Etabs Checklist
Etabs Checklist
Enter Correct Material , Modifiers and STRAND AREA for TENDON in format "TENDON THICKNESS GRADE"
Enter Correct Material , Modifiers and Rebars for DECK in format "DECK THICKNESS GRADE"
STEP-7 DRAW THE STRUCTURE (Take Care of One Storey and All Storey Option)
Draw Columns, Beams, Slabs and Walls
Check the model for cantilever slabs/projections/water tanks/planters /ramp/staircase if any.
Assign Fixed Support /Pinned Support at the Foundation Base as per the requirement
Draw Retaining Walls if required
Assign Releases to the beams
Assign the diaphragms , pier labels and spandrel labels as per the requirement
Check the Model for any modelling errors. Fix them if required
Check that the model does not run into the instability while analyzing by clicking on Show details. If the model is unstable or ill conditioned , go
to Step-7 and check the model for excessive deflection/displacement
Check the Analysis Log and result Warnings
Check the global forces and approximately cross check the result
Check the deformed shape under first mode and second mode. Desirable shapes under various country codes is linear translation
If the first or second mode is torsion ,go to Step-7 and introduce or delete the walls to remove the torsion behavior. Tip- Check the centre of
torsion to access the ground situation.
STEP-16 ANALYZE THE MODEL AGAIN TO CHECK DYNAMIC ANALYSIS CORRECTNESS AND COMPLIANCE WITH DESIGN CODES
Check that the Response Spectrum is correctly scaled.
Check the mass participation factor in first three modes and all modes. Check that the participation factor is compliant to codes or not.
Check Inter Story drift and overall deflections and that shall be chacked for service load combinations
Check Stiffnesses , Deflections and other important relavent design values from Tables.
If not compliant with the codes , go to Step-7.
STEP-18 SAVE AS THE MODEL FOR WIND LOAD ANALYSIS (Only for Buildings greater than 50m)
Save as the Model for Wind Load Analysis
Cracked Section properties shall be changed as per IS 16700 (Table 6)
Damping shall be changed for material to 2 percent
Design the structure for Wind load only and compare the results with Seismic case.
The structure shall be designed for the most sever case