Minera Santo Domingo PROJECT #M40405 Santo Domingo Project Basic Engineering - Lntp3 - 2
Minera Santo Domingo PROJECT #M40405 Santo Domingo Project Basic Engineering - Lntp3 - 2
pdf>
Created on 11/5/2020 at 12:4:12 Page 1
1 cristian.prado 06/05/2020 18:35:51
06-May-2020 // TTLS-0596
2 145966 10/05/2020 16:12:35
Eric
3 145966 10/05/2020 16:13:04
10/05/20
PROJECT Nº M40405
CALCULATION REPORT
COOPER CONCENTRATE FILTRATION AIR AND WATER
SERVICES - FOUNDATIONS
Nº M40405-2170-DD20-CAL-0105
CLIENT N° MSD-SD005-2170-HO-CAL-0105
Prepared by
Wood
Comments
MSD-SD005-2170-HO-CAL-0105
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 5
1 leonardo.delahoz 07/05/2020 10:54:11
MSD code
2 leonardo.delahoz 07/05/2020 10:54:40
Verify Revision
3 leonardo.delahoz 07/05/2020 10:56:34
Geotechnical report
1.0 INTRODUCTION
Wood is developing for POSCO E&C the engineering service which includes the review
of Definitive Feasibility Study of part of the Wet Area, and the development of Basic
Engineering for these areas of the Santo Domingo Project.
The mine and plant site are located 50 km west from El Salvador, 60 km east from
Chañaral and 130 km north from Copiapó, at an elevation ranging from 1.000 to 1.280
m.a.s.l, in the municipality of Diego de Almagro.
The magnetite concentrates filtration plant and the ship loading facilities are located at
Punta Roca Blanca area, in the municipality of Caldera.
2.0 SCOPE
This report covers the design, at a basic engineer level, of the air and water service
equipment and pumps, in accord to the design loads and the structural design criteria
M40405-0000-DD20-DSC-0001.
MSD code
1
3.0 REFERENCES Verify Revision
Geotechnical report
3
MSD-SD005-2170-HO-CAL-0105 PAGE 5 of 16
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 6
1 leonardo.delahoz 07/05/2020 10:59:42
Not a drawing
Drawings
N° Drawing Description
N° Document Description
MSD-SD005-2170-HO-CAL-0105 PAGE 6 of 16
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 9
1 leonardo.delahoz 07/05/2020 17:27:43
Why is not considered this indication for
calculations?
2 leonardo.delahoz 07/05/2020 11:38:37
Verify
3 leonardo.delahoz 07/05/2020 17:31:57
Iindicate Self weights in this section
Geotechnical report states that the structural fill will have a unit weight higher than 2,0
tonf/m3.
Verify
5.0 LOADS 2
Self weight
Obtained multiplying the concrete unit weight (2,5 tonf/m3) by the total foundation
volume.
MSD-SD005-2170-HO-CAL-0105 PAGE 9 of 16
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 10
1 leonardo.delahoz 10/05/2020 14:52:46
Indicate references for density. Verify with
liquid height on annexes.
2 leonardo.delahoz 07/05/2020 21:08:08
Ok, but why is not used the same criteria for
pumps?
I agree with 1,0 for pumps and 1,2 for tanks
but it is important a backup.
Indicate references
for density. Verify 3 leonardo.delahoz 07/05/2020 17:54:10
with liquid height on No reference, Standard for load estimation.
Tank and pump contents load according to table 3-3
annexes.
The weight of the tank contents is considered and calculated by multiplying the total
volume of the tank with the density of the content. The densities and volume are show
in the following Table 5-1.
Live loads are part of the pump loads. See pump loads for live loads. No additional live
loads are considered.
Foundation seismic loads are obtained through a static analysis, considering the
following NCh2369:2003 parameters:
MSD-SD005-2170-HO-CAL-0105 PAGE 10 of 16
No reference, Standard for load estimation.
according to table 3-3
3
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 14
1 leonardo.delahoz 07/05/2020 21:17:56
Verify results according comments on
annexes.
The following table summarizes stability results for the foundations of each tank in the copper
concentrate area. Corresponding calculations are presented on section of this document.
L B hf
Pump TAG N° Descripción
[m] [m] [m]
2179-PU-0407 Process water
1,4 0,8 1
2179-PU-0408 pump
2179-PU-0409 Desalinated water
1,2 0,6 1
2179-PU-0410 pump
2173-PU-0103 Recovered water
1,2 0,6 1
2173-PU-0104 pump
2172-PU-0304 Recovered copper
1,4 0,8 1
2172-PU-0305 concentrate pump
2179-PU-0412
Seal water pump 0,6 0,2 1
2179-PU-0413
MSD-SD005-2170-HO-CAL-0105 PAGE 14 of 16
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 16
1 leonardo.delahoz 07/05/2020 19:36:40
Where are presented those operational
requirements?
Please add in references and specify the
section where appear.
The dimensions of these foundations are defined by operational requirements, which explains the
high safety factors.
According to the design criteria for structures, for light vibratory equipment the foundation weight
must be 2.5 times the weight of the pump it supports. Table 6-5 shows that this is complied for
each pump.
Where are
Table 6-5: Vibration verification
presented those
operational Pump Foundation
Pump/Foundation
requirements? Pump TAG N° weight weight
weight ratio
Please add in [kgf] [kgf]
references and 2179-PU-0407
209 2800 13,4
specify the section 2179-PU-0408
where appear. 2179-PU-0409
101 2500 24,7
2179-PU-0410 1
2173-PU-0103
130 2500 19,23
2173-PU-0104
2172-PU-0304
209 2800 13,4
2172-PU-0305
2179-PU-0412
16,2 300 18,52
2179-PU-0413
MSD-SD005-2170-HO-CAL-0105 PAGE 16 of 16
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 18
1 leonardo.delahoz 07/05/2020 19:40:52
Tank has 4,4m of height. How was defined
this height?
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 19
1 leonardo.delahoz 07/05/2020 21:11:16
verify all calculations according to the
comment made before
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 24
1 leonardo.delahoz 07/05/2020 20:45:20
Tank has 4,4m of height. How was defined
this height?
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 30
1 leonardo.delahoz 07/05/2020 20:48:38
Tank has 3,3m of height. How was defined
this height?
Notes
Comments summary on <MSD-SD005-2170-HO-CAL-0105-B-AWC.pdf>
Created on 11/5/2020 at 12:4:12 Page 43
1 leonardo.delahoz 07/05/2020 20:54:48
OK with this, but need backup or a reason
for this factor assumed.
Notes