A Small-AC-Signal Injection Based Harmonic Power Sharing Method For Islanded Microgrids
A Small-AC-Signal Injection Based Harmonic Power Sharing Method For Islanded Microgrids
Abstract—This paper proposes a novel control method for both communication-based techniques [17-19] and
harmonic power sharing in an islanded microgrid, without communication-less approaches [11-16] have been proposed,
employing any control interconnections between the distributed and the latter ones are more attractive for microgrid
generation (DG) units. The fundamental real and reactive power application, which will be reviewed as follows.
is shared by implementing conventional P-f and Q-V droop
control. A virtual negative output impedance at harmonic A virtual output resistance at harmonic frequency is
frequency is introduced to control the distribution of harmonic suggested to realize harmonic power sharing in [11]. Then, the
power. Moreover, a small-AC-signal is injected in each DG unit output resistance is made highly simplified by eliminating the
for dynamically regulating the magnitude of its virtual negative band-pass filters using a proportional-multi-resonant voltage
harmonic output impedance to realize evenly sharing of controller in [13]. In [12] the author proposed a control strategy
harmonic power among all DG units according to their available that combines droop control and modified shunt harmonic
harmonic power capacities. This novel method can also provide impedance with programmable harmonic resistance (PR-SHI)
improved load voltage quality and does not need information together to address harmonic current sharing issue. These three
about line impedance. Simulation results on PSCAD are offered techniques can be summarized as virtual harmonic impedance
to validate the proposed method. (VHI) methods [11-13], since a virtual impedance is put in
series with line impedance to regulate the distribution of
Keywords—microgrid; power sharing; harmonic power; small
harmonic power. The VHI methods can achieve equal
signal injection;virtual negative impedance
harmonic power sharing among all DG units. However, there is
an inherent tradeoff between sharing accuracy and load voltage
I. INTRODUCTION quality.
Centralized power generation gradually loses its attraction To improve the load voltage quality as well as share the
with the increasing concern about the environment and energy harmonic power, a droop relationship between harmonic
crisis. Microgrid may be a promising solution for electrical conductance (G) and harmonic power (H) is adopted in [15],
energy revolution, as it can integrate renewable energy which can share harmonic power among paralleled inverters
resources, energy storage systems and distributed loads into a while minimize load voltage distortion. Nevertheless, the
controllable system that provide power reliably, flexibly and influence from the difference between line impedance of each
intelligently [1-3]. In normal condition, microgrid is connected DG unit is not considered. Furthermore, a negative virtual
to the utility grid to supply or consume electrical power harmonic impedance and harmonic power droop (Zh-H droop)
according to power management command. However, technique is proposed recently in [16], where the equivalent
microgrid should be capable of disconnecting from utility grid harmonic impedance in each transmission line is decreased due
and maintaining operation in islanded mode when grid faults to the presence of negative virtual impedance, and thus the load
and contingencies occur [4-5]. voltage distortion in the point of common coupling (PCC) is
During the islanded operation, it is critical to make all load minimized. However, the information about line impedance is
powers, including fundamental power and harmonic power, needed to design the droop coefficients properly.
evenly shared among all the distributed generation (DG) units For avoiding the requirement on the knowledge of line
and thereby no DG unit is overloaded. For fundamental power impedance, [14] developed a voltage loop bandwidth and
sharing, there are already several control methods [6-10]. distortion power droop relationship to share harmonic power.
Droop control is the most widely adopted one among them, as Meanwhile, each DG unit injects a small ac voltage signal,
it can provide real and reactive power sharing without using whose frequency is controlled by the harmonic power, into the
communication link. However, the conventional droop method microgrid as a control signal. The frequency of injected small-
is not able to share harmonic power because the droop unit AC-signal is identical in steady state, so the harmonic power is
doesn’t take it into account. Harmonic power, which is equally shared. Though small-AC-signal injection is an artful
produced by nonlinear loads, could be a significant part in load technique as it can achieve communication among DG units
power, especially in low voltage microgrid. The uneven through power line, the variation of voltage loop bandwidth
sharing of harmonic power may also lead to overloading of will affect the dynamic performance and stability of the
certain DG units. To address the harmonic power sharing issue, inverter.
This work was supported by the National Natural Science Foundation of
China under Grant 51437007, and the Power Electronics Science and
Education Development Program of Delta Environmental & Educational
Foundation under Grant DREM2014002.
L PCC
Udc LL1
Linear Load
LLn
DGn
Fig. 3. Overall control structure of the proposed method
droop block indicates equation (7), the second and third droop 2
S remaining = S rated − ( P2 + Q2 ) (12)
blocks represent (1), and fourth droop block shows (8). The
harmonic power is calculated by (9), where S is the output
The coefficient k1 is designed according to:
apparent power.
k1_1 k1_ 2 k1_n
H = S 2 − P2 − Q2 (9) = ="= (12)
S remaining _1 Sremaining _ 2 S remaining _n
The apparent power S can be derived by multiplying
current and voltage rms values as (10) shows. Here we assume • This method does not affect the sharing of real and
the system is three phase balanced. reactive power because the virtual impedance is only
valid for harmonic frequencies.
S = 3Vrms I rms (10)
• No communication link is needed; the small signal is
The voltage reference consists of three parts: fundamental transmitted through power transmission line.
voltage reference, injected small signal reference and voltage • Do not need to measure the line impedance. Rough
drop on the virtual output impedance. The voltage and inner estimation is enough.
current control loop track this composite voltage reference,
which is given by the following equation: • The equivalent line impedance is lower due to the
presents of negative virtual impedance, so the PCC
vref _ composite = E * sin ω *t + Ess* sin ωss* t voltage distortion is minimized.
(11)
− ¦ ¬ªihn ( − jωn LVNHI ) ¼º
n = 5,7,11"
Inverter
1.00k
0.90k
0.80k