.03 psi)
to give PB)
Max. at high setting 11 bar (159.5 psi) 12.6 bar (182.7 psi)
Maximum permissible Per cycle 25 bar (362.5 psi) 30 bar (435 psi)
pressure Accidental 45 bar (652.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 90 bar (1305 psi) 67.5 bar (978.75 psi)
Mechanical life 5 x 106 operating cycles 2 x 106 operating
cycles
Connection EN 175301-803-A 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x
(ex-DIN 43650A), 1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable
4-pin male connector. gland, clamping gland, clamping gland, clamping
For suitable female capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
connector, see page
68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB020A2S12
becomes XMLB020A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.25 bar (± 3.63 psi)
Operating curves Connection
bar
Pressure Terminal model
20
Rising pressure

PH
13

11
14

12

15
PB
1 2 Connector model
10 Pressure switch connector pin view

Time 1 → 11 and 13
5
1 2 2 → 12
3
3 → 14
1.3
0
0.3 5 9 10 15 18.4 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

45
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale

Adjustable range of switching point (PH) 1.3…20 bar (18.85…290 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, – – XMLCS20A2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLC020B2S12 XMLC020B2S13 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC020C2S12 XMLC020C2S13 –
Sea water, up to + 30 °C
Weight (kg) 0.685 0.685 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.7 bar (10.15 psi) 0.7 bar (10.15 psi)
(subtract from PH Min. at high setting (3) 1 bar (14.5 psi) 1.15 bar (16.67 psi)
to give PB)
Max. at high setting 11 bar (159.5 psi) 11.70 bar (169.6 psi)
Maximum permissible Per cycle 25 bar (362.5 psi) 30 bar (435 psi)
pressure Accidental 45 bar (652.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 90 bar (1305 psi) 67.5 bar (978.75 psi)
Mechanical life 5 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT 1 entry tapped M20 x 1.5 mm
for ISO cable gland, clamping for cable gland, clamping for ISO cable gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC020B2S12
becomes XMLC020B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.2 bar (± 2.9 psi)

Operating curves Connection


Terminal model
bar Pressure
13

11

23

21

20
Rising pressure

PH
14

12

24

22

15
PB
1 2
10

Time
5

1.3
0
0.6 5 9 10 15 19 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

46
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage 2.14…20 bar (31.03…290 psi)


switching point switching point (PH2)
(Rising pressure) 1st stage 0.9…18.76 bar (13.05…272.02 psi)
switching point (PH1)
Spread between 2 stages (PH2 - PH1) 1.24…9.55 bar (17.98…138.48 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLD020B1S12 XMLD020B1S13
(2) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLD020C1S12 –
Sea water, up to + 30 °C
Weight (kg) 0.705 0.705
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.7 bar (10.15 psi)
(subtract from PH1/PH2 At high setting (4) 1.3 bar (18.85 psi)
to give PB1/PB2)
Maximum permissible Per cycle 25 bar (362.5 psi)
pressure Accidental 45 bar (652.5 psi)
Destruction pressure 90 bar (1305 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD020B1S12
becomes XMLD020B1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.15 bar (± 2.18 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.3 bar (± 4.35 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure

PH2
bar bar H
20 20 PB2
Rising pressure

18.76
F
PH2 setting (rising pressure)

PH1
PB1
15 15

1 2
10.6 10
Time

5 5 –– Adjustable value
--- Non adjustable value
2.14 G
2.14
0.9 Connection model
0 0 E Terminal model
0.9 5 10.45 15 18.76 bar 0.2 1.44 5 10 15 17.46 18.7 bar
Falling pressure Contact 2 Contact 1
PH1 setting (rising pressure)
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

47
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 1.5…35 bar (21.75…507.5 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA035A2C11 XMLA035A2S12 XMLA035A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA035B2C11 XMLA035B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA035C2C11 XMLA035C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA035P2C11 XMLA035P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.725 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 1.25 bar (18.12 psi)
(subtract from PH At high setting (3) 1.25 bar (18.12 psi)
to give PB)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA035A2S12
becomes XMLA035A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.25 bar (± 3.62 psi)
Operating curves Connection
Terminal model
bar Pressure
13

11

35
PH
Rising pressure

14

12

30
PB

20
Connector model
Pressure switch connector pin view

10 Time

1 2 1 → 11 and 13
3
1.5 2 → 12
0
0.25 10 20 30 33.75 bar 3 → 14
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

48
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 3.5…35 bar (50.75…507.5 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB035A2C11 XMLB035A2S12 XMLB035A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB035B2C11 XMLB035B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLB035C2C11 XMLB035C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C – XMLB035P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.745 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1.7 bar (24.65 psi)
(subtract from PH Min. at high setting (3) 2.55 bar (36.97 psi)
to give PB)
Max. at high setting 20 bar (290 psi)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A connector 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
(ex-DIN 43650A), 4-pin male. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB035A2S12
becomes XMLB035A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
- 0.5 bar, + 0.7 bar (- 7.25 psi, + 10.15 psi).
Operating curves Connection
Terminal model
bar Pressure
13

11

35
Rising pressure

PH
14

12

30

1 PB
20 2
Connector model
Pressure switch connector pin view

10 Time

1 2 1 → 11 and 13
3.5 3
2 → 12
0
1.8 10 15 20 32.45 bar 3 → 14
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

49
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale

Adjustable range of switching point (PH) 3.5…35 bar (50.75…507.5 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLC035B2S12 XMLC035B2S13
(2) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC035C2S12 XMLC035C2S13
Sea water, up to + 30 °C
Weight (kg) 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1 bar (14.5 psi)
(subtract from PH Min. at high setting (4) 1.5 bar (21.75 psi)
to give PB)
Max. at high setting 22 bar (319 psi)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC035B2S12
becomes XMLC035B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.2 bar (± 2.9 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.5 bar (± 7.25 psi)
Operating curves Connection
Terminal model
bar Pressure
13

11

23

21

35
PH
Rising pressure

14

12

24

22

30
1

PB
20 2

10 Time

3.5

0
2.5 10 13 20 33.5 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

50
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 4.4…35 bar (63.8…507.5 psi)
switching point 1st stage switching point (PH1) 1.9…32.5 bar (27.55…471.25 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 2.5…20.4 bar (36.25…295.8 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLD035B1S12
(2) up to + 160 °C
Weight (kg) 0.715
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 1.5 bar (21.75 psi)
(subtract from PH1/PH2 At high setting (4) 2.6 bar (37.7 psi)
to give PB1/PB2)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD035B1S12
becomes XMLD035B1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.3 bar (± 4.35 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.7 bar (± 10.15 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar bar PH2
35 35 H
F
PH2 setting (rising pressure)

PB2
Rising pressure

32.5
30 30
PH1
1
PB1
22.3
20 2 20

Time
10 10

4.4 G –– Adjustable value


4.4
1.9 --- Non adjustable value
E
0
1.9 10 14.6 20 30 32.5 bar
0
0.4 2.9 10 20 29.9 32.4 bar
Connection
PH1 setting (rising pressure)
Falling pressure
Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

51
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 5…70 bar (72.5…1015 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLA070D2C11 XMLA070D2S12 XMLA070D2S13
(2) up to + 160 °C
Fresh water, XMLA070E2C11 XMLA070E2S12 XMLA070E2S13
up to + 160 °C
Corrosive fluids, air, XMLA070N2C11 XMLA070N2S12 –
up to + 160 °C
Weight (kg) 0.725 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 3 bar (43.5 psi)
(subtract from PH At high setting (3) 9.5 bar (137.75 psi)
to give PB)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA070D2S12
becomes XMLA070D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size: ± 1
bar (± 14.5 psi)
Operating curves Connection
Terminal model
Pressure
13

11

bar
70 PH
Rising pressure

14

12

60
PB

40
Connector model
Pressure switch connector pin view

20 Time

1 2 1 → 11 and 13
3
5 2 → 12
0 3 → 14
02 8 20 40 62.5 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

52
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 7…70 bar (101.5…1015 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLB070D2C11 XMLB070D2S12 XMLB070D2S13
(2) up to + 160 °C
Fresh water, XMLB070E2C11 XMLB070E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB070N2C11 XMLB070N2S12 –
up to + 160 °C
Weight (kg) 0.745 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 4.7 bar (68.15 psi)
(subtract from PH Min. at high setting (4) 9.5 bar (137.75 psi)
to give PB)
Max. at high setting 50 bar (725 psi)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A connector 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
(ex-DIN 43650A), 4-pin male for ISO cable gland, clamping for cable gland, clamping
connector. For suitable female capacity 7 to 13 mm capacity 7 to 13 mm
connector, see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB070D2S12
becomes XMLB070D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 0.4 bar, + 0.7 bar (- 5.8 psi, + 10.15 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 0.6 bar, + 0.8 bar (- 8.7 psi, + 11.6 psi).
Operating curves Connection
Terminal model
bar Pressure
13

11

70
Rising pressure

PH
60
14

12

1
PB
40
2
Connector model
Pressure switch connector pin view
20
Time

7 1 2 1 → 11 and 13
3
0 2 → 12
2.3 20 40 61.2 bar 3 → 14
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

53
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale

Adjustable range of switching point (PH) 7…70 bar (101.5…1015 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLC070D2S12 XMLC070D2S13
(2) up to + 160 °C
Fresh water, XMLC070E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLC070N2S12 –
up to + 160 °C
Weight (kg) 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 4.5 bar (65.25 psi)
(subtract from PH Min. at high setting (3) 9.5 bar (137.75 psi)
to give PB)
Max. at high setting 60 bar (870 psi)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC070D2S12
becomes XMLC070D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.8 bar (± 11.6 psi)
Operating curves Connection
Terminal model
bar Pressure
13

11

23

21

70
Rising pressure

PH
14

12

24

22

60

1
PB
40
2

20 Time

7
0
2.5 10 20 40 61.1 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

54
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 9.4…70 bar (136.3…1015 psi)
switching point 1st stage switching point (PH1) 6.6…67.2 bar (95.7…974.4 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 2.8…46 bar (40.6…667 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLD070D1S12 XMLD070D1S13
(2) up to + 160 °C
Corrosive fluids, air, XMLD070N1S12 –
up to + 160 °C
Weight (kg) 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 5 bar (72.5 psi)
(subtract from PH1/PH2 At high setting (4) 9.5 bar (137.75 psi)
to give PB1/PB2)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD070D1S12
becomes XMLD070D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 1.5 bar (± 21.75 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 2 bar (± 29 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
bar Pressure
bar
70 70 H PH2
Rising pressure
PH2 setting (rising pressure)

67.2 F
60 60 PB2
1
52.6 PH1
PB1
40
2 40

20 20 Time

9.4 9.4 G
6.6 E –– Adjustable value
0 0 --- Non adjustable value
1.6 4.4 20 40 57.7 60.5 bar
6.6 20 24 40 60 67.2 bar
PH1 setting (rising pressure) Falling pressure
Connection
Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

55
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 10…160 bar (145…2320 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLA160D2C11 XMLA160D2S12 XMLA160D2S13
(2) up to + 160 °C
Fresh water, XMLA160E2C11 XMLA160E2S12 XMLA160E2S13
up to + 160 °C
Corrosive fluids, air, XMLA160N2C11 XMLA160N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 5.5 bar (79.75 psi)
(subtract from PH At high setting (4) 18 bar (261 psi)
to give PB)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10,440 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA160D2S12
becomes XMLA160D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 1 bar (± 14.5 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 3 bar (± 43.5 psi)
Operating curves Connection
Terminal model
Pressure
13

11

bar
PH
Rising pressure

160
14

12

140 PB
120

100
Connector model
80
Pressure switch connector pin view
60
Time
40
20
1 2 1 → 11 and 13
3
10 2 → 12
0
3 → 14
4.5 20 40 60 80 100 120 142 160 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

56
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 10…160 bar (145…2320 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLB160D2C11 XMLB160D2S12 XMLB160D2S13
(2) up to + 160 °C
Fresh water, XMLB160E2C11 XMLB160E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB160N2C11 XMLB160N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 9.3 bar (134.85 psi)
(subtract from PH Min. at high setting (4) 20.8 bar (301.6 psi)
to give PB)
Max. at high setting 100 bar (1450 psi)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10,440 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB160D2S12
becomes XMLB160D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 1.8 bar, + 1.5 bar (- 26.1 psi, + 21.75 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 1.9 bar, + 1.6 bar (- 27.55 psi, + 23.2 psi).
Operating curves Connection
Terminal model
Pressure
13

11

bar
160
PH
Rising pressure

14

12

120
PB
1
80
2 Connector model
Pressure switch connector pin view

Time
40
1 2 1 → 11 and 13
3
10
2 → 12
0 3 → 14
0.7 40 60 80 120 139.2 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

57
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale

Adjustable range of switching point (PH) 12…160 bar (174…2320 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLC160D2S12 XMLC160D2S13
(2) up to + 160 °C
Fresh water, XMLC160E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLC160N2S12 –
up to + 160 °C
Weight (kg) 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 9 bar (130.5 psi)
(subtract from PH Min. at high setting (3) 21 bar (304.5 psi)
to give PB)
Max. at high setting 110 bar (1590 psi)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10 440 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC160D2S12
becomes XMLC160D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.9 bar (± 13.05 psi)
Operating curves Connection
Terminal model
Pressure
13

11

23

21

bar
160
Rising pressure

PH
14

12

24

22

100 2 PB

50 Time

12
0
50 100 139 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

58
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 16.5…160 bar (239.25…2320 psi)
switching point 1st stage switching point (PH1) 10.5…154 bar (152.25…2233 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 6…83 bar (87…1203.5 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, up to + 160 °C XMLD160D1S12 XMLD160D1S13
(2)
Fresh water, up to + 160 °C XMLD160E1S12 –

Weight (kg) 0.750 0.750


Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 8.8 bar (127.6 psi)
(subtract from PH1/PH2 At high setting (4) 20 bar (290 psi)
to give PB1/PB2)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10,440 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD160D1S12
becomes XMLD160D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 1.5 bar (± 21.75 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 7 bar (± 101.5 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar H
PH2
bar 154
Rising pressure

160 F PB2
140
PH2 setting (rising pressure)

120 PH1
120 PB1
1 100

94.5 2 80
80
60
Time
40
40 –– Adjustable value
16.5 G
10.5 --- Non adjustable value
16.5 E
10 0
1.7 7.7 40 60 80 100 134140 160 bar
Connection
0
0 10.5 40 60 77 100 120 154 bar
Falling pressure Terminal model
PH1 setting (rising pressure) Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

59
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 20…300 bar (290…4350 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLA300D2C11 XMLA300D2S12 XMLA300D2S13
(2) (5) up to + 160 °C
Fresh water, XMLA300E2C11 XMLA300E2S12 XMLA300E2S13
up to + 160 °C
Corrosive fluids, air, XMLA300N2C11 XMLA300N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 16.5 bar (239.25 psi)
(subtract from PH At high setting (4) 35 bar (507.5 psi)
to give PB)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19 575 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA300D2S12
becomes XMLA300D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 3 bar (± 43.5 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 6 bar (± 87 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13

11

bar
PH
Rising pressure

14

12

300
PB

200
Connector model
Pressure switch connector pin view

100 Time

1 2 1 → 11 and 13
3
20 2 → 12
0 3 → 14
3.5 100 200 265 300 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

60
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 22…300 bar (319…4350 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLB300D2C11 XMLB300D2S12 XMLB300D2S13
(2)(5) up to + 160 °C
Fresh water, XMLB300E2C11 XMLB300E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB300N2C11 XMLB300N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 19.4 bar (281.3 psi)
(subtract from PH Min. at high setting (4) 37 bar (536.5 psi)
to give PB)
Max. at high setting 200 bar (2900 psi)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19,575 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT for
43650A), 4-pin male connector. for ISO cable gland, clamping cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB300D2S12
becomes XMLB300D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 1.5 bar, + 1.7 bar (- 21.75 psi, + 24.65 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 1 bar, + 4 bar (- 14.5 psi, + 58 psi).
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13

11

bar
300 PH
Rising pressure

14

12

200 1 PB

Connector model
2 Pressure switch connector pin view

100 Time

1 2 1 → 11 and 13
3 2 → 12
22 3 → 14
0
2.6 100 200 263 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

61
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale

Adjustable range of switching point (PH) 22…300 bar (319…4350 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, XMLC300D2S12
(2) (4) up to + 160 °C
Fresh water, XMLC300E2S12
up to + 160 °C
Corrosive fluids, air, XMLC300N2S12
up to + 160 °C
Weight (kg) 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 16 bar (232 psi)
(subtract from PH Min. at high setting (3) 35 bar (507.5 psi)
to give PB)
Max. at high setting 240 bar (3480 psi)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19 575 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC300D2S12
becomes XMLC300D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.9 bar (± 13.05 psi)
(4) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13

11

23

21

bar
300
PH
Rising pressure

1
14

12

24

22

200 PB

100 Time

22
0
6 60 100 200 265 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

62
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 36…300 bar (522…4350 psi)
switching point 1st stage switching point (PH1) 25…289 bar (362.5…4190.5 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 11…189 bar (159.5…2740.5 psi)
Electrical connection Terminals
Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)
References (1)
Fluids controlled Hydraulic oils, XMLD300D1S12 XMLD300D1S13
(2) (5) up to + 160 °C
Fresh water, XMLD300E1S12 –
up to + 160 °C
Corrosive fluids, air, XMLD300N1S12 –
up to + 160 °C
Weight (kg) 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 17 bar (246.5 psi)
(subtract from PH1/PH2 At high setting (4) 42 bar (609 psi)
to give PB1/PB2)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19,575 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD300D1S12
beomes XMLD300D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 2.5 bar (± 36.25 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 9 bar (± 130.5 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar
300 H PH2
Rising pressure

bar 289
F PB2
PH2 setting (rising pressure)

300

PH1
1 200 PB1
215
200

2
100 Time
100

36 G
25 –– Adjustable value
36 E --- Non adjustable value
20 0
8 19 100 200 247 258 300 bar
0
Falling pressure Connection
0 25 111 200 289 bar
PH1 setting (rising pressure) Terminal model
Contact 2Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

63
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact

OsiSense XMLA pressure switches With setting scale

Adjustable range of switching point (PH) 30…500 bar (435…7250 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLA500D2C11 XMLA500D2S12 XMLA500D2S13
(2) (5) up to + 160 °C
Fresh water, XMLA500E2C11 XMLA500E2S12 XMLA500E2S13
up to + 160 °C
Corrosive fluids, air, XMLA500N2C11 XMLA500N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 20 bar (290 psi)
(subtract from PH At high setting (4) 45 bar (652.5 psi)
to give PB)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16,312.5 psi)
Destruction pressure 2250 bar (32,625 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA500D2S12
becomes XMLA500D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 6 bar (± 87 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 10 bar (± 145 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
bar
13

11

500
Rising pressure

PH
14

12

400
PB

300
Connector model
200
Pressure switch connector pin view

Time
100
1 2 1 → 11 and 13
3
30 2 → 12
0 3 → 14
10 100 200 300 400 455 bar
Falling pressure

–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

64
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

OsiSense XMLB pressure switches With setting scale

Adjustable range of switching point (PH) 30…500 bar (435…7250 psi)


(Rising pressure)
Electrical connection DIN connector Terminals

Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female)

References (1)
Fluids controlled Hydraulic oils, XMLB500D2C11 XMLB500D2S12 XMLB500D2S13
(2) (5) up to + 160 °C
Fresh water, XMLB500E2C11 XMLB500E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB500N2C11 XMLB500N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 23 bar (333.5 psi)
(subtract from PH Min. at high setting (4) 52.6 bar (762.7 psi)
to give PB)
Max. at high setting 300 bar (4350 psi)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16,312.5 psi)
Destruction pressure 2250 bar (32,625 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB500D2S12
becomes XMLB500D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 2.6 bar, + 3.8 bar (- 37.7 psi, + 55.1 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 14.8 bar, + 11.2 bar (- 214.6 psi, + 162.4 psi).
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13

11

bar
500 PH
Rising pressure

14

12

400

PB
300 1
Connector model
2 Pressure switch connector pin view
200
Time
100 1 2 1 → 11 and 13
3
30
2 → 12
0 3 → 14
7 100 200 400 447.4 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

65
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts

OsiSense XMLC pressure switches With setting scale

Adjustable range of switching point (PH) 30…500 bar (435…7250 psi)


(Rising pressure)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, XMLC500D2S12
(2) (4) up to + 160 °C
Corrosive fluids, air, XMLC500N2S12
up to + 160 °C
Weight (kg) 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 19 bar (275.5 psi)
(subtract from PH Min. at high setting (3) 52 bar (754 psi)
to give PB)
Max. at high setting 340 bar (4930 psi)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16 312.5 psi)
Destruction pressure 2250 bar (32 625 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tappedJe préfère acheter des.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC500D2S12
becomes XMLC500D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.9 bar (± 13.05 psi)
(4) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13

11

23

21

bar
500
Rising pressure

PH
14

12

24

22

400
1
PB
300

2
200
Time

100

30
0
11 100 160 200 300 400 448 bar
Falling pressure

1 Maximum differential –– Adjustable value


2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

Accessories: Dimensions:
page 68 pages 69 to 71

66
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts

OsiSense XMLD pressure switches Without setting scale

Adjustable range of each 2nd stage switching point (PH2) 41…500 bar (594.5…7250 psi)
switching point 1st stage switching point (PH1) 25…484 bar (362.5…7018 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 16…244 bar (232…3538 psi)
Electrical connection Terminals

Fluid connection G 1/4 (female)

References (1)
Fluids controlled Hydraulic oils, up to + 160 °C XMLD500D1S12
(2) (5)
Weight (kg) 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 21 bar (304.5 psi)
(subtract from PH1/PH2 At high setting (4) 65 bar (942.5 psi)
to give PB1/PB2)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16,312.5 psi)
Destruction pressure 2250 bar (32,625 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD500D1S12
becomes XMLD500D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 3 bar (± 43.5 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 10 bar (± 145 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar H
484
Rising pressure

bar F PH2
500
PB2
PH2 setting (rising pressure)

400
400 PH1
PB1
1 300
300
273.5
200
200 2
Time
100
100 41 G –– Adjustable value
25E --- Non adjustable value
41 0
0
4 20 100 200 300 419 435 bar Connection
25 100 200 256300 400 484 bar Falling pressure
Terminal model
PH1 setting (rising pressure)
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13

11

23

21

2 Minimum differential GH Contact 2 (stage 2)


14

12

24

22

Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.

67
References Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD
Accessories and replacement parts

Accessories for pressure switches and vacuum switches


Description Specific For use with Unit reference Weight
characteristics switches kg
Rear fixing bracket – XMLpL35 XMLZL006 0.230
for vibrations > 2 gn XMLp001

Additional top support bracket – XMLAM01 XMLZL002 0.020


for vibrations > 4 gn XMLpM05
XMLA004
XMLp010…
XMLp500

Knurled adjustment knob, Ø 36 mm – All models XMLZL003 0.010


fits over adjustment screws
to facilitate setting
XMLZL006
Fixing plate – XMLAM01 XMLZL004 0.110
for replacing an XMJA or XMGB switch with an XMLpM05
XML switch XMLA004
XMLp010…
XMLp500
XMLZL002
Lead sealable protective cover – XMLA XMLZL001 0.035
to prevent unauthorised access to adjustment XMLB
screws and fixing screw of switch cover

XMLZL003 XMLZL004
Lead sealable protective cover – All types XMLZL011 0.030
to prevent unauthorised access to adjustment
screws

Indicator modules Without setting a or c 24/48 V XMLA/B XMLZZ024 0.090


and associated covers, scale
2 LEDs (orange and green)
XMLZL001 a 110/240 V XMLA/B XMLZZ120 0.090

With setting scale a or c 24/48 V XMLA XMLZA024 0.090

XMLZL011 XMLB XMLZB024 0.090

a 110/240 V XMLA XMLZA120 0.090

XMLB XMLZB120 0.090

XMLZL005 Hydraulic block – All types XMLZL005 0.240


for base mounting directly onto fluid manifold

Female EN 175301-803-A connector – XMLppppppC11 XZCC43FCP40B 0.035


(ex-DIN 43650A)

Adaptor, G 1/4"/G 3/8" male/female – All types XMLZL012 0.130

Replacement parts
Sealing gasket For sizes u 300 bar (XMLA/B/C/D) XMLZL010 0.015
(pack of 10 gaskets)
XMLZAppp,
XMLZBppp
Diaphragms – XMLpS35 XMLZL013 0.060

XMLpS02 XMLZL014 0.040


XMLZL010

XMLpS04 XMLZL015 0.030

XZCC43FCP40B

68
Dimensions Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD

XMLpL35, XMLp001, XMLpS

XMLC/D : 46
a XMLA/B : 35

(2)

max 162
56,5

(1)
17

57 = 45 =

(1) 1 fluid entry, tapped G 1/4 (female) or 1/4”-18 NPTF (female)


(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5 or 1/2”-14 NPT

XMLBM03, XMLBL05

40 (3)

(2) (4)
65

.
145

10

56

(1) c2 20 20
c1

(1) 1 fluid entry, tapped G 1/4 (female) or 1/4”-18 NPTF (female) XML Øa c1 c2
(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5 BM03 150 155.5 80.5
or 1/2”-14 NPT
BL05 200 204 104
(3) 2 elongated holes Ø 10.2 x 5.2
(4) 1 elongated hole Ø 15.2 x 5.2 pL35, p001 110 – –
pS35, pS02, pS04 110 – –
pS10, pS20 86 – –

69
Dimensions (continued) Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD

XMLAM01, XMLBM05, XMLCM05, XMLA004, XMLp010…500


XMLC/D : 85 XMLC/D : 46
XMLA/B : 75 XMLA/B : 35

113
(2)
37 5
37

17,5
(1) 23 = 20-22 =
56

120

(1) 1 fluid entry, tapped G 1/4 (female) or 1/4”-18 NPTF (female)


(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5 or 1/2”-14 NPT
Ø: 2 elongated holes Ø 5.2 x 6.7

XMLpM02, XMLp002, XMLB004, XMLC004, XMLD004


55
XMLC/D : 90 XMLC/D : 46
XMLA/B : 77,5 XMLA/B : 35
Ø5,2
106

(2)
158
34

(1)
13

30 = 37-40 =
122

(1) 1 fluid entry, tapped G 1/4 (female) or 1/4”-18 NPTF (female)


(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5 or 1/2”-14 NPT
Ø: 2 elongated holes Ø 10.2 x 5.2

Characteristics: References:
pages 17 to 67 pages 18 to 67

70
Dimensions (continued) Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD

XMLBL35P, XMLB001P

(2)

175
86,5

(1) 55

(1) 1 fluid entry, tapped G 1¼ (female)


(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5

XMLBM05P, XMLA004P, XMLp010P, XMLp020P, XMLp035P


35

37 5
130

(2)
54

(1) 25

76

(1) 1 fluid entry, tapped G 1¼ (female)


(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5

71
Component materials of Electromechanical pressure
units in contact with fluid and vacuum switches
This information will assist in checking the corrosion resistance of
OsiSense XML
the pressure or vacuum switches in relation to the fluids controlled

Component materials in contact with fluid


Pressure or vacuum switch reference Zinc alloy Stainless Brass Steel Nitrile PTFE FPM, FKM Aluminium
steel
XMLAM01Vpppp, XMLpM02Vpppp (1)

XMLAM01Tpppp, XMLpM02Tpppp (2)

XMLBM03Rpppp

XMLBM03Spppp (3)

XMLpM05Apppp (1)

XMLpM05Bpppp (1)

XMLpM05Cpppp (1)

XMLBM05Ppppp (1)

XMLBL05Rpppp

XMLBL05Spppp (3)

XMLpL35Rpppp, XMLpS35Rpppp (1)

XMLpL35Spppp (3)

XMLBL35Ppppp (1)

XMLp001Rpppp (1)

XMLp001Spppp (3)

XMLB001Ppppp (1)

XMLp002Apppp

XMLp002Bpppp, XMLpS02Bpppp

XMLp002Cpppp (3)

XMLA004Apppp

XMLA004Bpppp

XMLA004Cpppp (2)

XMLA004Ppppp

Component materials in contact with fluid

(1) 1.4307 (AISI 304L)


(2) 1.4404 (AISI 316L)
(3) 1.4305 (AISI 303)

72
Component materials of Electromechanical pressure
units in contact with fluid and vacuum switches
This information will assist in checking the corrosion resistance of
OsiSense XML
the pressure or vacuum switches in relation to the fluids controlled

Component materials in contact with fluid


Pressure switch reference Zinc alloy Stainless Brass Steel Nitrile PTFE FPM, FKM Aluminium
steel
XMLB004Apppp

XMLp004Bpppp, XMLpS04Bpppp

XMLp004Cpppp (3)

XMLp010Apppp

XMLp010Bpppp

XMLp010Cpppp (2)

XMLp010Ppppp, XMLpS10Apppp

XMLp020Apppp, XMLp035Apppp

XMLp020Bpppp, XMLp035Bpppp

XMLp020Cpppp, XMLp035Cpppp (2)

XMLp020Ppppp, XMLp035Ppppp, XMLpS20Apppp

XMLp070Dpppp, XMLp160Dpppp

XMLp070Epppp, XMLp160Epppp (4)

XMLp070Npppp, XMLp160Npppp (5)

XMLp300Dpppp

XMLp300Epppp (4)

XMLp300Npppp (5)

XMLp500Dpppp

XMLp500Epppp

XMLp500Npppp4 (5)

Component materials in contact with fluid

(2) 1.4404 (AISI 316L)


(3) 1.4305 (AISI 303)
(4) 1.4404 (AISI 316L) + 1.4462
(5) 1.4404 (AISI 316L) + 1.4305 (AISI 303)

73
Presentation Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ACW and ADW

Presentation
Pressure switches OsiSense ACW and ADW are switches for control circuits, with
an adjustable differential.
Pressure switches OsiSense ACW are used to control the pressure of air, oils and
other non corrosive fluids, up to 131 bar.
Pressure switches OsiSense ADW are used to control the pressure of oils (including
synthetic), up to 340 bar.

Setting, operating principle


Pressure switches OsiSense ACW
1 The switching point on falling pressure (low point - PB) is adjusted using screw 1.

– The switching point on rising pressure (high point - PH) is made by adjusting screw 2.
+ 2 This sets the differential between the low and high points, giving a switching point
on rising pressure of the displayed low point setting plus the differential setting.

The two adjustments are completely independent.

Contact block operation


1 2 When the rising pressure reaches the high point setting (low point setting + differential
setting), contact B (1-2) opens and contact A (3-4) closes. The contacts remain
3 4 actuated until the pressure falls back to the low point setting.

Pressure switches OsiSense ADW


1 The switching point on rising pressure (high point - PH) is adjusted using screw 1.

6 –
2
The switching point on falling pressure (low point - PB) is made by adjusting screw 2.
+ This sets the differential between the high and low points, giving a switching point
on falling pressure of the displayed high point setting minus the differential setting.

The two adjustments are completely independent.

Contact block operation


When the rising pressure reaches the high point setting, contact B (1-2) opens and
1 2 contact A (3-4) closes. The contacts remain actuated until the pressure falls back
3 4 to the low point setting (high point setting - differential setting).

74
Characteristics Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ACW and ADW

Environment characteristics
Pressure switch type ACW (bellows operated) ADW (piston operated)

Conformity to standards e, IEC/EN 60947-5-1

Product certifications CSA, UL (Recognized), EAC

Protective treatment “TC”

Materials Zinc alloy case Zinc alloy case


Phosphor bronze bellows Pressure switches with drainage hole:
Buna N diaphragm, steel piston, cast iron
cylinder
Pressure switches with Quad-Ring piston
seal: Buna N diaphragm, Teflon and Viton
seal, stainless steel piston and cylinder

Ambient air temperature (for operation) °C - 56…+ 85 - 30…+ 85

Fluids controlled Air, oils and other non corrosive fluids, Oils and other fluids, from - 25 to + 120°C
from - 73 to + 125°C (for ADW5, ADW6, ADW7S1, ADW25
and ADW26)

Oils (including synthetic) only, from


- 30 to + 125°C (for ADW3, ADW4, ADW7,
ADW23, ADW24 and ADW27)
Degree of protection IP 65 conforming to IEC/EN 60529

Fluid connection G 1/4 (BSP female) conforming G 3/8 (BSP female) conforming
to NF E 03-005, ISO 228 to NF E 03-005, ISO 228
Electrical connection Terminals 1 tapped entry M20 x 1.5 mm for ISO cable gland.
(for ACWpM119012, ACWppM119012, ADWpM119012 and ADWppM119012).

1 tapped entry for n° 13 (DIN Pg 13.5) cable gland


(for ACWpM129012, ACWppM129012, ADWpM129012 and ADWppM129012).

Contact block characteristics


Rated operational current 1 CO single-pole 2 CO single-pole
pressure switches pressure switches
Category AC-15 Ue
24 V Ie Ie
110 V
220 V
5A
5A
3A
3A 6
500 V 3A 1.5 A
1.4 A 0.7 A
Category DC-13 Ue Ie Ie
24 V 5A 1.5 A
110 V 0.5 A 0.25 A
220 V 0.25 A –
500 V 0.10 A –
600 V 0.06 A –

Short-circuit protection 10 A cartridge fuse type gG

Connection Screw terminals


Minimum clamping capacity: 1 x 1 mm2
Maximum clamping capacity: 2 x 2.5 mm2

References: Dimensions:
pages 76 to 79 pages 80 and 81

75
References, Electromechanical pressure switches
characteristics, OsiSense XM
For control circuits, OsiSense ACW
curves, Sizes 0.70 to 131 bar (10.15 to 1900 psi)
connections Adjustable differential, for regulation between 2 thresholds
Fluid connection G 1/4 (female)

Pressure switches OsiSense ACW Bellows operated Bellows operated

MINI MINI MINI

MINI MINI

I I
MAXI MAX MAX
I I
MAX MAX

Adjustable range of switching point (PB) 0.07…0.70 bar 0.07…1.4 bar 0.07…5.2 bar 0.07…7.6 bar 1.4…12 bar 0.7…18 bar 0.7…21 bar 5.2…34 bar 10…69 bar 24…131 bar
(Falling pressure) (1.01…10.15 psi) (1.01…20.3 psi) (1.01…75.4 psi) (1.01…110.2 psi) (20.3…174 psi) (10.15…261 psi) (10.15…304.5 psi) (75.4…493 psi) (145…1000 psi) (348…1900 psi)

References References
Switches with 1 CO single-pole contact Switches with 1 CO single-pole contact
Electrical connection With one tapped entry ACW3M119012 ACW4M119012 ACW5M119012 ACW1M119012 ACW8M119012 ACW9M119012 ACW2M119012 ACW6M119012 ACW7M119012 ACW10M119012
M20 x 1.5 mm for ISO cable gland

With one tapped entry ACW3M129012 ACW4M129012 ACW5M129012 ACW1M129012 ACW8M129012 ACW9M129012 ACW2M129012 ACW6M129012 ACW7M129012 ACW10M129012
for n° 13 cable gland

Weight (kg) 1.750 1.550 1.550 2.100


Switches with 2 CO single-pole contacts Switches with 2 CO single-pole contacts
Electrical connection With one tapped entry ACW23M119012 ACW24M119012 ACW25M119012 ACW21M119012 ACW28M119012 – ACW22M119012 ACW26M119012 – ACW20M119012
M20 x 1.5 mm for ISO cable gland

With one tapped entry ACW23M129012 ACW24M129012 ACW25M129012 ACW21M129012 ACW28M129012 ACW29M129012 ACW22M129012 ACW26M129012 ACW27M129012 ACW20M129012
for n° 13 cable gland

Weight (kg) 1.750 1.550 1.550 2.100


Complementary characteristics not shown under general characteristics (page 75) Complementary characteristics not shown under general characteristics (page 75)
Possible differential 1 CO switches Min. 0.04 bar (0.58 psi) 0.10 bar (1.45 psi) 0.30 bar (4.35 psi) 0.50 bar (7.25 psi) 0.70 bar (10.15 psi) 1 bar (14.5 psi) 1.7 bar (24.7 psi) 3.4 bar (49.3 psi) 5.9 bar (85.6 psi) 11 bar (159.5 psi)
(add to PB to give PH)
Max. 0.34 bar (4.93 psi) 0.40 bar (5.8 psi) 1 bar (14.5 psi) 2 bar (29 psi) 2 bar (29 psi) 1.7 bar (24.7 psi) 8.6 bar (124.7 psi) 8.3 bar (120.4 psi) 10 bar (145 psi) 21 bar (304.5 psi)

6 6
2 CO switches Min. 0.05 bar (0.73 psi) 0.14 bar (2.03 psi) 0.41 bar (5.95 psi) 0.9 bar (13.05 psi) 1 bar (14.5 psi) 1.6 bar (23.2 psi) 2.4 bar (34.8 psi) 5.9 bar (85.6 psi) 9.3 bar (134.9 psi) 17 bar (246.5 psi)

Max. 0.48 bar (6.96 psi) 0.70 bar (10.15 psi) 1.4 bar (20.3 psi) 2.8 bar (40.6 psi) 2.8 bar (40.6 psi) 2.4 bar (34.8 psi) 10 bar (145 psi) 11 bar (159.5 psi) 14 bar (203 psi) 24 bar (348 psi)

Maximum permissible pressure 2 bar (29 psi) 7 bar (101.5 psi) 17 bar (246.5 psi) 17 bar (246.5 psi) 20 bar (290 psi) 41 bar (549.5 psi) 140 bar (2030 psi) 140 bar (2030 psi) 175 bar (2538 psi)

Fluids controlled Air, oils and other non corrosive fluids, from - 73 to + 125°C (1) Air, oils and other non corrosive fluids, from - 73 to + 125°C (1)

Mechanical life 1 x 10 operating cycles (average value, depending on application)


6
1 x 106 operating cycles (average value, depending on application)

Cable entry, ACWpM119012, ACW2pM119012 1 tapped entry M20 x 1.5 mm for ISO cable gland. 1 tapped entry M20 x 1.5 mm for ISO cable gland. Clamping capacity 7 to 13 mm
screw terminals Clamping capacity 7 to 13 mm

ACWpM129012, ACW2pM129012 1 tapped entry for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5). 1 tapped entry for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5). Clamping capacity 9 to 13 mm
Clamping capacity 9 to 13 mm

(1) See “Component materials of units in contact with the fluid”, page 75. Other versions Pressure switches with alternative tapped cable entries: NPT, etc. Please consult our Customer Care
Centre.
Operating curve Contact block connections
Pressure
2
4

PH
3

PB

Time

–– Adjustable value
Other versions Pressure switches with alternative tapped cable entries: NPT, etc. Please consult our Customer
Care Centre.

Dimensions: Dimensions:
page 80 page 80

76 77
References, Electromechanical pressure switches
characteristics OsiSense XM
For control circuits, OsiSense ADW
Sizes 69 to 340 bar (1000 to 4930 psi)
Adjustable differential, for regulation between 2 thresholds
Fluid connection G 3/8 (female)

Pressure switches OsiSense ADW Piston operated, with drainage hole (1) Pressure switches OsiSense ADW Piston operated, with Quad-Ring piston seal

MINI

MINI

I
MAX
I
MAX

Adjustable range of switching point (PH) 9.3…69 bar 28…210 bar 38…340 bar Adjustable range of switching point (PH) 9.3…69 bar 28…210 bar 38…340 bar
(Rising pressure) (135…1000 psi) (406…3045 psi) (551…4930 psi) (Falling pressure) (135…1000 psi) (406…3045 psi) (551…4930 psi)

References References
Switches with 1 CO single-pole contact Switches with 1 CO single-pole contact
Electrical connection With one tapped entry ADW3M119012 ADW4M119012 ADW7M119012 Electrical connection With one tapped entry ADW5M119012 ADW6M119012 –
M20 x 1.5 mm for ISO cable gland M20 x 1.5 mm for ISO cable gland

With one tapped entry ADW3M129012 ADW4M129012 ADW7M129012 With one tapped entry ADW5M129012 ADW6M129012 ADW7S1M129012
for n° 13 cable gland for n° 13 cable gland

Weight (kg) 1.880 Weight (kg) 1.880


Switches with 2 CO single-pole contacts Switches with 2 CO single-pole contacts
Electrical connection With one tapped entry ADW23M129012 ADW24M129012 ADW27M129012 Electrical connection With one tapped entry ADW25M129012 ADW26M129012 –
for n° 13 cable gland for n° 13 cable gland

Weight (kg) 1.880 Weight (kg) 1.880


Complementary characteristics not shown under general characteristics (page 75) Complementary characteristics not shown under general characteristics (page 75)
Possible differential 1 CO switches Min. 2.4 bar (34.8 psi) 6.9 bar (100 psi) 8.6 bar (124.7 psi) Possible differential 1 CO switches Min./max. at 4.8/6.9 bar (69.6/100 psi) 14/21 bar (203/304.5 psi) 19/25 bar (275.5/362.5 psi)
(subtract from PH to give PB) (subtract from PH to give PB) low setting
Max. 9.3 bar (135 psi) 28 bar (406 psi) 38 bar (551 psi) Min./max. at 8.6/10 bar (124.7/145 psi) 28/34 bar (406/493 psi) 38/45 bar (551/652.5 psi)
low setting
2 CO switches Min. 3.1 bar (45 psi) 8.6 bar (124.7 psi) 14 bar (203 psi) 2 CO switches Min./max. at 6.2/7.9 bar (89.9/114.6 psi) 17/24 bar (246.5/348 psi) 22/28 bar (319/406 psi)
low setting
Max. 14 bar (203 psi) 34 bar (493 psi) 41 bar (594.5 psi) Min./max. at 10/12 bar (145/174 psi) 34/39 bar (493/565.5 psi) 44/50 bar (638/725 psi)
high setting
Maximum permissible pressure 690 bar (10,000 psi)
Maximum permissible pressure 690 bar (10,000 psi)

6 Fluids controlled Oils (including synthetic) only, from - 30°C to + 125°C (2) (3)
Fluids controlled Oils and other fluids, from - 25°C to + 120°C (1) (2) 6
Mechanical life 1 x 10 operating cycles (average value, depending on application)
6

Mechanical life 1 x 106 operating cycles (average value, depending on application)


Cable entry, ADWpM119012 1 tapped entry M20 x 1.5 mm for ISO cable gland.
screw terminals Clamping capacity 7 to 13 mm Cable entry, ADWpM119012 1 tapped entry M20 x 1.5 mm for ISO cable gland.
screw terminals Clamping capacity 7 to 13 mm
ADWpM129012, 1 tapped entry for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5).
ADW2ppM129012 Clamping capacity 9 to 13 mm ADWpM129012, 1 tapped entry for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5).
ADW2ppM129012 Clamping capacity 9 to 13 mm
(1) Since it is normal for piston type pressure switches (not incorporating a piston seal) to have
a slight oil leakage past the piston, a drain hole through the cylinder wall is incorporated. (1) See “Component materials of units in contact with the fluid”, page 75.
To avoid back pressure, this hole should never be plugged. If for any reason this oil leakage (2) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
is undesirable, use pressure switches incorporating a Quad-Ring piston seal.
(2) See “Component materials of units in contact with the fluid”, page 75.
(3) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.

Operating curve Contact block connections Operating curve Contact block connections
Pressure Pressure

2
4
2
4

PH PH

1
3

PB PB

Time Time

–– Adjustable value –– Adjustable value


Other versions Pressure switches with alternative tapped cable entries: NPT, etc. Please consult our Customer Other versions Pressure switches with alternative tapped cable entries: NPT, etc. Please consult our Customer
Care Centre. Care Centre.

Dimensions: Dimensions:
page 81 page 81

78 79
Dimensions Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ACW

ACW3, ACW4, ACW23 and ACW24 ACW1, ACW5, ACW8, ACW9, ACW21, ACW25, ACW28 and ACW29
88 88
68 9,5 69 9,5 68 9,5 69 9,5
31 31 31 31

9,5
9,5

17
17

88
88

69
69

167
(1) (1)

190

9,5
9,5

18 18

31 31

31 31

(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model (1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
Ø: G 1/4 (female) Ø: G 1/4 (female)

ACW2 and ACW22 ACW6, ACW7, ACW10, ACW26, ACW27 and ACW20
88 88
68 69
6
9,5 69 9,5 68 9,5 9,5
31 31 31 31
9,5

9,5

17
17

88
88
69

69
173

(1) (1)
221
9,5
9,5

18

31 31

31 31

(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model (1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
Ø: G 1/4 (female) Ø: G 1/4 (female)

Characteristics: References:
pages 75 to 77 pages 76 and 77

80
Dimensions Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ADW

ADW3, ADW4, ADW7, ADW23, ADW24 and ADW27


88
68 9,5 69 9,5
31 31

9,5

16
88
69
(1)

176
9,5
18
(2)

31 31

(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
(2) Drainage hole, tapped G 1/8 (female)
Ø: G 3/8 (female)

ADW5, ADW6, ADW7S1, ADW25 and ADW26


88
68 9,5 69 9,5
31 31

6
9,5

16
88
69

(1)
176
9,5

18

31 31

(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
Ø: G 3/8 (female)

Characteristics: References:
pages 75 to 79 pages 78 and 79

81
Presentation Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense XMX and XMA

Presentation
Pressure switches OsiSense XMX and XMA are switches for control circuits, with
1 an adjustable differential.
They are used to control the pressure of water and air, up to 25 bar.

Equipment fitted to the various models


Location of setting screw

2 Pressure switches OsiSense XMX have an internal setting screw that is only
accessible after removing the cover.
Pressure switches OsiSense XMA have an external setting screw that is accessible
without removing the cover.

Case
Pressure switches OsiSense XMX have a black opaque case.
3 Pressure switches OsiSense XMA can have a transparent case or a black opaque
case.

Setting
1
2 When setting pressure switches XMX or XMA, adjust the switching point on rising
4 pressure (PH) first and then the switching point on falling pressure (PB).

Switching point on rising pressure


The switching point on rising pressure (PH) is set by adjusting screw-nut 1.

Switching point on falling pressure


The switching point on falling pressure (PB) is set by adjusting screw-nut 2.

10

References: Dimensions:
page 84 page 87

82
Characteristics Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense XMX and XMA

Environment characteristics
Conformity to standards e, IEC/EN 60947-5-1

Product certifications UL, CSA, CCC, EAC


1
Protective treatment "TC"

Ambient air temperature For operation °C - 25…+ 70 for 6 and 25 bar versions
- 25…+ 55 for 12 bar version
For storage - 40…+ 70
2
Fluids controlled °C Air, fresh water, sea water:
0…+ 70°C for 6 and 25 bar versions
0…+ 55°C for 12 bar version
Materials Case: polycarbonate impregnated with Lexan 500R fibreglass (black opaque cover)
or polycarbonate impregnated with Lexan 123 fibreglass (transparent cover)
Component materials in contact with fluid: chromated zinc alloy (fluid entry),
canvas covered nitrile (diaphragm) 3
Operating position All positions

Electric shock protection Class I conforming to IEC 536

Degree of protection IP 54 conforming to IEC/EN 60529

Operating rate Op.


cycles/h
600 4
Repeat accuracy < 3.5%

Fluid connection G 1/4 or 4 x G 1/4 (BSP female) conforming to NF E 03-005, ISO 228

Electrical connection Terminals


2 tapped entries for n° 13 (DIN Pg 13.5) cable gland
5
Contact block characteristics
Rated operational characteristics a AC-15, B300 (Ue = 240 V, Ie = 1.5 A; Ue = 120 V, Ie = 3 A)
c DC-13, R300 (Ue = 250 V, Ie = 0.1 A)

Rated insulation voltage V Ui = 500 conforming to IEC/EN 60947-1

Rated impulse withstand voltage kV U imp = 6 conforming to IEC/EN 60947-1 6


Type of contacts 1 CO single-pole contact, snap action

Terminal referencing Conforming to CENELEC EN 50013

Short-circuit protection 10 A cartridge fuse type gG (gl)

Connection Screw clamp terminals


7
Minimum clamping capacity: 1 x 1 mm2
Maximum clamping capacity: 2 x 2.5 mm2
Electrical durability AC supply 50/60Hz, Ith = 10 A
Inductive circuit, utilisation category AC-15, 3 A/240 V: 1 million operating cycles

10

References: Dimensions:
page 84 page 87

83
References, Electromechanical pressure switches
characteristics OsiSense XMX for control circuits
Sizes 6 to 25 bar (87 to 362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

Pressure switches OsiSense XMX (internal setting screw)

2
Adjustable range of switching point (PH) 1…6 bar 1.3…12 bar 3.5…25 bar 1…6 bar 1.3…12 bar 3.5…25 bar
(Rising pressure) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi)
Fluid connection G 1/4 (female) 4 x G 1/4 (female)

3 References
Switches with black opaque cover
Fluids controlled Air, fresh water, XMXA06L2135 XMXA12L2135 XMXA25L2135 XMXA06L2435 XMXA12L2435 XMXA25L2435
sea water (1)
Weight (kg) 0.430 0.650 0.430 0.650
Complementary characteristics not shown under general characteristics (page 83)

4
Possible differential Min. at low setting 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi)
(subtract from PH
to give PB) Min. at high setting 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi) 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi)

Max. at high setting 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi) 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi)

Maximum Per cycle 7.5 bar (108.7 psi) 15 bar (217.5 psi) 31.25 bar 7.5 bar 15 bar (217.5 psi) 31.25 bar
permissible pressure (453.1 psi) (108.7 psi) (453.1 psi)

5 Accidental 13.5 bar


(195.7 psi)
27 bar (391.5 psi) 56.25 bar
(815.6 psi)
13.5 bar
(195.7 psi)
27 bar (391.5 psi) 56.25 bar
(815.6 psi)
Destruction pressure 30 bar (435 psi) 100 bar (1450 psi) 30 bar (435 psi) 100 bar (1450 psi)

Mechanical life 1 x 106 operating cycles

Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)

6 Pressure switch type Diaphragm

(1) Component materials of units in contact with the fluid, see page 83.

Operating curves
XMXA06ppppp XMXA12ppppp XMXA25ppppp

7
Pressure
bar bar bar
6
12 30 PH
Rising pressure

1 1
Rising pressure

Rising pressure

5 10 25
2
2 1
4 8 20 PB

3 6 15 2

8 2 4 10
Time
1 2
1.3 3.5
0 0 0 –– Adjustable value
0.2 1 1.8 2 3 4 4.8 6 bar 0.3 2 3.6 4 6 8 10 10.3 bar
Falling pressure 0.1 5 10 15 20.5 25 30 bar
Falling pressure Falling pressure

9 1 Maximum differential 1 Maximum differential 1 Maximum differential


Connections
13

21

2 Minimum differential 2 Minimum differential 2 Minimum differential


14

22

Other versions Pressure switches with alternative tapped cable entries: ISO, NPT, etc. Please consult our
Customer Care Centre.
10

Accessories: Dimensions:
page 86 page 87

84
References, Electromechanical pressure switches
characteristics OsiSense XMA for control circuits
Sizes 6 to 25 bar (87 to 362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact

Pressure switches OsiSense XMA (external setting screw)

2
Adjustable range of switching point (PH) 1…6 bar 1.3…12 bar 3.5…25 bar 1…6 bar 1.3…12 bar 3.5…25 bar
(Rising pressure) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi)
Fluid connection G 1/4 (female) 4 x G 1/4 (female)
References
Switches with black opaque cover
3
Fluids controlled Air, fresh water, XMAH06L2135 XMAH12L2135 XMAH25L2135 XMAH06L2435 XMAH12L2435 XMAH25L2435
sea water (1)
Switches with transparent cover
Fluids controlled Air, fresh water, XMAV06L2135 XMAV12L2135 XMAV25L2135 XMAV06L2435 XMAV12L2435 XMAV25L2435
sea water (1)
Weight (kg)
Complementary characteristics not shown under general characteristics (page 83)
0.430 0.650 0.430 0.650
4
Possible differential Min. at low setting 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi)
(subtract from PH
to give PB) Min. at high setting 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi) 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi)

Max. at high setting 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi) 4.2 bar (60.9 psi) 8.4 bar 20 bar (290 psi)

Maximum Per cycle 7.5 bar (108.7 psi) 15 bar (217.5 psi) 31.25 bar 7.5 bar
(121.8 psi)
15 bar 31.25 bar
5
permissible pressure (453.1 psi) (108.7 psi) (217.5 psi) (453.1 psi)
Accidental 13.5 bar (195.7 psi) 27 bar (391.5 psi) 56.25 bar 13.5 bar 27 bar 56.25 bar
(815.6 psi) (195.7 psi) (391.5 psi) (815.6 psi)
Destruction pressure 30 bar (435 psi) 100 bar 30 bar (435 psi) 100 bar
(1450 psi) (1450 psi)
Mechanical life
Cable entry
1 x 106 operating cycles
2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 6
Pressure switch type Diaphragm
(1) Component materials of units in contact with the fluid, see page 83.

Operating curves
XMAp06ppppp XMAp12ppppp XMAp25ppppp

bar bar bar Pressure


7
6 12 30
PH
Rising pressure
Rising pressure

1 1
Rising pressure

5 10 25
2
4
2 20 1
8
PB
2
8
3 6 15

2 4 10

1 2 Time
3.5
1.3
–– Adjustable value
0 0 0
0.2 1 1.8 2 3 4 4.8 6 bar 0.3 2 3.6 4 6 8 10 10.3 bar 0.1 5 10 15 20.5 25 30 bar
Falling pressure Falling pressure Falling pressure
Connections
1 Maximum differential 1 Maximum differential 1 Maximum differential 9
13

21

2 Minimum differential 2 Minimum differential 2 Minimum differential


14

22

Other versions Pressure switches with alternative tapped cable entries: ISO, NPT, etc. Please consult our
Customer Care Centre.

10

Accessories: Dimensions:
page 86 page 87

85
References Electromechanical pressure switches
OsiSense XMX and XMA for control circuits
Accessories and replacement parts

References
Description Reference Weight
1 Fixing bracket XMAZL001
kg
0.035

XMAZL001
Knurled adjustment knob, Ø 36 mm XMLZL003 0.010
fits over adjustment screws to facilitate setting

2
13P cable gland With anti pull-out ring (for cable Ø 6…9 mm) DE9PM1201 0.005
XMLZL003

Without anti pull-out ring (for cable Ø 6…9 mm) DE9PM1202 0.005

3 DE9PM1201
With anti pull-out ring (for cable Ø 9…12.5 mm) DE9PM1203 0.005

Description For pressure switch Reference Weight

4
kg
Diaphragms Size 6 bar XMPZ31 0.005
DE9PM1202

Size 25 bar XMPZ33 0.005

5 XMPZ3p

10

Dimensions:
page 87

86
Dimensions Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense XMX and XMA

Accessories and replacement parts

Dimensions
XMXA06L2135, XMXA12L2135 XMXA06L2435, XMXA12L2435
XMAp06L2135, XMAp12L2135 XMAp06L2435, XMAp12L2435
1

XMA: 7
XMA: 7
2

106
106

(1)
30.5 43.5
=
30.5
=
3
= = 58
97.5 57
. 57

r = 63 (2) r = 63 (2)

D
4
A C A

B
5
ØA = G 1/4 (female) ØA = ØB = ØC = ØD = G 1/4 (female)
(1) 2 tapped entries for n° 13 cable gland (1) 2 tapped entries for n° 13 cable gland
(2) Minimum clearance zone for screwing-on pressure switch at point A (2) Minimum clearance zone for screwing-on pressure switch at point A
XMXA25L2135, XMXA25L2435 Fixing bracket
XMAp25L2135, XMAp25L2435 XMAZL001
6
XMA: 7

7
126

(1)

43.5 30.5
8
58 = =
97.5 57
r = 63 (2)

D
9
C A

B
10
XMpp25L2135: ØA only = G 1/4 (female) (1) 2 tapped entries for n° 13 cable gland
XMpp25L2435: ØA = ØB = ØC = ØD = G 1/4 (female) (2) Minimum clearance zone for screwing-on pressure switch at point A
Characteristics: References:
page 83 page 84

87
Presentation Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense FTG, FSG and FYG

Presentation
Pressure switches OsiSense FTG, FSG and FYG are switches for power circuits.
They are used to control the pressure of water, up to 10.5 bar.

2 types of product are available:


- pressure switches OsiSense FTG with fixed differential, for detection of a single
threshold,
- pressure switches OsiSense FSG and FYG with an adjustable differential, for
regulation between 2 thresholds.

For specific needs, these 2 types of product can be supplied in IP 65 versions, thus
ensuring a higher degree of protection. They feature 2 cable entries, fitted with cable
gland, and are referenced FpGpNE.

Setting
1 Pressure switches with fixed differential (FTG)
Only the switching point on rising pressure is adjustable.

Switching point on rising pressure


The switching point on rising pressure (PH) is set by adjusting screw-nut 1.

Switching point on falling pressure


The switching point on falling pressure (PB) is not adjustable.
The difference between the tripping and resetting points of the contact is the natural
differential of the switch (contact differential, friction, etc.).

Pressure switches with adjustable differential (FSG and FYG)


1 When setting the pressure switch, adjust the switching point on rising pressure (PH)
first and then the switching point on falling pressure (PB).
2
Switching point on rising pressure
The switching point on rising pressure (PH) is set by adjusting screw-nut 1.

6 Switching point on falling pressure


The switching point on falling pressure (PB) is set by adjusting screw-nut 2.

References: Dimensions:
pages 90 to 92 page 93

88
Characteristics Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense FTG, FSG and FYG

Environment characteristics
Pressure switch type FTGp FSGp and FYGp
FTGpNE FSGpNE and FYGpNE
Conformity to standards e, IEC/EN 60730

Protective treatment Standard version: "TC"

Ambient air temperature °C For operation: 0...+ 45. For storage: - 30...+ 80

Fluids controlled Fresh water, sea water (0…+ 70°C)

Materials Case: polystyrene, resistant to mechanical impact


Component materials in contact with fluid: nylon 6/6, zinc plated steel, nitrile

Operating position All positions

Electric shock protection Class I conforming to IEC 536

Degree of protection FTGp, FSGp and IP 20


conforming to IEC/EN 60529 FYGp
FTGpNE, FSGpNE IP 65
and FYGpNE
Operating rate Op. 600
cycles/h
Repeat accuracy < 2%

Fluid connection FpG 2, FYGp2 G 1/4 (BSP female) conforming to NF E 03-005, ISO 228

FpG 9 R 1/4 (BSP male) conforming to NF E 03-004, ISO 7

Electrical connection FTGp, FSGp and Terminals. 2 cable entries, with grommet
FYGp
FTGpNE, FSGpNE Terminals. 2 entries incorporating 13P cable gland (DIN Pg 13.5)
and FYGpNE

Contact block characteristics


Rated operational characteristics Ie = 10 A, Ue = a 250 V conforming to EN 60730-1

Power ratings of controlled motors Voltage a 2-pole a 2-pole a 2-pole a 2-pole

6
1-phase 3-phase 1-phase 3-phase

110 V 0.75 kW (1 HP) 1.1 kW (1.5 HP) 0.75 kW (1 HP) 1.1 kW (1.5 HP)

230 V 1.1 kW (1.5 HP) 1.5 kW (2 HP) 1.5 kW (2 HP) 2.2 kW (3 HP)

400 V 1.5 kW (2 HP) 1.5 kW (2 HP) 1.5 kW (2 HP) 2.2 kW (3 HP)

Rated insulation voltage V Ui = 500


conforming to IEC/EN 60947-1
Rated impulse withstand voltage kV U imp = 6
conforming to IEC/EN 60947-1
Type of contacts 1 2-pole 2 NC (4 terminal) contact, snap action

Short-circuit protection 20 A cartridge fuse type gG

Connection Screw clamp terminals.


Minimum clamping capacity: 1 x 1 mm2, max: 2 x 2 mm2

Electrical durability Op. 40 000 100 000


at an operating rate of cycles
600 operating cycles/hour

References: Dimensions:
pages 90 to 92 page 93

89
References, Electromechanical pressure switches
characteristics OsiSense XM
For power circuits, OsiSense FTG
Size 4.6 bar (66.7 psi), fixed differential, for detection
of a single threshold. Switches with 2-pole 2 NC contact.
Degree of protection IP 20 or IP 65

Fluid connection G 1/4 (female) R 1/4 (male) G 1/4 (female) R 1/4 (male)

Adjustable range of switching point (PH) 1.4…4.6 bar (20.3…66.7 psi)


(Rising pressure)
Degree of protection IP 20 IP 65
conforming to IEC/EN 60529
References
Fluids controlled Fresh water, sea water, from 0°C FTG2 FTG9 FTG2NE FTG9NE
to + 70°C (1)
Weight (kg) 0.340

Complementary characteristics not shown under general characteristics (page 89)


Natural differential At low setting 1.1 bar (15.95 psi)
(subtract from PH to give PB)
At middle setting 1.3 bar (18.85 psi)

At high setting 1.5 bar (21.75 psi)

Maximum permissible Per cycle 5.75 bar (83.38 psi)


pressure
Accidental 8 bar (116 psi)

Destruction pressure 20 bar (290 psi)

Mechanical life 4 x 105 operating cycles

Cable entry 2 cable entries, with grommet 2 entries with 13P cable gland
(DIN Pg 13.5)
Clamping capacity – 9 to 13 mm

6 Pressure switch type Diaphragm

(1) Component materials of units in contact with the fluid, see page 89.

Operating curves Connections


bar
5
Rising pressure

4.6

4
Pressure

3 PH

PB
2

1.4
1

1
2

0
0 0.3 1 2 3.1 4 5 bar Time
Falling pressure

–– Adjustable value
---- Non adjustable value

Dimensions:
page 93

90
References, Electromechanical pressure switches
characteristics OsiSense XM
For power circuits, OsiSense FSG
Size 4.6 bar (66.7 psi), adjustable differential, for regulation
between 2 thresholds. Switches with 2-pole 2 NC contact.
Degree protection IP 20 or IP 65

Fluid connection G 1/4 (female) R 1/4 (male) G 1/4 (female) R 1/4 (male)

Adjustable range of switching point (PH) 1.4…4.6 bar (20.3…66.7 psi)


(Rising pressure)
Degree of protection IP 20 IP 65
conforming to IEC/EN 60529
References
Fluids controlled Fresh water, sea water, from 0°C FSG2 FSG9 FSG2NE (2) FSG9NE
to + 70°C (1)
Weight (kg) 0.340

Complementary characteristics not shown under general characteristics (page 89)


Possible differential Max. at low setting 2.1 bar (30.45 psi)
(subtract from PH to give PB)
Max. at middle setting 2.2 bar (31.9 psi)

Max. at high setting 2.3 bar (33.35 psi)

Min. at low setting 1 bar (14.5 psi)

Min. at middle setting 1.1 bar (15.95 psi)

Min. at high setting 1.2 bar (17.4 psi)

Maximum permissible Per cycle 5.75 bar (83.38 psi)


pressure
Accidental 8 bar (116 psi)

Destruction pressure 20 bar (290 psi)

Mechanical life 1 x 106 operating cycles


6
Cable entry 2 cable entries, with grommet 2 entries with 13P cable gland
(DIN Pg 13.5)
Clamping capacity – 9 to 13 mm

Pressure switch type Diaphragm

(1) Component materials of units in contact with the fluid, see page 89.
(2) Variant: for a G 3/8 female fluid entry that pivots throughout 360°, select the FSG2NEG.

Operating curves Connections


bar
5
Rising pressure

4.6

4
Pressure

3 1 PH
2

1.4 PB
1

1
2

0
0 0.3 1 2 2.3 3 3.4 4 5 bar Time
Falling pressure
1 Maximum differential –– Adjustable value
2 Minimum differential

Dimensions:
page 93

91
References, Electromechanical pressure switches
characteristics OsiSense XM
For power circuits, OsiSense FYG
Sizes 7 and 10.5 bar (101.5 and 152.3 psi), adjustable
differential, for regulation between 2 thresholds. Switches
with 2-pole 2 NC contact. Degree of protection IP 20 or IP 65

Fluid connection G 1/4 (female)

Adjustable range of switching point (PH) 2.8…7 bar (40.6…101.5 psi) 5.6…10.5 bar (81.2…152.3 psi)
(Rising pressure)
Degree of protection IP 20 IP 65 IP 20 IP 65
conforming to EN/IEC 60529
References
Fluids controlled Fresh water, sea water, FYG22 (2) FYG22NE FYG32 (3) FYG32NE
from 0°C to + 70°C (1)
Weight (kg) 0.340

Complementary characteristics not shown under general characteristics (page 89)


Possible differential Max. at low setting 2.3 bar (33.35 psi) 3 bar (43.5 psi)
(subtract from PH to give PB)
Max. at middle setting 2.5 bar (36.25 psi) 3.2 bar (46.4 psi)

Max. at high setting 2.7 bar (39.15 psi) 3.4 bar (49.3 psi)

Min. at low setting 1.2 bar (17.4 psi) 1.9 bar (27.55 psi)

Min. at middle setting 1.4 bar (20.3 psi) 2.1 bar (30.45 psi)

Min. at high setting 1.6 bar (23.2 psi) 2.3 bar (33.35 psi)

Maximum permissible Per cycle 8.75 bar (126.9 psi) 13 bar (188.5 psi)
pressure
Accidental 15 bar (217.5 psi) 15 bar (217.5 psi)

Destruction pressure 20 bar (290 psi) 20 bar (290 psi)

6 Mechanical life 1 x 106 operating cycles

Cable entry 2 cable entries, with grommet

Pressure switch type Diaphragm

(1) Component materials of units in contact with the fluid, see page 89.
(2) Variant: for a 2.8 to 7 bar, IP 20, pressure switch with R 1/4 (male) fluid entry, select the FYG29.
(3) Variant: for a 5.6 to 10.5 bar, IP 20, pressure switch with R 1/4 (male) fluid entry, select the FYG39.

Operating curves Connections


FYG22 FYG32

bar bar
8
Rising pressure

Rising pressure

10
7
9
6 8
1 Pressure
5 7 2 PH
4 1 2 5.6
5

2.8 4
3 PB
2
1

2
1
1
0
2

0
4

0 0.5 1 2 3 4.3 5.4 6 7 8 bar 0 1 2.6 4 5 6 7.1 8.2 9 10 bar Time


Falling pressure Falling pressure

1 Maximum differential 1 Maximum differential –– Adjustable value


2 Minimum differential 2 Minimum differential

Dimensions:
page 93

92
Dimensions Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense FTG, FSG and FYG

Dimensions
FTG2, FSG2 FTG2NE, FSG2NE

102 72 106 72

Ø22
96

115
22
23

41
31 G 1/4 25
60 63
G 1/4

FTG9, FSG9 FTG9NE, FSG9NE


102 72 106 72

Ø22
105

123
22
32

49

25
31 R 1/4 63
60 R 1/4 6

FYG22, FYG32 FYG22NE, FYG32NE


102 72 106 72

Ø22
94

115
22
21

41

31 G 1/4
25
60
63
G 1/4

Characteristics: References:
page 89 pages 90 to 92

93
Presentation Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP

Presentation
Pressure switches OsiSense XMP are switches for power circuits (direct switching),
1 with an adjustable differential.
They are used to control the pressure of water and air, up to 25 bar.

Equipment fitted to the various models


Case
Pressure switches OsiSense XMP, depending on the model, include:
2 b 3 types of case:
v bare case,
v case with On/Off knob (black): used as a switch for starting and stopping the
installation,
v case with reset knob (yellow): necessary when the safety requirements of the
system include tripping in the event of overpressure. Resetting is not automatic
3 on return to normal pressure, and it can only be achieved by manually turning the
"Reset" knob.

b 2 degrees of protection:
v IP 54,
v IP 65.

4 Decompression valve
Depending on the model, 2 types of decompression valve can be fitted to pressure
switches OsiSense  XMP:
b Straight, instant connection, decompression valve (connection by Ø 6 mm
plastic tube).
b Straight, olive connection, decompression valve (connection by Ø 6 mm plastic
or metal tube).
5
Setting
1
When setting XMP pressure switches, adjust the switching point on rising pressure
(PH) first and then the switching point on falling pressure (PB).

2 Switching point on rising pressure


6 The switching point on rising pressure (PH) is set by adjusting the screw-nut
or knurled knob 1.
Tighten either the nut or knurled knob 1 to increase the high point switching value.

Switching point on falling pressure


The switching point on falling pressure is set by adjusting screw-nut 2.
Tighten nut 2 to reduce the low point switching value (increase in differential).
7

10

References: Dimensions:
pages 96 to 103 page 105

94
Characteristics Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP

Environment characteristics
Conformity to standards e, IEC/EN 60947-4-1

Product certifications EAC


1
Ambient air temperature °C For operation: - 25...+ 70
For storage: - 40...+ 70

Fluids controlled Air, fresh water, sea water (0…+ 70°C)

Materials Case: polyamide impregnated with fibreglass


Component materials in contact with fluid: chromated zinc alloy (fluid entry),
2
canvas covered nitrile (diaphragm)

Operating position All positions

Vibration resistance 3 gn (10…500 Hz) conforming to IEC 60068-2-6

Shock resistance 50 gn, conforming to IEC 60068-2-27 3


Electric shock protection Class I conforming to IEC 60536

Degree of protection IP 54 conforming to IEC/EN 60529 or IP 65 for universal model

Operating rate Op. cycles/h y 600

Repeat accuracy < 3.5%


4
Fluid connection G 1/4, 4 x G 1/4 or G 3/8 (BSP female) conforming to NF E 03-005, ISO 228

Electrical connection 2 tapped entries for n° 13 (DIN Pg 13.5) cable gland

Contact block characteristics


Rated insulation voltage V Ui = 500 conforming to IEC/EN 60947-1
5
Rated impulse withstand voltage V U imp = 6 kV conforming to IEC/EN 60947-1

Type of contacts One 2-pole 2 NC or 3-pole 3 NC contact, snap action

6
Resistance across terminals mW y 25 conforming to NF C 93-050 method A or IEC 255-7 category 3

Terminal referencing Conforming to CENELEC EN 50013

Short-circuit protection Cartridge fuse type Am

Connection Screw clamp terminals. Minimum clamping capacity: 2 x 4 mm2

Electrical durability
Operating rate: 600 operating cycles/hour
Power
kW
Number of operating cycles
a 400 V, 3-phase a 230 V, 3-phase
7
Load factor: 0.4
1.5 1 000 000 600 000
2.2 700 000 –
3 500 000 –

10

References: Dimensions:
pages 96 to 103 page 105

95
References, Electromechanical pressure switches
characteristics OsiSense XMP, IP 54
Size 6 bar (87 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact

Fluid connection G 1/4 (female) 4 x G 1/4 (female) G 3/8 (female)

1 1

2 1 2 2 1 2
2
Adjustable range of switching point (PH) 1…6 bar (14.5…87 psi) 1…6 bar (14.5…87 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC

3 References (1) References


Switches without decompression valve
3
Switches without decompression valve
Bare case 1 XMPA06B2131 XMPA06C2131 – XMPA06B2242 XMPA06C2242
Case with reset knob 2 XMPB06B2131 – – XMPB06B2242 –
Case with On/Off knob 2 XMPC06B2131 XMPC06C2131 – XMPC06B2242 XMPC06C2242
Weight (kg) 0.430 – 0.430

4 Switches with straight decompression valve, instant connection


Bare case 1 XMPD06B2131 XMPD06C2131
Switches with straight decompression valve, instant connection
– XMPD06B2242 XMPD06C2242 4
Case with On/Off knob 2 XMPE06B2131 XMPE06C2131 XMPE06C2431 – XMPE06C2242
Weight (kg) 0.450 0.450

Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
Possible differential Min. at low setting 0.8 bar (11.6 psi) 0.8 bar (11.6 psi)

5 (subtract from PH to give PB) Min. at high setting


Max. at high setting
1.2 bar (17.4 psi)
4.2 bar (60.9 psi)
1.2 bar (17.4 psi)
4.2 bar (60.9 psi)
5
Destruction pressure 30 bar (435 psi) 30 bar (435 psi)
Mechanical life 1 million operating cycles 1 million operating cycles
Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 2 entries tapped for n° 13 cable gland, conforming 2 entries incorporating n° 13 plastic cable gland (DIN Pg 13.5)
to NF C 68-300 (DIN Pg 13.5) Clamping capacity 9 to 13 mm
6 Pressure switch type Diaphragm Diaphragm 6
(1) References for individually packaged switches. Also available packaged in lots of 10. Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
To order, add the letter C to the reference selected from above. Example: reference for lot of reference. Please consult our Customer Care Centre.
of 10 pressure switches XMPA06B2131 in one package becomes XMPA06B2131C.

Operating curves Terminal connections


XMPpppBpppp XMPpppCpppp
7 7
bar Pressure
6
PH

5
Rising pressure

1
1

3
5 1
2
4

6
4

4
PB
3

8 2

1
8
Time
Adjustable value
0
0.2 1 1.8 2 3 4 4.8 6 bar
Falling pressure

9 1 Maximum differential
2 Minimum differential 9

10 10

Accessories: Dimensions: Accessories: Dimensions:


page 104 page 105 page 104 page 105

96 97
References, Electromechanical pressure switches
characteristics (continued) OsiSense XMP, IP 54
Size 12 bar (174 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact

Fluid connection G 1/4 (female) 4 x G 1/4 (female) G 3/8 (female)

1 1

2 1 2
2 1 2
2
Adjustable range of switching point (PH) 1.3…12 bar (18.85…174 psi) 1.3…12 bar (18.85…174 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC

3 References (1)
Switches without decompression valve
References
Switches without decompression valve
3
Bare case 1 XMPA12B2131 XMPA12C2131 – XMPA12B2242 XMPA12C2242
Case with reset knob 2 XMPB12B2131 – – XMPB12B2242 –
Case with On/Off knob 2 XMPC12B2131 XMPC12C2131 XMPC12B2431 – XMPC12B2242 XMPC12C2242
Weight (kg) 0.430 0.430

4 Switches with straight decompression valve, instant connection


Bare case 1 XMPD12B2131 XMPD12C2131
Switches with straight decompression valve, instant connection
– XMPD12C2431 XMPD12B2242 XMPD12C2242
4
Case with On/Off knob 2 XMPE12B2131 XMPE12C2131 XMPE12B2431 XMPE12C2431 XMPE12B2242 XMPE12C2242
Weight (kg) 0.450 0.450
Switches with straight decompression valve, olive connection Switches with straight decompression valve, olive connection
Case with On/Off knob 2 XMPR12B2131 XMPR12C2131 –

5 Weight (kg) 0.450 –


5
Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
Possible differential Min. at low setting 1 bar (14.5 psi) 1 bar (14.5 psi)
(subtract from PH to give PB) Min. at high setting 1.7 bar (24.6 psi) 1.7 bar (24.6 psi)
Max. at high setting 8.4 bar (121.8 psi) 8.4 bar (121.8 psi)

6 Destruction pressure
Mechanical life
30 bar (435 psi)
1 million operating cycles
30 bar (435 psi)
1 million operating cycles
6
Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 2 entries tapped for n° 13 cable gland, conforming 2 entries incorporating n° 13 plastic cable gland (DIN Pg 13.5)
to NF C 68-300 (DIN Pg 13.5) Clamping capacity 9 to 13 mm
Pressure switch type Diaphragm Diaphragm
(1) References for individually packaged switches. Also available packaged in lots of 10. Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
To order, add the letter C to the reference selected from above. Example: reference for lot of reference. Please consult our Customer Care Centre.
7 of 10 pressure switches XMPA12B2131 in one package becomes XMPA12B2131C.
7
Operating curves Terminal connections
bar Pressure XMPpppBpppp XMPpppCpppp
12
PH
Rising pressure

5
3

1
1

3
10

8 8
2
8

6
4

4
PB
6

2 Time
1.3

9 9
0
0.3 2 3.6 4 6 8 10 10.3 bar
Falling pressure

1 Maximum differential
2 Minimum differential

10 10

Accessories: Dimensions: Accessories: Dimensions:


page 104 page 105 page 104 page 105

98 99
References, Electromechanical pressure switches 
characteristics (continued) OsiSense XMP, IP 54
Size 25 bar (362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact

Fluid connection G 1/4 (female) G 1/4 (female)

1 1

2 1 2 1 2
2
Adjustable range of switching point (PH) 3.5…25 bar (50.75…362.5 psi) 3.5…25 bar (50.75…362.5 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC

3 References References 3
Switches without decompression valve Switches without decompression valve
Bare case 1 XMPA25B2131 XMPA25C2131
Case with reset knob 2 XMPB25B2131 –
Case with On/Off knob 2 XMPC25B2131 XMPC25C2131
Weight (kg) 0.650 0.650
4 Switches with straight decompression valve, olive connection
Case with On/Off knob 2 XMPR25B2131
Switches with straight decompression valve, olive connection
XMPR25C2131
4
Weight (kg) 0.670 0.670

Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
Possible differential Min. at low setting 3.4 bar (49.3 psi) 3.4 bar (49.3 psi)

5 5
(subtract from PH to give PB) Min. at high setting 4.5 bar (65.2 psi) 4.5 bar (65.2 psi)
Max. at high setting 20 bar (290 psi) 20 bar (290 psi)

Destruction pressure 100 bar (1450 psi) 100 bar (1450 psi)
Mechanical life 1 million operating cycles 1 million operating cycles
Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
Pressure switch type Diaphragm Diaphragm

6 Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
of reference. Please consult our Customer Care Centre.
6
Operating curves Terminal connections
bar XMPpppBpppp XMPpppCpppp
30
Rising pressure

5
3

3
7 7
25

20 1

6
4

4
15 2

10

8 8
3.5

0
0.1 5 10 15 20.5 25 30 bar
Falling pressure

1 Maximum differential
2 Minimum differential

9 9

10 10

Accessories: Dimensions: Accessories: Dimensions:


page 104 page 105 page 104 page 105

100 101
References, Electromechanical pressure switches
characteristics (continued) OsiSense XMP, IP 65
Sizes 6 to 25 bar (87 to 362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact

Fluid connection G 1/4 (female) 4 x G 1/4 (female)

1 1

2 2
Adjustable range of switching point (PH) 1…6 bar (14.5…87 psi) 1.3…12 bar (18.85…174 psi) 3.5…25 bar (50.75…362.5 psi) 1…6 bar (14.5…87 psi) 1.3…12 bar (18.85…174 psi) 3.5…25 bar (50.75…362.5 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC

3 References References
3
Switches with straight decompression valve, olive connection Switches with straight decompression valve, olive connection
Case with On/Off knob XMPR06B2133 XMPR06C2133 XMPR12B2133 XMPR12C2133 XMPR25B2133 XMPR25C2133 XMPR06B2433 XMPR06C2433 XMPR12B2433 XMPR12C2433 XMPR25B2433 XMPR25C2433
Weight (kg) 0.450 0.670 0.450 0.670

Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
4 Possible differential Min. at low setting 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 4
(subtract from PH Min. at high setting 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi) 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi)
to give PB)
Max. at high setting 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi) 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi)

Destruction pressure 30 bar (435 psi) 100 bar (1450 psi) 30 bar (435 psi) 100 bar (1450 psi)
Mechanical life 1 million operating cycles 1 million operating cycles

5 Cable entry
Adjustment of high setting point (PH)
2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
By screw-nut
2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
By screw-nut
5
Pressure switch type Diaphragm Diaphragm
Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
of reference. Please consult our Customer Care Centre.

Operating curves Terminal connections


6 XMPR06ppppp XMPR12ppppp XMPR25ppppp XMPpppBpppp XMPpppCpppp 6
bar bar Pressure
bar

5
3

3
6 12 30
PH
Rising pressure

Rising pressure

Rising pressure

5 1 10
1 25
2

6
4

4
2 20 1
4 8

7 7
PB
3 15 2
6

2 4 10

1 2 Time
3.5
1.3
0 0 0
0.2 1 1.8 2 3 4 4.8 6 bar Adjustable value
0.3 2 3.6 4 6 8 10 10.3 bar 0.1 5 10 15 20.5 25 30 bar

8 Falling pressure Falling pressure Falling pressure


8
1 Maximum differential 1 Maximum differential 1 Maximum differential
2 Minimum differential 2 Minimum differential 2 Minimum differential

9 9

10 10

Accessories: Dimensions: Accessories: Dimensions:


page 104 page 105 page 104 page 105

102 103
References Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP
Accessories and replacement parts

References
Description Reference Weight
1 Fixing bracket XMAZL001
kg
0.035

XMAZL001
Knurled adjustment knob, Ø 36 mm XMPMDR01 0.010
2 fits over adjustment screws to facilitate setting

XMPMDR01

13P cable gland With anti pull-out ring DE9PM1201 0.005


(for cable Ø 6…9 mm)

3
DE9PM1201
Without anti pull-out ring DE9PM1202 0.005
(for cable Ø 6…9 mm)

4
With anti pull-out ring DE9PM1203 0.005
(for cable Ø 9…12.5 mm)
DE9PM1202

5
Description For pressure Sold in lots of Unit Weight
switch reference kg
Diaphragms Size 6 bar 50 XMPZ31 0.005

6
XMPZ3p Size 25 bar 50 XMPZ33 0.005

10

104
Dimensions Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP
Accessories and replacement parts

Dimensions
XMPp06ppppp and XMPp12ppppp
Fluid connection G 1/4 or G 3/8 (female)
Without decompression valve
Fluid connection 4 x G 1/4 (female)
Without decompression valve
With straight, instant
connection, decompression
1
valve

19

19
2

106
106

119
(1) (1)

13
43.5
58 =
30.5
=
43.5
58 =
30.5
= 22.5 3
97.5 57 97.5 57
With straight, olive connection,
r = 63 (2) decompression valve
r = 63 (2)

D
4
A C A

119
B
5
13
ØA = G 1/4 or G 3/8 (female) ØA = ØB = ØC = ØD = G 1/4 (female)
(1) 2 tapped entries for n° 13 cable gland 22.5
(2) Minimum clearance zone for screwing-on pressure switch at point A

XMPp25ppppp Fixing bracket XMAZL001

6
Fluid connection G 1/4 or 4 x G 1/4 (female) With straight, olive connection,
Without decompression valve decompression valve
3.6
19

19
52
40

24.75

7
126

136

12.5 38
18.5 54

(1)

43.5
58 =
30.5
=
22.5 8
97.5 57
r = 63 (2)

9
C A

XMPp25p21pp: ØA only = G 1/4 (female)


10
XMPp25p24pp: ØA = ØB = ØC = ØD = G 1/4 (female)
(1) 2 tapped entries for n° 13 cable gland
(2) Minimum clearance zone for screwing-on pressure switch
at point A

105
Index Product reference index

A FSG2NE 91 XMLA020C2S12 44 XMLB004A2C11 37 XMLB500N2S12 65


ACW1M119012 76 FSG9 91 XMLA020P2C11 44 XMLB004A2S12 37 XMLBL05R2S12 23
ACW1M129012 76 FSG9NE 91 XMLA020P2S12 44 XMLB004A2S13 37 XMLBL05S2S12 23
ACW2M119012 77 FTG2 90 XMLA035A2C11 48 XMLB004B2C11 37 XMLBL35P2C11 26
ACW2M129012 77 FTG2NE 90 XMLA035A2S12 48 XMLB004B2S12 37 XMLBL35P2S12 26
ACW3M119012 76 FTG9 90 XMLA035A2S13 48 XMLB004C2C11 37 XMLBL35R2C11 26
ACW3M129012 76 FTG9NE 90 XMLA035B2C11 48 XMLB004C2S12 37 XMLBL35R2S12 26
ACW4M119012 76 FYG22 92 XMLA035B2S12 48 XMLB010A2C11 41 XMLBL35R2S13 26
ACW4M129012 76 FYG22NE 92 XMLA035C2C11 48 XMLB010A2S12 41 XMLBL35S2C11 26
ACW5M119012 76 FYG32 92 XMLA035C2S12 48 XMLB010A2S13 41 XMLBL35S2S12 26
ACW5M129012 76 FYG32NE 92 XMLA035P2C11 48 XMLB010B2C11 41 XMLBM02T2C11 19
ACW6M119012 77 XMLA035P2S12 48 XMLB010B2S12 41 XMLBM02T2S12 19
ACW6M129012 77 X
XMLA070D2C11 52 XMLB010B2S13 41 XMLBM02T2S13 19
ACW7M119012 77 XMAH06L2135 85
XMLA070D2S12 52 XMLB010C2C11 41 XMLBM02V2C11 19
ACW7M129012 77 XMAH06L2435 85
XMLA070D2S13 52 XMLB010C2S12 41 XMLBM02V2S12 19
ACW8M119012 77 XMAH12L2135 85
XMLA070E2C11 52 XMLB010C2S13 41 XMLBM02V2S13 19
ACW8M129012 77 XMAH12L2435 85
XMLA070E2S12 52 XMLB010P2C11 41 XMLBM03R2S12 22
ACW9M119012 77 XMAH25L2135 85
XMLA070E2S13 52 XMLB010P2S12 41 XMLBM03R2S13 22
ACW9M129012 77 XMAH25L2435 85
XMLA070N2C11 52 XMLB020A2C11 45 XMLBM05A2C11 24
ACW10M119012 77 XMAV06L2135 85
XMLA070N2S12 52 XMLB020A2S12 45 XMLBM05A2S12 24
ACW10M129012 77 XMAV06L2435 85
XMLA160D2C11 56 XMLB020A2S13 45 XMLBM05A2S13 24
ACW20M119012 77 XMAV12L2135 85
XMLA160D2S12 56 XMLB020B2C11 45 XMLBM05B2C11 24
ACW20M129012 77 XMAV12L2435 85
XMLA160D2S13 56 XMLB020B2S12 45 XMLBM05B2S12 24
ACW21M119012 76 XMAV25L2135 85
XMLA160E2C11 56 XMLB020B2S13 45 XMLBM05C2C11 24
ACW21M129012 76 XMAV25L2435 85
XMLA160E2S12 56 XMLB020C2C11 45 XMLBM05C2S12 24
ACW22M119012 77 XMAZL001 86
104 XMLA160E2S13 56 XMLB020C2S12 45 XMLBM05P2C11 24
ACW22M129012 77
XMLA001R2C11 30 XMLA160N2C11 56 XMLB020P2C11 45 XMLBM05P2S12 24
ACW23M119012 76
XMLA001R2S12 30 XMLA160N2S12 56 XMLB020P2S12 45 XMLBS02B2S12 34
ACW23M129012 76
XMLA001S2C11 30 XMLA300D2C11 60 XMLB035A2C11 49 XMLBS04B2S12 37
ACW24M119012 76
XMLA001S2S12 30 XMLA300D2S12 60 XMLB035A2S12 49 XMLBS10A2S12 41
ACW24M129012 76
XMLA001S2S13 30 XMLA300D2S13 60 XMLB035A2S13 49 XMLBS20A2S12 45
ACW25M119012 76
ACW25M129012 76 XMLA002A2C11 33 XMLA300E2C11 60 XMLB035B2C11 49 XMLBS35R2S12 27
ACW26M119012 77 XMLA002A2S12 33 XMLA300E2S12 60 XMLB035B2S12 49 XMLC001R2S12 32
ACW26M129012 77 XMLA002A2S13 33 XMLA300E2S13 60 XMLB035C2C11 49 XMLC001R2S13 32
ACW27M129012 77 XMLA002B2C11 33 XMLA300N2C11 60 XMLB035C2S12 49 XMLC001S2S12 32
ACW28M119012 77 XMLA002B2S12 33 XMLA300N2S12 60 XMLB035P2S12 49 XMLC001S2S13 32
ACW28M129012 77 XMLA002C2C11 33 XMLA500D2C11 64 XMLB070D2C11 53 XMLC002B2S12 35
ACW29M129012 77 XMLA002C2S12 33 XMLA500D2S12 64 XMLB070D2S12 53 XMLC002B2S13 35
ADW3M119012 78 XMLA004A2C11 36 XMLA500D2S13 64 XMLB070D2S13 53 XMLC004B2S12 38
ADW3M129012 78 XMLA004A2S12 36 XMLA500E2C11 64 XMLB070E2C11 53 XMLC004B2S13 38
ADW4M119012 78 XMLA004A2S13 36 XMLA500E2S12 64 XMLB070E2S12 53 XMLC004C2S12 38
ADW4M129012 78 XMLA004B2C11 36 XMLA500E2S13 64 XMLB070N2C11 53 XMLC004C2S13 38
ADW5M119012 79 XMLA004B2S12 36 XMLA500N2C11 64 XMLB070N2S12 53 XMLC010B2S12 42
ADW5M129012 79 XMLA004C2C11 36 XMLA500N2S12 64 XMLB160D2C11 57 XMLC010B2S13 42
ADW6M119012 79 XMLA004C2S12 36 XMLAM01T2C11 18 XMLB160D2S12 57 XMLC010C2S12 42
ADW6M129012 79 XMLA004P2C11 36 XMLAM01T2S12 18 XMLB160D2S13 57 XMLC010C2S13 42
ADW7M119012 78 XMLA004P2S12 36 XMLAM01V2C11 18 XMLB160E2C11 57 XMLC020B2S12 46
ADW7M129012 78 XMLA010A2C11 40 XMLAM01V2S12 18 XMLB160E2S12 57 XMLC020B2S13 46
ADW7S1M129012 79 XMLA010A2S12 40 XMLAM01V2S13 18 XMLB160N2C11 57 XMLC020C2S12 46
ADW23M129012 78 XMLA010A2S13 40 XMLB001P2S12 31 XMLB160N2S12 57 XMLC020C2S13 46
ADW24M129012 78 XMLA010B2C11 40 XMLB001R2C11 31 XMLB300D2C11 61 XMLC035B2S12 50
ADW25M129012 79 XMLA010B2S12 40 XMLB001R2S12 31 XMLB300D2S12 61 XMLC035B2S13 50
ADW26M129012 79 XMLA010C2C11 40 XMLB001R2S13 31 XMLB300D2S13 61 XMLC035C2S12 50
ADW27M129012 78 XMLA010C2S12 40 31 XMLB300E2C11 61 XMLC035C2S13 50
XMLB001S2C11
XMLA010C2S13 40 XMLB001S2S12 31 XMLB300E2S12 61 XMLC070D2S12 54
D
XMLA010P2C11 40 XMLB001S2S13 31 XMLB300N2C11 61 XMLC070D2S13 54
DE9PM1201 86
104 XMLA010P2S12 40 XMLB002A2C11 34 XMLB300N2S12 61 XMLC070E2S12 54
DE9PM1202 86 XMLA020A2C11 44 XMLB002A2S12 34 XMLB500D2C11 65 XMLC070N2S12 54
104 44 34 XMLB500D2S12 65 XMLC160D2S12 58
XMLA020A2S12 XMLB002A2S13
DE9PM1203 86
XMLA020A2S13 44 XMLB002B2C11 34 XMLB500D2S13 65 XMLC160D2S13 58
104
XMLA020B2C11 44 XMLB002B2S12 34 XMLB500E2C11 65 XMLC160E2S12 58
F XMLA020B2S12 44 XMLB002C2C11 34 XMLB500E2S12 65 XMLC160N2S12 58
FSG2 91 XMLA020C2C11 44 XMLB002C2S12 34 XMLB500N2C11 65 XMLC300D2S12 62

106
Index (continued) Product reference index

XMLC300E2S12 62 XMPA12B2242 99 XMXA12L2435 84


XMLC300N2S12 62 XMPA12C2131 98 XMXA25L2135 84
XMLC500D2S12 66 XMPA12C2242 99 XMXA25L2435 84
XMLC500N2S12 66 XMPA25B2131 100 XZCC43FCP40B 68
XMLCL35R2S12 28 XMPA25C2131 101
XMLCL35S2S12 28 XMPB06B2131 96
XMLCL35S2S13 28 XMPB06B2242 97
XMLCM02T2S12 20 XMPB12B2131 98
XMLCM02V2S12 20 XMPB12B2242 99
XMLCM05B2S12 25 XMPB25B2131 100
XMLCM05C2S12 25 XMPC06B2131 96
XMLCS02B2S12 35 XMPC06B2242 97
XMLCS02B2S13 35 XMPC06C2131 96
XMLCS04B2S12 38 XMPC06C2242 97
XMLCS10A2S12 42 XMPC12B2131 98
XMLCS20A2S12 46 XMPC12B2242 99
XMLCS35R2S12 28 XMPC12B2431 99
XMLCS35R2S13 28 XMPC12C2131 98
XMLD004B1S12 39 XMPC12C2242 99
XMLD010B1S11 43 XMPC25B2131 100
XMLD010B1S12 43 XMPC25C2131 101
XMLD010C1S11 43 XMPD06B2131 96
XMLD020B1S12 47 XMPD06B2242 97
XMLD020B1S13 47 XMPD06C2131 96
XMLD020C1S12 47 XMPD06C2242 97
XMLD035B1S12 51 XMPD12B2131 98
XMLD070D1S12 55 XMPD12B2242 99
XMLD070D1S13 55 XMPD12C2131 98
XMLD070N1S12 55 XMPD12C2242 99
XMLD160D1S12 59 XMPD12C2431 99
XMLD160D1S13 59 XMPE06B2131 96
XMLD160E1S12 59 XMPE06C2131 96
XMLD300D1S12 63 XMPE06C2242 97
XMLD300D1S13 63 XMPE06C2431 97
XMLD300E1S12 63 XMPE12B2131 98
XMLD300N1S12 63 XMPE12B2242 99
XMLD500D1S12 67 XMPE12B2431 99
XMLDL35R1S12 29 XMPE12C2131 98
XMLDM02T1S12 21 XMPE12C2242 99
XMLDM02V1S12 21 XMPE12C2431 99
XMLZA024 68 XMPMDR01 104
XMLZA120 68 XMPR06B2133 102
XMLZB024 68 XMPR06B2433 103
XMLZB120 68 XMPR06C2133 102
XMLZL001 68 103
XMPR06C2433
XMLZL002 68 98
XMPR12B2131
XMLZL003 68 102
XMPR12B2133
86
XMPR12B2433 103
XMLZL004 68
XMPR12C2131 98
XMLZL005 68
XMPR12C2133 102
XMLZL006 68
XMPR12C2433 103
XMLZL010 68
XMPR25B2131 100
XMLZL011 68
XMPR25B2133 102
XMLZL012 68
XMPR25B2433 103
XMLZL013 68
XMPR25C2131 101
XMLZL014 68
XMPR25C2133 102
XMLZL015 68
68 XMPR25C2433 103
XMLZZ024
68 XMPZ31 86
XMLZZ120
104
XMPA06B2131 96
XMPZ33 86
XMPA06B2242 97 104
XMPA06C2131 96 XMXA06L2135 84
XMPA06C2242 97 XMXA06L2435 84
XMPA12B2131 98 XMXA12L2135 84

107
Schneider Electric Industries SAS www.tesensors.com
Head Office The information provided in this documentation contains general descriptions and/or technical
35, rue Joseph Monier characteristics of the performance of the products contained herein. This documentation is not
F-92500 Rueil-Malmaison intended as a substitute for and is not to be used for determining suitability or reliability of these
France products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
DIA4ED2150201EN

relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein.

Design: Schneider Electric


Photos: Schneider Electric

June 2016 - V2.0