Contents Electromechanical pressure and
vacuum switches OsiSense XM
For controlling the pressure of air, water, hydraulic oils and corrosive fluids
bb Presentation and setting......................................................................... page 74
bb Characteristics........................................................................................ page 75
bb References
vv OsiSense ACW, sizes from: 0.7 to 131 bar................................... pages 76 and 77
vv OsiSense ADW, sizes from: 69 to 340 bar ................................... pages 78 and 79
vv Dimensions.................................................................................. pages 80 and 81
1
Selection guide Electromechanical sensors
for pressure control
OsiSense XM
Fluids controlled Air, water, hydraulic oils, corrosive fluids, viscous products Air, water, hydraulic oils, corrosive fluids, Air, hydraulic oils, corrosive fluids
viscous products
Type of operation Detection of a single Regulation between 2 thresholds (adjustable differential) Dual stage switches Regulation between 2 thresholds (adjustable differential)
threshold Detection at each threshold (fixed differential)
(fixed differential)
Fluid characteristics Air, fresh water, corrosive fluids, viscous products, up to 160°C Air, fresh water, corrosive fluids, viscous products, Air, oils and other non corrosive fluids Oils and other fluids (- 25…+ 120 °C)
Sea water, up to 30 °C, depending on model up to 160°C (- 73…+ 125°C)
Sea water, up to 30 °C, depending on model Only oils, including synthetic oils,
(- 30…+ 125 °C), depending on model
Sizes - 1 bar…500 bar (- 14.5 psi…7250 psi) - 1 bar…500 bar (- 14.5 psi…7250 psi) 0.7 bar…131 bar (10.15 psi…1900 psi) 69 bar…340 bar (1000 psi…4930 psi)
Type of contacts 1 CO single-pole, snap action 2 CO single-pole, simultaneous, 2 CO single-pole, staggered, snap action 1 CO or 2 CO single-pole, snap action
snap action
Degree of protection IP 66: switches with terminal connections IP 66: switches with terminal IIP 66: switches with terminal connections IP 65
IP 65: switches with connector connections
Fluid connection G 1/4 (female) G 1/4 (female) G 1/4 (femelle) G 3/8 (female)
1/4” - 18 NPTF (female) 1/4” - 18 NPTF (female)
G 1¼” (female) for viscous products G 1¼” (female) for viscous products
Pages 18 to 67 18 to 67 76 and 77 78 and 79
Other versions Electromechanical pressure and vacuum switches with alternative tapped cable entries and/
or fluid entries: NPT etc. Please consult our Customer Care Centre.
2 3
Selection guide (continued) Electromechanical sensors
for pressure control
OsiSense XM
Type of operation Regulation between 2 thresholds (adjustable differential) Detection of a single Regulation between 2 thresholds (adjustable differential)
threshold (fixed differential)
Fluid characteristics Air, fresh water, sea water (0…+ 70°C) Fresh water, sea water (0…+ 70°C) Air, fresh water, sea water
(0…+ 70°C)
Sizes 6 bar, 12 bar and 25 bar (87 psi, 174 psi and 362.5 psi) 4.6 bar (66.7 psi) 7 bar (101.5 psi) 10.5 bar (152.3 psi) 6 bar, 12 bar and 25 bar
(87 psi, 174 psi and 362.5 psi)
Dimensions of case (mm) Width x height x depth 57 x 78 x 97.5 73 x 73 x 102 72 x 77 x 106 72 x 73 x 102 57 x 78 x 97.5
Fluid connection G 1/4 or 4 x G 1/4 (female), depending on model G 1/4 or R 1/4 (female or male) G 1/4, G 3/8 or 4 x G 1/4
(female), depending on model
Type reference XMX XMA FTGp, FTGpNE FSGp, FSGpNE FYG22, FYG22NE FYG32, FYG32NE XMP
Other versions Electromechanical pressure switches with alternative tapped cable entries and/or fluid entries:
ISO, NPT, etc. Please consult our Customer Care Centre.
4 5
General Electromechanical pressure
and vacuum switches
OsiSense XM
Function
The function of pressure and vacuum switches is the control or regulation of
pressure or vacuum levels in hydraulic or pneumatic systems.
They transform the pressure change into a digital electrical signal when the preset
switching points are reached.
13
11
13
11
differential
PB
14
12
14
12
Time 1 2
1 2 1 2
11
13
11
differential
PB
14
12
14
12
Time 1 2
1 2 1 2
11
23
21
PB2 spread
ential
1
PH1
Fixed
14
12
24
22
PB1 differential
13
11
23
21
Time
2
1 2 3 4 1 2 3 4
14
12
24
22
11
23
21
12
24
22
13
11
23
21
4
14
12
24
22
6
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM
13
11
13
11
14
12
14
12
PH
Fixed
differential 1 2
PB
1 2 1 2
Vacuum
13
11
13
11
PH
14
12
14
12
Adjustable
differential
1 2
PB
1 2 1 2
Vacuum
Detection of 2 thresholds
The dual stage switches, for detection at each threshold, have an adjustable high
point setting for each stage (PH1 and PH2). Both of these points can be
independently adjusted.
For both stages, the differential between the high point and the low point (PH1 - PB1
and PH2 - PB2) depends upon the natural characteristics of the switch. It is not
adjustable.
Time Example: contact
schematics of XMLD
PH1
13
11
23
21
Fixed
PB1 differ- Adjustable 1
ential spread
14
12
24
22
PH2
Fixed
13
11
23
21
differential
PB2 2
1 2 3 4 1 2 3 4
14
12
24
22
Vacuum
11
23
21
12
24
22
13
11
23
21
4
14
12
24
22
7
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM
Terminology
Operating range
The difference between the minimum low point (PB) and the maximum high point
(PH) setting values.
Size
Pressure switches and vacuum-pressure switches (vacu-pressure switches)
Maximum value of the operating range.
Vacuum switches
Minimum value of the operating range.
Vacuum switches
The lower vacuum setting at which the vacuum switch will reset the contacts on
rising pressure.
Differential
The difference between the switching point on rising pressure (PH) and the switching
point on falling pressure (PB).
Spread
6 For dual stage switches, the spread indicates the difference between the 2 switching
points on rising pressure (PH2 and PH1) and, for vacuum switches, the difference
between the 2 switching points on falling pressure (PB2 and PB1).
8
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM
Terminology (continued)
Repeat accuracy (R)
The tolerance between two consecutive
switching operations.
R
Drift (F)
The tolerance of the switching point
throughout the entire service life
F of the switch.
Accidental overpressure
bar This is an accidental pressure surge of
300 very short duration (a few milliseconds).
50
0
6
0 50 100 150
ms
Its minimum value is at least equal to 1.25 times the switch size.
Destruction pressure
The maximum guaranteed pressure that the switch will withstand before its destruction,
i.e. bursting, rupturing, component failure, etc.
9
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM
Application range of pressure and vacuum switches XML, XMA and XMX, for control circuits
On standard loads
Continuous duty, frequent switching.
Insulation voltage limit
V
500
240 3
200
150
4
120
100
60
Inductive loads
24
20
1
15
6 2
10
5 I
1 mA 2 mA 3 mA 6 mA 10 mA 1A 1,5 A 2A 3A 6A 10 A
10
General (continued) Electromechanical pressure
and vacuum switches
OsiSense XM
7 6.5
7 6
7
5
0.6 1 1.5
XMLA010ppppp XMLA020ppppp XMLA035ppppp
Differential = 0.5 bar Differential = 1 bar Differential = 2 bar
Select an XMLA010ppppp (the lowest size)
25 45
20
35
12
12
1
1.5
XMLA020ppppp XMLA035ppppp
Permissible accidental Permissible accidental
overpressure = 45 bar overpressure = 80 bar
Select an XMLA035ppppp (the highest size) 6
Main criterion: repeat accuracy, precision and minimum drift
Example: for a selected high point (PH) of 18 bar
20 bar 35 bar As a general rule, working
18 at the upper or lower limits
of the operating range
18
should be avoided.
1 1.5
XMLA020ppppp XMLA035ppppp
Adjustable from 1 to 20 bar Adjustable from 1.5 to 35 bar
Select an XMLA035ppppp
1 Pa = 1.45 x 10-4 1.0197 x 10-5 10-5 9.8695 x 10-6 7.5 x 10-3 0.10197 1
11
Operating curves Electromechanical pressure
and vacuum switches
Fixed differential switches, for detection
of a single threshold
Rising pressure
Adjustment
range of the Defined by the difference between the
1 high point
+
Maxi
minimum and maximum high point (PH)
setting values.
2 Mini
higher point (PH1 or PH2) is fixed and
cannot be adjusted.
– 0
0 Low point (PB) Falling
range pressure
3 rising +
PH
pressure or vacuum switch will actuate
the contacts on rising pressure.
pressure
(PH) Adjustable throughout the range on
rising pressure.
4
– 0
0 Falling pressure
6 – 0
0 PB
Falling pressure
10 0
v the differential will be 40 - 28 = 12 bar.
03 20 28 40 60 bar
PB Falling pressure
12
Operating curves Electromechanical pressure
and vacuum switches
Adjustable differential switches, for regulation
between 2 thresholds
Rising pressure
Adjustment
range of the Defined by the difference between the
+
high point Maxi
minimum and maximum high point (PH)
setting values. 1
Mini
2
– 0
0 Low point (PB) Falling
range pressure
4
– 0
0 Falling pressure
– 0
6
0 PB' PB"
Falling pressure
PH 1 2
PH - PB" = minimum differential
7
The difference between the switching
PH – PB" point on rising pressure (PH) and the
PH – PB'
PB" switching point on falling pressure (PB).
PB'
Note: the low point can be set at any value
– 0
between PB' and PB".
8
0 PB' PB"
Falling pressure
9
which the contact will change state on
PH 22 1 2 rising pressure).
20 b It can be seen that the switching
point on falling pressure (PB) can be
between 4 and 19 bar inclusive
10 (set value at which the contact will
return to its original state).
10
Conclusion:
1 Maximum differential 0 v the maximum differential will be:
0 4 10 19 20 30 bar
2 Minimum differential PB' PB" 22 - 4 = 18 bar,
Falling pressure v the minimum differential will be:
22 - 19 = 3 bar.
13
Operating curves Electromechanical pressure
(switching points on rising and vacuum switches
pressure) Dual stage, fixed differential switches,
for detection at each threshold
Rising pressure
Adjustment
ranges of the Defined by the difference between the
1
+ minimum and maximum high point
switching setting values of each stage (PH1 and
points PH1
Adjustment range of
1 2 PH2).
2
– 0
0 Adjustment range Falling
of high point PH1 pressure
4 – 0
0
Falling pressure
PH1"
PH1'
6 – 0
0 PH1' PH1"
Falling pressure
8 – 0
0 PH1' PH1"
Falling pressure
14
Operating curves Electromechanical pressure
(switching points on falling and vacuum switches
pressure) Dual stage, fixed differential switches,
for detection at each threshold
of switching point
Adjustable range
For a high set point (PH), the lower
point (PB) is fixed and cannot be
adjusted.
Mini
For a low set point (PB1 or PB2), the
higher point (PH1 or PH2) is fixed and 2
– 0 cannot be adjusted.
0 Low point (PB) Falling
range pressure
– 0
4
0 Falling pressure
– 0
0 PB
6
Falling pressure
Differential Rising pressure
PH - PB = natural differential
+ The difference between the switching
PH point on rising pressure (PH) and the
PH – PB
switching point on falling pressure (PB),
for each stage. 7
This point is not adjustable and therefore,
PB the value of the differential is fixed.
It is the natural differential of the switch
(contact differential, friction, etc.),
8
– 0 for each of its 2 stages.
0 PB
Falling pressure
15
Presentation Electromechanical pressure
and vacuum switches
OsiSense XM
OsiSense XML for control circuits
Presentation
OsiSense XML pressure and vacuum switches are designed for use in control
circuits.
They are used to control the pressure of hydraulic oils, fresh water, sea water, air,
steam, corrosive fluids or viscous products, up to 500 bar.
OsiSense XMLA pressure and vacuum switches have a fixed differential and are
used for detection of a single threshold. They incorporate 1 CO single-pole contact.
OsiSense XMLB pressure and vacuum switches have an adjustable differential and
are used for regulation between 2 thresholds. They incorporate 1 CO single-pole
contact.
OsiSense XMLC pressure and vacuum switches have an adjustable differential and
are used for regulation between 2 thresholds. They incorporate 2 CO single-pole
contacts.
OsiSense XMLD pressure and vacuum switches are dual stage switches, each
stage with a fixed differential, and are used for detection at each threshold. They
incorporate 2 CO single-pole contacts (one per stage).
Setting
When setting OsiSense XML pressure and vacuum switches, adjust the switching
point on rising pressure (PH) first and then the switching point on falling pressure
(PB).
OsiSense XMLB and XMLC pressure and vacuum switches with adjustable
differential
1 2 Switching point on rising pressure
The switching point on rising pressure (PH) is set by adjusting the red screw 1.
OsiSense XMLD dual stage pressure and vacuum switches with fixed
differential for each threshold
1 2 Switching point on rising pressure of stage 1 and stage 2
The first stage switching point on rising pressure (PH1) is set by adjusting the red
screw 1.
The second stage switching point on rising pressure (PH2) is set by adjusting the
blue screw 2.
16
Characteristics Electromechanical pressure
and vacuum switches
OsiSense XM
OsiSense XML for control circuits
Environment characteristics
Conformity to standards e, IEC/EN 60947-5-1, UL 508, CSA C22-2 no. 14
Product certifications All products: UL, CSA, EAC
XMLA and XMLB: CCC, BV, LROS
Protective treatment Standard version “TC”. Special version “TH”
Ambient air temperature °C For operation: -25…+70. For storage: -40…+70
Fluids or products controlled Hydraulic oils, air, fresh water, sea water
Steam, corrosive fluids, viscous products, depending on model
Materials Case: zinc alloy
Component materials in contact with fluid: see pages 72 and 73
Operating position All positions
Vibration resistance 4 gn (30...500 Hz) conforming to IEC 60068-2-6 except XMLpL35ppppp,
XMLp001ppppp and XMLBM03ppppp: 2 gn
Shock resistance 50 gn conforming to IEC 60068-2-27 except XMLpL35ppppp, XMLp001ppppp
and XMLBM03ppppp: 30 gn
Electric shock protection Class I conforming to IEC 1140, IEC 536 and NF C 20-030
Degree of protection Screw terminal models: IP 66 conforming to IEC/EN 60529
Connector models: IP 65 conforming to IEC/EN 60529
Operating rate Op. Piston version switches: y 60 (for temperatures > 0 °C)
cycles/ Diaphragm version switches: y 120 (for temperatures > 0 °C)
min
Repeat accuracy < 2%
Fluid connection G 1/4 (BSP female) conforming to NF E 03-005, ISO 228 or 1/4”-18 NPTF
For sizes u 300 bar, use the gasket supplied with the product.
This gasket is also available as a separate part, reference XMLZL010.
Electrical connection Screw terminal models: ISO M20 x 1.5 or 1/2” NPT tapped entry
For an entry tapped for no.13 (DIN Pg 13.5) cable gland, replace the last number of
the reference with 1 (for example, XMLA010A2S12 becomes XMLA010A2S11)
Connector models: EN 175301-803-A (ex-DIN 43650) connector
3 2
2
48 V 230 V 48 V
1
1
0,5
0,5
230 V 110 V
0,2
0,1
110 V
0,1
0,3 0,5 1 2 5 10 20 0,5 1 2 3 4 5 10
Current in A Current in A
DC supply c DC supply c
Power broken in W Power broken in W for 5 million operating
for 1 million operating cycles cycles
Voltage V 24 48 120 Voltage V 24 48 120
o W 31 29 26 o W 10 7 4
17
References, Electromechanical vacuum switches
characteristics OsiSense XML
Size - 1 bar (- 14.5 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
Adjustable range of switching point (PB) - 0.28…- 1 bar (- 4.06…- 14.5 psi)
(Falling pressure)
Electrical connection DIN connector Terminals
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLAM01V2C11 XMLAM01V2S12 XMLAM01V2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLAM01T2C11 XMLAM01T2S12 –
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 0.685 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.24 bar (3.48 psi)
(add to PB At high setting (3) 0.24 bar (3.48 psi)
to give PH)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLAM01V2S12
becomes XMLAM01V2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.05 bar (± 0.72 psi).
Operating curves Connection
Terminal model
Rising pressure
13
11
12
-0.2
-0.28
1 → 11 and 13
-0.8 Vacuum 2 → 12
1 2
3 3 → 14
-1
bar
–– Adjustable value
--- Non adjustable value
Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
18
References, Electromechanical vacuum switches
characteristics OsiSense XM, OsiSense XML
Size - 1 bar (- 14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
Adjustable range of switching point (PB) - 0.14…- 1 bar (- 2.03…- 14.5 psi)
(Falling pressure)
Electrical connection DIN connector Terminals
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLBM02V2C11 XMLBM02V2S12 XMLBM02V2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLBM02T2C11 XMLBM02T2S12 XMLBM02T2S13
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 1.015 1.030 1.030
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.13 bar (1.88 psi)
(add to PB Min. at high setting (3) 0.13 bar (1.88 psi)
to give PH)
Max. at high setting 0.8 bar (11.6 psi)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBM02V2S12
becomes XMLBM02V2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves Connection
Terminal model
Rising pressure
13
11
12
-0.14
-0.2
PH
-0.4 Connector model
2 Vacuum switch connector pin view
-0.6 PB
1 → 11 and 13
Falling pressure
Vacuum 2 → 12
1 1 2 3 → 14
-0.8
3
-1
bar
19
References, Electromechanical vacuum switches
characteristics (continued) OsiSense XML
Size - 1 bar (- 14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
Adjustable range of switching point (PB) - 0.14…- 1 bar (- 2.03…- 14.5 psi)
(Falling pressure)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLCM02V2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLCM02T2S12
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 1.015
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.13 bar (1.89 psi)
(add to PB Min. at high setting (3) 0.14 bar (2.03 psi)
to give PH)
Max. at high setting 0.8 bar (11.6 psi)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLCM02V2S12
becomes XMLCM02V2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves Connection
Terminal model
Rising pressure Time
-0.86 -0.6 -0.4 -0.14 0
13
11
23
21
bar -0.01
14
12
24
22
-0.2
PH
-0.4
2 PB
-0.6
Vacuum
Falling pressure
-0.8
bar
Accessories: Dimensions:
page 68 pages 69 to 71
20
References, Electromechanical vacuum switches
characteristics OsiSense XML
Size - 1 bar (- 14.5 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PB2) - 0.12…- 1 bar (- 1.74…- 14.5 psi)
switching point 1st stage switching point (PB1) - 0.10…- 0.98 bar (- 1.45…- 14.21 psi)
(Falling pressure)
Spread between 2 stages (PB2 - PB1) 0.02…0.88 bar (0.29…12.76 psi)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLDM02V1S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLDM02T1S12
corrosive fluids, up to + 160 °C
Sea water, up to + 30 °C
Weight (kg) 1.015
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.1 bar (1.45 psi)
(add to PB1/PB2 At high setting (4) 0.1 bar (1.45 psi)
to give PH1/PH2)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLDM02V1S12
becomes XMLDM02V1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.035 bar (± 0.51 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.02 bar (± 0.29 psi).
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
-0.4
PB1
-0.4
2 PH2
-0.6 -0.6 PB2
Falling pressure
Vacuum
1
-0.8 -0.8 –– Adjustable value
F --- Non adjustable value
-0.98 -0.98
bar H bar Connection
Terminal model
Contact 1 Contact 2
(stage 1) (stage 2)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.
21
References, Electromechanical vacuum switches
characteristics OsiSense XML
Size - 200 mbar (- 2.9 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
Adjustable range of switching point (PB) - 20…- 200 mbar (- 0.29…- 2.9 psi)
(Falling pressure)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, air, XMLBM03R2S12 XMLBM03R2S13
(2) up to + 160 °C
Weight (kg) 3.310 3.310
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 18 mbar (0.26 psi)
(add to PB Min. at high setting (3) 18 mbar (0.26 psi)
to give PH)
Max. at high setting 180 mbar (2.6 psi)
Maximum permissible Per cycle 1 bar (14.5 psi)
pressure Accidental 2 bar (29 psi)
Destruction pressure 3.5 bar (50.75 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Vacuum switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBM03R2S12
becomes XMLBM03R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 2 mbar (± 0.29 psi).
Operating curves Connection
Terminal model
Rising pressure Time
13
11
12
-20
-40
PH
-80
2 PB
-120
Vacuum
Falling pressure
-160
1
-200
mbar
Other versions For vacuum switches with alternative tapped cable entries, such as NPT, etc. please consult our
Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
22
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 50 mbar (0.72 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, air, XMLBL05R2S12
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLBL05S2S12
up to + 160 °C
Weight (kg) 2.420
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1.4 mbar (0.02 psi)
(subtract from PH Min. at high setting (4) 4 mbar (0.06 psi)
to give PB)
Max. at high setting 40 mbar (0.58 psi)
Maximum permissible Per cycle 62.5 mbar (0.90 psi)
pressure Accidental 112.5 mbar (1.63 psi)
Destruction pressure 225 mbar (3.26 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBL05R2S12
becomes XMLBL05R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 0.8 mbar, + 1.1 mbar (- 0.01 psi, + 0.02 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 1.4 mbar, (+ 0.02 psi).
Operating curves Connection
Terminal model
Pressure
mbar
50 PH
Rising pressure
13
11
1
40
14
12
PB
30
2
20
Time
10
2.6
0
1.2 10 20 30 40 46 mbar
Falling pressure
Other versions For pressure switches with EN 175301-803-A (ex-DIN 43650A) connector or with alternative
tapped cable entries, such as NPT, etc. please consult our Customer Care Centre.
23
References, Electromechanical vacu-pressure
characteristics switches
OsiSense XML. Size 5 bar (72.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLBM05A2C11 XMLBM05A2S12 XMLBM05A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLBM05B2C11 XMLBM05B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLBM05C2C11 XMLBM05C2S12 –
Viscous products, up to + 160 °C XMLBM05P2C11 XMLBM05P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.5 bar (7.25 psi)
(subtract from PH Min. at high setting (3) 0.5 bar (7.25 psi)
to give PB)
Max. at high setting 6 bar (87 psi)
Maximum permissible Per cycle 6.25 bar (90.62 psi)
pressure Accidental 11.25 bar (163.12 psi)
Destruction pressure 23 bar (333.5 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Vacu-pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBM05A2S12
becomes XMLBM05A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.05 bar (± 0.72 psi).
Operating curves Connection
Terminal model
Pressure
13
11
bar PH1
5
Rising pressure
14
12
PB1
1
4
3 PH2
0 Connector model
1 Time
2 PB2 Vacu-pressure switch pin view
2 2
1 3
PH3
0.5 1 2 1 → 11 and 13
0 3
PB3 2 → 12
-0.5
Vacuum 3 → 14
-1
-1 0 1 2 3 4 4.5 5 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
24
References, Electromechanical vacu-pressure
characteristics switches
OsiSense XML. Size 5 bar (72.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLCM05B2S12
(2) up to + 160 °C
Corrosive fluids, XMLCM05C2S12
up to + 160 °C
Weight (kg) 0.685
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.45 bar (6.52 psi)
(subtract from PH Min. at high setting (3) 0.45 bar (6.52 psi)
to give PB)
Max. at high setting 6 bar (87 psi)
Maximum permissible Per cycle 6.25 bar (90.62 psi)
pressure Accidental 11.25 bar (163.12 psi)
Destruction pressure 23 bar (333.5 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Vacu-pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLCM05B2S12
becomes XMLCM05B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.1 bar (± 1.45 psi).
Operating curves Connection
Terminal model
bar Pressure
13
11
23
21
5
Rising pressure
PH1
PB1
14
12
24
22
4
1
3
PH2
2
1
0
2 Time Connector model
PB2
1
2 Vacu-pressure switch pin view
0.5
3 1 → 11 and 13
0 PH3
-0.55 1 2 2 → 12
PB3 3
-1 3 → 14
-1 0 1 2 3 4 4.55 5 bar Vacuum
Falling pressure
Other versions For vacu-pressure switches with alternative tapped cable entries, such as NPT, etc. please
consult our Customer Care Centre.
25
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 350 mbar (5.07 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, air, XMLBL35R2C11 XMLBL35R2S12 XMLBL35R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLBL35S2C11 XMLBL35S2S12 –
up to + 160 °C
Viscous products, up to + 160 °C XMLBL35P2C11 XMLBL35P2S12 –
(G 1¼" fluid connection)
Weight (kg) 2.590 2.575 2.575
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 42 mbar (0.60 psi)
(subtract from PH Min. at high setting (4) 50 mbar (0.72 psi)
to give PB)
Max. at high setting 300 mbar (4.35 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 million operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBL35R2S12
becomes XMLBL35R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 8 mbar, + 3 mbar (- 0.12 psi, + 0.04 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 8 mbar (± 0.11 psi).
Operating curves Connection
Terminal model
mbar Pressure
13
11
350
PH
Rising pressure
14
12
300
1
PB
Connector model
200 2 Pressure switch connector pin view
100 Time
1 2 1 → 11 and 13
3 2 → 12
45
3 → 14
0
–– Adjustable value
3 50 100 200 300 mbar
Falling pressure
1 Maximum differential
2 Minimum differential
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
26
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 350 mbar (5.07 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, air, XMLBS35R2S12
(2) up to + 160 °C
Weight (kg) 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 33 mbar (0.48 psi)
(subtract from PH Min. at high setting (4) 58 mbar (0.84 psi)
to give PB)
Max. at high setting 250 mbar (3.62 psi)
Maximum permissible Per cycle 30 bar (435 psi)
pressure Accidental 37.5 bar (543.75 psi)
Destruction pressure 67.5 bar (978.75 psi)
Mechanical life 2 million operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Connector type for connector models EN 175301-803-A (ex-DIN 43650A), 4-pin male connector. For suitable female connector,
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLBS35R1S12
becomes XMLBS35R1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 8 mbar, + 3 mbar (- 0.12 psi, + 0.04 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 8 mbar (± 0.11 psi).
Operating curves Connection
Terminal model
13
11
mbar Pressure
350
Rising pressure
PH
14
12
300
1
PB
Connector model
200 2 Pressure switch connector pin view
100 1 2 1 → 11 and 13
Time 3 2 → 12
45 3 → 14
0
3 50 100 200 300 mbar
Falling pressure
27
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 350 mbar (5.07 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
OsiSense XMLC pressure switches With setting scale 30 bar (435 psi) overpressure
With setting scale
Adjustable range of switching point (PH) 45…350 mbar (0.65…5.07 psi) 42…330 mbar (0.61…4.78 psi)
(Rising pressure)
Electrical connection Terminals Terminals
Fluid connection G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female) 1/4”-18 NPTF (female)
References (1)
Fluids controlled Hydraulic oils, air, XMLCL35R2S12 – XMLCS35R2S12 XMLCS35R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLCL35S2S12 XMLCL35S2S13 – –
up to + 160 °C
Weight (kg) 2.575 2.575 3.500 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 20 mbar (0.29 psi) 40 mbar (0.58 psi)
(subtract from PH Min. at high setting (3) 35 mbar (0.51 psi) 88 mbar (1.27 psi)
to give PB)
Max. at high setting 300 mbar (4.35 psi) 230 mbar (3.33 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi) 30 bar (435 psi)
pressure Accidental 2.25 bar (32.62 psi) 37.5 bar (543.75 psi)
Destruction pressure 4.5 bar (65.25 psi) 67.5 bar (978.75 psi)
Mechanical life 4 million operating cycles 2 million operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x 1 entry tapped
1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable 1/2”-14 NPT for cable
gland, clamping gland, clamping gland, clamping gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLCL35R2S12
becomes XMLCL35R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 20 mbar (± 0.29 psi).
Operating curves Connection
Terminal model
Pressure
13
11
23
21
mbar
350
PH
Rising pressure
1
14
12
24
22
300
PB
200
2
Time
100
45
0
0 25 50 100 200 315 mbar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
28
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 350 mbar (5.07 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 58…350 mbar (0.84…5.07 psi)
switching point 1st stage switching point (PH1) 33…325 mbar (0.48…4.71 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 25…310 mbar (0.36…4.50 psi)
Electrical connection Terminals
Fluid connection G 1/4 (female)
References (1)
Fluids controlled Hydraulic oils, air, XMLDL35R1S12
(2) up to + 160 °C
Weight (kg) 2.575
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 30 mbar (0.44 psi)
(subtract from PH1/PH2 At high setting (4) 30 mbar (0.44 psi)
to give PB1/PB2)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 million operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLDL35R1S12
becomes XMLDL35R1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 10 mbar (± 0.15 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 8 mbar (± 0.11 psi).
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
mbar mbar PH2
350 350 H
PH2 setting (falling pressure)
343
Falling pressure
1 325 F PB2
300 300
PH1
PB1
200 200
2
Time
100 100
G –– Adjustable value
58 58
33 --- Non adjustable value
E
0 0 Connection
0 33 100 200 300 325mbar 3 28 100 200 295 320 mbar
PH1 setting (falling pressure) Rising pressure Terminal model
Contact 1 Contact 2
(stage 1) (stage 2)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
29
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 1 bar (14.5 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, air, XMLA001R2C11 XMLA001R2S12 –
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLA001S2C11 XMLA001S2S12 XMLA001S2S13
up to + 160 °C
Weight (kg) 2.570 2.555 2.555
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.02 bar (0.29 psi)
(subtract from PH At high setting (3) 0.04 bar (0.58 psi)
to give PB)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA001R2S12
becomes XMLA001R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.01 bar (± 0.14 psi)
Operating curves Connection
Terminal model
Pressure
13
11
bar
1 PH
Rising pressure
14
12
0.8 PB
Connector model
0.6
Pressure switch connector pin view
0.4
Time
1 2 1 → 11 and 13
3
0.2 2 → 12
3 → 14
0.03
0
0.01 0.2 0.4 0.6 0.8 0.96
bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
30
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 1 bar (14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, air, XMLB001R2C11 XMLB001R2S12 XMLB001R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLB001S2C11 XMLB001S2S12 XMLB001S2S13
up to + 160 °C
Viscous products, up to + 160 °C – XMLB001P2S12 –
(G 1¼" fluid connection)
Weight (kg) 2.590 2.575 2.575
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.04 bar (0.58 psi)
(subtract from PH Min. at high setting (4) 0.06 bar (0.87 psi)
to give PB)
Max. at high setting 0.75 bar (10.87 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB001R2S12
becomes XMLB001R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 10 mbar (± 0.14 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
± 20 mbar (± 0.29 psi).
Operating curves Connection
Terminal model
Pressure
13
11
bar
1 PH
Rising pressure
14
12
0.8
1
PB
0.6
Connector model
Pressure switch connector pin view
2
0.4
Time
1 2 1 → 11 and 13
3
0.2 2 → 12
3 → 14
0.05
0
0.01 0.25 0.4 0.6 0.8 0.94
bar
Falling pressure
31
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 1 bar (14.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, air, XMLC001R2S12 XMLC001R2S13
(2) up to + 160 °C
Fresh water, corrosive fluids, XMLC001S2S12 XMLC001S2S13
up to + 160 °C
Weight (kg) 2.555 2.555
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.03 bar (0.43 psi)
(subtract from PH Min. at high setting (4) 0.04 bar (0.58 psi)
to give PB)
Max. at high setting 0.8 bar (11.6 psi)
Maximum permissible Per cycle 1.25 bar (18.12 psi)
pressure Accidental 2.25 bar (32.62 psi)
Destruction pressure 4.5 bar (65.25 psi)
Mechanical life 4 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC001R2S12
becomes XMLC001R2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.01 bar (± 0.14 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.03 bar (± 0.43 psi)
Operating curves Connection
Terminal model
Pressure
13
11
23
21
bar
1 PH
Rising pressure
14
12
24
22
PB
0.6
2
0.4
Time
0.2
0.05
0
0.02 0.2 0.4 0.6 0.8 0.96 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
32
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 2.5 bar (36.25 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA002A2C11 XMLA002A2S12 XMLA002A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA002B2C11 XMLA002B2S12 –
up to + 160 °C
Corrosive fluids, XMLA002C2C11 XMLA002C2S12 –
up to + 160 °C
Weight (kg) 1.010 0.995 0.995
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.13 bar (1.88 psi)
(subtract from PH At high setting (3) 0.13 bar (1.88 psi)
to give PB)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 8 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA002A2S12
becomes XMLA002A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.03 bar (± 0.43 psi).
Operating curves Connection
Terminal model
Pressure
13
11
bar
2.5 PH
Rising pressure
14
12
2 PB
Connector model
Pressure switch connector pin view
1
Time 1 2 1 → 11 and 13
3
2 → 12
3 → 14
0.15
0
0.02 1 2 2.37 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
33
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 2.5 bar (36.25 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
Fluid connection G 1/4 (female) G 1/4 (female) 1/4”-18 NPTF (female) G 1/4 (female)
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB002A2C11 XMLB002A2S12 XMLB002A2S13 –
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB002B2C11 XMLB002B2S12 – XMLBS02B2S12
up to + 160 °C
Corrosive fluids, XMLB002C2C11 XMLB002C2S12 – –
up to + 160 °C
Weight (kg) 1.030 1.015 1.015 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.16 bar (2.32 psi) 0.1 bar (1.45 psi)
(subtract from PH Min. at high setting (3) 0.21 bar (3.04 psi) 0.22 bar (3.19 psi)
to give PB)
Max. at high setting 1.75 bar (25.37 psi) 1.45 bar (21 psi)
Maximum permissible Per cycle 5 bar (72.5 psi) 30 bar (435 psi)
pressure Accidental 9 bar (130.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 18 bar (261 psi) 67.5 bar (978.75 psi)
Mechanical life 8 x 106 operating cycles 2 x 106 operating
cycles
Connection EN 175301-803-A 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x
(ex-DIN 43650A), 1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable
4-pin male connector. gland, clamping gland, clamping gland, clamping
For suitable female capacity 7 to 13 mm capacity 7 to 13 mmcapacity 7 to 13 mm
connector, see page
68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB002A2S12
becomes XMLB002A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
- 0.03 bar, + 0.05 bar (- 0.43 psi, + 0.72 psi).
Operating curves Connection
bar
Pressure Terminal model
2.5 PH
Rising pressure
13
11
2
14
12
1 PB
Connector model
Pressure switch connector pin view
2
1
Time
1 2 1 → 11 and 13
3
0.3 2 → 12
3 → 14
0
0.14 0.75 1 2 2.29 bar
Falling pressure
34
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 2.5 bar (36.25 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
OsiSense XMLC pressure switches With setting scale 30 bar (435 psi) overpressure
With setting scale
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLC002B2S12 XMLC002B2S13 XMLCS02B2S12 XMLCS02B2S13
(2) up to + 160 °C
Weight (kg) 0.995 0.995 3.500 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.13 bar (1.89 psi) 0.1 bar (1.45 psi)
(subtract from PH Min. at high setting (4) 0.17 bar (2.47 psi) 0.18 bar (2.61 psi)
to give PB)
Max. at high setting 2 bar (29 psi) 1.25 bar (18.12 psi)
Maximum permissible Per cycle 5 bar (72.5 psi) 30 bar (435 psi)
pressure Accidental 9 bar (130.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 18 bar (261 psi) 67.5 bar (978.75 psi)
Mechanical life 8 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1 entry tapped 1 entry tapped M20 x 1 entry tapped
1.5 mm for ISO cable 1/2”-14 NPT for cable 1.5 mm for ISO cable 1/2”-14 NPT for cable
gland, clamping gland, clamping gland, clamping gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC002B2S12
becomes XMLC002B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.02 bar (± 0.29 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.03 bar (± 0.43 psi)
Operating curves Connection
Terminal model
Pressure
13
11
23
21
bar
2.5 PH
Rising pressure
14
12
24
22
1
2
PB
2
1
Time
0.3
0
0.17 0.5 1 2 2.33 bar
Falling pressure
35
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA004A2C11 XMLA004A2S12 XMLA004A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA004B2C11 XMLA004B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA004C2C11 XMLA004C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA004P2C11 XMLA004P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.35 bar (5.07 psi)
(subtract from PH
to give PB) At high setting (3) 0.35 bar (5.07 psi)
11
bar
4 PH
Rising pressure
14
12
PB
3
Connector model
2 Pressure switch connector pin view
Time
1 1 2 1 → 11 and 13
3
2 → 12
0.4 3 → 14
0
0.05 1 2 3 3.65 4 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
36
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
13
11
14
12
3
PB
1 2 Connector model
2 Pressure switch connector pin view
Time 1 → 11 and 13
1
1 2 2 → 12
3
3 → 14
0.25
0
0.05 1 1.6 2 3 3.75 bar
Falling pressure
37
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
OsiSense XMLC pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLC004B2S12 XMLC004B2S13 XMLCS04B2S12
(2) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC004C2S12 XMLC004C2S13 –
11
23
21
bar
4 PH
Rising pressure
14
12
24
22
3
1
PB
2 2
Time
1
0.3
0
0.15 1 1.5 2 3 3.83 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
38
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 4 bar (58 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 0.40…4 bar (5.8…58 psi)
switching point 1st stage switching point (PH1) 0.19…3.79 bar (2.76…54.96 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 0.21…2.18 bar (3.05…31.61 psi)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLD004B1S12
(2) up to + 160 °C
Weight (kg) 1.015
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.15 bar (2.18 psi)
(subtract from PH1/PH2 At high setting (3) 0.19 bar (2.76 psi)
to give PB1/PB2)
Maximum permissible Per cycle 5 bar (72.5 psi)
pressure Accidental 9 bar (130.5 psi)
Destruction pressure 18 bar (261 psi)
Mechanical life 8 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD004B1S12
becomes XMLD004B1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.03 bar (± 0.43 psi).
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar bar H PH2
4 4
PH2 setting (rising pressure)
Rising pressure
3.79
F PB2
PH1
3
1
3 PB1
2.35
2 2 2
Time
1 1
–– Adjustable value
0.4 0.40 G --- Non adjustable value
0.19
0 0 E Connection
0.19 1 1.82 2 3 3.79 bar 0.04 1 2 3 3.6 3.81 bar
PH1 setting (rising pressure) Falling pressure Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
39
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 10 bar (145 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA010A2C11 XMLA010A2S12 XMLA010A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA010B2C11 XMLA010B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA010C2C11 XMLA010C2S12 XMLA010C2S13
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA010P2C11 XMLA010P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.5 bar (7.25 psi)
(subtract from PH At high setting (3) 0.5 bar (7.25 psi)
to give PB)
Maximum permissible Per cycle 12.5 bar (181.25 psi)
pressure Accidental 22.5 bar (326.25 psi)
Destruction pressure 45 bar (652.5 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA010A2S12
becomes XMLA010A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size: ± 0.05
bar (± 0.72 psi)
Operating curves Connection
Terminal model
Pressure
13
11
bar
10 PH
Rising pressure
14
12
8 PB
6
Connector model
Pressure switch connector pin view
4
Time
2 1 2 1 → 11 and 13
1 3
2 → 12
0.6
0 3 → 14
0.1 2 4 6 8 9.5 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
40
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 10 bar (145 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
13
11
8
14
12
1
PB
6 Connector model
2
Pressure switch connector pin view
4
Time 1 → 11 and 13
2 1 2 2 → 12
3
3 → 14
0.7
0
0.13 2.5 4 6 8 9.15
bar
Falling pressure
41
References, Electromechanical pressure switches
characteristics (continued) OsiSense XML
Size 10 bar (145 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
OsiSense XMLC pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
References (1)
Fluids controlled Hydraulic oils, fresh water, air, – – XMLCS10A2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLC010B2S12 XMLC010B2S13 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC010C2S12 XMLC010C2S13 –
Sea water, up to + 30 °C
Weight (kg) 0.685 0.685 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.45 bar (6.53 psi) 0.25 bar (3.62 psi)
(subtract from PH Min. at high setting (4) 0.70 bar (10.15 psi) 0.65 bar (9.42 psi)
to give PB)
Max. at high setting 8 bar (116 psi) 5.6 bar (81.2 psi)
Maximum permissible Per cycle 12.5 bar (181.25 psi) 30 bar (435 psi)
pressure Accidental 22.5 bar (326.25 psi) 37.5 bar (543.75 psi)
Destruction pressure 45 bar (652.5 psi) 67.5 bar (978.75 psi)
Mechanical life 5 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT 1 entry tapped M20 x 1.5 mm
for ISO cable gland, clamping for cable gland, clamping for ISO cable gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC010B2S12
becomes XMLC010B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.05 bar (± 0.72 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.01 bar (± 1.45 psi)
Operating curves Connection
Terminal model
bar Pressure
13
11
23
21
10
PH
Rising pressure
1
14
12
24
22
PB
6
2
4
Time
2
0.7
0
0.25 2 4 6 8 9.3 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
42
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 10 bar (145 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 1.2…10 bar (17.4…145 psi)
switching point 1st stage switching point (PH1) 0.52…9.32 bar (7.54…135.14 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 0.68…5.8 bar (9.86…84.1 psi)
Fluid connection G 1/4 (female)
References
Fluids controlled Hydraulic oils, fresh water, air, XMLD010B1S11 XMLD010B1S12
(1) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLD010C1S11 –
Sea water, up to + 30 °C
Weight (kg) 0.705 0.705
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (2) 0.45 bar (6.53 psi)
(subtract from PH1/PH2 At high setting (3) 0.6 bar (8.7 psi)
to give PB1/PB2)
Maximum permissible Per cycle 12.5 bar (181.25 psi)
pressure Accidental 22.5 bar (326.25 psi)
Destruction pressure 45 bar (652.5 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped for no. 13 cable gland 1 entry tapped M20 x 1.5 mm for ISO cable
gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For component materials of units in contact with the fluid, see pages 72 and 73.
(2) Deviation of the differential at low setting point for switches of the same size:
± 0.05 bar (± 0.72 psi)
(3) Deviation of the differential at high setting point for switches of the same size:
± 0.1 bar (± 1.45 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
bar Pressure
bar H
10 10
Rising pressure
PH2 setting (rising pressure)
PH2
9.32 F PB2
8 8
1 PH1
6.34 PB1
6 6
2
4 4
Time
2 2
–– Adjustable value
1.2 1.2 G
0.52
--- Non adjustable value
0 0 E Connection
0.52 2 4.2 6 8 9.32 bar 0.07 0.75 2 4 6 8.72 9.4 bar
PH1 setting (rising pressure) Falling pressure Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
43
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA020A2C11 XMLA020A2S12 XMLA020A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA020B2C11 XMLA020B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA020C2C11 XMLA020C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA020P2C11 XMLA020P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.715 0.685 0.685
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.4 bar (5.8 psi)
(subtract from PH At high setting (3) 1 bar (14.5 psi)
to give PB)
Maximum permissible Per cycle 25 bar (362.5 psi)
pressure Accidental 45 bar (652.5 psi)
Destruction pressure 90 bar (1305 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA020A2S12
becomes XMLA020A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at high setting point for switches of the same size:
± 0.1 bar (± 1.45 psi)
Deviation of the differential at low setting point: ± 0.2 bar (± 2.9 psi)
11
20
PH
Rising pressure
14
12
15 PB
10 Connector model
Pressure switch connector pin view
5 Time
1 2 1 → 11 and 13
3
1 2 → 12
0 3 → 14
0.6 5 10 15 19 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
44
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
OsiSense XMLB pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
PH
13
11
14
12
15
PB
1 2 Connector model
10 Pressure switch connector pin view
Time 1 → 11 and 13
5
1 2 2 → 12
3
3 → 14
1.3
0
0.3 5 9 10 15 18.4 bar
Falling pressure
45
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
OsiSense XMLC pressure switches With setting scale 30 bar (435 psi)
overpressure
With setting scale
References (1)
Fluids controlled Hydraulic oils, fresh water, air, – – XMLCS20A2S12
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLC020B2S12 XMLC020B2S13 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC020C2S12 XMLC020C2S13 –
Sea water, up to + 30 °C
Weight (kg) 0.685 0.685 3.500
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 0.7 bar (10.15 psi) 0.7 bar (10.15 psi)
(subtract from PH Min. at high setting (3) 1 bar (14.5 psi) 1.15 bar (16.67 psi)
to give PB)
Max. at high setting 11 bar (159.5 psi) 11.70 bar (169.6 psi)
Maximum permissible Per cycle 25 bar (362.5 psi) 30 bar (435 psi)
pressure Accidental 45 bar (652.5 psi) 37.5 bar (543.75 psi)
Destruction pressure 90 bar (1305 psi) 67.5 bar (978.75 psi)
Mechanical life 5 x 106 operating cycles 2 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT 1 entry tapped M20 x 1.5 mm
for ISO cable gland, clamping for cable gland, clamping for ISO cable gland, clamping
capacity 7 to 13 mm capacity 7 to 13 mm capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC020B2S12
becomes XMLC020B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.2 bar (± 2.9 psi)
11
23
21
20
Rising pressure
PH
14
12
24
22
15
PB
1 2
10
Time
5
1.3
0
0.6 5 9 10 15 19 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
46
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 20 bar (290 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLD020B1S12 XMLD020B1S13
(2) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLD020C1S12 –
Sea water, up to + 30 °C
Weight (kg) 0.705 0.705
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 0.7 bar (10.15 psi)
(subtract from PH1/PH2 At high setting (4) 1.3 bar (18.85 psi)
to give PB1/PB2)
Maximum permissible Per cycle 25 bar (362.5 psi)
pressure Accidental 45 bar (652.5 psi)
Destruction pressure 90 bar (1305 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD020B1S12
becomes XMLD020B1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.15 bar (± 2.18 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.3 bar (± 4.35 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
PH2
bar bar H
20 20 PB2
Rising pressure
18.76
F
PH2 setting (rising pressure)
PH1
PB1
15 15
1 2
10.6 10
Time
5 5 –– Adjustable value
--- Non adjustable value
2.14 G
2.14
0.9 Connection model
0 0 E Terminal model
0.9 5 10.45 15 18.76 bar 0.2 1.44 5 10 15 17.46 18.7 bar
Falling pressure Contact 2 Contact 1
PH1 setting (rising pressure)
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
47
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLA035A2C11 XMLA035A2S12 XMLA035A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLA035B2C11 XMLA035B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLA035C2C11 XMLA035C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C XMLA035P2C11 XMLA035P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.725 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 1.25 bar (18.12 psi)
(subtract from PH At high setting (3) 1.25 bar (18.12 psi)
to give PB)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA035A2S12
becomes XMLA035A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.25 bar (± 3.62 psi)
Operating curves Connection
Terminal model
bar Pressure
13
11
35
PH
Rising pressure
14
12
30
PB
20
Connector model
Pressure switch connector pin view
10 Time
1 2 1 → 11 and 13
3
1.5 2 → 12
0
0.25 10 20 30 33.75 bar 3 → 14
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
48
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLB035A2C11 XMLB035A2S12 XMLB035A2S13
(2) up to + 70 °C
Hydraulic oils, fresh water, air, XMLB035B2C11 XMLB035B2S12 –
up to + 160 °C
Corrosive fluids, up to + 160 °C XMLB035C2C11 XMLB035C2S12 –
Sea water, up to + 30 °C
Viscous products, up to + 160 °C – XMLB035P2S12 –
(G 1¼" fluid connection)
Weight (kg) 0.745 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1.7 bar (24.65 psi)
(subtract from PH Min. at high setting (3) 2.55 bar (36.97 psi)
to give PB)
Max. at high setting 20 bar (290 psi)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Connection EN 175301-803-A connector 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
(ex-DIN 43650A), 4-pin male. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB035A2S12
becomes XMLB035A2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
- 0.5 bar, + 0.7 bar (- 7.25 psi, + 10.15 psi).
Operating curves Connection
Terminal model
bar Pressure
13
11
35
Rising pressure
PH
14
12
30
1 PB
20 2
Connector model
Pressure switch connector pin view
10 Time
1 2 1 → 11 and 13
3.5 3
2 → 12
0
1.8 10 15 20 32.45 bar 3 → 14
Falling pressure
49
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLC035B2S12 XMLC035B2S13
(2) up to + 160 °C
Corrosive fluids, up to + 160 °C XMLC035C2S12 XMLC035C2S13
Sea water, up to + 30 °C
Weight (kg) 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 1 bar (14.5 psi)
(subtract from PH Min. at high setting (4) 1.5 bar (21.75 psi)
to give PB)
Max. at high setting 22 bar (319 psi)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC035B2S12
becomes XMLC035B2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.2 bar (± 2.9 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.5 bar (± 7.25 psi)
Operating curves Connection
Terminal model
bar Pressure
13
11
23
21
35
PH
Rising pressure
14
12
24
22
30
1
PB
20 2
10 Time
3.5
0
2.5 10 13 20 33.5 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
50
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 35 bar (507.5 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 4.4…35 bar (63.8…507.5 psi)
switching point 1st stage switching point (PH1) 1.9…32.5 bar (27.55…471.25 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 2.5…20.4 bar (36.25…295.8 psi)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, fresh water, air, XMLD035B1S12
(2) up to + 160 °C
Weight (kg) 0.715
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 1.5 bar (21.75 psi)
(subtract from PH1/PH2 At high setting (4) 2.6 bar (37.7 psi)
to give PB1/PB2)
Maximum permissible Per cycle 45 bar (652.5 psi)
pressure Accidental 80 bar (1160 psi)
Destruction pressure 160 bar (2320 psi)
Mechanical life 5 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Diaphragm
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD035B1S12
becomes XMLD035B1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 0.3 bar (± 4.35 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 0.7 bar (± 10.15 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar bar PH2
35 35 H
F
PH2 setting (rising pressure)
PB2
Rising pressure
32.5
30 30
PH1
1
PB1
22.3
20 2 20
Time
10 10
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
51
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLA070D2C11 XMLA070D2S12 XMLA070D2S13
(2) up to + 160 °C
Fresh water, XMLA070E2C11 XMLA070E2S12 XMLA070E2S13
up to + 160 °C
Corrosive fluids, air, XMLA070N2C11 XMLA070N2S12 –
up to + 160 °C
Weight (kg) 0.725 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 3 bar (43.5 psi)
(subtract from PH At high setting (3) 9.5 bar (137.75 psi)
to give PB)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA070D2S12
becomes XMLA070D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size: ± 1
bar (± 14.5 psi)
Operating curves Connection
Terminal model
Pressure
13
11
bar
70 PH
Rising pressure
14
12
60
PB
40
Connector model
Pressure switch connector pin view
20 Time
1 2 1 → 11 and 13
3
5 2 → 12
0 3 → 14
02 8 20 40 62.5 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
52
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLB070D2C11 XMLB070D2S12 XMLB070D2S13
(2) up to + 160 °C
Fresh water, XMLB070E2C11 XMLB070E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB070N2C11 XMLB070N2S12 –
up to + 160 °C
Weight (kg) 0.745 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 4.7 bar (68.15 psi)
(subtract from PH Min. at high setting (4) 9.5 bar (137.75 psi)
to give PB)
Max. at high setting 50 bar (725 psi)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A connector 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
(ex-DIN 43650A), 4-pin male for ISO cable gland, clamping for cable gland, clamping
connector. For suitable female capacity 7 to 13 mm capacity 7 to 13 mm
connector, see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB070D2S12
becomes XMLB070D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 0.4 bar, + 0.7 bar (- 5.8 psi, + 10.15 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 0.6 bar, + 0.8 bar (- 8.7 psi, + 11.6 psi).
Operating curves Connection
Terminal model
bar Pressure
13
11
70
Rising pressure
PH
60
14
12
1
PB
40
2
Connector model
Pressure switch connector pin view
20
Time
7 1 2 1 → 11 and 13
3
0 2 → 12
2.3 20 40 61.2 bar 3 → 14
Falling pressure
53
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, XMLC070D2S12 XMLC070D2S13
(2) up to + 160 °C
Fresh water, XMLC070E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLC070N2S12 –
up to + 160 °C
Weight (kg) 0.695 0.695
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 4.5 bar (65.25 psi)
(subtract from PH Min. at high setting (3) 9.5 bar (137.75 psi)
to give PB)
Max. at high setting 60 bar (870 psi)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC070D2S12
becomes XMLC070D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.8 bar (± 11.6 psi)
Operating curves Connection
Terminal model
bar Pressure
13
11
23
21
70
Rising pressure
PH
14
12
24
22
60
1
PB
40
2
20 Time
7
0
2.5 10 20 40 61.1 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
54
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 70 bar (1015 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 9.4…70 bar (136.3…1015 psi)
switching point 1st stage switching point (PH1) 6.6…67.2 bar (95.7…974.4 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 2.8…46 bar (40.6…667 psi)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, XMLD070D1S12 XMLD070D1S13
(2) up to + 160 °C
Corrosive fluids, air, XMLD070N1S12 –
up to + 160 °C
Weight (kg) 0.715 0.715
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 5 bar (72.5 psi)
(subtract from PH1/PH2 At high setting (4) 9.5 bar (137.75 psi)
to give PB1/PB2)
Maximum permissible Per cycle 90 bar (1035 psi)
pressure Accidental 160 bar (2320 psi)
Destruction pressure 320 bar (4640 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD070D1S12
becomes XMLD070D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 1.5 bar (± 21.75 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 2 bar (± 29 psi)
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
bar Pressure
bar
70 70 H PH2
Rising pressure
PH2 setting (rising pressure)
67.2 F
60 60 PB2
1
52.6 PH1
PB1
40
2 40
20 20 Time
9.4 9.4 G
6.6 E –– Adjustable value
0 0 --- Non adjustable value
1.6 4.4 20 40 57.7 60.5 bar
6.6 20 24 40 60 67.2 bar
PH1 setting (rising pressure) Falling pressure
Connection
Terminal model
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
55
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLA160D2C11 XMLA160D2S12 XMLA160D2S13
(2) up to + 160 °C
Fresh water, XMLA160E2C11 XMLA160E2S12 XMLA160E2S13
up to + 160 °C
Corrosive fluids, air, XMLA160N2C11 XMLA160N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 5.5 bar (79.75 psi)
(subtract from PH At high setting (4) 18 bar (261 psi)
to give PB)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10,440 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA160D2S12
becomes XMLA160D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 1 bar (± 14.5 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 3 bar (± 43.5 psi)
Operating curves Connection
Terminal model
Pressure
13
11
bar
PH
Rising pressure
160
14
12
140 PB
120
100
Connector model
80
Pressure switch connector pin view
60
Time
40
20
1 2 1 → 11 and 13
3
10 2 → 12
0
3 → 14
4.5 20 40 60 80 100 120 142 160 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
56
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLB160D2C11 XMLB160D2S12 XMLB160D2S13
(2) up to + 160 °C
Fresh water, XMLB160E2C11 XMLB160E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB160N2C11 XMLB160N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 9.3 bar (134.85 psi)
(subtract from PH Min. at high setting (4) 20.8 bar (301.6 psi)
to give PB)
Max. at high setting 100 bar (1450 psi)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10,440 psi)
Mechanical life 6 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB160D2S12
becomes XMLB160D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 1.8 bar, + 1.5 bar (- 26.1 psi, + 21.75 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 1.9 bar, + 1.6 bar (- 27.55 psi, + 23.2 psi).
Operating curves Connection
Terminal model
Pressure
13
11
bar
160
PH
Rising pressure
14
12
120
PB
1
80
2 Connector model
Pressure switch connector pin view
Time
40
1 2 1 → 11 and 13
3
10
2 → 12
0 3 → 14
0.7 40 60 80 120 139.2 bar
Falling pressure
57
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, XMLC160D2S12 XMLC160D2S13
(2) up to + 160 °C
Fresh water, XMLC160E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLC160N2S12 –
up to + 160 °C
Weight (kg) 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 9 bar (130.5 psi)
(subtract from PH Min. at high setting (3) 21 bar (304.5 psi)
to give PB)
Max. at high setting 110 bar (1590 psi)
Maximum permissible Per cycle 200 bar (2900 psi)
pressure Accidental 360 bar (5220 psi)
Destruction pressure 720 bar (10 440 psi)
Mechanical life 6 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC160D2S12
becomes XMLC160D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.9 bar (± 13.05 psi)
Operating curves Connection
Terminal model
Pressure
13
11
23
21
bar
160
Rising pressure
PH
14
12
24
22
100 2 PB
50 Time
12
0
50 100 139 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
58
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 160 bar (2320 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 16.5…160 bar (239.25…2320 psi)
switching point 1st stage switching point (PH1) 10.5…154 bar (152.25…2233 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 6…83 bar (87…1203.5 psi)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, up to + 160 °C XMLD160D1S12 XMLD160D1S13
(2)
Fresh water, up to + 160 °C XMLD160E1S12 –
160 F PB2
140
PH2 setting (rising pressure)
120 PH1
120 PB1
1 100
94.5 2 80
80
60
Time
40
40 –– Adjustable value
16.5 G
10.5 --- Non adjustable value
16.5 E
10 0
1.7 7.7 40 60 80 100 134140 160 bar
Connection
0
0 10.5 40 60 77 100 120 154 bar
Falling pressure Terminal model
PH1 setting (rising pressure) Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
59
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLA300D2C11 XMLA300D2S12 XMLA300D2S13
(2) (5) up to + 160 °C
Fresh water, XMLA300E2C11 XMLA300E2S12 XMLA300E2S13
up to + 160 °C
Corrosive fluids, air, XMLA300N2C11 XMLA300N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 16.5 bar (239.25 psi)
(subtract from PH At high setting (4) 35 bar (507.5 psi)
to give PB)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19 575 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA300D2S12
becomes XMLA300D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 3 bar (± 43.5 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 6 bar (± 87 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13
11
bar
PH
Rising pressure
14
12
300
PB
200
Connector model
Pressure switch connector pin view
100 Time
1 2 1 → 11 and 13
3
20 2 → 12
0 3 → 14
3.5 100 200 265 300 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
60
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLB300D2C11 XMLB300D2S12 XMLB300D2S13
(2)(5) up to + 160 °C
Fresh water, XMLB300E2C11 XMLB300E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB300N2C11 XMLB300N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 19.4 bar (281.3 psi)
(subtract from PH Min. at high setting (4) 37 bar (536.5 psi)
to give PB)
Max. at high setting 200 bar (2900 psi)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19,575 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT for
43650A), 4-pin male connector. for ISO cable gland, clamping cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB300D2S12
becomes XMLB300D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 1.5 bar, + 1.7 bar (- 21.75 psi, + 24.65 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 1 bar, + 4 bar (- 14.5 psi, + 58 psi).
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13
11
bar
300 PH
Rising pressure
14
12
200 1 PB
Connector model
2 Pressure switch connector pin view
100 Time
1 2 1 → 11 and 13
3 2 → 12
22 3 → 14
0
2.6 100 200 263 bar
Falling pressure
61
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, XMLC300D2S12
(2) (4) up to + 160 °C
Fresh water, XMLC300E2S12
up to + 160 °C
Corrosive fluids, air, XMLC300N2S12
up to + 160 °C
Weight (kg) 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 16 bar (232 psi)
(subtract from PH Min. at high setting (3) 35 bar (507.5 psi)
to give PB)
Max. at high setting 240 bar (3480 psi)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19 575 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC300D2S12
becomes XMLC300D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.9 bar (± 13.05 psi)
(4) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13
11
23
21
bar
300
PH
Rising pressure
1
14
12
24
22
200 PB
100 Time
22
0
6 60 100 200 265 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
62
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 300 bar (4350 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 36…300 bar (522…4350 psi)
switching point 1st stage switching point (PH1) 25…289 bar (362.5…4190.5 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 11…189 bar (159.5…2740.5 psi)
Electrical connection Terminals
Fluid connection G 1/4 (female) 1/4”-18 NPTF (female)
References (1)
Fluids controlled Hydraulic oils, XMLD300D1S12 XMLD300D1S13
(2) (5) up to + 160 °C
Fresh water, XMLD300E1S12 –
up to + 160 °C
Corrosive fluids, air, XMLD300N1S12 –
up to + 160 °C
Weight (kg) 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 17 bar (246.5 psi)
(subtract from PH1/PH2 At high setting (4) 42 bar (609 psi)
to give PB1/PB2)
Maximum permissible Per cycle 375 bar (5437.5 psi)
pressure Accidental 675 bar (9787.5 psi)
Destruction pressure 1350 bar (19,575 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable 1 entry tapped 1/2”-14 NPT for cable gland,
gland, clamping capacity 7 to 13 mm clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD300D1S12
beomes XMLD300D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 2.5 bar (± 36.25 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 9 bar (± 130.5 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar
300 H PH2
Rising pressure
bar 289
F PB2
PH2 setting (rising pressure)
300
PH1
1 200 PB1
215
200
2
100 Time
100
36 G
25 –– Adjustable value
36 E --- Non adjustable value
20 0
8 19 100 200 247 258 300 bar
0
Falling pressure Connection
0 25 111 200 289 bar
PH1 setting (rising pressure) Terminal model
Contact 2Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
63
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Fixed differential, for detection of a single threshold
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLA500D2C11 XMLA500D2S12 XMLA500D2S13
(2) (5) up to + 160 °C
Fresh water, XMLA500E2C11 XMLA500E2S12 XMLA500E2S13
up to + 160 °C
Corrosive fluids, air, XMLA500N2C11 XMLA500N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 20 bar (290 psi)
(subtract from PH At high setting (4) 45 bar (652.5 psi)
to give PB)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16,312.5 psi)
Destruction pressure 2250 bar (32,625 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLA500D2S12
becomes XMLA500D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 6 bar (± 87 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 10 bar (± 145 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
bar
13
11
500
Rising pressure
PH
14
12
400
PB
300
Connector model
200
Pressure switch connector pin view
Time
100
1 2 1 → 11 and 13
3
30 2 → 12
0 3 → 14
10 100 200 300 400 455 bar
Falling pressure
–– Adjustable value
--- Non adjustable value
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
Accessories: Dimensions:
page 68 pages 69 to 71
64
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
References (1)
Fluids controlled Hydraulic oils, XMLB500D2C11 XMLB500D2S12 XMLB500D2S13
(2) (5) up to + 160 °C
Fresh water, XMLB500E2C11 XMLB500E2S12 –
up to + 160 °C
Corrosive fluids, air, XMLB500N2C11 XMLB500N2S12 –
up to + 160 °C
Weight (kg) 0.780 0.750 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 23 bar (333.5 psi)
(subtract from PH Min. at high setting (4) 52.6 bar (762.7 psi)
to give PB)
Max. at high setting 300 bar (4350 psi)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16,312.5 psi)
Destruction pressure 2250 bar (32,625 psi)
Mechanical life 3 x 106 operating cycles
Connection EN 175301-803-A (ex-DIN 1 entry tapped M20 x 1.5 mm 1 entry tapped 1/2”-14 NPT
43650A), 4-pin male connector. for ISO cable gland, clamping for cable gland, clamping
For suitable female connector, capacity 7 to 13 mm capacity 7 to 13 mm
see page 68
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLB500D2S12
becomes XMLB500D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
- 2.6 bar, + 3.8 bar (- 37.7 psi, + 55.1 psi).
(4) Deviation of the differential at high setting point for switches of the same size:
- 14.8 bar, + 11.2 bar (- 214.6 psi, + 162.4 psi).
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13
11
bar
500 PH
Rising pressure
14
12
400
PB
300 1
Connector model
2 Pressure switch connector pin view
200
Time
100 1 2 1 → 11 and 13
3
30
2 → 12
0 3 → 14
7 100 200 400 447.4 bar
Falling pressure
65
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2 CO single-pole contacts
References (1)
Fluids controlled Hydraulic oils, XMLC500D2S12
(2) (4) up to + 160 °C
Corrosive fluids, air, XMLC500N2S12
up to + 160 °C
Weight (kg) 0.750
Complementary characteristics not shown under general characteristics (page 17)
Possible differential Min. at low setting (3) 19 bar (275.5 psi)
(subtract from PH Min. at high setting (3) 52 bar (754 psi)
to give PB)
Max. at high setting 340 bar (4930 psi)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16 312.5 psi)
Destruction pressure 2250 bar (32 625 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tappedJe préfère acheter des.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLC500D2S12
becomes XMLC500D2S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low and high setting points for switches of the same size:
± 0.9 bar (± 13.05 psi)
(4) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves Connection
Terminal model
Pressure
13
11
23
21
bar
500
Rising pressure
PH
14
12
24
22
400
1
PB
300
2
200
Time
100
30
0
11 100 160 200 300 400 448 bar
Falling pressure
Accessories: Dimensions:
page 68 pages 69 to 71
66
References, Electromechanical pressure switches
characteristics OsiSense XML
Size 500 bar (7250 psi)
Dual stage, fixed differential, for detection at each threshold
Switches with 2 CO single-pole contacts
Adjustable range of each 2nd stage switching point (PH2) 41…500 bar (594.5…7250 psi)
switching point 1st stage switching point (PH1) 25…484 bar (362.5…7018 psi)
(Rising pressure)
Spread between 2 stages (PH2 - PH1) 16…244 bar (232…3538 psi)
Electrical connection Terminals
References (1)
Fluids controlled Hydraulic oils, up to + 160 °C XMLD500D1S12
(2) (5)
Weight (kg) 0.750
Complementary characteristics not shown under general characteristics (page 17)
Natural differential At low setting (3) 21 bar (304.5 psi)
(subtract from PH1/PH2 At high setting (4) 65 bar (942.5 psi)
to give PB1/PB2)
Maximum permissible Per cycle 625 bar (9062.5 psi)
pressure Accidental 1125 bar (16,312.5 psi)
Destruction pressure 2250 bar (32,625 psi)
Mechanical life 3 x 106 operating cycles
Cable entry for terminal models 1 entry tapped M20 x 1.5 mm for ISO cable gland, clamping capacity 7 to 13 mm
Pressure switch type Piston
(1) For 1 entry tapped for no. 13 cable gland, replace S12 with S11 (for example, XMLD500D1S12
becomes XMLD500D1S11).
(2) For component materials of units in contact with the fluid, see pages 72 and 73.
(3) Deviation of the differential at low setting point for switches of the same size:
± 3 bar (± 43.5 psi)
(4) Deviation of the differential at high setting point for switches of the same size:
± 10 bar (± 145 psi)
(5) Only for control of group 2 fluids, in accordance with directive 97/23/EEC.
Operating curves
High setting tripping points of contacts 1 and 2 Natural differential of contacts 1 and 2
Pressure
bar H
484
Rising pressure
bar F PH2
500
PB2
PH2 setting (rising pressure)
400
400 PH1
PB1
1 300
300
273.5
200
200 2
Time
100
100 41 G –– Adjustable value
25E --- Non adjustable value
41 0
0
4 20 100 200 300 419 435 bar Connection
25 100 200 256300 400 484 bar Falling pressure
Terminal model
PH1 setting (rising pressure)
Contact 2 Contact 1
(stage 2) (stage 1)
1 Maximum differential EF Contact 1 (stage 1)
13
11
23
21
12
24
22
Other versions For pressure switches with alternative tapped cable entries, such as NPT, etc. please consult
our Customer Care Centre.
67
References Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD
Accessories and replacement parts
XMLZL003 XMLZL004
Lead sealable protective cover – All types XMLZL011 0.030
to prevent unauthorised access to adjustment
screws
Replacement parts
Sealing gasket For sizes u 300 bar (XMLA/B/C/D) XMLZL010 0.015
(pack of 10 gaskets)
XMLZAppp,
XMLZBppp
Diaphragms – XMLpS35 XMLZL013 0.060
XZCC43FCP40B
68
Dimensions Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD
XMLC/D : 46
a XMLA/B : 35
(2)
max 162
56,5
(1)
17
57 = 45 =
XMLBM03, XMLBL05
40 (3)
(2) (4)
65
.
145
10
56
(1) c2 20 20
c1
(1) 1 fluid entry, tapped G 1/4 (female) or 1/4”-18 NPTF (female) XML Øa c1 c2
(2) 1 electrical connections entry, tapped M20 x 1.5 mm or Pg 13.5 BM03 150 155.5 80.5
or 1/2”-14 NPT
BL05 200 204 104
(3) 2 elongated holes Ø 10.2 x 5.2
(4) 1 elongated hole Ø 15.2 x 5.2 pL35, p001 110 – –
pS35, pS02, pS04 110 – –
pS10, pS20 86 – –
69
Dimensions (continued) Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD
113
(2)
37 5
37
17,5
(1) 23 = 20-22 =
56
120
(2)
158
34
(1)
13
30 = 37-40 =
122
Characteristics: References:
pages 17 to 67 pages 18 to 67
70
Dimensions (continued) Electromechanical pressure
and vacuum switches
OsiSense XMLA, XMLB, XMLC and XMLD
XMLBL35P, XMLB001P
(2)
175
86,5
(1) 55
37 5
130
(2)
54
(1) 25
76
71
Component materials of Electromechanical pressure
units in contact with fluid and vacuum switches
This information will assist in checking the corrosion resistance of
OsiSense XML
the pressure or vacuum switches in relation to the fluids controlled
XMLBM03Rpppp
XMLBM03Spppp (3)
XMLpM05Apppp (1)
XMLpM05Bpppp (1)
XMLpM05Cpppp (1)
XMLBM05Ppppp (1)
XMLBL05Rpppp
XMLBL05Spppp (3)
XMLpL35Spppp (3)
XMLBL35Ppppp (1)
XMLp001Rpppp (1)
XMLp001Spppp (3)
XMLB001Ppppp (1)
XMLp002Apppp
XMLp002Bpppp, XMLpS02Bpppp
XMLp002Cpppp (3)
XMLA004Apppp
XMLA004Bpppp
XMLA004Cpppp (2)
XMLA004Ppppp
72
Component materials of Electromechanical pressure
units in contact with fluid and vacuum switches
This information will assist in checking the corrosion resistance of
OsiSense XML
the pressure or vacuum switches in relation to the fluids controlled
XMLp004Bpppp, XMLpS04Bpppp
XMLp004Cpppp (3)
XMLp010Apppp
XMLp010Bpppp
XMLp010Cpppp (2)
XMLp010Ppppp, XMLpS10Apppp
XMLp020Apppp, XMLp035Apppp
XMLp020Bpppp, XMLp035Bpppp
XMLp070Dpppp, XMLp160Dpppp
XMLp300Dpppp
XMLp300Epppp (4)
XMLp300Npppp (5)
XMLp500Dpppp
XMLp500Epppp
XMLp500Npppp4 (5)
73
Presentation Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ACW and ADW
Presentation
Pressure switches OsiSense ACW and ADW are switches for control circuits, with
an adjustable differential.
Pressure switches OsiSense ACW are used to control the pressure of air, oils and
other non corrosive fluids, up to 131 bar.
Pressure switches OsiSense ADW are used to control the pressure of oils (including
synthetic), up to 340 bar.
– The switching point on rising pressure (high point - PH) is made by adjusting screw 2.
+ 2 This sets the differential between the low and high points, giving a switching point
on rising pressure of the displayed low point setting plus the differential setting.
6 –
2
The switching point on falling pressure (low point - PB) is made by adjusting screw 2.
+ This sets the differential between the high and low points, giving a switching point
on falling pressure of the displayed high point setting minus the differential setting.
74
Characteristics Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ACW and ADW
Environment characteristics
Pressure switch type ACW (bellows operated) ADW (piston operated)
Fluids controlled Air, oils and other non corrosive fluids, Oils and other fluids, from - 25 to + 120°C
from - 73 to + 125°C (for ADW5, ADW6, ADW7S1, ADW25
and ADW26)
Fluid connection G 1/4 (BSP female) conforming G 3/8 (BSP female) conforming
to NF E 03-005, ISO 228 to NF E 03-005, ISO 228
Electrical connection Terminals 1 tapped entry M20 x 1.5 mm for ISO cable gland.
(for ACWpM119012, ACWppM119012, ADWpM119012 and ADWppM119012).
References: Dimensions:
pages 76 to 79 pages 80 and 81
75
References, Electromechanical pressure switches
characteristics, OsiSense XM
For control circuits, OsiSense ACW
curves, Sizes 0.70 to 131 bar (10.15 to 1900 psi)
connections Adjustable differential, for regulation between 2 thresholds
Fluid connection G 1/4 (female)
MINI MINI
I I
MAXI MAX MAX
I I
MAX MAX
Adjustable range of switching point (PB) 0.07…0.70 bar 0.07…1.4 bar 0.07…5.2 bar 0.07…7.6 bar 1.4…12 bar 0.7…18 bar 0.7…21 bar 5.2…34 bar 10…69 bar 24…131 bar
(Falling pressure) (1.01…10.15 psi) (1.01…20.3 psi) (1.01…75.4 psi) (1.01…110.2 psi) (20.3…174 psi) (10.15…261 psi) (10.15…304.5 psi) (75.4…493 psi) (145…1000 psi) (348…1900 psi)
References References
Switches with 1 CO single-pole contact Switches with 1 CO single-pole contact
Electrical connection With one tapped entry ACW3M119012 ACW4M119012 ACW5M119012 ACW1M119012 ACW8M119012 ACW9M119012 ACW2M119012 ACW6M119012 ACW7M119012 ACW10M119012
M20 x 1.5 mm for ISO cable gland
With one tapped entry ACW3M129012 ACW4M129012 ACW5M129012 ACW1M129012 ACW8M129012 ACW9M129012 ACW2M129012 ACW6M129012 ACW7M129012 ACW10M129012
for n° 13 cable gland
With one tapped entry ACW23M129012 ACW24M129012 ACW25M129012 ACW21M129012 ACW28M129012 ACW29M129012 ACW22M129012 ACW26M129012 ACW27M129012 ACW20M129012
for n° 13 cable gland
6 6
2 CO switches Min. 0.05 bar (0.73 psi) 0.14 bar (2.03 psi) 0.41 bar (5.95 psi) 0.9 bar (13.05 psi) 1 bar (14.5 psi) 1.6 bar (23.2 psi) 2.4 bar (34.8 psi) 5.9 bar (85.6 psi) 9.3 bar (134.9 psi) 17 bar (246.5 psi)
Max. 0.48 bar (6.96 psi) 0.70 bar (10.15 psi) 1.4 bar (20.3 psi) 2.8 bar (40.6 psi) 2.8 bar (40.6 psi) 2.4 bar (34.8 psi) 10 bar (145 psi) 11 bar (159.5 psi) 14 bar (203 psi) 24 bar (348 psi)
Maximum permissible pressure 2 bar (29 psi) 7 bar (101.5 psi) 17 bar (246.5 psi) 17 bar (246.5 psi) 20 bar (290 psi) 41 bar (549.5 psi) 140 bar (2030 psi) 140 bar (2030 psi) 175 bar (2538 psi)
Fluids controlled Air, oils and other non corrosive fluids, from - 73 to + 125°C (1) Air, oils and other non corrosive fluids, from - 73 to + 125°C (1)
Cable entry, ACWpM119012, ACW2pM119012 1 tapped entry M20 x 1.5 mm for ISO cable gland. 1 tapped entry M20 x 1.5 mm for ISO cable gland. Clamping capacity 7 to 13 mm
screw terminals Clamping capacity 7 to 13 mm
ACWpM129012, ACW2pM129012 1 tapped entry for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5). 1 tapped entry for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5). Clamping capacity 9 to 13 mm
Clamping capacity 9 to 13 mm
(1) See “Component materials of units in contact with the fluid”, page 75. Other versions Pressure switches with alternative tapped cable entries: NPT, etc. Please consult our Customer Care
Centre.
Operating curve Contact block connections
Pressure
2
4
PH
3
PB
Time
–– Adjustable value
Other versions Pressure switches with alternative tapped cable entries: NPT, etc. Please consult our Customer
Care Centre.
Dimensions: Dimensions:
page 80 page 80
76 77
References, Electromechanical pressure switches
characteristics OsiSense XM
For control circuits, OsiSense ADW
Sizes 69 to 340 bar (1000 to 4930 psi)
Adjustable differential, for regulation between 2 thresholds
Fluid connection G 3/8 (female)
Pressure switches OsiSense ADW Piston operated, with drainage hole (1) Pressure switches OsiSense ADW Piston operated, with Quad-Ring piston seal
MINI
MINI
I
MAX
I
MAX
Adjustable range of switching point (PH) 9.3…69 bar 28…210 bar 38…340 bar Adjustable range of switching point (PH) 9.3…69 bar 28…210 bar 38…340 bar
(Rising pressure) (135…1000 psi) (406…3045 psi) (551…4930 psi) (Falling pressure) (135…1000 psi) (406…3045 psi) (551…4930 psi)
References References
Switches with 1 CO single-pole contact Switches with 1 CO single-pole contact
Electrical connection With one tapped entry ADW3M119012 ADW4M119012 ADW7M119012 Electrical connection With one tapped entry ADW5M119012 ADW6M119012 –
M20 x 1.5 mm for ISO cable gland M20 x 1.5 mm for ISO cable gland
With one tapped entry ADW3M129012 ADW4M129012 ADW7M129012 With one tapped entry ADW5M129012 ADW6M129012 ADW7S1M129012
for n° 13 cable gland for n° 13 cable gland
6 Fluids controlled Oils (including synthetic) only, from - 30°C to + 125°C (2) (3)
Fluids controlled Oils and other fluids, from - 25°C to + 120°C (1) (2) 6
Mechanical life 1 x 10 operating cycles (average value, depending on application)
6
Operating curve Contact block connections Operating curve Contact block connections
Pressure Pressure
2
4
2
4
PH PH
1
3
PB PB
Time Time
Dimensions: Dimensions:
page 81 page 81
78 79
Dimensions Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ACW
ACW3, ACW4, ACW23 and ACW24 ACW1, ACW5, ACW8, ACW9, ACW21, ACW25, ACW28 and ACW29
88 88
68 9,5 69 9,5 68 9,5 69 9,5
31 31 31 31
9,5
9,5
17
17
88
88
69
69
167
(1) (1)
190
9,5
9,5
18 18
31 31
31 31
(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model (1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
Ø: G 1/4 (female) Ø: G 1/4 (female)
ACW2 and ACW22 ACW6, ACW7, ACW10, ACW26, ACW27 and ACW20
88 88
68 69
6
9,5 69 9,5 68 9,5 9,5
31 31 31 31
9,5
9,5
17
17
88
88
69
69
173
(1) (1)
221
9,5
9,5
18
31 31
31 31
(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model (1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
Ø: G 1/4 (female) Ø: G 1/4 (female)
Characteristics: References:
pages 75 to 77 pages 76 and 77
80
Dimensions Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense ADW
9,5
16
88
69
(1)
176
9,5
18
(2)
31 31
(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
(2) Drainage hole, tapped G 1/8 (female)
Ø: G 3/8 (female)
6
9,5
16
88
69
(1)
176
9,5
18
31 31
(1) Tapped entry for n° 13 or ISO M20 cable gland, depending on model
Ø: G 3/8 (female)
Characteristics: References:
pages 75 to 79 pages 78 and 79
81
Presentation Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense XMX and XMA
Presentation
Pressure switches OsiSense XMX and XMA are switches for control circuits, with
1 an adjustable differential.
They are used to control the pressure of water and air, up to 25 bar.
2 Pressure switches OsiSense XMX have an internal setting screw that is only
accessible after removing the cover.
Pressure switches OsiSense XMA have an external setting screw that is accessible
without removing the cover.
Case
Pressure switches OsiSense XMX have a black opaque case.
3 Pressure switches OsiSense XMA can have a transparent case or a black opaque
case.
Setting
1
2 When setting pressure switches XMX or XMA, adjust the switching point on rising
4 pressure (PH) first and then the switching point on falling pressure (PB).
10
References: Dimensions:
page 84 page 87
82
Characteristics Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense XMX and XMA
Environment characteristics
Conformity to standards e, IEC/EN 60947-5-1
Ambient air temperature For operation °C - 25…+ 70 for 6 and 25 bar versions
- 25…+ 55 for 12 bar version
For storage - 40…+ 70
2
Fluids controlled °C Air, fresh water, sea water:
0…+ 70°C for 6 and 25 bar versions
0…+ 55°C for 12 bar version
Materials Case: polycarbonate impregnated with Lexan 500R fibreglass (black opaque cover)
or polycarbonate impregnated with Lexan 123 fibreglass (transparent cover)
Component materials in contact with fluid: chromated zinc alloy (fluid entry),
canvas covered nitrile (diaphragm) 3
Operating position All positions
Fluid connection G 1/4 or 4 x G 1/4 (BSP female) conforming to NF E 03-005, ISO 228
10
References: Dimensions:
page 84 page 87
83
References, Electromechanical pressure switches
characteristics OsiSense XMX for control circuits
Sizes 6 to 25 bar (87 to 362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
2
Adjustable range of switching point (PH) 1…6 bar 1.3…12 bar 3.5…25 bar 1…6 bar 1.3…12 bar 3.5…25 bar
(Rising pressure) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi)
Fluid connection G 1/4 (female) 4 x G 1/4 (female)
3 References
Switches with black opaque cover
Fluids controlled Air, fresh water, XMXA06L2135 XMXA12L2135 XMXA25L2135 XMXA06L2435 XMXA12L2435 XMXA25L2435
sea water (1)
Weight (kg) 0.430 0.650 0.430 0.650
Complementary characteristics not shown under general characteristics (page 83)
4
Possible differential Min. at low setting 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi)
(subtract from PH
to give PB) Min. at high setting 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi) 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi)
Max. at high setting 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi) 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi)
Maximum Per cycle 7.5 bar (108.7 psi) 15 bar (217.5 psi) 31.25 bar 7.5 bar 15 bar (217.5 psi) 31.25 bar
permissible pressure (453.1 psi) (108.7 psi) (453.1 psi)
Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
(1) Component materials of units in contact with the fluid, see page 83.
Operating curves
XMXA06ppppp XMXA12ppppp XMXA25ppppp
7
Pressure
bar bar bar
6
12 30 PH
Rising pressure
1 1
Rising pressure
Rising pressure
5 10 25
2
2 1
4 8 20 PB
3 6 15 2
8 2 4 10
Time
1 2
1.3 3.5
0 0 0 –– Adjustable value
0.2 1 1.8 2 3 4 4.8 6 bar 0.3 2 3.6 4 6 8 10 10.3 bar
Falling pressure 0.1 5 10 15 20.5 25 30 bar
Falling pressure Falling pressure
21
22
Other versions Pressure switches with alternative tapped cable entries: ISO, NPT, etc. Please consult our
Customer Care Centre.
10
Accessories: Dimensions:
page 86 page 87
84
References, Electromechanical pressure switches
characteristics OsiSense XMA for control circuits
Sizes 6 to 25 bar (87 to 362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 1 CO single-pole contact
2
Adjustable range of switching point (PH) 1…6 bar 1.3…12 bar 3.5…25 bar 1…6 bar 1.3…12 bar 3.5…25 bar
(Rising pressure) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi) (14.5…87 psi) (18.85…174 psi) (50.75…362.5 psi)
Fluid connection G 1/4 (female) 4 x G 1/4 (female)
References
Switches with black opaque cover
3
Fluids controlled Air, fresh water, XMAH06L2135 XMAH12L2135 XMAH25L2135 XMAH06L2435 XMAH12L2435 XMAH25L2435
sea water (1)
Switches with transparent cover
Fluids controlled Air, fresh water, XMAV06L2135 XMAV12L2135 XMAV25L2135 XMAV06L2435 XMAV12L2435 XMAV25L2435
sea water (1)
Weight (kg)
Complementary characteristics not shown under general characteristics (page 83)
0.430 0.650 0.430 0.650
4
Possible differential Min. at low setting 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi)
(subtract from PH
to give PB) Min. at high setting 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi) 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi)
Max. at high setting 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi) 4.2 bar (60.9 psi) 8.4 bar 20 bar (290 psi)
Maximum Per cycle 7.5 bar (108.7 psi) 15 bar (217.5 psi) 31.25 bar 7.5 bar
(121.8 psi)
15 bar 31.25 bar
5
permissible pressure (453.1 psi) (108.7 psi) (217.5 psi) (453.1 psi)
Accidental 13.5 bar (195.7 psi) 27 bar (391.5 psi) 56.25 bar 13.5 bar 27 bar 56.25 bar
(815.6 psi) (195.7 psi) (391.5 psi) (815.6 psi)
Destruction pressure 30 bar (435 psi) 100 bar 30 bar (435 psi) 100 bar
(1450 psi) (1450 psi)
Mechanical life
Cable entry
1 x 106 operating cycles
2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 6
Pressure switch type Diaphragm
(1) Component materials of units in contact with the fluid, see page 83.
Operating curves
XMAp06ppppp XMAp12ppppp XMAp25ppppp
1 1
Rising pressure
5 10 25
2
4
2 20 1
8
PB
2
8
3 6 15
2 4 10
1 2 Time
3.5
1.3
–– Adjustable value
0 0 0
0.2 1 1.8 2 3 4 4.8 6 bar 0.3 2 3.6 4 6 8 10 10.3 bar 0.1 5 10 15 20.5 25 30 bar
Falling pressure Falling pressure Falling pressure
Connections
1 Maximum differential 1 Maximum differential 1 Maximum differential 9
13
21
22
Other versions Pressure switches with alternative tapped cable entries: ISO, NPT, etc. Please consult our
Customer Care Centre.
10
Accessories: Dimensions:
page 86 page 87
85
References Electromechanical pressure switches
OsiSense XMX and XMA for control circuits
Accessories and replacement parts
References
Description Reference Weight
1 Fixing bracket XMAZL001
kg
0.035
XMAZL001
Knurled adjustment knob, Ø 36 mm XMLZL003 0.010
fits over adjustment screws to facilitate setting
2
13P cable gland With anti pull-out ring (for cable Ø 6…9 mm) DE9PM1201 0.005
XMLZL003
3 DE9PM1201
With anti pull-out ring (for cable Ø 9…12.5 mm) DE9PM1203 0.005
4
kg
Diaphragms Size 6 bar XMPZ31 0.005
DE9PM1202
5 XMPZ3p
10
Dimensions:
page 87
86
Dimensions Electromechanical pressure switches
OsiSense XM
For control circuits, OsiSense XMX and XMA
Dimensions
XMXA06L2135, XMXA12L2135 XMXA06L2435, XMXA12L2435
XMAp06L2135, XMAp12L2135 XMAp06L2435, XMAp12L2435
1
XMA: 7
XMA: 7
2
106
106
(1)
30.5 43.5
=
30.5
=
3
= = 58
97.5 57
. 57
r = 63 (2) r = 63 (2)
D
4
A C A
B
5
ØA = G 1/4 (female) ØA = ØB = ØC = ØD = G 1/4 (female)
(1) 2 tapped entries for n° 13 cable gland (1) 2 tapped entries for n° 13 cable gland
(2) Minimum clearance zone for screwing-on pressure switch at point A (2) Minimum clearance zone for screwing-on pressure switch at point A
XMXA25L2135, XMXA25L2435 Fixing bracket
XMAp25L2135, XMAp25L2435 XMAZL001
6
XMA: 7
7
126
(1)
43.5 30.5
8
58 = =
97.5 57
r = 63 (2)
D
9
C A
B
10
XMpp25L2135: ØA only = G 1/4 (female) (1) 2 tapped entries for n° 13 cable gland
XMpp25L2435: ØA = ØB = ØC = ØD = G 1/4 (female) (2) Minimum clearance zone for screwing-on pressure switch at point A
Characteristics: References:
page 83 page 84
87
Presentation Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense FTG, FSG and FYG
Presentation
Pressure switches OsiSense FTG, FSG and FYG are switches for power circuits.
They are used to control the pressure of water, up to 10.5 bar.
For specific needs, these 2 types of product can be supplied in IP 65 versions, thus
ensuring a higher degree of protection. They feature 2 cable entries, fitted with cable
gland, and are referenced FpGpNE.
Setting
1 Pressure switches with fixed differential (FTG)
Only the switching point on rising pressure is adjustable.
References: Dimensions:
pages 90 to 92 page 93
88
Characteristics Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense FTG, FSG and FYG
Environment characteristics
Pressure switch type FTGp FSGp and FYGp
FTGpNE FSGpNE and FYGpNE
Conformity to standards e, IEC/EN 60730
Ambient air temperature °C For operation: 0...+ 45. For storage: - 30...+ 80
Fluid connection FpG 2, FYGp2 G 1/4 (BSP female) conforming to NF E 03-005, ISO 228
Electrical connection FTGp, FSGp and Terminals. 2 cable entries, with grommet
FYGp
FTGpNE, FSGpNE Terminals. 2 entries incorporating 13P cable gland (DIN Pg 13.5)
and FYGpNE
6
1-phase 3-phase 1-phase 3-phase
References: Dimensions:
pages 90 to 92 page 93
89
References, Electromechanical pressure switches
characteristics OsiSense XM
For power circuits, OsiSense FTG
Size 4.6 bar (66.7 psi), fixed differential, for detection
of a single threshold. Switches with 2-pole 2 NC contact.
Degree of protection IP 20 or IP 65
Fluid connection G 1/4 (female) R 1/4 (male) G 1/4 (female) R 1/4 (male)
Cable entry 2 cable entries, with grommet 2 entries with 13P cable gland
(DIN Pg 13.5)
Clamping capacity – 9 to 13 mm
(1) Component materials of units in contact with the fluid, see page 89.
4.6
4
Pressure
3 PH
PB
2
1.4
1
1
2
0
0 0.3 1 2 3.1 4 5 bar Time
Falling pressure
–– Adjustable value
---- Non adjustable value
Dimensions:
page 93
90
References, Electromechanical pressure switches
characteristics OsiSense XM
For power circuits, OsiSense FSG
Size 4.6 bar (66.7 psi), adjustable differential, for regulation
between 2 thresholds. Switches with 2-pole 2 NC contact.
Degree protection IP 20 or IP 65
Fluid connection G 1/4 (female) R 1/4 (male) G 1/4 (female) R 1/4 (male)
(1) Component materials of units in contact with the fluid, see page 89.
(2) Variant: for a G 3/8 female fluid entry that pivots throughout 360°, select the FSG2NEG.
4.6
4
Pressure
3 1 PH
2
1.4 PB
1
1
2
0
0 0.3 1 2 2.3 3 3.4 4 5 bar Time
Falling pressure
1 Maximum differential –– Adjustable value
2 Minimum differential
Dimensions:
page 93
91
References, Electromechanical pressure switches
characteristics OsiSense XM
For power circuits, OsiSense FYG
Sizes 7 and 10.5 bar (101.5 and 152.3 psi), adjustable
differential, for regulation between 2 thresholds. Switches
with 2-pole 2 NC contact. Degree of protection IP 20 or IP 65
Adjustable range of switching point (PH) 2.8…7 bar (40.6…101.5 psi) 5.6…10.5 bar (81.2…152.3 psi)
(Rising pressure)
Degree of protection IP 20 IP 65 IP 20 IP 65
conforming to EN/IEC 60529
References
Fluids controlled Fresh water, sea water, FYG22 (2) FYG22NE FYG32 (3) FYG32NE
from 0°C to + 70°C (1)
Weight (kg) 0.340
Max. at high setting 2.7 bar (39.15 psi) 3.4 bar (49.3 psi)
Min. at low setting 1.2 bar (17.4 psi) 1.9 bar (27.55 psi)
Min. at middle setting 1.4 bar (20.3 psi) 2.1 bar (30.45 psi)
Min. at high setting 1.6 bar (23.2 psi) 2.3 bar (33.35 psi)
Maximum permissible Per cycle 8.75 bar (126.9 psi) 13 bar (188.5 psi)
pressure
Accidental 15 bar (217.5 psi) 15 bar (217.5 psi)
(1) Component materials of units in contact with the fluid, see page 89.
(2) Variant: for a 2.8 to 7 bar, IP 20, pressure switch with R 1/4 (male) fluid entry, select the FYG29.
(3) Variant: for a 5.6 to 10.5 bar, IP 20, pressure switch with R 1/4 (male) fluid entry, select the FYG39.
bar bar
8
Rising pressure
Rising pressure
10
7
9
6 8
1 Pressure
5 7 2 PH
4 1 2 5.6
5
2.8 4
3 PB
2
1
2
1
1
0
2
0
4
Dimensions:
page 93
92
Dimensions Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense FTG, FSG and FYG
Dimensions
FTG2, FSG2 FTG2NE, FSG2NE
102 72 106 72
Ø22
96
115
22
23
41
31 G 1/4 25
60 63
G 1/4
Ø22
105
123
22
32
49
25
31 R 1/4 63
60 R 1/4 6
Ø22
94
115
22
21
41
31 G 1/4
25
60
63
G 1/4
Characteristics: References:
page 89 pages 90 to 92
93
Presentation Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP
Presentation
Pressure switches OsiSense XMP are switches for power circuits (direct switching),
1 with an adjustable differential.
They are used to control the pressure of water and air, up to 25 bar.
b 2 degrees of protection:
v IP 54,
v IP 65.
4 Decompression valve
Depending on the model, 2 types of decompression valve can be fitted to pressure
switches OsiSense XMP:
b Straight, instant connection, decompression valve (connection by Ø 6 mm
plastic tube).
b Straight, olive connection, decompression valve (connection by Ø 6 mm plastic
or metal tube).
5
Setting
1
When setting XMP pressure switches, adjust the switching point on rising pressure
(PH) first and then the switching point on falling pressure (PB).
10
References: Dimensions:
pages 96 to 103 page 105
94
Characteristics Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP
Environment characteristics
Conformity to standards e, IEC/EN 60947-4-1
6
Resistance across terminals mW y 25 conforming to NF C 93-050 method A or IEC 255-7 category 3
Electrical durability
Operating rate: 600 operating cycles/hour
Power
kW
Number of operating cycles
a 400 V, 3-phase a 230 V, 3-phase
7
Load factor: 0.4
1.5 1 000 000 600 000
2.2 700 000 –
3 500 000 –
10
References: Dimensions:
pages 96 to 103 page 105
95
References, Electromechanical pressure switches
characteristics OsiSense XMP, IP 54
Size 6 bar (87 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact
1 1
2 1 2 2 1 2
2
Adjustable range of switching point (PH) 1…6 bar (14.5…87 psi) 1…6 bar (14.5…87 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC
Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
Possible differential Min. at low setting 0.8 bar (11.6 psi) 0.8 bar (11.6 psi)
5
Rising pressure
1
1
3
5 1
2
4
6
4
4
PB
3
8 2
1
8
Time
Adjustable value
0
0.2 1 1.8 2 3 4 4.8 6 bar
Falling pressure
9 1 Maximum differential
2 Minimum differential 9
10 10
96 97
References, Electromechanical pressure switches
characteristics (continued) OsiSense XMP, IP 54
Size 12 bar (174 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact
1 1
2 1 2
2 1 2
2
Adjustable range of switching point (PH) 1.3…12 bar (18.85…174 psi) 1.3…12 bar (18.85…174 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC
3 References (1)
Switches without decompression valve
References
Switches without decompression valve
3
Bare case 1 XMPA12B2131 XMPA12C2131 – XMPA12B2242 XMPA12C2242
Case with reset knob 2 XMPB12B2131 – – XMPB12B2242 –
Case with On/Off knob 2 XMPC12B2131 XMPC12C2131 XMPC12B2431 – XMPC12B2242 XMPC12C2242
Weight (kg) 0.430 0.430
6 Destruction pressure
Mechanical life
30 bar (435 psi)
1 million operating cycles
30 bar (435 psi)
1 million operating cycles
6
Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 2 entries tapped for n° 13 cable gland, conforming 2 entries incorporating n° 13 plastic cable gland (DIN Pg 13.5)
to NF C 68-300 (DIN Pg 13.5) Clamping capacity 9 to 13 mm
Pressure switch type Diaphragm Diaphragm
(1) References for individually packaged switches. Also available packaged in lots of 10. Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
To order, add the letter C to the reference selected from above. Example: reference for lot of reference. Please consult our Customer Care Centre.
7 of 10 pressure switches XMPA12B2131 in one package becomes XMPA12B2131C.
7
Operating curves Terminal connections
bar Pressure XMPpppBpppp XMPpppCpppp
12
PH
Rising pressure
5
3
1
1
3
10
8 8
2
8
6
4
4
PB
6
2 Time
1.3
9 9
0
0.3 2 3.6 4 6 8 10 10.3 bar
Falling pressure
1 Maximum differential
2 Minimum differential
10 10
98 99
References, Electromechanical pressure switches
characteristics (continued) OsiSense XMP, IP 54
Size 25 bar (362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact
1 1
2 1 2 1 2
2
Adjustable range of switching point (PH) 3.5…25 bar (50.75…362.5 psi) 3.5…25 bar (50.75…362.5 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC
3 References References 3
Switches without decompression valve Switches without decompression valve
Bare case 1 XMPA25B2131 XMPA25C2131
Case with reset knob 2 XMPB25B2131 –
Case with On/Off knob 2 XMPC25B2131 XMPC25C2131
Weight (kg) 0.650 0.650
4 Switches with straight decompression valve, olive connection
Case with On/Off knob 2 XMPR25B2131
Switches with straight decompression valve, olive connection
XMPR25C2131
4
Weight (kg) 0.670 0.670
Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
Possible differential Min. at low setting 3.4 bar (49.3 psi) 3.4 bar (49.3 psi)
5 5
(subtract from PH to give PB) Min. at high setting 4.5 bar (65.2 psi) 4.5 bar (65.2 psi)
Max. at high setting 20 bar (290 psi) 20 bar (290 psi)
Destruction pressure 100 bar (1450 psi) 100 bar (1450 psi)
Mechanical life 1 million operating cycles 1 million operating cycles
Cable entry 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5) 2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
Pressure switch type Diaphragm Diaphragm
6 Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
of reference. Please consult our Customer Care Centre.
6
Operating curves Terminal connections
bar XMPpppBpppp XMPpppCpppp
30
Rising pressure
5
3
3
7 7
25
20 1
6
4
4
15 2
10
8 8
3.5
0
0.1 5 10 15 20.5 25 30 bar
Falling pressure
1 Maximum differential
2 Minimum differential
9 9
10 10
100 101
References, Electromechanical pressure switches
characteristics (continued) OsiSense XMP, IP 65
Sizes 6 to 25 bar (87 to 362.5 psi)
Adjustable differential, for regulation between 2 thresholds
Switches with 2-pole 2 NC or 3-pole 3 NC contact
1 1
2 2
Adjustable range of switching point (PH) 1…6 bar (14.5…87 psi) 1.3…12 bar (18.85…174 psi) 3.5…25 bar (50.75…362.5 psi) 1…6 bar (14.5…87 psi) 1.3…12 bar (18.85…174 psi) 3.5…25 bar (50.75…362.5 psi)
(Rising pressure)
Type of contact 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC 2-pole 2 NC 3-pole 3 NC
3 References References
3
Switches with straight decompression valve, olive connection Switches with straight decompression valve, olive connection
Case with On/Off knob XMPR06B2133 XMPR06C2133 XMPR12B2133 XMPR12C2133 XMPR25B2133 XMPR25C2133 XMPR06B2433 XMPR06C2433 XMPR12B2433 XMPR12C2433 XMPR25B2433 XMPR25C2433
Weight (kg) 0.450 0.670 0.450 0.670
Complementary characteristics not shown under general characteristics (page 95) Complementary characteristics not shown under general characteristics (page 95)
4 Possible differential Min. at low setting 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 0.8 bar (11.6 psi) 1 bar (14.5 psi) 3.4 bar (49.3 psi) 4
(subtract from PH Min. at high setting 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi) 1.2 bar (17.4 psi) 1.7 bar (24.6 psi) 4.5 bar (65.2 psi)
to give PB)
Max. at high setting 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi) 4.2 bar (60.9 psi) 8.4 bar (121.8 psi) 20 bar (290 psi)
Destruction pressure 30 bar (435 psi) 100 bar (1450 psi) 30 bar (435 psi) 100 bar (1450 psi)
Mechanical life 1 million operating cycles 1 million operating cycles
5 Cable entry
Adjustment of high setting point (PH)
2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
By screw-nut
2 entries tapped for n° 13 cable gland, conforming to NF C 68-300 (DIN Pg 13.5)
By screw-nut
5
Pressure switch type Diaphragm Diaphragm
Other versions Pressure switches not listed above, comprising the equipment proposed for the choice
of reference. Please consult our Customer Care Centre.
5
3
3
6 12 30
PH
Rising pressure
Rising pressure
Rising pressure
5 1 10
1 25
2
6
4
4
2 20 1
4 8
7 7
PB
3 15 2
6
2 4 10
1 2 Time
3.5
1.3
0 0 0
0.2 1 1.8 2 3 4 4.8 6 bar Adjustable value
0.3 2 3.6 4 6 8 10 10.3 bar 0.1 5 10 15 20.5 25 30 bar
9 9
10 10
102 103
References Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP
Accessories and replacement parts
References
Description Reference Weight
1 Fixing bracket XMAZL001
kg
0.035
XMAZL001
Knurled adjustment knob, Ø 36 mm XMPMDR01 0.010
2 fits over adjustment screws to facilitate setting
XMPMDR01
3
DE9PM1201
Without anti pull-out ring DE9PM1202 0.005
(for cable Ø 6…9 mm)
4
With anti pull-out ring DE9PM1203 0.005
(for cable Ø 9…12.5 mm)
DE9PM1202
5
Description For pressure Sold in lots of Unit Weight
switch reference kg
Diaphragms Size 6 bar 50 XMPZ31 0.005
6
XMPZ3p Size 25 bar 50 XMPZ33 0.005
10
104
Dimensions Electromechanical pressure switches
OsiSense XM
For power circuits, OsiSense XMP
Accessories and replacement parts
Dimensions
XMPp06ppppp and XMPp12ppppp
Fluid connection G 1/4 or G 3/8 (female)
Without decompression valve
Fluid connection 4 x G 1/4 (female)
Without decompression valve
With straight, instant
connection, decompression
1
valve
19
19
2
106
106
119
(1) (1)
13
43.5
58 =
30.5
=
43.5
58 =
30.5
= 22.5 3
97.5 57 97.5 57
With straight, olive connection,
r = 63 (2) decompression valve
r = 63 (2)
D
4
A C A
119
B
5
13
ØA = G 1/4 or G 3/8 (female) ØA = ØB = ØC = ØD = G 1/4 (female)
(1) 2 tapped entries for n° 13 cable gland 22.5
(2) Minimum clearance zone for screwing-on pressure switch at point A
6
Fluid connection G 1/4 or 4 x G 1/4 (female) With straight, olive connection,
Without decompression valve decompression valve
3.6
19
19
52
40
24.75
7
126
136
12.5 38
18.5 54
(1)
43.5
58 =
30.5
=
22.5 8
97.5 57
r = 63 (2)
9
C A
105
Index Product reference index
106
Index (continued) Product reference index
107
Schneider Electric Industries SAS www.tesensors.com
Head Office The information provided in this documentation contains general descriptions and/or technical
35, rue Joseph Monier characteristics of the performance of the products contained herein. This documentation is not
F-92500 Rueil-Malmaison intended as a substitute for and is not to be used for determining suitability or reliability of these
France products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
DIA4ED2150201EN
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein.