Project Job Ref

The document provides calculations for the design of a pad footing to support a water tank column. It includes details of the pad footing and column geometry, soil properties, applied loads, and calculations of bearing pressure, base reactions, moments, and ultimate capacities. The maximum bearing pressure and ultimate moments are determined to be less than allowable values.

Uploaded by

christopher
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views6 pages

Project Job Ref

The document provides calculations for the design of a pad footing to support a water tank column. It includes details of the pad footing and column geometry, soil properties, applied loads, and calculations of bearing pressure, base reactions, moments, and ultimate capacities. The maximum bearing pressure and ultimate moments are determined to be less than allowable values.

Uploaded by

christopher
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Project Job Ref.

CONSTRUCTION OF WATER TANK AT WTP1


Section Sheet no./rev.
IAG INTERNATIONAL LLC
Hodan –Tarbunka Avenue
PAD DESIGN CALCULATION GRAVITY LOADS 1
Mogadishu - Somalia Calc. by Date Chk'd by Date App'd by Date

EEC 2/25/2021

PAD FOOTING ANALYSIS AND DESIGN (BS8110-1:1997)


Tedds calculation version 2.0.07

Pad footing details


Length of pad footing; L = 1300 mm
Width of pad footing; B = 1300 mm
Area of pad footing; A = L  B = 1.690 m2
Depth of pad footing; h = 300 mm
Depth of soil over pad footing; hsoil = 300 mm
Density of concrete; conc = 24.0 kN/m3

Column details
Column base length; lA = 300 mm
Column base width; bA = 300 mm
Column eccentricity in x; ePxA = 0 mm
Column eccentricity in y; ePyA = 0 mm
Soil details
Dense, moderately graded, sub-angular, gravel
Mobilisation factor; m= ;1.5;
Density of soil; soil = 12.0 kN/m3
Design shear strength; ’ = 25.0 deg
Design base friction;  = 19.3 deg
Allowable bearing pressure; Pbearing = 200 kN/m2
Axial loading on column
Dead axial load on column; PGA = 167.7 kN
Imposed axial load on column; PQA = 0.0 kN
Project Job Ref.

CONSTRUCTION OF WATER TANK AT WTP1


Section Sheet no./rev.
IAG INTERNATIONAL LLC
Hodan –Tarbunka Avenue
PAD DESIGN CALCULATION GRAVITY LOADS 2
Mogadishu - Somalia Calc. by Date Chk'd by Date App'd by Date

EEC 2/25/2021

Wind axial load on column; PWA = 0.0 kN


Total axial load on column; PA = 167.7 kN
Foundation loads
Dead surcharge load; FGsur = 10.000 kN/m2
Imposed surcharge load; FQsur = 0.000 kN/m2
Pad footing self weight; Fswt = h  conc = 7.200 kN/m2
Soil self weight; Fsoil = hsoil  soil = 3.600 kN/m2
Total foundation load; F = A  (FGsur + FQsur + Fswt + Fsoil) = 35.2 kN

Calculate pad base reaction


Total base reaction; T = F + PA = 202.9 kN
Eccentricity of base reaction in x; eTx = (PA  ePxA + MxA + HxA  h) / T = 0 mm
Eccentricity of base reaction in y; eTy = (PA  ePyA + MyA + HyA  h) / T = 0 mm

Check pad base reaction eccentricity


abs(eTx) / L + abs(eTy) / B = 0.000
Base reaction acts within middle third of base
Calculate pad base pressures
q1 = T / A - 6  T  eTx / (L  A) - 6  T  eTy / (B  A) = 120.043 kN/m2
q2 = T / A - 6  T  eTx / (L  A) + 6  T  eTy / (B  A) = 120.043 kN/m2
q3 = T / A + 6  T  eTx / (L  A) - 6  T  eTy / (B  A) = 120.043 kN/m2
q4 = T / A + 6  T  eTx / (L  A) + 6  T  eTy / (B  A) = 120.043 kN/m2
Minimum base pressure; qmin = min(q1, q2, q3, q4) = 120.043 kN/m2
Maximum base pressure; qmax = max(q1, q2, q3, q4) = 120.043 kN/m2
PASS - Maximum base pressure is less than allowable bearing pressure
Project Job Ref.

CONSTRUCTION OF WATER TANK AT WTP1


Section Sheet no./rev.
IAG INTERNATIONAL LLC
Hodan –Tarbunka Avenue
PAD DESIGN CALCULATION GRAVITY LOADS 3
Mogadishu - Somalia Calc. by Date Chk'd by Date App'd by Date

EEC 2/25/2021

Partial safety factors for loads


Partial safety factor for dead loads; fG = 1.40
Partial safety factor for imposed loads; fQ = 1.60
Partial safety factor for wind loads; fW = 0.00

Ultimate axial loading on column


Ultimate axial load on column; PuA = PGA  fG + PQA  fQ + PWA  fW = 234.8 kN

Ultimate foundation loads


Ultimate foundation load; Fu = A  [(FGsur + Fswt + Fsoil)  fG + FQsur  fQ] = 49.2 kN

Ultimate horizontal loading on column


Ultimate horizontal load in x direction; HxuA = HGxA  fG + HQxA  fQ + HWxA  fW = 0.0 kN
Ultimate horizontal load in y direction; HyuA = HGyA  fG + HQyA  fQ + HWyA  fW = 0.0 kN

Ultimate moment on column


Ultimate moment on column in x direction; MxuA = MGxA  fG + MQxA  fQ + MWxA  fW = 0.000 kNm
Ultimate moment on column in y direction; MyuA = MGyA  fG + MQyA  fQ + MWyA  fW = 0.000 kNm

Calculate ultimate pad base reaction


Ultimate base reaction; Tu = Fu + PuA = 284.0 kN
Eccentricity of ultimate base reaction in x; eTxu = (PuA  ePxA + MxuA + HxuA  h) / Tu = 0 mm
Eccentricity of ultimate base reaction in y; eTyu = (PuA  ePyA + MyuA + HyuA  h) / Tu = 0 mm

Calculate ultimate pad base pressures


q1u = Tu/A - 6TueTxu/(LA) - 6TueTyu/(BA) = 168.060 kN/m2
q2u = Tu/A - 6TueTxu/(LA) + 6Tu eTyu/(BA) = 168.060 kN/m2
q3u = Tu/A + 6TueTxu/(LA) - 6TueTyu/(BA) = 168.060 kN/m2
q4u = Tu/A + 6TueTxu/(LA) + 6TueTyu/(BA) = 168.060 kN/m2
Minimum ultimate base pressure; qminu = min(q1u, q2u, q3u, q4u) = 168.060 kN/m2
Maximum ultimate base pressure; qmaxu = max(q1u, q2u, q3u, q4u) = 168.060 kN/m2
Calculate rate of change of base pressure in x direction
Left hand base reaction; fuL = (q1u + q2u)  B / 2 = 218.478 kN/m
Right hand base reaction; fuR = (q3u + q4u)  B / 2 = 218.478 kN/m
Length of base reaction; Lx = L = 1300 mm
Rate of change of base pressure; Cx = (fuR - fuL) / Lx = 0.000 kN/m/m
Calculate pad lengths in x direction
Left hand length; LL = L / 2 + ePxA = 650 mm
Right hand length; LR = L / 2 - ePxA = 650 mm
Calculate ultimate moments in x direction
Ultimate moment in x direction; Mx = fuL  LL2 / 2 + Cx  LL3 / 6 - Fu  LL2 / (2  L) = 38.156 kNm

Calculate rate of change of base pressure in y direction


Top edge base reaction; fuT = (q2u + q4u)  L / 2 = 218.478 kN/m
Bottom edge base reaction; fuB = (q1u + q3u)  L / 2 = 218.478 kN/m
Length of base reaction; Ly = B = 1300 mm
Rate of change of base pressure; Cy = (fuB - fuT) / Ly = 0.000 kN/m/m
Project Job Ref.

CONSTRUCTION OF WATER TANK AT WTP1


Section Sheet no./rev.
IAG INTERNATIONAL LLC
Hodan –Tarbunka Avenue
PAD DESIGN CALCULATION GRAVITY LOADS 4
Mogadishu - Somalia Calc. by Date Chk'd by Date App'd by Date

EEC 2/25/2021

Calculate pad lengths in y direction


Top length; LT = B / 2 - ePyA = 650 mm
Bottom length; LB = B / 2 + ePyA = 650 mm
Calculate ultimate moments in y direction
Ultimate moment in y direction; My = fuT  LT2 / 2 + Cy  LT3 / 6 - Fu  LT2 / (2  B) = 38.156 kNm

Material details
Characteristic strength of concrete; fcu = 30 N/mm2
Characteristic strength of reinforcement; fy = 460 N/mm2
Characteristic strength of shear reinforcement; fyv = 460 N/mm2
Nominal cover to reinforcement; cnom = 35 mm
Moment design in x direction
Diameter of tension reinforcement; xB = 12 mm
Depth of tension reinforcement; dx = h - cnom - xB / 2 = 259 mm

Design formula for rectangular beams (cl 3.4.4.4)


Kx = Mx / (B  dx2  fcu) = 0.015
Kx’ = 0.156
Kx < Kx' compression reinforcement is not required
Lever arm; zx = dx  min([0.5 + (0.25 - Kx / 0.9)], 0.95) = 246 mm
Area of tension reinforcement required; As_x_req = Mx / (0.87  fy  zx) = 356 mm2
Minimum area of tension reinforcement; As_x_min = 0.0013  B  h = 507 mm2
Tension reinforcement provided; 9 No. 12 dia. bars bottom (150 centres)
Area of tension reinforcement provided; As_xB_prov = NxB    xB2 / 4 = 1018 mm2
PASS - Tension reinforcement provided exceeds tension reinforcement required
Moment design in y direction
Diameter of tension reinforcement; yB = 12 mm
Depth of tension reinforcement; dy = h - cnom - xB - yB / 2 = 247 mm

Design formula for rectangular beams (cl 3.4.4.4)


Ky = My / (L  dy2  fcu) = 0.016
Ky’ = 0.156
Ky < Ky' compression reinforcement is not required
Lever arm; zy = dy  min([0.5 + (0.25 - Ky / 0.9)], 0.95) = 235 mm
Area of tension reinforcement required; As_y_req = My / (0.87  fy  zy) = 374 mm2
Minimum area of tension reinforcement; As_y_min = 0.0013  L  h = 507 mm2
Tension reinforcement provided; 9 No. 12 dia. bars bottom (150 centres)
Area of tension reinforcement provided; As_yB_prov = NyB    yB2 / 4 = 1018 mm2
PASS - Tension reinforcement provided exceeds tension reinforcement required
Calculate ultimate shear force at d from top face of column
Ultimate pressure for shear; qsu = (q1u - Cy  (B / 2 + ePyA + bA / 2 + dy) / L + q4u) / 2
qsu = 168.060 kN/m2
Area loaded for shear; As = L  (B / 2 - ePyA - bA / 2 - dy) = 0.329 m2
Ultimate shear force; Vsu = As  (qsu - Fu / A) = 45.697 kN
Project Job Ref.

CONSTRUCTION OF WATER TANK AT WTP1


Section Sheet no./rev.
IAG INTERNATIONAL LLC
Hodan –Tarbunka Avenue
PAD DESIGN CALCULATION GRAVITY LOADS 5
Mogadishu - Somalia Calc. by Date Chk'd by Date App'd by Date

EEC 2/25/2021

Shear stresses at d from top face of column (cl 3.5.5.2)


Design shear stress; vsu = Vsu / (L  dy) = 0.142 N/mm2

From BS 8110:Part 1:1997 - Table 3.8


Design concrete shear stress; vc = 0.79 N/mm2  min(3, [100  As_yB_prov / (L  dy)]1/3)  max((400 mm /
dy)1/4, 0.67)  (min(fcu / 1 N/mm2, 40) / 25)1/3 / 1.25 = 0.517 N/mm2
Allowable design shear stress; vmax = min(0.8 N/mm2  (fcu / 1 N/mm2), 5 N/mm2) = 4.382 N/mm2
PASS - vsu < vc - No shear reinforcement required
Calculate ultimate punching shear force at face of column
Ultimate pressure for punching shear; qpuA = q1u+[(L/2+ePxA-lA/2)+(lA)/2]Cx/B-[(B/2+ePyA-bA/2)+(bA)/2]Cy/L =
168.060 kN/m2
Average effective depth of reinforcement; d = (dx + dy) / 2 = 253 mm
Area loaded for punching shear at column; ApA = (lA)(bA) = 0.090 m2
Length of punching shear perimeter; upA = 2(lA)+2(bA) = 1200 mm
Ultimate shear force at shear perimeter; VpuA = PuA + (Fu / A - qpuA)  ApA = 222.303 kN
Effective shear force at shear perimeter; VpuAeff = VpuA = 222.303 kN
Punching shear stresses at face of column (cl 3.7.7.2)
Design shear stress; vpuA = VpuAeff / (upA  d) = 0.732 N/mm2
Allowable design shear stress; vmax = min(0.8N/mm2  (fcu / 1 N/mm2), 5 N/mm2) = 4.382 N/mm2
PASS - Design shear stress is less than allowable design shear stress
Calculate ultimate punching shear force at perimeter of 1.5 d from face of column
Ultimate pressure for punching shear; qpuA1.5d = q1u+[L/2]Cx/B-[(B/2+ePyA-bA/2-1.5d)+(bA+21.5d)/2]Cy/L =
168.060 kN/m2
Average effective depth of reinforcement; d = (dx + dy) / 2 = 253 mm
Area loaded for punching shear at column; ApA1.5d = L(bA+21.5d) = 1.377 m2
Length of punching shear perimeter; upA1.5d = 2L = 2600 mm
Ultimate shear force at shear perimeter; VpuA1.5d = PuA + (Fu / A - qpuA1.5d)  ApA1.5d = 43.530 kN
Effective shear force at shear perimeter; VpuA1.5deff = VpuA1.5d  1.25 = 54.412 kN

Punching shear stresses at perimeter of 1.5 d from face of column (cl 3.7.7.2)
Design shear stress; vpuA1.5d = VpuA1.5deff / (upA1.5d  d) = 0.083 N/mm2

From BS 8110:Part 1:1997 - Table 3.8


Design concrete shear stress; vc = 0.79 N/mm2  min(3, [100  (As_xB_prov / (B  dx) + As_yB_prov / (L  dy)) /
2]1/3)  max((800 mm / (dx + dy))1/4, 0.67)  (min(fcu / 1 N/mm2, 40) / 25)1/3 /
1.25 = 0.509 N/mm2
Allowable design shear stress; vmax = min(0.8N/mm2  (fcu / 1 N/mm2), 5 N/mm2) = 4.382 N/mm2
PASS - vpuA1.5d < vc - No shear reinforcement required
Project Job Ref.

CONSTRUCTION OF WATER TANK AT WTP1


Section Sheet no./rev.
IAG INTERNATIONAL LLC
Hodan –Tarbunka Avenue
PAD DESIGN CALCULATION GRAVITY LOADS 6
Mogadishu - Somalia Calc. by Date Chk'd by Date App'd by Date

EEC 2/25/2021