Seismic Co-Efficient Calculation As Per NBCC - Equivalent Static Force Procedure For Structures Satisfying The Conditions of Article
Seismic Co-Efficient Calculation As Per NBCC - Equivalent Static Force Procedure For Structures Satisfying The Conditions of Article
Equivalent Static Force Procedure for Structures Satisfying the Conditions of Article 4.1.8.7.
As per NBCC 2010, sec 4.1.8.11 (1) Equivalent Static Procedure shall be used for the structures that meet any of the following conditions
V=𝑆(𝑇_𝑎 ) 𝑀_𝑣 𝐼_𝐸 𝑊/(𝑅_𝑑 𝑅_0)
4.1.8.7 i IE. Fa.Sa(0.2) < 0.35 Not satisfied
ii Height of structure < 60m Ta = 0.05 (hn)3/4 Satisfied conditions : satisfied
iii Structures with structural irregularity that are less than 20m height have Ta < 0.5 Satisfied
4.1.8.11. (2) a. Lateral Earthquake Cooefficient, V = 0.43 Constant
𝑆(𝑇)=𝐹𝑎𝑆𝑎(0.2)𝑓𝑜𝑟 𝑇≤0.2𝑠
b. Site Class 𝑆(𝑇)=𝐹𝑣𝑆𝑎(0.5)"or " 𝐹𝑎𝑆𝑎"(0.2), whichever is smaller for T = 0.5 s" = C
4.1.8.4.A(For Stiff Soil)
c.
4.1.8.11. (3).(c) The fundamental lateral period for other structures, Ta = 0.07 seconds
𝑆(𝑇)=𝐹𝑣𝑆𝑎(1.0)𝑓𝑜𝑟 𝑇=1.0𝑠
𝑆(𝑇)=𝐹𝑣𝑆𝑎(2.0)𝑓𝑜𝑟 𝑇=2.0𝑠
OK
𝑆(𝑇)=𝐹𝑣𝑆𝑎(2.0)/2 𝑓𝑜𝑟 𝑇≥4.0𝑠
d.
The height of the structure hn = 1.7 m
= 1.3 Constant
4.1.8.5.(1) n. The earthquake importance factor IE
4.1.8.18 a. Lateral force, Vp Vp= 〖 0.3𝐹_𝑎 𝑆_𝑎 〗 _ ( 〖 0.2) 𝐼 〗 _(𝐸 ) 𝑆_(𝑝 ) 𝑊_𝑝
Table 4.1.8.4B b. Site coeff. Fa
c. Sa(0.2)
4.1.8.5 d. Imprtance factor, Ie
e. Sp = CpArAx/Rp
Table 4.1.8.18 f. Element or component factor, Cp
Table 4.1.8.18 g. component force amplification factor, Ar
4.1.8.18 sent-1
h. Height factor, Ax = (1 + 2hx/hn )
hx
hn
Table 4.1.8.18 i. Component response modification factor, Rp
j. Weight factor
010| 4.1.8.11
= 1.00
= 0.00
= 3.00
= 1.5
= 1.00
1 Equipment time period:
1 Natural Frequency of Centrifuge = 10 Hz
2 Natural time period of Centrifuge = 0.1 sec
Per support
Vertical upper load = -1124.25 lb
Vertical lower load = -4496.25 lb