Spec 3000 MT 020514

The document provides specifications for constructing a conventional godown with a capacity of 3000 metric tons. It details the size, foundation, walls, flooring, roofing, doors, and other structural elements. The specifications are general and may vary depending on the site conditions and design requirements.

Uploaded by

Sarthak Shukla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views

Spec 3000 MT 020514

The document provides specifications for constructing a conventional godown with a capacity of 3000 metric tons. It details the size, foundation, walls, flooring, roofing, doors, and other structural elements. The specifications are general and may vary depending on the site conditions and design requirements.

Uploaded by

Sarthak Shukla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

ENGINEERING SPECIFICATIONS

SCHEDULE – I

General details of standard conventional godown of 3000 Metric tonne


capacity (MTC)

(A) Details for 21.80 m C/C span godown (capacity = 3000 MT, No. of
compartment = 2 Nos.):

• Godown size (Centre to Centre) = 69.75m x 21.80m


• Godown size (Outer to Outer) = 70.21m x 22.26m
• Godown size excluding Verandah = 70.21m x 22.26m
• Godown size including one Verandah (1.83m) = 70.21m x 24.09m
General details:

1. Front Road side Verandah Width: 1.83m


2. Plinth level: 0.60m to 0.91m depending upon the topography of plot.
3. 3000 MT godowns: Two compartments.
4. Compartments C/C length: 41.85m and 2nd compartment of 27.90m.
5. Total No. of stacks (size = 6.10m x 9.14m) in both the compartments: 18
Nos. + 3 half sized stacks.
6. Godown height on each side: 5.48m from plinth/floor level.
7. Verandah Truss height: 3.48m from plinth/floor level.
8. No. of Rolling shutters/steel garage doors: 8 Nos. in 3000 MT for 21.80m
span.
9. Size of rolling shutters/garage doors (clear opening): 1.83m x 2.44m.
10. Bottom ventilators (V6) size 0.60m x 0.60m: 22 Nos. (Both long walls).
11. Top ventilators size 1.50m x 0.60m: 30 Nos. (Both long walls and one in each
panel).

NOTE:

(i) Continuous platform of 1.83 meter width shall be provided on front side of
the godowns. On the back side, 0.23 mt projected RCC nosing is provided
only in front of garage doors/rolling shutters or 0.90 mt wide platform is
provided in front of garage shutters/rolling shutters openings only as per site
requirement.

(ii) Any details not mentioned above will be as per the CWC existing
specifications for conventional godowns. In case CWC does not have any
specifications, then relevant IS code 607 of 1971 for construction of godowns
will be followed.

(iii) Tubular Trusses: As per the wind speed zone (33m/sec to 55m/sec) classified
in the relevant latest BIS code.

(iv) Total Carpet area of the godowns: (41.39m+27.44m) x21.34 = 1467.77 Sqm.

(v) Ancillaries Required: Compound wall, office block alongwith sanitary,


electrification & water supply work as per the requirement.
SCHEDULE-II

SPECIFICATIONS FOR THE CONSTRUCTION OF CONVENTIONAL TYPE


GODOWNS

GODOWN

1. Normal Size of Godown of 3,000 MT capacity.


Internal dimensions of the godown:
41.39m x 21.34m + 27.44m x 21.34m = 1468.83 sq.mt

1. FOUNDATION: The depth of foundation is proposed for Ordinary Soils at 1.30 M


for columns and 1.20 M for panel walls (foundation design is based on for soil
capacity of 10 tonnes per sq.mt).For expensive soils/black cotton soils, foundation
should be suitably designed alongwith requirement of pile foundations as per site
requirement.
PCC 1:5:10 (1 cement: 5 coarse sand: 10 stone aggregate of 40 mm nominal size) is
provided under columns and panel walls respectively. R.R. Masonry/Brick Masonry in
cement mortar 1:6 (1 cement: 6coarse sand) is proposed for the foundation and
superstructure. The excavated good quality of earth shall be reused to fill in the
wall- trenches and remaining earth is used for filling under floors. Blanket course of
sand/moorum under bed concrete are provided for black cotton soils/poor soils to
increase soil bearing capacity. Design of footings of structure should be in
accordance with the bearing capacity of soil at site.

2. PLINTH BEAM, TIE BEAM & COLUMNS: All RCC works shall be executed in
design mix of M 25 or nominal mix of 1:1½:3 (1 cement: 1½ coarse sand: 3 stone
aggregate of 20 mm nominal size). 0.15m thick RCC tie beam is provided on all the
walls at a height of 5.18m from floor level in the godown. Grade beam at ground
level & an additional beam at door level are to be provided in earthquake Zone iii &iv
as per design to withstand the bearing loads & earthquake forces.

3. SUPER STRUCTURE: All the walls are to be provided with 34 cm thick brick
masonry or 38 cm thick RR masonry in cement mortar 1:6 (1 cement: 6 coarse
sand).

4. FINISHINGS: 12mm thick cement plaster in cement mortar 1:6 (1 cement: 6


fine sand) on both sides of walls, 6mm thick plaster in cement mortar 1:3
(1cement:3 fine sand) on exposed surface of columns is provided. 3 or more coats
of white wash on inner side of walls & colour wash/ snowcem on external side of
walls are to be provided.

5. PLATFORM: Covered verandah of 1.83 m wide with cantilever Truss on road side
to be provided.
6. FLOORING:
(A) In Ordinary soils:
(a) Rammed Earth filing as per requirement. (b) 150 mm thick sand filling (c) WBM
with 150 mm thick stone aggregate of grade II in two layers and 75mm thick layer
of stone aggregate of grade III(d) 50mm thick C.C flooring 1:2:4 (1 cement: 2
coarse sand: 4 coarse aggregate 20 mm nominal size)with a floating coat of neat
cement. Total crust thickness of flooring is 27.5 cm.

(B) In Expansive soils/Black cotton soils:


(a) WBM with 150 mm thick stone aggregate of grade I, 100 mm thick layer of stone
aggregate grade II and 75 mm thick layer of stone aggregate grade III (b) 50 mm
thick CC flooring 1:2:4 (1 cement: 2coarse sand: 4 coarse aggregate 20 mm nominal
size) with a floating coat of neat cement.
Total crust thickness of the flooring is 37.5 cm.
An additional 235 mm thick blanket course of moorum underneath the WBM grade-I
is provided in such soils.

7. ROOFING: Tubular trusses on RCC columns to support Pre-painted polyester


coated sheets/GI/Galvalume sheeting shall be provided. Fibre glass (Translucent)
sheets are provided for about 2% of the roofing area for natural light. Inside height
of godown from Plinth level to Bottom of Trusses is 5.48 m. Pre-engineered steel
structures with pre-painted polyester coated sheets with turbo ventilators,
translucent sheets etc. are also used in the warehouses.

8. WINDOWS, VENTILATORS, ROLLING SHUTTERS AND STEEL DOORS:


Previously we were providing Rolling shutters (clear opening) of size 1.83m x 2.44m
in the godowns. Now1.83x2.44m size steel garage doors are provided in place of
rolling shutters and these doors are to be fixed on outer edge of the walls for easy
and full opening of the doors. Windows of size 0.60m X0.60m and ventilators of size
1.50m X 0.60 m with angle iron frame as shown in the relevant drawing fixed on
inner edge of the walls. Top ventilators are also covered with semi barrel type
expanded metal grill for checking the entry of birds.

9. ROADS:
(A) In ordinary soils:
(a) WBM with 100 mm thick layer of stone aggregate grade I, over it 20 cm thick
plane cement concrete road in the mix of 1:1½:3 (1 cement: 1½ coarse sand:3
stone aggregate 40mm nominal size)
Total thickness is 30 cm.

(B) In Expansive soils/Black cotton soils:


(a) WBM with 230 mm thick layer of stone aggregate grade I, over it 20 cm thick
plane cement concrete road in the mix of 1:1½:3 (1 cement: 1½ coarse sand:3
stone aggregate 40mm nominal size)
Total thickness is 43 cm.
An additional 300 mm thick blanket course of moorum beneath the WBM of grade-I
is provided in such soils.
10. COMPOUND WALL: 1.83 m high boundary wall in brick/RR masonry above
Ground level with0.6m high, 6 rows of barbed wire/concertina coils with angle iron
posts 1.02m C/C on top of wall is to be provided. 15mm thick plastering in cement
mortar 1:6 on rough side of the wall and 12mm thick plastering with cement mortar
1:6 on plain side of the wall is to be provided.

11. BOUNDARY WALL GATE & WICKET GATE: 4.90 m wide main steel gate and
0.91mwide wicket gate are provided as per drawing.

12. OFFICE BUILDING: Office space is provided as per the requirement of the
staff/external customer’s alongwith all allied facilities of toilets, drinking water etc.

The above specifications are general specifications and these are not
exhaustive. These specifications would vary as per need of the site and as per the
design requirement at a particular site.
ABSTRACT OF COST/BILL OF QUANTITIES FOR THE
CONSTRUCTION OF 3000 MT CAPACITY GODOWN

(CIVIL WORKS)
SL. DESCRIPTION QTY. UNIT RATE AMOUNT Remark
NO.

1. Earth work in excavation by mechanical


means (Hydraulic excavator)/ manual means
in foundation trenches or drains (not
exceeding 1.5 m in width or 10 sqm. on plan)
including dressing of sides and ramming of
bottoms, lift up to 1.5 m including getting out
the excavated soil and disposal of surplus
excavated soil as directed, within a lead of
50 m.
2.8.1
a) All kinds of soil 395.00 Cum
72

2. Filling available excavated earth (excluding


rock) in trenches, plinth, sides of foundations
etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by 395.00 Cum 2.25
ramming and watering, lead up to 50 m and
lift up to 1.5 m. 75

3. Supplying and filling in plinth with fine sand


under floors including, watering, ramming
consolidating and dressing complete. 24.00 Cum. 2.27

75

4 Providing and laying in position cement


concrete of specified grade excluding the cost
of centering and shuttering – All work up to
plinth level:
a) 1:5:10 (1 Cement : 5 coarse sand : 10 73.50 Cum 4.1.10
graded stone aggregate 40 mm
nominal size). 85

5. Providing and laying cement concrete in


retaining walls, return walls, walls (any
thickness) including attached pilasters,
columns, piers, abutments, pillars, posts,
struts, buttresses, string or lacing courses,
parapets, coping, bed blocks, anchor blocks,
plain window sills, fillets etc. up to floor five
level, excluding the cost of centering,
shuttering and finishing:

a) 1:2:4 (1 cement : 2 coarse sand : 4 3.60 Cum 4.2.3


graded stone aggregate 20 mm nominal
size). 85

6. Supply & filling selected earth obtained from


approved source (excluding rock) in layers
not exceeding 20 cm. in depth breaking
clods, watering and consolidation of each
layer by half tonne roller or by using wooden
or steel hammer and rolling every third and 328.00 Cum 4AR-12
top most layer with power roller of minimum
8 tonnes and dressing up in embankments
or roads plinth filling or filling of ground
depressions within the campus, i/c of all
leads and lifts (no royalty or segonorage
shall be paid by the CWC to contractor)

7 Providing and laying in position specified


grade of reinforced cement concrete
excluding the cost of centering, shuttering,
finishing and reinforcement – All work up to
plinth level:
47.00 Cum 5.1.2
a) 1:1.5:3 (1 Cement 1.5 coarse sand : 3
graded stone aggregate 20 mm 96
nominal size).
8 Reinforced cement concrete work in walls
(any thickness), including attached pilasters,
buttresses, plinth and string courses, fillets,
columns, pillars, piers, abutments, posts and
struts etc. up to floor five level excluding cost
of centering, shuttering, finishing and
reinforcement:
a) 1:1.5:3 ( 1 cement : 1.5 coarse sand : 3
graded stone aggregate 20 mm nominal size) 46.00 Cum 5.2

96

9 Reinforced cement concrete work in beams,


suspended floors, roofs having slope up to 15
degree landings, balconies, shelves, chajjas, 11.60 Cum 5.3
lintels, bands, plain window sills, staircases
and spiral stair cases up to floor five level 96
excluding the cost of centering, shuttering,
finishing and reinforcement with 1:2:4 (1
cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size).

10 Reinforced cement concrete work in vertical


and horizontal fins individually or forming box
louvers, facias and eaves boards up to floor
five level excluding the cost of centering, 0.30 Cum 5.8
shuttering, finishing and reinforcement with
1: 1.5 : 3 (1 cement : 1.5 coarse sand : 3 97
graded stone aggregate 20 mm nominal
size).

11. “steel work in single section for door frame,


made of M.S. angle 75× 75× 6 mm, joints
mitered welded with 8 nos. 30 cm long lugs 24 AR-
of M.S angle 40x40× 6 mm to act as hold 12
fasts, complete “ as per drg. No. 456.00 Kg.
CWC/PG/380/5 i/c applying priming coat of
yellow zinc chromate primer, fixing of
Cement. Conc Block of Cement. Concrete
1:2:4( 1 cement : 2 coarse and : 4 graded
stone aggregate 20 mm nominal size ) of size
30× 30× 23 cm etc. (Cement.conc. Blocks
shall be paid separately)

12. Providing, hoisting and fixing up to floor five


level precast reinforced cement concrete in
small lintels not exceeding 1.5m clear span
up to floor five level including the cost of
required centering, shuttering and finishing
smooth with 6 mm thick cement plaster 1:3
(1 cement : 3 fine sand) on exposed surfaces 0.18 Cum 5.13
but excluding the cost of reinforcement with
1:2:4 (1 cement : 2 coarse sand : 4 graded 98
stone aggregate 20mm nominal size)

13. Centering and shuttering including strutting, 5.9


propping etc. and removal of form for :
97
a) Foundations, footings, bases of
columns, etc. for mass concrete. 134.00 Sqm
b) Columns, Pillars, piers, Abutments,
Posts and Struts. 422.00 Sqm.
c) Lintels, beams, plinth beams, girders,
111.00 Sqm.
bressumers and cantilevers.
d) Walls (any thickness) including
41.00 Sqm
attached pilasters, butteresses, plinth
and string courses etc.

e) Vertical and horizontal fins individually 8.70 Sqm


or forming box louvers band, facias
and eaves boards. 19.00 Sqm.
f) Small lintels not exceeding 1.5m clear
span, moulding as in cornices,
window sills, string courses, bands,
copings, bed plates, anchor blocks
and the like.
14. Reinforcement for R.C.C. work including 5.22.6
straightening, cutting, bending, placing in
position and binding all complete upto floor V 99
level:

a) TMT bars 5896.00 kg

b) Mild steel & medium tensile steel bars 1156.00 Kg

15. Brick work with common brunt clay FPS (Non 6.4.2
modular) bricks of class designation 7.5 in
superstructure above plinth level up to floor V 395.00 Cum
level in all shapes and sizes. Cement Mortar
1:6 (1 cement : 6 Coarse Sand)

16. Brick work with common brunt clay F.P.S.( 6.1.2


non-modular) bricks of class designation 7.5
in foundation and plinth in : 182.00 Sqm.
a) Cement mortar 1:6 (1 cement : 6
coarse sand)
17. Structural steel work in single section fixed 10.1
with or without connecting plate including
cutting, hosting, fixing in position and 176
applying a priming coat of approved steel
primer all complete:

a) For steel fenders 100 X 100 X 8 mm.


1013.00 Kg.

18. Providing and fixing M.S. round holding down 10.19


bolts with nuts and washer plates complete
for fixing platform trusses and embedded in 179
RCC column as per drawing No.
CWC/PG/393/A/1:

a) 20mm dia bolts 0.91m long with 10mm


thick MS anchor plate size 10 x 10 cm. 361.00 Kg.

b) 20 mm dia .3 mt. long with 100 mm thick


MS plate of size 20 X 8 cm for every pair of
96.00 Kg.
bolts.

19. Providing and fixing bolts including nuts and 124.00 Kg. 10.20
washers complete.
179

20. Steel frame work in single section including 31 AR-


cutting hoisting fixing including applying 12
priming coat of zinc chromate yellow primer
for fire bucket stand” embedded in C.C.
1:2:4 (1 cement: 2 coarse sand : 4 graded
stone aggregate 20mmnominal size) Blocks
of size 0.26m x 0.15m x 0.15m including
providing and fixing of 6 nos of fire buckets
of 10Ltrs/capacity each having hemispherical
bottom of approved quality with 6 nos of 4 sets Each
16mm dia hooks for hanging fire buckets
including making holes welding, lettering on Set
fire buckets complete as per the instruction
of Engineer in Charge and drawings
No.CWC/PG/226. a) In angles of size
50x50x6 mm.
21. a) Providing and fixing steel glazed 8 AR-12
ventilators of steel sections of 40x40x6 mm
size Angle iron, 40x40x6 mm Tee Section for
ventilators frame and 25x25x4 mm. Angle
iron for ventilator shutter with 15x3 M.S. flat,
Beading, Joints mitered with M.S. fittings and
40x40x6 mm M.S. angle hold fasts 30 cm.
Long embedded in cement concrete block of
size 35x10x10 cm of C.Conc. Mix 1:3:6 ( 1
cement : 3 coarse sand: 6 graded stone
aggregate 20 mm nominal size) including
providing and fixing of glass panes of nominal
thickness 4 mm (weighing not less than
10.00 Kg)/Sqm.) with glazing clips and
special metal sash putty of approved quality
and manufacture complete including a 31.00 Sqm.
priming coat with ready mixed Zinc Chromate
yellow primer of approved brand and
manufacture with necessary M.S.
pivot/hinges 50 mm projecting type
catchers/handles, M.S. Tower bolts 100 mm
long and necessary eyes welded to frame.

Note: the ventilator to be fabricated as per


drg. No. CWC/PG/380/5 and as per latest
CPWD specifications )Rate includes cost of all
materials and labour but excluding cement
conc. Blocks which shall be paid separately
and measurement would be done for outer to
outer dimension of frame)

22. Providing and fixing 1.25 mm thick M.S sheet 32.75 Sqm. 22 AR-
steel door with frame of 40X40X6 mm Angle, 12
3 mm thick gusset plates at junction and
corners by using MS angle 40X40X6 mm
diagonal braces, necessary fittings like Bush
hinges, handles, tower bolts sliding door bolts
as per Drg. No. CWC/PG/380/5 including a
priming coat of approved steel primer of zinc
chromate yellow.
23. Providing & fixing expanded metal mesh 21 AR-
frame with expanded metal 20x6 mm strands 12
3.25 mm wide and 1.6 mm thick, weighing
not less than 4.078 kg/sqm and frame made
of 25x4 mm M.S. flat sub divided into three
equal panels with 25x4 mm M.S. flat
expanded metal to be fixed with 19x3 mm
M.S. beading tack welded, 4 nos. of M.S.
cleats of size 50x50x4 mm size with holes for
12 mm dia bolt i/c and manufacture complete
as per drg. No.CWC/PG/382 and as per
instructions of Engineer in charge. The whole
frame with expanded metal mesh is to be
fixed on the outer side of V4 openings with 40.00 Sqm
12 mm dia 250 mm long bolts with nuts &
washers embedded in C.Conc. Blocks of size
75x75x125 mm of C.Conc. 1:2:4 (1 cement :
2 coarse sand : 4 graded stone aggregate 20
mm nominal size) in brick bands/RCC lintel if
any of the ventilators.

NOTE: Payment for cement conc. Blocks,


Bolts, shall be paid separately under relevant
items, payment for M.S. frame shall be paid
on area basis of outer to outer dimension of
frame.

24 Cement concrete flooring 1:2:4 (1 cement : 2 36 AR-


coarse sand : 4 graded stone aggregate) 12
finished with a floating coat of neat cement
including cement slurry but excluding the
cost of nosing of steps etc. complete.:

a) 50 mm thick with 20 mm nominal size


stone aggregate 1684.00 Sqm.

25. Providing and fixing Glass strips in joints 23 AR-


terrazzo/cement concrete floors: 12

a) 50mm wide and 4 mm thick.


2863.00 Metre

26. Supplying and stacking at site 43.00 Cum 16.3.10

a) Moorum 263

27 Laying spreading and compacting stone 16.4


aggregate of specified sizes to WBM
specifications including spreading in uniform 263
thickness, hand picking, rolling with 3
wheeled road/vibratory roller 8-10 tonne in 358.00 Cum
stages to proper grade and camber, applying
and brooming requisite type of
screening/binding material to fill up
interstices of coarse aggregate watering and
compacting to the required density.

28 12 mm cement plaster of mix: 13.1.2


a) 1:6 (1 cement : 6 fine sand)
2595.00 Sqm 222

29. 6 mm cement plaster of mix: 222.00 Sqm. 13.16


a) 1:3 (1 cement : 3 fine sand)
223

30. White washing with lime to give an even 13.37.1


shade
1645.00 Sqm 225
(a) New work (three or more coats)

31. Colour Wash such as green, blue or buff to 13.39.1


give an even shade
1102.00 Sqm 225
a) New Work (Two or more coats) with a
base of white washing with lime.

32. Painting with synthetic enamel paint of 13.61.1


approved brand and manufacture to give an
even shade: 1009.00 Sqm. 222
a) Two or more coats on new work
33. Supply & stacking of graded stone 16.3
aggregate at site of size range.:
(a) 63 mm to 45 mm size stone aggregate 290.00 Cum 263
(b) 53 mm to 22.4 mm size stone aggregate
145.00 Cum
(c) Stone screening 13.2 mm nominal size
(Type A) 38.00 Cum
(d) Stone screening 11.2 mm nominal size
(Type B) 28.70 Cum

34 Making plinth protection 50mm thick of 4.17


cement concrete 1:3:6 ( 1 cement : 3 coarse
sand : 6 graded stone aggregate 20 mm 88
nominal size) over 75mm bed by dry brick
ballast 40mm nominal size well rammed and 86.70 Sqm.
consolidated and grouted with fine sand
including finishing the top smooth.

35. Providing gola 75x75 mm in cement concrete 12.21.1


1:2:4 (1 cement : 2 coarse sand : 4 stone
aggregate 10mm and down gauge) including 207
finishing with cement mortar 1:3 (1 cement :
3 fine sand) as per standard design : 132.00 Metre
a) In 75x75 mm deep chase
36. Steel work in built up tubular trusses
including cutting hoisting fixing in position
and applying a priming coat of approved steel
primer, welded and bolted including special
shaped washers etc. complete. This includes
the cost of trusses, rafter purlins, sleeves
false rafter base plates lacing and bracing MS
bolts and nuts and base plate on top of
column as per relevant approved drawings
and direction of Engineer-in-charge (There is
no trusses over G/walls and partition walls)

The work including cost of material shall be


executed as per latest CPWD specification
and I.S. code of design. The trusses shall be
fabricated by the contractor at his own cost
exactly as per approved drawings of CWC
and nothing extra shall be paid.

Payment on weight basis would be made as


per the theoretical or actual weight
whichever is less:
21630.00 Kg.
a) Electric resistance or butt welded
tubes

37. Providing and fixing percoated galvanized 12.50


iron profiles sheets (size, shape and pitch for
corrugation as approved by Engineer –in – 1961.00 Sqm. 212
charge ) 0.55 mm (+0.05%) total coated
thickness with zinc coating 120 grams per
sqm as per IS:277, in 240 mpa steel grade
,5-7 microns epoxy primer on both side of
the sheet and polyster top coat 15-18
microns. Sheet should have protective guard
film of 25 microns minimum to avoid
scratches during transportation and should
be supplied in single length upto 12 metre or
as desired by Engineer –in-charge. The sheet
shall be fixed using self drilling /self tapping
screws of size (5.5 x5.5 mm ) with EPDM
seal, complete upto any pitch in horizontal
/vertical or curved surfaces, excluding the
cost of purlins, rafters and trusses and
including cutting of size and shape wherever
required.

38 Providing and fixing precoated galvanized 12.51.1


steel sheet roofing accessories 0.50mm
(+0.05%) total coated thickness, Zinc coating 75.00 Metre 212
120 grams per sqm as per IS:277, in 240
mpa steel grade ,5-7 microns epoxy primer
on both side of the street and polyster top
coat 15-18 microns using self drilling /self
tapping screws complete.

a)Ridges plain (500 -600mm)

39. Providing and fixing plastic translucent 1 AR-12


corrugated sheets made from thermox
setting polyester Resin, (Glass fiber
reinforced) of thickness 3.00 mm (with
variation up to 15% having minimum total
light transmission of 80% confirming to IS :
12866 – 1989, having length, width and
profile in accordance with those of adjoining
main roofing sheet, including supplying and
fixing fixtures like 8 mm dia G.I. ‘J’ hook bolts
& nuts, GI limpet washer and bitumen
washers as per the direction of Engineer-in-
charge. Excluding the cost of purlins, rafters
and trusses.: 33.00 Sqm.
a) Over lapping with one and a half
Corrugation
40. Supply & laying saturated felt type 3 grade-I 11 AR-
(Hessian base) on top of AC Ridges with 12
suitable residual petroleum bitumen of grade
VG-10 of approved quality by applying 1.45
Kgs./Sqm. (The Hessian type tarfelt should 75.60 Sqm.
be approved quality and confirm to I.S.1322).

41. Supply & fixing fire extinguishers of approved 30 AR-


I.S.I. mark each of 9 litres capacity in the 12
existing recess or on wall as per instruction of
Engineer-in-charge:

a) Water/carbon dioxide gas pressure 2.00 Each


type fire extinguishers capacity 9 litre
as per IS- 15683 -2006.
b) Mechanical type fire extinguishers
foam type 9 ltrs. Capacity as per I.S. 1.00. Each
15683 -2006.
c) Dry Chemical powder type fire 1.00. Each
extinguishers capacity 10 kg. As per
I.S. 15683 -2006.

42. Steel frame work in single section for air inlet 37 AR-
of MS joint mitred welded with 4 Nos. 15 cm 12
long lugs of MS flat 20X6mm to act as hold
fast to be fixed in cement concrete blocks of
size 200X100X100mm in cement concrete
mix 1:2:4 (1 cement : 2 coarse sand :4
graded stone aggregate 12.5 mm nominal
size) including providing and fixing GI fabric
(jail) in squared mesh of size not more than
17 mm X 17 mm, made of GI wire of dia
2mm , weighing 2.15 kg/sqm. In GI wire
fabric to be fixed with 15X3mm MS flat
beading, tack welded including applying
priming coat of zinc chromate yellow primer.
Cleats are to be provided on inner side of 448.60 Kg.
withhold/support the covering. Slanted MS
flat strip of size 40 mm X 4 mm to be
provided as per the drawing. Complete air
inlet to be manufactured and fixed in position
as per drawing No. CWC/PG/414 and as per
direction for Engineer in Charge.

Note: Cement concrete block shall be paid


separately under relevant item.

43. Applying a coat of residual petroleum 4.13


bitumen of grade VG-10 of approved quality
using 1.7 kg. per square metre on damp 61.90 Sqm. 87
proof course after cleaning the surface with
brushes and finally with a piece of cloth
lightly soaked in kerosene oil.
 

44. Providing and laying damp proof coarse 50 61.90 SQM 4.


mm thick with cement concrete 1:2:4((1
cement : 2 coarse sand :4 graded stone 87
aggregate 20 mm nominal size
 
ABSTRACT OF COST/BILL OF QUANTITIES FOR THE
CONSTRUCTION OF 3000 MT CAPACITY

(ELECTRICAL WORK)
S. No. Description of work Quantity Unit Rate Amount Remarks

1 Supplying and fixing of following sizes of


steel conduit along with accessories in
surface/recess including cutting the wall DSR
and making good the same in case of 2012(EL)
recessed conduit as required.(ISI Marked) P-5

I-20.2
510.00 Meter
(a) 25mm

2 Supplying and drawing following sizes of DSR 2012


FR PVC insulated copper conductor, single (EL) P-4
core cable in the existing surface/recessed
steel/PVC conduit as required. I-1.17.3
124.00 Meter
(a) 3x1.5 sqmm I-1.17.4
(b) 4x1.5 sqmm 50.00 Meter
I-1.17.5
(C) 5x1.5 sqmm 44.00 Meter
I-1.17.6
(d) 6x1.5 sqmm 95.00 Meter
I-1.17.7
(e) 7x1.5 sqmm 40.00 Meter
I-1.17.8
(f)8x1.5sqmm 6.00 Meter
I-1.17.9
(g) 9x1.5sqmm 6.00 Meter
I-1.17.12
(h)3x2.5 sqmm 55.00 Meter
I-1.17.15
(i)6x2.5sqmm 70.00 Meter
I-1.17.21
(j)3x4sqmm 50.00 Meter

3 Supplying and fixing 12/13 mm flexible


metal conduit including connection,
painting etc on surface/recessed as per
direction of Engineer in Charge. 14.00 Meter Market rate
4 Supplying and fixing 3 pin,5 amp. Ceiling DSR 2012
rose on the existing junction box/wooden (E) P-8
block including connection etc as required
I-1.33
46.00 Meter

5 Supplying of 1X28 watt T-5 lamp


luminaries, prewired with electronic choke,
and T-5 28 W lamp having powder coated
CRCA M.S. Box complete with all
accessories as required. Make surya –
UNIARY-Cat/Sub 128 T-5 EB-I/P-
3/Crompton cat ref. T-5 RSF 28 E/ or
equivalent in Bajaj

For office block and godown 40.00 Each Market rate

6 Installation, testing and commissioning of DSR-


prewired, fluorescent fitting/compact 2012(E)
fluorescent fitting of all types, complete
with all accessories and tube etc. directly P-8
on ceiling/wall/truss, including connection
with 1.5 sq. mm FR PVC insulated, copper
conductor, single core cable and earthing I-1.41
etc. as required. 40.00 Each

7 Supplying , installation, testing


commissioning of 36 w/40w LED warm
white , street light fitting, operating voltage
90-270 V. A.C, beam angle 30/90, IP
65/66, lumen more than 4000, pole die
60mm, life span 50000 hour, antiglare,
driver etc. complete with all accessories
etc. (with manufacturer certificate ) make -
NTL- Pharox -40watts LED or equivalent
6.00 Each Market rate
in Bajaj and Crompton

8 Supplying and fixing GI Pipe bracket on


wall, suitable for fixing above street light
made out of 40mm OD B-class GI pipe up
to 2.00 meter length along with 2 sets
suitable clamps, nut bolts/fastners
including bending the shape, smoke gray 6.00 Each Market rate
painted with primer etc. as required.

9 Supplying and fixing following way, single DSR-2012


pole and neutral, prewired, sheet steel,
MCB distribution board, 240 volts, on P-11
surface/recess, complete with tinned
copper bus bar, neutral link, earth bar, din
bar, detachable gland plate,
interconnections, phosphatized and powder
painted including earthing etc. as required.
(But without MCB/RCCB/Isolator)

(a) 2+12 way, Double Door 5 Each I-2.3.8

(b) 2+ 8 way, Double Door 4 Each I-2.3.7

10 Supplying and fixing following rating, DSR2012


double pole, 240 volts, isolator in the (EL) P-13
existing MCB DB complete with
connections, testing and commissioning
etc. as required. I-2.12.1
6 Each
(a) 40 amps

11 Supplying and fixing 5 amps to 32 amps


rating, 240 volts, ‘C’ curve, miniature
circuit breaker suitable for inductive load
of following poles in the existing MCB DB DSR2012
complete with connections,testing and (EL)p-13
commissioning etc. as required.
I-2.10.1
(a) Single Pole 104.00 Each

12 Providing and fixing M.V. danger notice DSR 2012


plate of 200 mm x 150 mm, made of mild (EL)P-14
steel at least 2 mm thick, and vitreous
enameled white on both sides, and with
inscription in single red color on front side I-2.21
as required. 1.00 Each

13 Earthing with G.I. earth pipe 4.5 meter DSR 2012


long, 40 mm dia including accessories and
providing masonry enclosure with cover (EL)P-23
plate having locking arrangement and
watering pipe etc. with charcoal / coke and
salt as required. 1.00 Set I-5.2

14 Proving and laying earth connection from DSR 2012


earth electrode with 6 SWG dia G.I. Wire (EL)P-24
in 15mm dia G.I Pipe from earth electrode
including connection with G.I thimble
excavation and re-filling as required. I-5.12
15.00 meter

15 Supplying of aluminum conductor PVC


insulated, PVC sheathed/xLPE inner
sheathed flat steel strip armoured power
cable of 1.1 KV grade conforming to
IS:1554 (Part-I) 1988 or latest amended
following sizes etc Make - Havels
/NICCO/GRANDLAY

(a) 2x16 sqmm


30.00 Meter Market rate

16 Laying of one number PVC insulated and DSR 2012


PVC sheathed/XLPE power cable of 1.1
KV grade of size not exceeding 25 Sq. mm P-26
direct in ground including excavation, sand
cushioning, protective covering and
refilling the trench etc. as required.

Upto 35 sq mm 20.00 Meter I-7.1.1

17 Laying of one number PVC insulated and DSR


PVC sheathed/XLPE power cable of 1.1 2012(E)
KV grade of size not exceeding 25 sq. mm
in the existing RCC / HUME / P-26
STONEWARE/METAL pipe as required

Upto 35 sq mm
10.00 Meter I-7.5

18 Providing and fixing G.I. Pipes complete DSR-2012


with G.I. Fitting including trenching and (C )
refilling etc (external work)
P-314

I-18.12.6
(a) 50 mm dia nominal bore 10.00 Meter

19 Supplying and fixing 20 amps, 415 volts, DSR-2012


SPN industrial type, socket outlet, with 2 (EL) P-14
pole and earth, metal enclosed plug top
along with 20 amps “C” curve, SP,MCB in
steel sheet enclosure on surface or in recess
with chained metal cover for the socket
out let and complete with connections, I-2.18
testing and commissioning etc as required 2 each

20 Supplying and making indoor end DSR-


termination with brass compression gland 2012(EL)
and aluminium lugs for following size of
PVC insulated and PVC sheathed /XLPE P-30
aluminium conductor cable of 1.1 KV
grade as required.
I-9.1.3
a)2x16 sq. mm(22mm) 02 Each

NOTE: 

1. The above quantification of items is for godown only and does not include office, 
boundary  wall  and  road  etc.  These  may  vary  from  place  to  place  as  per  the  site 
conditions.  
2. Cost  estimate  may  be  prepared  by  applying  the  local  schedule  of  rates  of 
PWD/CPWD or any other Govt. Authority.  
3. Drawings of the godown, office block and the layout plan have also been uploaded 
for guidance.  
 