TM - 5ce - 2016
TM - 5ce - 2016
CEILING MOUNTED
C SERIES
A5CM-C SERIES
Table of Contents
Table of Contents
Nomenclature......................................................................................................................1
Indoor ............................................................................................................................1
Outdoor..........................................................................................................................1
Product Line-Up.............................................................................................................2
Application Information .....................................................................................................4
Operating Range ...........................................................................................................4
Refrigerant Circuit Diagrams .........................................................................................5
Installation Guideline .....................................................................................................7
Sound Data........................................................................................................................10
Sound Pressure Level .................................................................................................10
NC Curve ..................................................................................................................... 11
Engineering & Physical Data ...........................................................................................15
Performance Data .............................................................................................................19
Calculation Steps.........................................................................................................19
Performance Tables .....................................................................................................22
Outlines & Dimensions ....................................................................................................31
Wiring Diagrams ...............................................................................................................34
Service & Maintenance ....................................................................................................40
Troubleshooting ...............................................................................................................42
Nomenclature
Nomenclature
Indoor
A 5 CM 15 C - A M FBA Revision
A: Revision A
Specification
B: Bare Unit
Handset
F: Wireless Handset
Factory Origin
M: Malaysia
Power Supply
A: 220-240V / 1 Phase / 50 Hz
Series
C: C series
Capacity*
15: 15,000 Btu/hr
Model
CM: Ceiling Exposed
Refrigerant
5: R410A
Brand
A: ACSON
Outdoor
A 5 LC15 F - A M ROB
Revison
B: Revision B
Fin
O: Bare Fin
Compressor Brand
R: Rechi
Factory Origin
M: Malaysia
Power Supply
A: 220-240V / 1 Phase / 50Hz
F: 380-415V / 3 Phase / 50Hz
Series
F: F series
Capacity*
15: 15,000 Btu/hr
Model
LC: Outdoor Condensing Unit
Refrigerant
5: R410A
Brand
A: ACSON
Remark:
*: Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value.
1
Nomenclature
Product Line-Up
Indoor Unit
A5CM
Classification
Refrigerant Control
Air Purification
Handset
Others
PCB
Fin
Model
Saranet Filter
Convertible
L208A EC
Cap Tube
Ionizer
SLM9
GS02
A5CM15C-AMFBA X X X X X
A5CM20C-AMFBA X X X X X
COOLING ONLY
A5CM25C-AMFBA X X X X X
A5CM30C-AMFBA X X X X X
A5CM35C-AMFBA X X X X X
A5CM40C-AMFBA X X X X X
A5CM50C-AMFBA X X X X X
A5CM62C-AMFBB X X X X X
2
Nomenclature
Outdoor Unit
A5LC
Classification
Refrigerant Control
Safety Devices
Compressor
Fin
Model
Contactor
Rotary
Scroll
A5LC15F-AMROB X X X
A5LC20C-AMPOG X X X
A5LC25C-AMPOG X X X
A5LC28C-AMPOB X X X
A5LC30C-AMPOA X X X
A5LC35D-AMPOA X X X X X X
A5LC40D-FMCOD X X X X X X
COOLING ONLY
A5LC50D-FMCOD X X X X X X
A5LC61D-FMCOB X X X X X X
A5LC15F-AMRIB X X X
A5LC20C-AMPIG X X X
A5LC25C-AMPIG X X X
A5LC28C-AMPIB X X X
A5LC30C-AMPIA X X X
A5LC35D-AMPIA X X X X X X
A5LC40D-FMCID X X X X X X
A5LC50D-FMCID X X X X X X
A5LC61D-FMCIB X X X X X X
3
Application Information
Application Information
Operating Range
Cooling
Outdoor
DB (°C)
46
43
19
14 19 23 Indoor WB (°C)
4
Application Information
Model: A5CM30C-A5LC28/30C
5
Application Information
Model: A5CM35C-A5LC35D
6
Application Information
Installation Guideline
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
Installation Diagram
Indoor Unit
Air Intake
Air Intake
Outdoor Unit
Outdoor Clearance
B
Return air
Service access
Return air
Discharge air
Obstacle
Obstacle
Obstacle
Obstacle
ALL MODELS A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm
7
Application Information
Cable Size
A5CM15C A5CM20C A5CM25C A5CM30C A5CM35C
Model Unit
A5LC15F A5LC20C A5LC25C A5LC28C A5LC30C A5LC35D
Power supply cable size mm2 2.5 2.5 2.5 2.5 2.5 4.0
Number of wire 3 3 3 3 3 3
Interconnection cable size mm2 2.5 2.5 2.5 2.5 2.5 2.5
Number of wire 3 3 3 3 3 4
Recommended fuse A 15 16 20 20 25 25
Refrigerant Piping
If the pipe length is too long, both the capacity and the reliability of the unit will decrease. As the number
of bends increases, resistance of the piping system to the refrigerant flow increases and thus lowering the
capacity, as a result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated as below
8
Application Information
Additional Charge
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.5m, then additional
charge after vacuuming is not necessary. If the piping length is more than 7.5m, then use the additional
charge (g) per additional 1m length as tabulated:
Example:
A5CM15C & A5LC15F with 18m piping length, additional piping length is 5.5m.
Thus, Additional charge = 5.5[m] x 18[g/m]
= 99[g]
Note: Installation and maintenance are to be performed only by qualified personnel who
are familiar with local codes and regulations, and experienced with this type of
equipment.
9
Sound Data
Sound Data
Sound Pressure Level
1/1 Octave Sound Pressure (dB, ref 20μPa) A Noise
Model Speed
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) Criteria
High 42 41 39 39 34 32 20 43 38
A5CM15C Med 37 37 36 34 29 25 17 38 33
Low 36 35 32 29 25 19 15 34 28
High 40 41 41 42 39 35 24 46 41
A5CM20C Med 37 39 39 39 36 31 18 43 38
Low 34 35 35 36 31 26 13 39 35
High 40 41 41 42 39 35 24 46 41
A5CM25C Med 37 39 39 39 36 31 18 43 38
Low 34 35 35 36 31 26 13 39 35
High 46 44 42 42 38 32 21 46 41
A5CM30C Med 45 43 40 40 36 29 18 44 39
Low 42 39 37 36 31 24 15 40 35
High 44 45 43 45 40 34 23 48 44
A5CM35C Med 43 42 40 41 35 27 19 44 40
Low 42 39 38 38 32 24 17 41 37
High 44 46 44 46 42 33 25 49 45
A5CM40C Med 43 43 40 41 39 29 20 45 40
Low 42 41 39 39 37 25 15 43 38
High 45 50 49 51 46 39 31 54 50
A5CM50C Med 43 48 47 49 44 36 28 52 48
Low 43 47 46 47 42 33 25 50 46
High 35 46 50 53 50 45 38 56 52
A5CM62C Med 33 44 47 50 47 42 34 53 49
Low 27 37 41 43 39 33 25 46 42
A5CM15C 0.8m
A5CM20C
A5CM25C Microphone
1m
A5CM30C
A5CM35C
A5CM40C
1m
A5CM50C Microphone
A5CM62C
1m
10
Sound Data
NC Curve
A5CM15C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
A5CM20C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
11
Sound Data
A5CM25C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
A5CM30C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
12
Sound Data
A5CM35C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
A5CM40C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
13
Sound Data
A5CM50C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
A5CM62C
80
70 NC-70
Sound pressure level (dB, ref 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
14
Engineering & Physical Data
TYPE SIROCCO
FAN
DRIVE DIRECT
TYPE PERMANENT SPLIT CAPACITOR
INDEX OF PROTECTION (IP) 20 20 20 20
INSULATION GRADE B B B B
FAN MOTOR RATED INPUT POWER W 84 81 81 128
RATED RUNNING CURRENT A 0.36 0.35 0.35 0.55
MOTOR OUTPUT W 45 95 95 85
POLES 4 4 4 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00
COIL MATERIAL ALUMINIUM
FIN FACE AREA m2 0.160 0.160 0.160 0.218
ROW 2 3 3 3
TYPE SARANET
AIR QUALITY FILTER
QUANTITY pc 3 3 3 4
CASING COLOUR WHITE
AIR FLOW CFM 827 1430 1600 1712
SOUND PRESSURE LEVEL dBA 48 52 52 54
HEIGHT X WIDTH X
UNIT DIMENSION mm 550 x 658 x 273 651 x 855 x 328 651 x 855 x 328 753 x 855 x 328
DEPTH
HEIGHT X WIDTH X
PACKING DIMENSION mm 580 x 775 x 355 693 x 990 x 415 693 x 990 x 415 793 x 990 x 415
DEPTH
UNIT WEIGHT kg 29 43 47 57
TYPE FLARE VALVE
PIPE
LIQUID mm 6.35 6.35 6.35 9.52
CONNECTION SIZE
GAS mm 12.70 12.70 15.88 15.88
TYPE PROPELLER
FAN
DRIVE DIRECT
TYPE PERMANENT SPLIT CAPACITOR
OUTDOOR UNIT
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
INDOOR: 27°C DB / 19°C WB
OUTDOOR: 35°C DB / 24°C WB
15
Engineering & Physical Data
TYPE SIROCCO
FAN
DRIVE DIRECT
TYPE PERMANENT SPLIT CAPACITOR
INDEX OF PROTECTION (IP) 20 20 20 20
INSULATION GRADE B B B B
FAN MOTOR RATED INPUT POWER W 128 187 202 237
RATED RUNNING CURRENT A 0.55 0.84 0.89 1.05
MOTOR OUTPUT W 85 110 110 140
POLES 4 4 4 4
MATERIAL COPPER
TUBE
DIAMETER mm 7.00 9.52
COIL MATERIAL ALUMINIUM
FIN FACE AREA m 2
0.218 0.277 0.335 0.335
ROW 3 3 3 4
TYPE SARANET
AIR QUALITY FILTER
QUANTITY pc 4 5 5 5
CASING COLOUR WHITE
AIR FLOW CFM 1712 3000 3150 3400
SOUND PRESSURE LEVEL dBA 56 58 60 63
HEIGHT X WIDTH X
UNIT DIMENSION mm 753 x 855 x 328 852 x 1030 x 400 852 x 1030 x 400 852 x 1030 x 400
DEPTH
HEIGHT X WIDTH X
PACKING DIMENSION mm 793 x 990 x 415 1010 x 1180 x 514 1010 x 1180 x 514 1010 x 1180 x 514
DEPTH
UNIT WEIGHT kg 57 71 95 98
TYPE FLARE VALVE
PIPE
LIQUID mm 9.52 9.52 9.52 9.52
CONNECTION SIZE
GAS mm 15.88 15.88 15.88 15.88
TYPE PROPELLER
FAN
DRIVE DIRECT
TYPE PERMANENT SPLIT CAPACITOR
OUTDOOR UNIT
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
INDOOR: 27°C DB / 19°C WB
OUTDOOR: 35°C DB / 24°C WB
16
Engineering & Physical Data
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
INDOOR: 27°C DB / 19°C WB
OUTDOOR: 35°C DB / 24°C WB
17
Engineering & Physical Data
Safety Device
INDOOR A5CM15C A5CM20C A5CM25C A5CM30C
MODEL
OUTDOOR A5LC15F A5LC20C A5LC25C A5LC28C A5LC30C
HIGH TYPE N/A
PRESSURE OPEN kPa / psi N/A
SWITCH CLOSE kPa / psi N/A
LOW TYPE N/A
SAFETY
PRESSURE OPEN kPa / psi N/A
DEVICE
SWITCH CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISCHARGE
°C / °F N/A
THERMOSTAT
18
Performance Data
Performance Data
Calculation Steps
Interpolation method can be used to get the total cooling capacity, TC and sensible cooling capacity, SC
and power input, PI at those temperatures which are not stated out in the table. Extrapolation method is not
allowed to be used.
Example:
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 2.02 1.54 0.49 1.95 1.50 0.53 1.87 1.46 0.58 1.80 1.42 0.63 1.65 1.32 0.68 1.52 1.24 0.75
24°C 2.02 1.84 0.49 1.95 1.80 0.53 1.88 1.76 0.58 1.80 1.71 0.63 1.66 1.60 0.68 1.53 1.51 0.75
16°C
27°C 2.04 2.04 0.49 1.97 1.97 0.54 1.90 1.90 0.58 1.83 1.83 0.63 1.69 1.69 0.68 1.57 1.57 0.75
30°C 2.10 2.10 0.50 2.04 2.04 0.54 1.98 1.98 0.58 1.91 1.91 0.63 1.77 1.77 0.69 1.66 1.66 0.76
24°C 2.23 1.44 0.50 2.15 1.40 0.54 2.07 1.36 0.59 1.99 1.32 0.64 1.83 1.23 0.69 1.69 1.16 0.76
27°C 2.23 1.64 0.50 2.15 1.61 0.54 2.07 1.57 0.59 1.99 1.53 0.64 1.83 1.43 0.69 1.69 1.36 0.76
195 19°C
30°C 2.23 2.03 0.50 2.15 1.99 0.54 2.08 1.94 0.59 2.00 1.89 0.64 1.84 1.77 0.69 1.71 1.68 0.76
33°C 2.26 2.26 0.50 2.18 2.18 0.54 2.11 2.11 0.59 2.04 2.04 0.64 1.89 1.89 0.70 1.77 1.77 0.77
27°C 2.45 1.41 0.51 2.36 1.37 0.55 2.28 1.34 0.60 2.19 1.30 0.65 2.01 1.21 0.71 1.86 1.14 0.78
30°C 2.45 1.71 0.51 2.36 1.68 0.55 2.28 1.64 0.60 2.19 1.60 0.65 2.01 1.50 0.71 1.86 1.42 0.78
22°C
33°C 2.45 2.00 0.51 2.37 1.96 0.55 2.28 1.92 0.60 2.19 1.88 0.65 2.02 1.77 0.71 1.87 1.68 0.78
36°C 2.46 2.27 0.51 2.38 2.22 0.55 2.29 2.18 0.60 2.21 2.13 0.65 2.04 2.00 0.71 1.90 1.89 0.78
Solution:
19
Performance Data
TC SC PI
Repeat the same process for (c) & (d) in 1st Step (d) x4 = 1.83 W; y4 = 1.30 kW; z4 = 0.69 kW
20
Performance Data
3rd Step:
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Outdoor temperature
EWB EDB 35°C 37°C 40°C
TC SC PI TC SC PI TC SC PI
21
Performance Data
Performance Tables
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
22
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
23
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
24
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
25
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
26
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
27
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
28
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
29
Performance Data
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB without pressure trip.
30
Outlines & Dimensions
Model: A5CM15/20/25/30/35/40/50/62C
Dimension
A B C D E F G H I J K L
Model
A5CM15C 1050 40 36 1203 1130 680 352 292 235 140 1180 250
A5CM20C 1050 40 36 1203 1130 680 352 292 235 140 1180 250
A5CM25C 1050 40 36 1203 1130 680 352 292 235 140 1180 250
A5CM30C 1400 40 36 1553 1480 680 352 292 235 140 1530 250
A5CM35C 1750 40 36 1903 1830 680 352 292 235 140 1880 250
A5CM40C 1750 40 36 1903 1830 680 352 292 235 140 1880 250
A5CM50C 1750 40 36 1903 1830 680 352 292 235 140 1880 250
A5CM62C 1750 40 36 1903 1830 680 352 292 285 140 1880 250
Note: Dimension in mm
31
Outlines & Dimensions
Outdoor Unit
Model: A5LC15F
Dimension
A B C D E F G H I J K L M N O P Q
Model
A5LC15F 550 658 51 11 273 16 14 470 96 93 94 60 14 133 8 10 299
Note: Dimension in mm
Model: A5LC20/25/28/30C
L K L
N
M
C
N
A G H
O
F
D
E
B
R S
I J
P
Dimension
A B C D E F G H I J K L M N O P Q R S
Model
A5LC20/25C 855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 23 362 73 75
A5LC28/30C 855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 23 362 73 75
Note: Dimension in mm
32
Outlines & Dimensions
Model: A5LC35/40/50/61D
Dimension
A B C D E F G H I J K L M N O
Model
A5LC35/40/50/61D 1030 826 400 695 57 72 90 40 746 142 60 26 448 22 28
Note: Dimension in mm
33
Wiring Diagrams
Wiring Diagrams
Cooling Only
Indoor Unit Outdoor Unit
Model: A5CM15C Model: A5LC15F
34
Wiring Diagrams
35
Wiring Diagrams
36
Wiring Diagrams
1 PHASE
220/240VAC 50Hz
NOTE :
------- - FIELD SUPPLY WIRING
37
Wiring Diagrams
38
Wiring Diagrams
39
Service & Maintenance
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
• When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
• For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.
40
Service & Maintenance
The design of the A5LC-C outdoor series allows servicing to be carried out readily and easily. The removal of
the top/front and back panel make almost every part accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface
once quarterly. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be
regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and
proper operation. Otherwise, the systems life span may be shortened.
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into
the unit when performing a leakage test or an air tight test. These gases could cause severe
explosion and damage if expose to high temperature and pressure.
41
Troubleshooting
Troubleshooting
Indicator Lights
LED Indicator Light Display - Cooling Only
Error
Operation / Faulty
Code Action
GREEN RED Indication
GREEN Orange (SLM8)
- Cooling mode -
- Dry mode -
- Fan mode -
- Sleep mode -
Check room sensor
Room air sensor
E1 connection / change room
contact open / short
sensor
Check indoor coil sensor
Indoor coil sensor
E2 connection / change indoor
contact open
coil sensor
Compressor overload If running ampere highly
/ Indoor coil sensor increase, change the
E4
short / Outdoor coil compressor. If not, replace
sensor short the coil sensor
Check for leakage & repair /
E5 Gas leak
Top up refrigerant
Hardware error (tact Replace the tact switch
E8
Blink Cool, follow by Fan, Dry
switch pin short) control board
ON BLINKING
42
Troubleshooting
Phase Sequencer
The unit with Scroll Compressor only can rotate in one direction. For this reason, a protective device (phase
sequencer) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not
connected correctly, the phase sequencer operates, and the unit will not start.
The following table shows the LED indicator light for phase sequencer under normal operation and fault
conditions.
LED PW P_S P_T Actions
Description (Red) (Yellow) (Yellow)
Normal Operation -
Note:
1. “ * ” indicates additional function for PP01 phase sequencer.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (COMMON) and 81 (NO) will
cut off.
3. The unit will check discharge sensor availability only during power up.
4. All errors can only recover through manually reset.
43
Troubleshooting
44
Troubleshooting
Diagnostic Guidelines
A little high
Probable cause
A little low
Too high
Too low
Circuit Normal
High side • 1. Overcharged with refrigerant.
Low side • 2. Non-condensable gases in refrigerant circuit (e.g. air).
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side • 1. Poor compression /no compression (compressor
Low side • defective)
2. Reversing valve leaking.
High side • 1. Undercharged with refrigerant.
Low side • 2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up
(heating).
6. Outdoor fan locked / seized (heating).
High side • 1. Outdoor fan blocked (cooling).
Low side • 2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air).
High side • 1. Air intake temperature of indoor unit too high.
Low side •
45
ACSON MALAYSIA SALES & SERVICE SDN.BHD. (129688-D)
a member of DAIKIN group
Lot 4, Lorong 19/1A, Seksyen 19, 46300 Petaling Jaya, Authorized Dealer :
Selangor Darul Ehsan, MALAYSIA.
Tel : +603 7964 8200 Sales Fax : +603 7956 9909
Sernice Fax : +603 7956 9907 Acson Careline : 1300 22 3344
www.acson.com.my TM-A5CM-2016
2