Protectorelay Flame Safeguard Controls: Specifications Selection Guide

The document provides specifications for R4780B and R4780C flame safeguard controls used to automatically operate and safely control combustion in oil or gas fired burners over 500,000 Kcal/h. The controls use reliable components to ensure correct combustion sequence. They monitor flame detection, have timing controls for pre-ignition, ignition, and more. The controls can interface with auxiliary devices and have LED indicators, terminal contact ratings, and dimensions are provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views1 page

Protectorelay Flame Safeguard Controls: Specifications Selection Guide

The document provides specifications for R4780B and R4780C flame safeguard controls used to automatically operate and safely control combustion in oil or gas fired burners over 500,000 Kcal/h. The controls use reliable components to ensure correct combustion sequence. They monitor flame detection, have timing controls for pre-ignition, ignition, and more. The controls can interface with auxiliary devices and have LED indicators, terminal contact ratings, and dimensions are provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

FLAME SAFEGUARD CONTROLS

R4780B,C
Protectorelay Flame Safeguard Controls

The R4780B, C are flame safeguard controls used to provide automatic


operation and safety of combustion in oil-fired, gas-fired, or oil-gas fired
burners with a burning capacity of 500,000 Kcal/h or greater.

They are constructed from reliable components to ensure that the


combustion equipment operates without fail in the correct sequence.

Specifications Selection Guide


Model No. R4780B R4780C Model No. Power Sequence timing (under normal temperature, normal humidity, rated voltage)
Flame detector C7007A, C7008A, or C7012A C7027, C7035A supply Pre- Ignition Ignition Pilot- Main Main Post- Lockout Flame response
Standard flame current 2µA min. 4µA min. (50/60Hz) purge waiting trial only trial stabilized purge
Power consumption 9W +25% max. R4780B1003-1 100Vac When flame current is
Ambient temperature -20 to +60°C R4780B1011-1 200Vac max. 2µA 1.5 = 0.5s
35 ± 5s 7.5 ± 2.5s 4 ± 1s 8.5 ± 3.5s 6.5 ± 2s 8.5 ± 3s 20 ± 8s
Ambient humidity 90%RH at 40°C R4780C1001-2 100Vac 30s When flame current is
Mounting of protectorelay Plug-in to sub-base R4780C1019-2 200Vac 8.5µA
Weight Approx. 1.0kg Sequence at flame failure: Non-recycle (for a pilot system, it is possible to use either an interrupted
Auxiliary devices Flame current tester and Flame simulator pilot or an intermittent pilot.)
Flame/alarm indicator LED Lit: Normal combustion
Flashing: Loss of flame whilst burner, ground short-circuit, or
false flame signal at start-up
Accessories Surge absorber 83968019-109 (for R4780B), 83968019-001 (for R4780C)
Contact Ratings
Terminal No. Load Contact rating
3 Blower 4A 120Vac
Dimensions (unit:mm) 2A 240Vac
4 Ignition transformer 400VA
5 Intermittent pilot 400VA
6 Interrupted pilot 400VA
7 Main valve 800VA
8 · 9 · 10 · 11 Control meter 200VA
21 Alarm 75VA
Total load under normal condition: Max. 6A 200Vac.