0% found this document useful (0 votes)
125 views1 page

Metering CT Burden Calculation

This document provides calculations for sizing a metering current transformer (CT) with the following key details: - The CT will have a primary to secondary ratio of 200:1 with an accuracy class of 0.2 and an rated burden of 10VA. - Factors considered in the sizing include the ammeter and meter burden, lead resistance, and adding a 20% margin to the total burden of 1.43VA. - The recommended CT has a ratio of 200:1, accuracy class of 0.2, VA rating of 10VA, and an insulation factor less than or equal to 5.

Uploaded by

lalitendu jena
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views1 page

Metering CT Burden Calculation

This document provides calculations for sizing a metering current transformer (CT) with the following key details: - The CT will have a primary to secondary ratio of 200:1 with an accuracy class of 0.2 and an rated burden of 10VA. - Factors considered in the sizing include the ammeter and meter burden, lead resistance, and adding a 20% margin to the total burden of 1.43VA. - The recommended CT has a ratio of 200:1, accuracy class of 0.2, VA rating of 10VA, and an insulation factor less than or equal to 5.

Uploaded by

lalitendu jena
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CT sizing calculation for

Metering CT
MV SWITCHGEAR, L&T ELECTRICAL and AUTOMATION SAUDI ARABIA CO.LTD
SWITCHBOARD

CUSTOMER : ZAHRAN OPERATIONS & MAINTENANCE


Project: DAMMAP PORT
Consultant: RADICON GULF CONSULT

Rev Remark Date Prepared CKD By Appd.


By By
A ISSUED FOR INFORMATION ONLY 02.12.15 SN AMF AKM

Calculation of metering CT for

CT LT ratio (primary/Secondary) Ip/Is 200 / 1


ISF 5
Class of accuracy 0.2
One way lead length o relay (L) Meter 5
Wire cross section (A) Sq. mm 2.5
RL 2way [2RL=2*8.87*(L/1000)*2.5/A]… Wire resistance 8.87 ohm/Km for 2.5 Sq.mm Ohm 0.0887

VA burden of ammeter VA 0.6


VA burden of MFM VA 0.5
Burden of lead VA 0.0887
Total burden including 20% margin VA 1.43
Recommended VA of CT VA 10

CT specification
CT ratio 200 / 1
Class 0.2
VA rating 10
ISF<= 5

1 OF 1