Design of End Plate Connection

The document summarizes the design of an end plate moment connection according to AISC specifications. It provides the beam and column data, load information, and calculations for bolt checks, end plate sizing, and weld sizes. It calculates the required end plate thickness as 25 mm. It also checks the column for yielding and web buckling.

Uploaded by

Andro Rebuyas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
773 views

Design of End Plate Connection

The document summarizes the design of an end plate moment connection according to AISC specifications. It provides the beam and column data, load information, and calculations for bolt checks, end plate sizing, and weld sizes. It calculates the required end plate thickness as 25 mm. It also checks the column for yielding and web buckling.

Uploaded by

Andro Rebuyas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DESIGN OF END PLATE MOMENT CONNECTION (AS PER AISC FOR TENSION BOLT END PLATE CONNECTION DESIGN)

ASpectrum Designs Plus Engineering Services Project Title: Proposed Two Store Residential Building
Address: 8487 Sandoval Avenue, Pinagbuhatan, Pasig City 1602 Project Location: Villa Cuana Phase 1, Pinagbuhata, Pasig City 1602
Contact: 09982028893 Structural Engineer: Engr. Andro S Rebuyas, RCE, ME-1, RMP, M.Eng-SE
Gmail add: [email protected] Membership: M.PICE, M.ASCE, M.PAMEA, M.FPEA, M.PSUMP, M.NAMPAP, M.SEAD

BEAM DATA

Beam W4x13 C.L. STAAD Input


End Plate
("tp" x "Bp" x "Lp") Member Forces
2
Fy = 248 N/mm E
M= 118.112 kN-m Moment
Pf A= 31.165 kN Axial
S
D 10.57 cm Depth V= 87.405 kN Shear
(Beam)
fw = 10.31 cm Flange Width
P
ft = 0.88 cm Flange Thickness M Node 140
Wt = 0.71 cm Web Thickness R Member 1179
3
tw= 89.0 cm Section Modulus LC 182
2 S
Pf
Zxx = 24.71 cm Sectional Area
2 E
Af = 9.04 cm Area of Tension Flange
2
"Nb" - "db" Bolts
Aw = 6.64 cm Area of Web on "g" Gage

LOAD DATA

Ma = 14.57 kN-m Moment Capacity, (Ma =0.66Fy x Zxx) Gb = 10.9 Grade of Bolts
Design for 90.0% Capacity db = 24 mm Diameter of Bolts
M= 13.11 kN-m Design Moment Tb = 4 Number of Tension Bolts
10 Total Number of Bolts
Tc = 275.8 kN Axial Capacity, (Ta = 0.45Fy x As)
P= 31.17 kN Axial Force Ft = 357 N/mm2 Tensile Stresss
Fv = 238 N/mm2 Shear Stress
Vc = 65.83 kN Shear Capacity, (Va =0.40Fy x Aw)
2
Design for 40.0% Capacity Root Area of Bolt = 366.58 mm
V= 26.33 kN Design Shear
Capacity of Bolt
Check for Combined Moment and Tension Tension, Tc = 130.87 kN
Interaction Ratio = M/Ma + T/Tc Shear, Vc = 87.25 kN

1.01 >1.0, REVISE

BOLT CHECK

Tension Check Shear Check Check for Combined Tension & Shear

Flange Force, Ff = (M/ Nominal Depth) + (P*Af/As) f v = V/ nos of bolts Interaction Ratio = T/Tc + f v/Vc

Ff = 135.51 kN

Tension in bolt, T = 33.88 kN < Ten Capacity, OK Ff = 2.63 kN < Shear Capacity, OK 0.29 <1.4, OK

END PLATE CALCULATIONS, FLANGE FILLET AND WEB FILLET CALCULATIONS

End Plate Calculations Flange Fillet Calculations

Pf = 50 mm 1st row of bolts from flange Flange Fillet reqd, w = Ff / sw(2(fw+tf)-tw)


db = 24 mm Diameter of Bolt
w= 12 mm Weld Thickness sw = 110 N/mm2
w= 8.04 mm
Pe = Pf - (db/4) - .707w Effective bolt distance
Pe = 35.52 mm Hence Provide,
8.04 mm Flange fillet weld
bp = 180 Width of End of Plate -
Ca = 1.13
Cb = 0.76 Web Fillet Calculations
(Af/Aw)1/3 = 1.11
1/4
(Pe/db) = 1.10 web Fillet reqd, w = 0.60Fy tw / sw

1/3 1/4
am = Ca Cb (Af/Aw) (Pe/db) w= 6.8 mm < web thk, Fillet weld is OK
am = 1.05
Hence Provide,
Me = am Ff Pe/4 10.0 mm thk web weld
Me = 1.26 kN-m

tp = sq rt (6Me /0.75Fy bp) Plate Thickness Required


tp = 15.02 mm

Provide 25 mm thk Plate


COLUMN DATA AND CHECKS FOR COLUMN SECTION

Column Data Check for Column Yeilding

Column UC 305x305x158 Flange force for Check = 5/3 * Flange Force

2
Fy = 250 N/mm 40 ksi Ff = 135.51 kN
Pbf = 225.86 kN
D= 327.00 mm 12.87 inch Depth
fw = 311.00 mm 12.24 inch Flange Width Pbf allow = Fyc x twc x (tfb+ 6k + 2 tp + 2w)
tf = 25.00 mm 0.98 inch Flange Thickness
twc = 15.8 mm 0.62 inch Web Thickness Pbf allow = 1,274.9 kN > Pbf, OK
k= 40.00 mm 1.57 inch
dc = 247.00 mm 9.72 inch Effective depth Check for Column web buckling

2
As = 203.40 cm Sectional Area Pbf allow = 4100 x twc3 x sqrt(fyc) / dc Imperical Formulae
2
Af = 77.75 cm Area of Web
2
Aw = 47.90 cm Pbf allow = 641.8 kips
Pbf allow = 2,917.4 kN > Pbf, OK
tfb = 8.76 mm 0.35 inch Thickness of Beam Flange
tp = 25 mm 0.98 inch Thickness of End Plate Check for Column flange bending opposite Tension Flange
w= 12 mm 0.47 inch Weld Thickness
g= 100 mm
Design Result db = 24 mm Diameter of Bolt
C= 125 mm Vertical Distance between rows of Bolts
k1 = 23 mm

Pe = (g/2) - (db/4) - .k1


Pe = 20.90 mm

bs = 313 Effective Width of Column Flange


Ca = 1.13
Cb = 1.00
(Af/Aw)1/3 = 1.18
(Pe/db)1/4 = 0.97

1/3 1/4
am = Ca Cb (Af/Aw) (Pe/db)
am = 1.28

Me = am Ff Pe/4
Me = 0.91 kN-m

tfc = sq rt (6Me /0.75Fy bs) Required Flange Thickness


tfc = 9.63 mm < 25 mm, Hence Stiffeners not Reqd

This Spreadsheets is licensed only to Engr. Andro S. Rebuyas, RCE, ME-1, RMP, M.Eng-SE