Technical Information

Deltabar S PMD70/75, FMD76/77/78


Differential pressure measurement
Differential pressure transmitter with ceramic and silicon sensors
Overload-resistant and function-monitored, Communication via
HART, PROFIBUS PA or FOUNDATION Fieldbus

Application Your benefits


The Deltabar S differential pressure transmitter is used • Very good reproducibility and long-term stability
for the following measuring tasks: • High reference accuracy: up to 0.075%,
• Flow measurement (volume or mass flow) in as PLATINUM version: 0.05%
conjunction with primary elements in gases, vapours • Turn down 100:1, higher on request
and liquids • Used for flow and differential pressure monitoring
• Level, volume or mass measurement in liquids up to SIL 3, certified to IEC 61508 by TÜV SÜD
• Differential pressure monitoring, e.g. of filters and • HistoROM®/M-DAT memory module
pumps • Function-monitored from the measuring cell to the
• International usage thanks to a wide range of approvals electronics
• Continuous modularity for differential pressure,
hydrostatic and pressure (Deltabar S, Deltapilot S,
Cerabar S), e.g.
– replaceable display
– universal electronics for pressure and
differential pressure
• Quick commissioning thanks to quick setup menu
• Easy and safe menu-guided operation on-site,
via 4...20 mA with HART, via PROFIBUS PA or
via FOUNDATION Fieldbus
• Extensive diagnostic functions

TI382P/00/EN/06.09
No. 71095431
Deltabar S

Table of contents

Function and system design. . . . . . . . . . . . . . . . . . . . . 4 Warm-up period – PMD70, FMD76 . . . . . . . . . . . . . . . . . . . . . 22


Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Influence of the operating pressure on zero point and span – PMD70,
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 FMD76 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Flow measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Thermal change of the zero output and the output span – PMD70,
Level measurement (level, volume and mass) . . . . . . . . . . . . . . . . 7 FMD76 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Communication protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating conditions (Installation) . . . . . . . . . . . . . . 23
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . 23
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Measuring arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Heat insulation – FMD77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Wall- and pipe-mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
"Separate housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Turn the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Oxygen applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ultra pure gas applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Signal range – 4...20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . 10 Process isolating diaphragms for materials with hydrogen build-up
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 (Gold-Rhodium coating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Load – 4...20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dynamic behavior current output . . . . . . . . . . . . . . . . . . . . . . . . 11 Operating conditions (Environment) . . . . . . . . . . . . . 27
Dynamic behavior HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dynamic behavior PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . 12 Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dynamic behavior FOUNDATION Fieldbus . . . . . . . . . . . . . . . . 12 Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Data of the FOUNDATION Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fieldbus interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Overvoltage protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . 28
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Operating conditions (Process) . . . . . . . . . . . . . . . . . 28
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Process temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Process temperature range, seals . . . . . . . . . . . . . . . . . . . . . . . . 28
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 30
Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Housing dimensions T14, optional display on the side . . . . . . . . . 30
Housing dimensions T15, optional display on the top . . . . . . . . . 30
Performance characteristics – general . . . . . . . . . . . . 19 Housing dimensions T17, optional display on the top . . . . . . . . . 30
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Process connections PMD70 with ceramic process isolating
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Influence of the installation position . . . . . . . . . . . . . . . . . . . . . . 19 Process connections PMD70 with ceramic process isolating
Vibration effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Process connections PMD75 with metallic process isolating
diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Performance characteristics – metallic process isolating Process connections PMD75 with metallic process isolating
diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Reference accuracy – PMD75, FMD77, FMD78 . . . . . . . . . . . . . 20 Process connections PMD75 with metallic process isolating
Total performance – PMD75 . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Total Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Process connection FMD76 with ceramic process isolating
Warm-up period – PMD75, FMD77, FMD78 . . . . . . . . . . . . . . . 21 diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Influence of the operating pressure on zero point and span – PMD75, Process connection FMD76 with ceramic process isolating
FMD77, FMD78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Thermal change of the zero output and the output Process connection FMD76 with ceramic process isolating
span -- PMD75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Process connections FMD77 with metallic process isolating
Performance characteristics – ceramic process isolating diaphragms, low-pressure side . . . . . . . . . . . . . . . . . . . . . . . . . . 38
diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Process connections FMD77 with metallic process isolating
diaphragms, high-pressure side . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Reference accuracy – PMD70, FMD76 . . . . . . . . . . . . . . . . . . . 22
Process connections FMD77 with metallic process isolating
Total performance – PMD70, FMD76 . . . . . . . . . . . . . . . . . . . . 22
diaphragms, high-pressure side (continued) . . . . . . . . . . . . . . . . 40
Total Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2 Endress+Hauser
Deltabar S

Process connections FMD77 with metallic process isolating FMD78 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81


diaphragms, high-pressure side (continued) . . . . . . . . . . . . . . . . 41
FMD78 Basic unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Additional documentation . . . . . . . . . . . . . . . . . . . . . 82
Process connection FMD78 with metallic process isolating
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Process connection FMD78 with metallic process isolating
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
diaphragm (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Brief operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Process connection FMD78 with metallic measuring
Manual for Functional Safety (SIL) . . . . . . . . . . . . . . . . . . . . . . . 82
diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Process connection FMD78 with metallic measuring
Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 83
diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Overspill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Process connection FMD78 with metallic measuring
diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Process connection FMD78 with metallic measuring
diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Process connection FMD78 with metallic measuring
diaphragms (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
"Separate housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Hard- und Software for on-site and remote operation . . . . . . . . . 56

Planning instructions, diaphragm seal systems . . . . . 58


Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Design and operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Diaphragm seal filling oils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Influence of the temperature on the zero point . . . . . . . . . . . . . . 60
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 66


CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Ex approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Marine certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Functional Safety SIL / IEC 61508 Declaration of conformity
(optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Overspill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
CRN approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . . . . . . 66
Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 67
PMD70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
PMD70 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
PMD70 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
PMD75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
PMD75 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
PMD75 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
FMD76 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
FMD76 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
FMD76 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
FMD77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
FMD77 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
FMD77 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
FMD78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
FMD78 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

3 Endress+Hauser
Deltabar S

Function and system design


Device selection

Deltabar S – PMD70 PMD75 FMD76 FMD77 FMD78


product family

+ –

+ –

P01-PMD70xxx-16-xx-xx-xx-000 P01-PMD75xxx-16-xx-xx-xx-000 P01-FMD76xxx-16-xx-xx-xx-000 P01-FMD77xxx-16-xx-xx-xx-000 P01-FMD78xxx-16-xx-xx-xx-003

With ceramic process With metallic process With ceramic process With metallic process With metallic process
isolating diaphragms isolating diaphragms isolating diaphragms isolating diaphragms isolating diaphragms and
and diaphragm seal capillary diaphragm
mounted on one side seals
Field of – Flow – Flow – Level – Level – Level
application – Level – Level – Differential pressure
– Differential pressure – Differential pressure
Process – 1/4 – 18 NPT – 1/4 – 18 NPT Low-pressure side (–): Low-pressure side (–): – Wide range of
connections – RC 1/4 – RC 1/4 – 1/4 – 18 NPT – 1/4 – 18 NPT diaphragm seals
– RC 1/4 – RC 1/4
High-pressure side (+): High-pressure side (+):
– DN 80 – DN 100 – DN 50 – DN 100
– ANSI 3" – 4" – ANSI 2" – 4"
– JIS 80A – 100A – JIS 80A – 100A
Measuring ranges from –25...+25 mbar from –10...+10 mbar from –100...+100 mbar from –100...+100 mbar from –100...+100 mbar
to –3...+3 bar to –40...+40 bar to –3...+3 bar to –16 bar...+16 bar to –40...+40 bar
Overload 1 on one side: max. 100 bar on one side: max. 420 bar on one side: max. 100 bar on one side: max. 160 bar on one side: max. 160 bar
on both sides: max. 150 bar on both sides: max. 630 bar on both sides: max. 240 bar
Process –20...+85°C –40...+120°C –20...+85°C up to + 400°C (+752°F) up to +400°C (+752°F)
temperature range (–4...+185°F) (–40...+248°F) (–4...+185°F)
Ambient –20...+85°C –40...+85°C –20...+85°C –40...+85°C –40...+85°C
temperature range (–4...+185°F) (–40...+185°F) 2 (–4...+185°F) (–40...+185°F) 2 (–40...+185°F) 2
Ambient –40 to +60°C (–40 to +140°F)
temperature range
separate housing
Reference – Up to 0.075% of the set span – Up to 0.075 % of the set span
Accuracy – PLATINUM version: up to 0.05% of the set span
Supply voltage – For non-hazardous areas: 10.5...45 V DC
– Ex ia: 10.5...30 V DC
Output 4...20 mA with superimposed HART protocol, PROFIBUS PA or FOUNDATION Fieldbus
Options – High-pressure version up to pstat 700 bar
– PMD75, FMD77, FMD78: Gold-Rhodium-coated process isolating diaphragm, NACE-compliant materials
– Separate housing
Specialities – Metal-free measurement – pstat up to 420 bar – Abrasion-resistant and – For high media – Wide range of
(options) with PVDF flange – Process isolating corrosion-resistant temperatures diaphragm seals
– Available with Deltatop diaphragm: tantalum – No diaphragm-seal
as flow compact device – Available with Deltatop temperature effects
as flow compact device – Metal-free
measurement possible
with ECTFE-coated
process connection
– HistoROM®/M-DAT memory module

1) dependent on the lowest-rated element, with regard to pressure, of the selected components
2) lower temperature on request

4 Endress+Hauser
Deltabar S

Measuring principle

Ceramic process isolating diaphragms used for Metallic process isolating diaphragms used for PMD75, FMD77 and FMD78
PMD70 and FMD76


➀ ➁
➁ ➆

p1 p2
➂ ➇
➂ p1 ➃ p2 p1 p2

➃ ➄

P01-xMD7xxxx-03-xx-xx-xx-000 P01-xMD7xxxx-03-xx-xx-xx-002 P01-xMD7xxxx-03-xx-xx-xx-003

Ceramic measuring cell PMD70 and FMD76 Metal measuring cell 10 mbar and 30 mbar Metal measuring cell as of 100 mbar
1 Meter body 1 Sensing element 6 Sensing element
2 Process isolating diaphragm 2 Silicon diaphragm 7 Overload diaphragm
3 Electrodes 3 Process isolating diaphragm 8 Filling oil
4 Glass frit fixes the process isolating 4 Filling oil 9 Process isolating diaphragm
diaphragm onto the meter body 5 Overload diaphragm
5 Temperature sensor

Ceramic process isolating diaphragms used for PMD70 and FMD76


The ceramic measuring cell is based on the principle of a plate capacitor with an electrode on (1) and a movable
electrode on the interior of the diaphragm (3). Standard silicone oil or mineral oil filling oils for this measuring
cell.
A differential pressure (p1 p2) causes a corresponding deflection of both diaphragms. Both capacitance values
are converted and are fed to the microprocessor of the transmitter as a digital signal.
Advantages:
• Self-monitoring for process isolating diaphragm break or oil loss (constant comparison of the measured
temperature with a temperature calculated from the capacitance values)
• Extremely high resistance to aggressive media
• Suitable for vacuums up to 1 mbarabs
• Metal-free versions available
• Second process barrier (Secondary Containment) for enhanced integrity

Metallic process isolating diaphragms used for PMD75, FMD77 and FMD78
The process isolating diaphragms (3/9) are deflected on both sides by the acting pressures. A filling oil (4/8)
transfers the pressure to a resistance circuit bridge (semi-conductor technology). The differential-pressure-
dependent change of the bridge output voltage is measured and further processed.
Advantages:
• Standard operating pressures: 160 bar and 420 bar
• High long-term stability
• Very high single-sided overload resistance
• Second process barrier (Secondary Containment) for enhanced integrity

Endress+Hauser 5
Deltabar S

Flow measurement Design and operation mode

+ – + –
Q ~ Δp p1 p2 Q ~ Δp p1 p2

Q Q

P01-PMD7xxxx-15-xx-xx-xx-000

Flow measurement with Deltabar S and primary element, left: Orifice plate and right: Pitot tube
Q Flow
p Differential pressure, p = p1 – p2

Your benefits
• Choice of four flow modes of operation: volume flow, norm volume flow (European norm conditions),
standard volume flow (American standard conditions) and mass flow.
• Choice of diverse flow units with automatic unit conversion.
• A customised unit can be specified
• Low flow cut off: when activated, this function suppresses small flows which can lead to large fluctuations
in the measured value.
• Contains two totalizers as standard. One totalizer can be reset to zero.
• The totalizing mode and unit can be individually set for each totalizer. This allows independent daily and
annual quantity totalizing.
• With the product family Deltatop, Endress+Hauser is offering a universal and reliable solutions for flow
measurement:
– Deltatop, the compact, ready-to-use flow measuring unit including differential pressure transmitter
Deltabar S
Note!
For more information about flow measurement with the Deltabar S differential pressure transmitter
• Deltabar S with orifice plate (TI422P, Deltatop DO6x)
• Deltabar S with pitot tube (TI425P, Deltatop DP6x)

6 Endress+Hauser
Deltabar S

Level measurement (level, Design and operation mode


volume and mass)

– – Δp
h= ρ g


h

➁ +

+
P01xMD7xxxx-15-xx-xx-xx-000

Level measurement with Deltabar S


1 Level measurement via impulse piping and PMD70
2 Level measurement with FMD76
3 Level measurement with FMD78
h Height (level)
p Differential pressure
 Density of the medium
g Gravitation constant

Your benefits
• Choice of three level operating modes
• Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve
• Choice of diverse level units with automatic unit conversion
• A customised unit can be specified
• Has a wide range of uses, e.g.
– for level measurement in tanks with superimposed pressure
– in the event of foam formation
– in tanks with agitators of screen fittings
– in the event of liquid gases
– for standard level measurement

Communication protocol • 4...20 mA with HART communication protocol


• PROFIBUS PA
– The Endress+Hauser devices meet the requirements as per the FISCO model.
– Due to the low current consumption of 13 mA ± 1 mA
– up to 7 Deltabar S for Ex ia, CSA IS and FM IS applications
– up to 27 Deltabar S for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
can be operated at one bus segment with installation as per FISCO.
Further information on PROFIBUS PA, such as requirements for bus system components, can be found in
the Operating Instructions BA034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and in
the PNO guideline.
• FOUNDATION Fieldbus
– The Endress+Hauser devices meet the requirements as per the FISCO model.
– Due to the low current consumption of 15 mA ± 1 mA
– up to 6 Deltabar S for Ex ia, CSA IS and FM IS applications
– up to 24 Deltabar S for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
can be operated at one bus segment with installation as per FISCO.
Further information on FOUNDATION Fieldbus, such as requirements for bus system components can be
found in the Operating Instructions BA013S "FOUNDATION Fieldbus Overview".

Endress+Hauser 7
Deltabar S

Input
Measured variable Differential pressure, from which flow (volume or mass current) and level (level, volume or mass) are derived

Measuring range PMD75, FMD77, FMD78 (with metallic process isolating diaphragms)

Nominal Measurement Smallest MWP 1 Overload 2 Min. operating pressure 3 Versions in the
value limit calibratable order code 4
span 5

lower upper on one side on both sides PN 160 6 PN 420 6


(LRL) (URL)

[mbar] [mbar] [mbar] [mbar] [bar] [bar] [bar] [mbarabs]


7
10 –10 +10 0.25 160 160 240 0.1 7B –

30 7 –30 +30 0.3 160 160 240 0.1 7C –


8
100 –100 +100 1/5 160 160 240 0.1 7D –
9
500 –500 +500 5 160/420 160/420 240/630 0.1 7F 8F

3000 –3000 +3000 30 160/420 9 160/420 240/630 0.1 7H 8H


9
16000 –16000 +16000 160 160/420 160/420 240/630 0.1 7L 8L
9
40000 –40000 +40000 400 160/420 "+"side: 240/630 0.1 7M 8M
160/420 10

PMD70, FMD76 (with ceramic process isolating diaphragms)

Nominal Measurement Smallest MWP 1 Overload 2 Min. operating pressure 3 Versions in the
value limit calibratable order code 4
span 5

lower upper on one side on both sides


(LRL) (URL)

[mbar] [mbar] [mbar] [mbar] [bar] [bar] [bar] [mbarabs]

25 –25 +25 0.25 10 10 15 1 7B

100 –100 +100 1 16 16 24 1 7D

500 –500 +500 5 100 100 150 1 7F

3000 –3000 +3000 30 100 100 150 1 7H

1) The MWP (maximum working pressure; MWP = PN) for the measuring device depends on the weakest element of the components selected with regard to
pressure, i.e. the process connection ( ä 30 ff) has to be taken into consideration in addition to the measuring cell ( see table above). Also observe
pressure-temperature dependency. For the appropriate standards and further information, see  ä 29, "Pressure specifications" section.
2) The maximum pressure for the measuring device is dependent on the lowest-rated element, with regard to pressure, of the selected components. See also
 ä 29, section "Pressure specifications".
3) The minimum operating pressure indicated in the table applies to silicone oil under reference operating conditions.
Min. operating pressure at 85°C (185°F) for silicone oil: 10 mbarabs.
FMD77 and FMD78: Min. operating pressure: 50 mbarabs; observe also the pressure and temperature application limits of the selected filling oil on  ä 59.
For vacuum applications, please observe the installation instructions on  ä 65 ff.
4) Versions in the order code  ä 71 ff, feature 40 "Nominal range; PN"
5) Turn down > 100:1 on request
6) PN 160 versions with stainless steel A2 screws, PN 420 versions with stainless steel A4 M12 screws
PN 420 versions for PMD75 only.
7) PMD75 only
8) minimum span that can be calibrated for PMD75: 1 mbar; minimum span that can be calibrated for FMD77 and FMD78: 5 mbar
9) For PMD75 with CRN-approved process connections, the MWP is 315 bar.
10) "–" side: 100 bar

8 Endress+Hauser
Deltabar S

Explanation of terms Explanation of the terms: Turn down (TD), set span and zero based span

Case 1:
• Lower range value Upper range value ➀=➁
Example: LRL LRV URV URL
• Lower range value (LRV) = 0 mbar
• Upper range value (URV) = 100 mbar –500 mbar 0 100 +500 mbar
• Nominal value (URL) = 500 mbar
Turn down:
• TD = URL /URV:1

set span: ➃
• URV – LRV = 100 mbar
This span is based on the zero point. ➄
P01-xxxxxxxx-05-xx-xx-xx-001

Example: 500 mbar sensor

Case 2:
• Lower range value Upper range value ➀=➁
Example: LRL LRV URV URL
• Lower range value (LRV) = –300 mbar
• Upper range value (URV) = 0 bar
• Nominal value (URL) = 500 mbar –500 mbar 0 +500 mbar

Turn down: –300 mbar


• TD = URL / (LRV) = 1.67:1 ➂
set span:
• URV – LRV = 300 mbar ➃
This span is based on the zero point.

P01-xMD7xxxx-05-xx-xx-xx-007

Example: 500 mbar sensor


1 Set span
2 Zero based span
3 Nominal value i Upper range limit (URL)
4 Nominal measuring range
5 Sensor measuring range
LRL Lower range limit
URL Upper range limit
LRV Lower range value
URV Upper range value

Endress+Hauser 9
Deltabar S

Output
Output signal • 4...20 mA with superimposed digital communication protocol HART 5.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.0)
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
• Digital communication signal FOUNDATION Fieldbus
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode

Signal range – 3.8 mA to 20.5 mA


4...20 mA HART

Signal on alarm As per NAMUR NE 43


• 4...20 mA HART
Options:
– Max. alarm*: can be set from 21...23 mA
– Keep measured value: last measured value is kept
– Min. alarm: 3.6 mA
* Factory setting: 22 mA
• PROFIBUS PA: can be set in the Analog Input block,
options: Last Valid Out Value, Fsafe Value (factory setting), Status bad
• FOUNDATION Fieldbus: can be set in the Analog Input Block,
options: Last Good Value, Fail Safe Value (factory setting), Wrong Value

Load – 4...20 mA HART


➀ RLmax ➁ RLmax
[Ω] [Ω]
Test 1500 Test
1456
1282 1239

847 804
➃ ➃
413
➂ 369

10.5 20 30 40 45 U 11.5 20 30 40 45 U
[V] [V]

U – 10.5 V U – 11.5 V
RLmax ≤ RLmax ≤
23 mA 23 mA
P01-xMD7xxxx-05-xx-xx-xx-000

Load diagram, observe the position of the jumper and the explosion protection ( ä 17, section "Taking 4...20 mA test
signal".)
1 Jumper for 4...20 mA test signal inserted in "Non-test" position
2 Jumper for 4...20 mA test signal inserted in "Test" position
3 Supply voltage 10.5 (11.5)...30 V DC for 1/2 D, 1 GD, 1/2 GD, FM IS, CSA IS, IECEx ia, NEPSI Ex ia
4 Supply voltage 10.5 (11.5)...45 V DC for device for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d, 3 G Ex nA, FM
XP, FM DIP, FM NI, CSA XP, CSA Dust-Ex, NEPSI Ex d
RLmax Maximum load resistance
U Supply voltage

Note!
When operating via a handheld terminal or via PC with an operating program, a minimum communication
resistance of 250 must exist within the loop.

Resolution • Current output: 1 A


• Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)

10 Endress+Hauser
Deltabar S

Dynamic behavior Dead time, Time constant (T63)


current output

I
100 %
90 %

63 %

t1 t2 t

P01-xxxxxxxx-05-xx-xx-xx-007

Presentation of the dead time and the time constant

Type Dead time t1 Time constant (T63), t2

PMD75 45 ms • 10 mbar and 30 mbar measuring cell: 200 ms


• 100 mbar measuring cell: 60 ms
• 500 mbar measuring cell: 45 ms
• 3 bar measuring cell: 40 ms
• 16 bar and 40 bar measuring cell: 60 ms

FMD77, FMD78 dependent on the diaphragm seal

PMD70, FMD76 90 ms • 25 mbar measuring cell: 4700 ms


• 100 mbar measuring cell: 280 ms
• 500 mbar measuring cell: 210 ms
• 3 bar measuring cell: 110 ms

Dynamic behavior HART Dead time, Time constant (T63)


A typical parametrization for the PLC of 3 to 4 values per second results in the following total dead time:

Type Dead time t1 Time constant (T63), t2

PMD75 295 ms • 10 mbar and 30 mbar measuring cell: 200 ms


• 100 mbar measuring cell: 60 ms
• 500 mbar measuring cell: 45 ms
• 3 bar measuring cell: 40 ms
• 16 bar and 40 bar measuring cell: 60 ms

FMD77, FMD78 dependent on the diaphragm seal

PMD70, FMD76 340 ms • 25 mbar measuring cell: 4700 ms


• 100 mbar measuring cell: 280 ms
• 500 mbar measuring cell: 210 ms
• 3 bar measuring cell: 110 ms

Reading cycle
• HART commands: on average 3 to 4 per second on average.
The Deltabar S commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.

Response time
 250 ms

Cycle time (Update time)


On average 250...330 ms.

Endress+Hauser 11
Deltabar S

Dynamic behavior Dead time, Time constant (T63)


PROFIBUS PA
A typical cyclic parametrization for the PLC of 20 values per second results in the following total dead time:

Type Dead time t1 Time constant (T63), t2

PMD75 295 ms • 10 mbar and 30 mbar measuring cell: 200 ms


• 100 mbar measuring cell: 60 ms
• 500 mbar measuring cell: 45 ms
• 3 bar measuring cell: 40 ms
• 16 bar and 40 bar measuring cell: 60 ms

FMD77, FMD78 dependent on the diaphragm seal

PMD70, FMD76 340 ms • 25 mbar measuring cell: 4700 ms


• 100 mbar measuring cell: 280 ms
• 500 mbar measuring cell: 210 ms
• 3 bar measuring cell: 110 ms

Response time
• cyclic: approx. 10 ms per request
• acyclic: < 50 ms
All values are typical values.

Cycle time (Update time)


The cycle time in a bus segment in cyclic data communication depends on the number of devices, on the
segment coupler used and on the internal PLC cycle time.

Dynamic behavior Dead time, Time constant (T63)


FOUNDATION Fieldbus
If the macro cycle time (Hostsystem) is set to a typical value of 250 ms, the following total dead time results:

Type Dead time t1 Time constant (T63), t2

PMD75 295 ms • 10 mbar and 30 mbar measuring cell: 200 ms


• 100 mbar measuring cell: 60 ms
• 500 mbar measuring cell: 45 ms
• 3 bar measuring cell: 40 ms
• 16 bar and 40 bar measuring cell: 60 ms

FMD77, FMD78 dependent on the diaphragm seal

PMD70, FMD76 340 ms • 25 mbar measuring cell: 4700 ms


• 100 mbar measuring cell: 280 ms
• 500 mbar measuring cell: 210 ms
• 3 bar measuring cell: 110 ms

Reading cycle
• cyclic: up to 5/s, dependent on the number and type of function blocks used in a closed-control loop
• acyclic: 10/s

Response time
• cyclic: < 80 ms
• acyclic: < 40 ms
All values are typical values.

Cycle time (Update time)


250 ms

12 Endress+Hauser
Deltabar S

Damping A damping affects all outputs (output signal, display).


• Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s
• Additionally for HART and PROFIBUS PA: via DIP-switch on the electronic insert, switch position
"on" = set value and "off"
• Factory setting: 2 s

Data of the FOUNDATION Basic Data


Fieldbus interface
Device Type 1009F (hex)

Device Revision 06 (hex)

DD Revision 01 (hex)

CFF Revision 01 (hex)

ITK Version 5.0

ITK-Certification Driver-No. IT054700

Link-Master (LAS) cabable yes

Link Master / Basic Device selectable yes; Default: Basic Devce

Number VCRs 44

Number of Link-Objects in VFD 50

Virtual communication references (VCRs)

Permanent Entries 44

Client VCRs 0

Server VCRs 5
Source VCRs 8

Sink VCRs 0

Subscriber VCRs 12
Publisher VCRs 19

Link Settings

Slot time 4

Min. Inter PDU delay 12


Max. response delay 10

Transducer Blocks

Block Content Output values

TRD1 Block contains all parameters related to the measurement • Pressure, Flow or Level (Channel 1)
• Process temperatur (Channel 2)

Service Block contains service information • Pressure after damping (Channel 3)


• Pressure drag indicator (Channel 4)
• Counter for max. pressure transgressi-
ons (Channel 5)

Dp Flow Block contains flow and totalizer parameter Totalizer 1 (Channel 6)

Diagnsotic Block contains diagnostiv information Error code via DI channels (channel 0 to
6)

Display Block contains parameters to configure the local display no output values

Endress+Hauser 13
Deltabar S

Function Blocks

Block Content Number of Execution Functionality


Function Blocks time

Resource Block The Resource Block contains all the data that uni- enhanced
quely identifies the field device. It is an electronic
version of a nameplate of the device.

Analog Input The AI block takes the manufacturer's input data, 45 ms enhanced
Block 1 selected by channel number, and makes it avai-
Analog Input lable to other function blocks at its output.
Block 2 Enhancement: digital outputs for process alarms,
fail safe mode

Digital Input This block contains the discrete data of the diag- 40 ms standard
Block nose block (selectable via a channel number 0 to
16) and provides them for the blocks at the out-
put.

Digital Output This block converts the discrete input and thus 60 ms standard
Block initiates an action (selectable via a channel num-
ber) in the dp flow block or in the service block.
Channel 1 resets the counter for max. pressure
transgressions..

PID Block The PID block serves as proportional-integral-deri- 120 ms standard


vative controller and is used almost universally to
do closed-loop-control in the field including cas-
cade and feedforward. Input IN can be indicated
on the display. The selection is performed in the
display block
(DISPLAY_MAIN_LINE_CONTENT).
Arithmetic Block This block is designed to permit simple use of 50 ms standard
popular measurement math functions. The user
does not have to know how to write equations.
The math algorithm is selected by name, chosen
by the user for the function to be done.

Input Selector The input selector block provides selection of up 35 ms standard


Block to four inputs and generates an output based on
the configured action. This block normally recei-
ves its inputs from AI blocks. The block performs
maximum, minimum, middle, average and ‘first
good’ signal selection. INPUT IN1 to IN4 can be
indicated on the display. The selection is perfor-
med in the display block
(DISPLAY_MAIN_LINE_CONTENT).

Signal Characte- The signal characterizer block has two sections, 30 ms standard
rizer Block each with an output that is a non-linear function
of the respective input. The non-linear function is
determined by a single look-up table with 21 arbi-
trary x-y pairs.

Integrator Block The Integrator Function Block integrates a vari- 35 ms standard


able as a function of the time or accumulates the
counts from a Pulse Input block. The block may
be used as a totalizer that counts up until reset or
as a batch totalizer that has a setpoint, where the
integrated or accumulated value is compared to
pre-trip and trip settings, generating discrete
signals when these settings are reached.

Analog Alarm This block contains all process alarm conditions 35 ms standard
Block (working like a comparator) and represents them
at the output.

Additional Function Block informations:

Instantiate Function Block YES

Number of instantiate blocks 15

14 Endress+Hauser
Deltabar S

Power supply
Electrical connection Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.  ä 82,
section "Safety Instructions" and "Installation/Control Drawings".
• Devices with integrated overvoltage protection must be earthed.  ä 28.
• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.

4...20 mA HART

➀ ➅ 10.5 V DC
➆ 11.5 V DC

4…20 mA
Test

Test

➁ 4... 20mA Test

➂ ➄

4... 20mA Test


P01-xMx7xxxx-04-xx-xx-xx-001

Electrical connection 4...20 mA HART


1 Housing
2 Jumper for 4...20 mA test signal.  ä 17, section "Taking 4...20 mA test signal" .
3 Internal earth terminal
4 External earth terminal
5 4...20 mA test signal between positive and test terminal
6 minimum supply voltage = 10.5 V DC, jumper is inserted in accordance with the illustration.
7 minimum supply voltage = 11.5 V DC, jumper is inserted in "Test" position.
8 Devices with integrated overvoltage protection are labelled OVP (overvoltage protection) here ( ä 28).

PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA034S
"Guidelines for planning and commissioning PROFIBUS DP/PA" and the PNO Guideline.
Cable specifications:
• Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA034S
Guidelines for planning and commissioning PROFIBUS DP/PA", PNO Guideline 2.092 "
PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).

Endress+Hauser 15
Deltabar S

FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA013S
"FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Cable specifications:
• Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA013S "FOUNDATION
Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).

Devices with Harting plug Han7D

+
7
+ – – 8 6
1
2 5
3 4
Han7D

+ –
P01-xMD7xxxx-04-xx-xx-xx-000

Left: electrical connection for devices with Harting plug Han7D


Right: view of the plug connector at the device

Devices with M12 plug

+ –
– +

M12

+ –
P01-xMD7xxxx-04-xx-xx-xx-008

Left: electrical connection for devices with M12 plug


Right: view of the plug at the device

Endress+Hauser offers for devices with M12 plug the following accessories:
Plug-in jack M 12x1, straight
• Material: Body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 52006263
Plug-in jack M 12x1, elbowed
• Material: Body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 51006327
Cable 4x0.34 mm2 with M12 socket, elbowed, screw plug, 5 m length
• Material: Body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP67
• Order number: 52010285

16 Endress+Hauser
Deltabar S

Devices with 7/8" plug


+ –

7/8” +

+–
P01-xxx7xxxx-04-xx-xx-xx-003

Left: electrical connection for devices with 7/8" plug


Right: view of the plug at the device

Kabel gland

Approval Typ Clamping range

Standard, II1/2G Exia, IS Plastic M20x1.5 5...10 mm

ATEX II1/2D, II1/3D,


II1/2GD Exia, II1GD Exia Metal M20x1.5 (Ex e) 7...10.5 mm
II3G Ex nA

Terminals
for wire cross-sections of 0.5 to 2.5 mm2

Taking 4...20 mA test signal


A 4...20 mA signal may be measured via the positive and test terminal without interrupting the measurement.
The minimum supply voltage of the device can be reduced by simply changing the position of the jumper. As
a result, operation is also possible with lower voltage sources. Observe the position of the jumper in accordance
with the following table.

Jumper position for test signal Description

– Taking 4...20 mA test signal via plus and test terminal:


Test possible. (Thus, the output current can be measured without
interruption via the diode.)
– Delivery status
– minimum supply voltage: 11.5 V DC

– Taking 4...20 mA test signal via plus and test terminal:


Test not possible.
– minimum supply voltage: 10.5 V DC

Endress+Hauser 17
Deltabar S

Supply voltage Note!


• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
• All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
 ä 82, sections "Safety Instructions" and "Installation/Control Drawings".

4...20 mA HART
• Version for non-hazardous areas, jumper for 4...20 mA test signal in "Test" position (delivery status):
11.5...45 V DC
• Version for non-hazardous areas, jumper for 4...20 mA test signal in "Non-test" position: 10.5...45 V DC

PROFIBUS PA
• Version for non-hazardous areas: 9...32 V DC

FOUNDATION Fieldbus
• Version for non-hazardous areas: 9...32 V DC

Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry  ä 67 ff, feature 30 "Housing, Cable entry, Protection".

Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.


• Terminals for wire cross-sections 0.5...2.5 mm2
• Cable external diameter: 5...9 mm

Residual ripple Without influence on 4...20 mA signal up to 5 % residual ripple within the permitted voltage range [according
to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply 0.0006% of URL/1 V

18 Endress+Hauser
Deltabar S

Performance characteristics – general


Reference operating • As per IEC 60770
conditions • Ambient temperature TU = constant, in the range of: +21...+33°C (+69.8...+91.4°F)
• Humidity = constant, in the range of: 5...80 % r.H
• Ambient pressure pU = constant, in the range of: 860...1060 mbar
• Position of the measuring cell: constant, in the range of: 1°
• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value
• Zero based span
• Material of the process isolating diaphragm
– PMD75: AISI 316L/1.4435, Alloy C276, Gold-Rhodium coated, Monel
– FMD77, FMD78: AISI 316L/1.4435
– PMD70, FMD76: Al2O3 (Aluminium-oxide-ceramic)
• Filling oil: silicone oil
• Side flanges material PMD75: AISI 316L/1.4435
• Supply voltage: 24 V DC ± 3 V DC
• Load with HART: 250 

Long-term stability 1 year 5 years 10 year

Measuring range [mbar] % of URL

10 ±0.150 -- --

100 ±0.180 -- --
500 ±0.025 ±0.050 ±0.075

3000 ±0.038 ±0.075 ±0.150

16000 ±0.025 ±0.110 ±0.210

Influence of the installation • PMD70, FMD76:  3 mbar 1, 3


position • PMD75: 4 mbar 1, 3
• FMD77: 32 mbar 2, 3

1) Device is rotated vertically to the axis of the process isolating diaphragm.


2) Device rotated vertically to the process isolating diaphragm of the flange .
3) The value is doubled for devices with inert oil.

Note!
Position-dependent zero shift can be corrected.  ä 23, section "General installation instructions" and
 ä 62 ff, section "Response time".

Vibration effects Device Housing Test standard Vibration effects

PMD70/ optional on-site display on GL reference accuracy to


FMD76 the side (T14) 10...18 Hz: ±4 mm;
18...500 Hz: 5 g

PMD75 optional on-site display on reference accuracy to


the side (T14) 10...38 Hz: ±0.35 mm;
38...2000 Hz: 2 g
IEC 61298-3
PMD75 optional on-site display on reference accuracy to
the top (T15) 10...60 Hz: ±0.35 mm;
60...2000 Hz: 5 g

Endress+Hauser 19
Deltabar S

Performance characteristics – metallic process isolating


diaphragms
Reference accuracy – The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and
PMD75, FMD77, FMD78 non-reproducibility as per IEC 60770. The data refer to the calibrated span.
The following applies for the root-extracting characteristic curve:
The accuracy data of the Deltabar S is taken into the accuracy calculation of the flow rate with a factor of 0.5.

PMD75
Measuring cell % of the set span

• TD 1:1 = ±0.15
10 mbar, 30 mbar
• TD > 1:1 = ±0.15 x TD

• TD 1:1 to TD 4:1 = ±0.075


100 mbar
• TD > 4:1 = (0.012 x TD + 0.027)

• TD 1:1 to TD 15:1 = ±0.075


500 mbar
• TD > 15:1 = (0.0015 x TD + 0.053)

Platinum version:
• TD 1:1 = ±0.05
00 mbar

FMD77, FMD78
Measuring FMD77 FMD78
cell
% of the set span (influence of the diaphragm seal included)

• TD 1:1 to TD 4:1 = ±0.15 • TD 1:1 to TD 4:1 = ±0.15


100 mbar
• TD > 4:1 = (0.03 x TD + 0.03) • TD > 4:1 = (0.03 x TD + 0.03)
500 mbar, • TD 1:1 to TD 15:1 = ±0.075 • TD 1:1 to TD 4:1 = ±0.15
3 bar, 16 bar • TD > 15:1 = (0.0015 x TD + 0.053) • TD > 4:1 = (0.02 x TD + 0.07)

• TD 1:1 to TD 4:1 = ±0.15


40 bar 
• TD > 4:1 = (0.02 x TD + 0.07)

Total performance – PMD75 The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility, the
thermal change of the zero point as well as the influence of the line pressure (pst = 70 bar).

Measuring cell AISI 316L/1.4435, Alloy, Gold-Rhodium Tantal process isolating diaphragm
or Monel process isolating diaphragm

% of the set span

500 mbar to TD 2:1 0.15 0.30

All specifications apply to the temperature range –10...+60°C (+14...+140°F).

Total Error The total error comprises the long-term stability and the total performance:

Measuring cell AISI 316L/1.4435, Alloy, Gold-Rhodium Tantal process isolating diaphragm
or Monel process isolating diaphragm

% of URL/year

10 mbar, 30 mbar,
0.33 0.48
100 mbar

500 mbar 0.20 0.35

20 Endress+Hauser
Deltabar S

Warm-up period – • 4...20 mA HART : < 10 s


PMD75, FMD77, FMD78 • PROFIBUS PA: 6 s
• FOUNDATION Fieldbus: 50 s

Influence of the operating Measuring AISI 316L/1.4435, Alloy, Gold-Rhodium Tantal process isolating diaphragm
pressure on zero point and cell coated or Monel process isolating diaphragm
span – PMD75, FMD77,
FMD78 Influence of the Influence of the Influence of the Influence of the
operating pressure on operating pressure on operating pressure on operating pressure on
the zero point the span the zero point the span

10 mbar 0.15 % of URL/7 bar 0.035 % of URL/7 bar 0.28 % of URL/7 bar 0.28 % of URL/7 bar
30 mbar 0.35 % of URL/70 bar 0.14 % of URL/70 bar 0.70 % of URL/70 bar 0.70 % of URL/70 bar

100 mbar 0.15 % of URL/70 bar 0.14 % of URL/70 bar 0.42 % of URL/70 bar 0.42 % of URL/70 bar

500 mbar 0.075 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar

3 bar 0.075 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar

16 bar 0.075 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar

40 bar 0.075 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar 0.14 % of URL/70 bar

Note!
The influence of the operating pressure on the zero point can be calibrated out.

Thermal change of the zero Measuring cell –10...+60 °C (+14...+140°F)


output and the output
span -- PMD75 AISI 316L/1.4435, Alloy, Gold-Rhodium Tantal process isolating diaphragm
coated or Monel process isolating
diaphragm

% of the set span

10 mbar, 30 mbar (0.31 x TD + 0.06)

100 mbar (0.18 x TD + 0.02) (0.24 x TD + 0.06)


500 mbar, 3 bar (0.08 x TD + 0.05)

16 bar (0.1 x TD + 0.1)

40 bar (0.08 x TD + 0.05)

Measuring cell –40...-10 °C, +60...+85 °C


(–40...+14°F, +140...+185°F)

all process isolating diaphragm materials

% of the set span


10 mbar, 30 mbar (0.45 x TD + 0.1)

100 mbar (0.3 x TD + 0.15)

500 mbar, 3 bar (0.12 x TD + 0.1)


16 bar (0.15 x TD + 0.2)

40 bar (0.37 x TD + 0.1)

Endress+Hauser 21
Deltabar S

Performance characteristics – ceramic process isolating


diaphragms
Reference accuracy – The reference accuracy comprises the non-linearity including hysteresis and non-reproducibility in accordance
PMD70, FMD76 with the limit point method as per IEC 60770. The data refer to the calibrated span.
The following applies for the root-extracting characteristic curve:
The accuracy data of the Deltabar S is taken into the accuracy calculation of the flow rate with a factor of 0.5.

Measuring cell % of the set span

• TD 1:1 = ±0.15
25 mbar
• TD > 1:1 = ±0.15 x TD

• TD 1:1 to TD 4:1 = ±0.075


100 mbar
• TD > 4:1 = (0.012 x TD + 0.027)
• TD 1:1 to TD 15:1 = ±0.075
500 mbar, 3 bar
• TD > 15:1 = (0.0015 x TD + 0.05252)

Platinum version: 100 mbar, 500 mbar, 3 bar • TD 1:1 = ±0.05

Total performance – The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility, the
PMD70, FMD76 thermal change of the zero point as well as the influence of the line pressure (pst = 70 bar).

Measuring cell % of the set span

500 mbar to TD 1:1 • 0.15


All specifications apply to the temperature range –10...+60°C (+14...+140°F).

Total Error The total error comprises the long-term stability and the total performance:

Measuring cell % of URL/year

25 mbar, 100 mbar • 0.33

500 mbar, 3 bar • 0.20

Warm-up period – • 4...20 mA HART : < 10 s


PMD70, FMD76 • PROFIBUS PA: 6 s
• FOUNDATION Fieldbus: 50 s

Influence of the operating Measuring cell Influence of the operating pressure on the Influence of the operating pressure on the
pressure on zero point and zero point span
span – PMD70, FMD76
25 mbar 0.7 % of URL/7 bar 0.14 % of URL/7 bar

100 mbar 0.175 % of URL/70 bar 0.14 % of URL/70 bar


500 mbar 0.075 % of URL/70 bar 0.14 % of URL/70 bar

3 bar 0.075 % of URL/70 bar 0.14 % of URL/70 bar

Note!
The influence of the operating pressure on the zero point can be calibrated out.

Thermal change of the zero Measuring cell –10...+60 °C –20...–10 °C, +60...+85 °C
output and the output span – (+14...+140°F) (–4...+14°F, +140...+185°F)
PMD70, FMD76
% of the set span

25 mbar (0.35 x TD + 0.05) (0.3 x TD + 0.15)

 100 mbar (0.05 x TD + 0.05) (0.08 x TD + 0.07)

22 Endress+Hauser
Deltabar S

Operating conditions (Installation)


General installation • The position-dependent zero shift can be corrected directly at the device via operating key, for devices with
instructions external operation even in hazardous areas. Diaphragm seals also shift the zero point, depending on the
installation position ( ä 64 ff, "Installation instructions").
• The housing of the Deltabar S can be rotated up to 380°.  ä 26, section "Turn the housing".
• Endress+Hauser offers a mounting bracket for installing the device on pipes or walls.  ä 24, section "Wall-
and pipe-mounting".
• When measuring in media with solid proportions, such as dirty liquids, installing separators and drain valves
is useful for capturing and removing sediment.
• Using a three-valve or five-valve manifold allows for easy commissioning, installation and maintenance
without interrupting the process.
• General recommendations for the impulse piping can be found in DIN 19210 "Methods for measurement of
fluid flow; differential piping for flow measurement devices" or the corresponding national or international
standards.
• Install the impulse piping with a continuous gradient of at least 10%.
• When routing the impulse piping outdoors, ensure that sufficient anti-freeze protection is used, e.g. by using
pipe heat tracing.
• For FMD77 and FMD78: See page 64 ff, "Installation instructions, Diaphragm seal systems" section.

Measuring arrangement Flow measurement


• The PMD70 and PMD75 are best suited to flow measurement.
• Measuring arrangement for gases: Mount device above the measuring point.
• Measuring arrangement for liquids and vapours: Mount device below tapping point.
• For flow measurement in vapours, mount the condensate traps at the same level as the same the tapping
point and at the same distance from Deltabar S.

Level measurement
• PMD70, PMD75, FMD76 and FMD77 are best suited to level measurement in open tanks. All Deltabar S
devices are suitable for level measurement in closed tanks.

Measuring arrangement level measurement in open tanks


• PMD70, PMD75: Mount device below the lower measuring connection. The negative side is open to
atmosphere pressure.
• FMD76, FMD77: Mount device direct on the tank. The negative side is open to atmosphere pressure.

Measuring arrangement level measurement in closed tanks and closed tanks with superimposed vapour
• PMD70, PMD75: Mount device below the lower measuring connection. Always connect the negative side
above the maximum level.
• FMD76, FMD77: Mount device direct on the tank. Always connect the negative side above the maximum
level.
• In the case of level measurement in closed tanks with superimposed vapour, a condensate trap ensures
pressure which remains constant on the minus side.

Pressure measurement
• The PMD70 and PMD75 are best suited to differential pressure measurement.
• Measuring arrangement for gases: Mount device above the measuring point.
• Measuring arrangement for liquids and steams: Mount device below tapping point.
• For differential pressure measurement in vapour, mount the condensate traps at the same level as the same
the tapping point and at the same distance from Deltabar S.

Endress+Hauser 23
Deltabar S

Heat insulation – FMD77 The FMD77 must only be insulated up to a certain height. The maximum permitted insulation height is labelled
on the devices and applies to an insulation material with a heat conductivity
 0.04 W/(m x K) and to the maximum permitted ambient and process temperature ( see table below). The
data were determined under the most critical application "quiescent air".

TA λ ≤ 0.04 W
m•K

TP
P01-FMD77xxxx-11-xx-xx-xx-000

Maximum permitted insulation height

FMD77

Ambient temperature (TA)  70°C (158°F)


Process temperature (TP) max. 400°C (752°F), depending on the
diaphragm seal filling oil used ( see
page 59)

Wall- and pipe-mounting Endress+Hauser offers a mounting bracket for installing the device on pipes or walls.  ä 67 ff, feature 110,
"Additional options 2".
Note!
If a valve block is used, its dimensions should also be taken into consideration.
37.5


135

74
12 74
4 6
10

P01-xMD7xxxx-11-xx-xx-xx-008

Mounting bracket for wall and pipe-mounting


A bracket including mounting accessories for pipe mounting is included with the device.
1 Device mounting

24 Endress+Hauser
Deltabar S

"Separate housing" version With the "separate housing" version, you are able to mount the housing with the electronics insert at a distance
from the measuring point. This facilitates trouble-free measurement:
• Under particularly difficult measuring conditions (at installation locations that are cramped or difficult to
access)
• If rapid cleaning of the measuring point is required
• If the measuring point is exposed to vibrations.
You can choose between different cable versions:
• PE (2 m, 5 m and 10 m)
• FEP (5 m).
 ä 68 ff, Feature 110, "Additional options 2", Version "G".
 For the dimensions, see  ä 50.

FEP cable:
IP 69K
IP 66/68 NEMA 4/6P ➃ IP xx
(see chapter
PE cable: “Ordering information”)
IP 66/68 NEMA 4/6P

r ³ 120 mm

P01-xMD7xxxx-11-xx-xx-en-010

In the case of the "separate housing" version, the sensor is delivered with the process connection and cable ready
mounted. The housing and a mounting bracket are enclosed as separate units. The cable is provided with a socket at both
ends. These sockets are simply connected to the housing and the sensor.
1 Process connection with sensor
2 Cable, both ends are fitted with a socket
3 Mounting bracket provided, suitable for pipe and wall mounting
4 Housing with electronic insert

Degree of protection for the process connection with sensor with the use of
• FEP cable:
– IP 69K
– IP 66 NEMA 4/6P
– IP 68 (1.83 mH2O for 24 h) NEMA 4/6P
• PE cable:
– IP 66 NEMA 4/6P
– IP 68 (1.83 mH2O for 24 h) NEMA 4/6P
Technical data of the PE and FEP cable:
• Minimum bending radius: 120 mm (4.72 inch)
• Cable extraction force: max. 450 N
• Resistance to UV light
Use in hazardous area:
• Intrinsically safe installations (Ex ia/IS)
• FM/CSA IS: for Div.1 installatin only

Endress+Hauser 25
Deltabar S

Turn the housing The housing can be rotated up to 380° by loosening the Allen screw.
Your benefits
• Simple mounting by optimally aligning the housing
• Good, accessible device operation
• Optimum readability of the on-site display (optional).

max. 380°

P01-xMD7xxxx-17-xx-xx-xx-001

Align the housing by loosening the Allen screw.


T14 and T15 housing: 2 mm Allen key; T17 housing: 3 mm Allen key

Oxygen applications Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other things, the
following precautions must be taken:
– All components of the system, such as measuring devices, must be cleaned in accordance with the BAM
(DIN 19247) requirements.
– Dependent on the materials used, a certain maximum temperature and a maximum pressure for oxygen
applications must not be exceeded.
The devices suitable for gaseous oxygen applications are listed in the following table with the specification pmax.

Order code for devices cleaned for pmax for oxygen applications Tmax for oxygen
oxygen applications applications

PMD70 – * * * ** * * * 2 * *, 30 bar 60°C (140°F)


Devices with 500 mbar or 3000 mbar
measuring cell

PMD70 – * * * ** * * * 2 * *, PN of the flange 60°C (140°F)


Devices with 25 mbar or 100 mbar
measuring cell

PMD75 – * * * ** * * * K * * 160 bar 85°C (185°F)


PMD75 – * * * ** * * * 2 * * 160 bar 60°C (140°F)

PMD75 – * * * ** * * * 3 * * 160 bar 60°C (140°F)

FMD76 – * * * ** * T * * *, 30 bar 60°C (140°F)


Devices with 500 mbar or 3000 mbar
measuring cell

FMD76 – * * * ** * T * * *, PN of the measuring cell 60°C (140°F)


Devices with 25 mbar or 100 mbar
measuring cell

FMD77 – * * * ** T * F * * PN of the flange 60°C (140°F)

FMD78 – * * * ** * ** 4 * * 90 bar 85°C (185°F)


FMD78 – * * * ** * ** D * *

Ultra pure gas applications Endress+Hauser also offers devices for special applications, such as ultra pure gas, cleaned from oil and grease.
No special restrictions regarding the process conditions apply to these devices.
 ä 67 ff, PMD70 and PMD75: feature 80 "Seal", FMD76 and FMD77: feature 70 "Process connection low-
pressure side, material, seal".

26 Endress+Hauser
Deltabar S

Process isolating diaphragms With regard to materials in which hydrogen build-up takes place, hydrogen atoms can diffuse through the
for materials with hydrogen metalic process isolating diaphragms. This can result in incorrect measurement results.
build-up (Gold-Rhodium Endress+Hauser offers process isolating diaphragms with Gold-Rhodium coating for this application.
coating)
 ä 71 ff "Ordering information PMD75",  ä 70 "Ordering information FMD77" or  ä 76 "Ordering
information FMD78", feature 60 "Process isolating diaphragm material".

Operating conditions (Environment)

Ambient temperature range • PMD75, FMD77, FMD78: –40...+85°C (–40...+185°F), devices for lower temperatures on request
• PMD70, FMD76: –20...+85°C (–4...+185°F)
• On-site display: –20...+70°C (–4...+158°F)
Extended temperature application range with restrictions in optical properties such as display speed and
contrast: –40...+85°C (–40...+185°F)
• Separate housing: –40 to +60°C (–40 to +140°F)
For devices for use in hazardous areas, see Safety instructions, Installation or Control Drawing ( ä 82,
sections "Safety Instructions" and "Installation/Control Drawings").
The device can be used in this temperature range. The values of the specification, such as thermal change, may
be exceeded. See also DIN 16086.

Storage temperature range • –40...+ 90°C (–40...+194°F)


• On-site display: –40...+85°C (–40...+185°F)
• Separate housing: –40 to +60°C (–40 to +140°F)

Degree of protection •  ä 67 ff, feature 30 "Housing, Cable entry, Protection".


• Degree of protection IP 68 for T17 housing: 1.83 mH2O for 24 h
• Seperate housing  ä 25

Climate class Class 4K4H (air temperature: –20...55°C/–4...+131F, relative humidity: 4...100%) fulfilled as per
DIN EN 60721-3-4 (condensation possible)

Vibration resistance Device/Additional option Housing Test standard Vibration resistance

PMD70/ optional on-site display on GL guaranteed for:


FMD76 the side (T14) 2...18 Hz: ±4 mm;
18...500 Hz: 5 g in all 3 planes

PMD75 optional on-site display on IEC 61298-3 guaranteed for:


the side (T14) 10...60 Hz: ±0.35 mm;
60...2000 Hz: 5 g in all 3 planes
PMD75 optional on-site display on
the top (T15)

with mounting bracket IEC 61298-3 guaranteed for:


10...60 Hz: ±0.15 mm;
60...500 Hz: 2 g in all 3 planes

Electromagnetic compatibility • Electromagnetic compatibility to EN 61326 and NAMUR recommendation EMC (NE21). For details refer
to the declaration of conformity.
• With enhanced immunity against electromagnetic fields as per EN 61000-4-3:
30 V/m with closed cover (for devices with T14 or T15 housing)
• Maximum deviation: < 0.5% of span 1
• All EMC measurements were performed with a turn down (TD) = 2:1.

1) Larger deviations possible with PMD70 with 25 mbar or 100 mbar sensor

Endress+Hauser 27
Deltabar S

Overvoltage protection • Overvoltage protection:


(optional) – Nominal functioning DC voltage: 600 V
– Nominal discharge current: 10 kA
• Surge current check î = 20 kA as per DIN EN 60079-14: 8/20 s satisfied
• Arrester AC current check I = 10 A satisfied
 ä 68 ff, feature 100 "Additional options 1" and feature 110 "Additional options 2", version "M Overvoltage
protection".
Note!
Devices with integrated overvoltage protection must be earthed.

Operating conditions (Process)

Process temperature limits • PMD70: –20...+85°C (–4...+185°F)


• FMD76: –20...+85 °C (–4...+185°F)
• PMD75 with impulse piping longer than 100 mm: –40...+120°C (–40...+248°F),
with side flanges C22.8 and impulse piping longer than 100 mm: –10...+120°C (14...+248°F)
• FMD77 and FMD78, depending on the diaphragm seal and filling oil: up to + 400°C (+752°F)
Note!
• For oxygen applications, observe page 26 "Oxygen applications" section.
• PMD70, FMD76, PMD75 and FMD78: Observe the Process temperature range of the seal.
See also the following section "Process temperature range, seals".
• FMD77 and FMD78: Observe the temperature application limits of the diaphragm seal oil.
 ä 59, sections "Diaphragm seal filling oils".
• FMD77 and FMD78: Do not use diaphragm seals with 0.09 mm PTFE foil on AISI 316L (1.4435/1.4405)
for vacuum applications, upper temperature limit +204°C (+400°F).

Process temperature range, PMD70 (with ceramic process isolating diaphragms)


seals
Versions for feature 80 in the order code Seal Process temperature range
A FKM Viton –20...+85°C (–4...+185°F)

B EPDM –20...+85°C (–4...+185°F)

D Kalrez, Compound 4079 +5...+85°C (+41...+185°F)


E Chemraz, Compound 505 –20...+85°C (–4...+185°F)

1 FKM Viton, cleaned from oil and greace –10...+85°C (+14...+185°F)

2 FKM Viton, cleaned for oxygen service –10...+60°C (+14...+140°F)

FMD76 (with ceramic process isolating diaphragms)

Versions for feature 70 in the order code Seal Temperature operating range

B, D, F, G, U FKM Viton –20...+85°C (–4...+185°F)

K, L EPDM –20...+85°C (–4...+185°F)


FDA 21 CFR 177.2600

M, N Kalrez, Compound 4079 +5...+85°C (+41...+185°F)

P, Q Chemraz, Compound 505 –20...+85°C (–4...+185°F)

S FKM Viton, cleaned from oil and greace –10...+85°C (+14...+185°F)

T FKM Viton, cleaned for oxygen service –10...+60°C (+14...+140°F)

28 Endress+Hauser
Deltabar S

PMD75 (with metallic process isolating diaphragms)

Versions for feature 80 in the Seal Process temperature range 1


order code

A FKM Viton –20...+85°C (–4...+185°F)

C PTFE –40...+85°C (–40...+185°F)

F NBR –20...+85°C (–4...+185°F)

H Copper –40...+85°C (–40...+185°F)

K Copper, cleaned for oxygen service –20...+85°C (–4...+185°F)

1 FKM Viton, cleaned from oil and greace –10...+85°C (+14...+185°F)

2 FKM Viton, cleaned for oxygen service –10...+60°C (+14...+140°F)

3 PTFE, cleaned for oxygen service –20...+60°C (–4...+140°F)

1) lower temperature on request

FMD77 (with metallic process isolating diaphragms)

Versions for feature 70 in the Seal on the LP side (–) Process temperature range 1
order code

B, D, F, G FKM Viton –20...+85°C (–4...+185°F)

H, J PTFE –40...+85°C (–40...+185°F)

K, L EPDM –40...+85°C (–40...+185°F)

M, N Kalrez, Compound 6375 +5...+85°C (+41...+185°F)


P, Q Chemraz, Compound 505 –20...+85°C (–4...+185°F)

S FKM Viton, cleaned from oil and greace –10...+85°C (+14...+185°F)

T FKM Viton, cleaned for oxygen service –10...+60°C (+14...+140°F)

1) lower temperature on request

Pressure specifications • The maximum pressure for the measuring device is dependent on the lowest-rated element with regard to
pressure, see the following sections for this:
–  ä 8 ff, section "Measuring range"
– chapter "Mechanical construction".
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference
temperature of 20°C (68°F) or 100°F for ANSI flanges and may be applied to the device for an unlimited
time. Observe pressure-temperature dependency.
• The pressure values permitted at higher temperatures can be found in the following standards:
– EN 1092-1: 2001 Tab. 18 1
– ASME B 16.5a – 1998 Tab. 2-2.2 F316
– ASME B 16.5a – 1998 Tab. 2.3.8 N10276
– JIS B 2220
• For PMD70 and PMD75, the MWP applies for the temperature ranges specified in the "Ambient temperature
range" ( ä 27) and "Process temperature limits" ( ä 28) sections.
• The test pressure corresponds to the over pressure limit of the measuring instrument (Over pressure limits
OPL = 1.5 x MWP) and may fit only temporally limited, so that no permanent damage develops.
• The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The abbreviation
"PS" corresponds to the MWP (maximum working pressure) of the measuring device.
• In the case of sensor range and process connections where the OPL (Over Pressure Limit) of the pressure
connection is smaller than the nominal value of the sensor, the device is set at the factory, at the very
maximum, to the OPL value of the process connection. If you want to use the entire sensor range, select a
process connection with a higher OPL value (1.5 x PN; PN = MWP).
• In oxygen applications, the values for "pmax and Tmax for oxygen applications" as per  ä 26, "Oxygen
applications" may not be exceeded.

1) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO
in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.

Endress+Hauser 29
Deltabar S

Mechanical construction
Housing dimensions T14,
optional display on the side 152
111 111

FIELD TERMINALS
H
P01-xMD7xxxx-06-00-xx-xx-000

Front view, left-hand side view, top view


 See the process connection in question for installation height. Housing weight see  ä 51.

Housing dimensions T15,


155
optional display on the top
115 127
H
H

P01-xMD7xxxx-06-00-xx-xx-001

Front view, left-hand side view, top view


 See the process connection in question for installation height. Housing weight see  ä 51.

Housing dimensions T17,


132
optional display on the top
102 115
H

P01-xMD7xxxx-06-00-xx-xx-002

Front view, left-hand side view, top view


 See the process connection in question for installation height. Housing weight see  ä 51.

30 Endress+Hauser
Deltabar S

Process connections PMD70 Note!


with ceramic process isolating Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
diaphragms ( ä 68, feature 70 "Process connection") has to be ordered with a CSA approval ( ä 67, feature 10
"Approval"). These devices are fitted with a separate plate bearing the registration number 0F10524.5C.

+ – – +

7/16-20 UNF +
M10

41.3
108
H

1/4-18 NPT
RC1/4

54 96
84

P01-PMD70xxx-06-09-xx-xx-000

Process connection PMD70, oval flange


H Device height see  ä 32, section "Device height H"

Ver- Connection Mounting Material Accessories Weight 1


sion

B 1/4-18 NPT IEC 61518 7/16-20 UNF Steel C 22.8 2 vent valves (AISI 316L/1.4404) 4.0 kg
2
included
D 1/4-18 NPT IEC 61518 7/16-20 UNF AISI 316L 4.0 kg
3
F 1/4-18 NPT IEC 61518 7/16-20 UNF Alloy C276 Vent valves (Alloy C276/2.4819), 4.2 kg
see  ä 68 feature 110
"Additional options 2".

U RC 1/4 7/16-20 UNF AISI 316L 2 2 vent valves (AISI 316L/1.4404) 4.0 kg
included
1 1/4-18 NPT IEC 61518 PN 160: M10 Steel C 22.8 4.0 kg
2 1/4-18 NPT IEC 61518 PN 160: M10 AISI 316L 2 4.0 kg
3
3 1/4-18 NPT IEC 61518 PN 160: M10 Alloy C276 Vent valves (Alloy C276/2.4819), 4.2 kg
see  ä 68, feature 110
"Additional options 2".

1) Process connection weight, for housing weight see  ä 51


2) AISI 316L/1.4435
3) Alloy C276/2.4819

Endress+Hauser 31
Deltabar S

Process connections PMD70


with ceramic process isolating
(continued) + –

7/16-20 UNF + PVDF

H
108
41.3
1/4-18 NPT

54 96
84

P01-PMD70xxx-06-09-xx-xx-001

Process connection PMD70, version G, PVDF inlay, PN = 10 bar, process temperature T = –10...+60°C (14...+140°F)

H Device height see  ä 32, section "Device height H"

Version Connection Mounting Material Weight 1

G 1/4-18 NPT IEC 61518 7/16-20 UNF PVDF 3.8 kg

1) Process connection weight, for housing weight see  ä 51

Device height H

Description Device height H

T14 housing, optional display on the side 253 mm

T15 housing without display, flat cover 259 mm

T15 housing with display, high cover 271.5 mm

T17 housing, optional display on the side 269 mm

32 Endress+Hauser
Deltabar S

Process connections PMD75 Note!


with metallic process isolating Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
diaphragms ( ä 71, feature 70 "Process connection") has to be ordered with a CSA approval ( ä 68, feature 10
"Approval"). These devices are fitted with a separate plate bearing the registration number 0F10524.5C.

Oval flange, connection 1/4-18 NPT or RC 1/4

7/16-20 UNF
M 10
H

41.3 + – – +
85

1/4-18 NPT
RC1/4

54 106
85
100

7/16-20 UNF
M10 (M12)
H

41.3
72

+– 1/4-18 NPT –+
RC1/4

54 100
87
98
P01-PMD75xxx-06-09-xx-xx-005

Process connection PMD75,


above 10 mbar and 30 mbar measuring cell; below: Measuring cell 100 mbar
H Device height see  ä 35, section "Device height H"

Ver- Connection Mounting Material Accessories Weight 1


sion

B 1/4-18 NPT IEC 61518 7/16-20 UNF Steel C 22.8 2 vent valves (AISI 316L/1.4404) 4.2 kg
2
included
D 1/4-18 NPT IEC 61518 7/16-20 UNF AISI 316L 4.2 kg

F 1/4-18 NPT IEC 61518 7/16-20 UNF Alloy C276 3 Vent valves (Alloy C276/2.4819), 4.5 kg
see  ä 72, feature 110
"Additional options 2".

U RC 1/4 7/16-20 UNF AISI 316L 2 2 vent valves (AISI 316L/1.4404) 4.2kg
included
1 1/4-18 NPT IEC 61518 – PN 160: M10 Steel C 22.8 4.2 kg
– PN 420: M12

2 1/4-18 NPT IEC 61518 – PN 160: M10 AISI 316L 2 4.2 kg


– PN 420: M12

3 1/4-18 NPT IEC 61518 – PN 160: M10 Alloy C276 3 Vent valves (Alloy C276/2.4819), 4.5 kg
– PN 420: M12 see  ä 72 ff, feature 110
"Additional options 2".

1) Weight of process connections without vent valves with 10 mbar or 30 mbar sensors, process connections without
vent valves with sensors  100 mbar weght approx. 800 g less. Housing weight see  ä 51.
2) AISI 316L/1.4435 or 1.4404
3) Alloy C276/2.4819

Endress+Hauser 33
Deltabar S

Process connections PMD75 Oval flange, connection 1/4-18 NPT or RC 1/4, with side vent
with metallic process isolating
diaphragms (continued)

7/16-20 UNF 1/4-18 NPT

41.3
+ – – +
85

42
1/4-18 NPT
RC1/4

54 106
85
100
P01-PMD75xxx-06-09-xx-xx-004

Process connection PMD75, 10 mbar and 30 mbar measuring cell

7/16-20 UNF
1/4-18 NPT
H

41.3

28
72

+– 1/4-18 NPT –+
RC1/4

54 100
87
98
P01-PMD75xxx-06-09-xx-xx-003

Process connection PMD75, nominal value 100 mbar


H Device height see  ä 35, section "Device height H"

Ver- Connection Mounting Material Accessories Weight 1


sion

C 1/4-18 NPT IEC 61518 7/16-20 UNF Steel C 22.8 4 locking screws and 4.2 kg
2 vent valves included
E 1/4-18 NPT IEC 61518 7/16-20 UNF AISI 316L 2 4.2 kg
(AISI 316L/1.4404)

H 1/4-18 NPT IEC 61518 7/16-20 UNF Alloy C276 3 Vent valves (Alloy C276/2.4819), 4.5 kg
see  ä 72, feature 110
"Additional options 2".

V RC 1/4 7/16-20 UNF AISI 316L 2 4 looking screws and 4.2 kg


2 vent valves included
(AISI 316L/1.4404)

1) Weight of process connections without vent valves with 10 mbar or 30 mbar sensors, process connections without
vent valves with sensors  100 mbar weght approx. 800 g less. Housing weight see  ä 51
2) PN 160 bar measuring cells: AISI 316L/1.4435, PN 420 bar measuring cells: AISI 316L/1.4435 or 1.4404
3) Alloy C276/2.4819

34 Endress+Hauser
Deltabar S

Process connections PMD75 Oval flange, prepared for diaphragm seal mount
with metallic process isolating
diaphragms (continued)
7/16-20 UNF

H


41.3
72
+– M6 –+

54 54
87
98

P01-PMD75xxx-06-09-xx-xx-002

Left: Process connection PMD75, version W, prepared for diaphragm seal mount
Right: Position of the copper ring seal
H Device height see the following section "Device height H"
1 Diaphragm seal attachment
2 Copper ring seal
3 Process isolating diaphragm

Device height H

Description Device height H 1

T14 housing, optional display on the side 217 mm (230 mm)

T15 housing without display, flat cover 223 mm (236 mm)


T15 housing with display, high cover 235.5 mm (248.5 mm)

T17 housing, optional display on the side 233 mm (246 mm)

1) Values for devices with 10 mbar and 30 mbar measuring cell in brackets

Endress+Hauser 35
Deltabar S

Process connection FMD76 Note!


with ceramic process isolating • Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
diaphragms ( ä 74, feature 70 "Process connection") has to be ordered with a CSA approval ( ä 73, feature 10
"Approval"). These devices are fitted with a separate plate bearing the registration number 0F10524.5C.
• FMD76 devices with an EN/DIN flange DN 80 PN 40, an ANSI flange 3" 150 lbs or a JIS flange 80 A 10 K
can only be mounted with an open-ended wrench.

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527

41

41.3

7/16-20 UNF

H
h
g2
1/4-18 NPT
2

ø46

b
g
k
D

P01-FMD76xxx-06-09-xx-xx-000

Process connection FMD76, high-pressure side: EN/DIN flange,


low-pressure side: connection 1/4-18 NPT
Application limits for version "G" in feature 70 "Process connection low-pressure side" with PVDF inlay:
PN = 10 bar, process temperature T = –10...+60°C (14...+140°F)
H Device height see  ä 38, section "Device height H, devices with flange"
h Height of the device without flange thickness b

Flange 1 Boltholes
Version Material Nominal Shape 2 Nominal Diameter Thickness Raised Quantity Diameter Hole Flange
diameter pressure face circle weight 3

D b g g2 k

[mm] [mm] [mm] [mm] [mm] [kg]

B AISI 316L DN 80 B1 (D) PN 10-40 200 24 138 8 18 160 5.3


4
D ECTFE DN 80 – PN 10-40 200 24 – 8 18 160 5.3
E Alloy C276 5 DN 80 B1 (D) PN 10-40 200 24 138 8 18 160 6

F AISI 316L DN 100 B1 (C) PN 10-16 220 22 – 8 18 180 6

G AISI 316L DN 100 B1 (D) PN 25-40 235 26 162 8 22 190 8

H ECTFE  DN 100 – PN 25-40 235 26 – 8 22 190 8



J Alloy C276 DN 100 B1 (D) PN 25-40 235 26 162 8 22 190 9

L ECTFE DN 100 – PN 10-16 220 22 – 8 18 180 6

M Alloy C276  DN 100 B1 (C) PN 10-16 220 22 – 8 18 180 6.8

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets
3) Housing weight see  ä 51
4) ECTFE coating on AISI 316L/1.4435,
When operating in hazardous area, avoid electrostatic charge of the plastic surfaces.
5) Alloy C276/2.4819

36 Endress+Hauser
Deltabar S

Process connection FMD76 ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF and
with ceramic process isolating JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF
diaphragms (continued)
41
1.61 in
41.3
1.63 in

7/16-20 UNF

H
h
g2
1/4-18 NPT

ø46

b
ø1.81 in

1.6 (0.06 in)

2 (0.078 in)
g
k
ANSI

JIS
D
P01-FMD76xxx-06-09-xx-xx-001

Process connection FMD76, high-pressure side: ANSI or JIS flange (see table below),
low-pressure side: connection 1/4-18 NPT
H Device height see  ä 38, section "Device height H, devices with flange"
h Height of the device without flange thickness b

Flange 1 Boltholes
Version Material Nominal Class/ Diameter Thickness Raised face Quantity Diameter Hole circle Flange
diameter Nominal weight 2
pressure

D b g g2 k

[in] / [mm] [in] / [mm] [in] / [mm] [in] / [mm] [in] / [mm] [kg]

ANSI flanges

P AISI 316/316L 3 3 in 150 lb./sq.in 7.5 / 190.5 0.94 / 23.9 5 / 127 4 0.75 / 19.1 6 / 152.4 4.9

R ECTFE 4 4.9

S Alloy C276 5.5

T AISI 316/316L  4 in 150 lb./sq.in 9 / 228.5 0.94 / 23.9 6.19 / 157.2 8 0.75 / 19.1 7.5 / 190.5 7.1

U ECTFE  7.1

V Alloy C276 8

W AISI 316/316L  4 in 300 lb./sq.in 10 / 254 1.25 / 31.8 6.19 / 157.2 8 0.88 / 22.4 7.88 / 200.2 11.7

JIS flanges

1 AISI 316L 80 A 10 K 7.32 / 185 0.71 / 18 5 / 127 8 0.75 / 19.1 5.9 / 150 3.3

3 Alloy C276 3.7

4 AISI 316L 100 A 10 K 8.27 / 210 0.71 / 18 5.95 / 151 8 0.75 / 19.1 6.89 / 175 4.4

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.
2) Housing weight see  ä 51
3) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
4) ECTFE coating on AISI 316L.
When operating in hazardous area, avoid electrostatic charge of the plastic surfaces.

Endress+Hauser 37
Deltabar S

Process connection FMD76 Device height H, devices with flange


with ceramic process isolating
diaphragms (continued) Description Device height H (h + b)

T14 housing, optional display on the side 175 mm + flange thickness b (see tables)

T15 housing without display, flat cover 181 mm + flange thickness b (see tables)

T15 housing with display, high cover 193.5 mm + flange thickness b (see tables)

T17 housing, optional display on the side 191 mm + flange thickness b (see tables)

Process connections FMD77


100
with metallic process isolating
diaphragms, low-pressure
side 7/16-20 UNF

41.3
+– –+

1/4-18 NPT
150

103.7
P01-FMD77xxx-06-xx-xx-xx-001

Low-pressure side: connection 1/4-18 NPT, mounting optionally 7/16-20 UNF,


Side flanges material of the basic device: AISI 316L/1.4435 or 1.4404
high-pressure side, see the following section "Process connections, high-pressure side FMD77"

38 Endress+Hauser
Deltabar S

Process connections FMD77 Note!


with metallic process isolating • Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
diaphragms, high-pressure ( ä 77, feature 70 "Process connection") has to be ordered with a CSA approval ( ä 76, feature 10
side "Approval"). These devices are fitted with a separate plate bearing the registration number 0F10524.5C.
• Specifications for the "TK Ambient" and "TK Process" are listed in the following tables. These are typical
values. These temperature coefficients apply to silicone oil and the process isolating diaphragm material AISI
316L/1.4435. For other filling oils, this temperature coefficient must be multiplied by the TK correction
factor of the corresponding filling oil. For the TK correction factors, see also page 59, section "Diaphragm seal
filling oils".

EN/DIN flanges, connections as per EN 1092-1/DIN 2527

H
h
g2

b
dM
1.6 mm
0.06 in

L
g

k d3
D g

P01-FMD77xxx-06-09-xx-xx-002

Process connection FMD77, high-pressure side EN/DIN flange with and without extended diaphragm seal, material
AISI 316L
H Device height see  ä 41, section "Device height H"
h Height of the device without flange thickness b

Flange 1 Boltholes Diaphragm seal

Ver- No- Nominal Shape Dia- Thick- Raised Exten- Exten- Quan- Dia- Hole max. TK TK Flange
2
sion minal pressure meter ness face sion sion tity meter circle Dia- Am- Pro- weight 3
dia- length dia- phragm bient cess
meter meter dia-
meter

D b g L d3 g2 k dM

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]

A DN 50 PN 10-40 B1 (D) 165 20 102 – – 4 18 125 59 +3.02 +1.25 3.0


B DN 80 PN 10-40 B1 (D) 200 24 138 – – 8 18 160 89 +0.23 +0.18 5.2

C DN 80 PN 10-40 B1 (D) 200 24 – 50 76 8 18 160 72 +0.23 +0.11 6.2

100 6.7
200 7.8

F DN 100 PN 10-16 B1 (C) 220 20 – – – 8 18 180 89 +0.23 +0.28 4.8

G DN 100 PN 25-40 B1 (D) 235 24 162 – – 8 22 190 89 +0.23 +0.11 6.7

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets
3) Housing weight see  ä 51

Endress+Hauser 39
Deltabar S

Process connections FMD77 ANSI flanges, connection dimensions as per B 16.5, raised face RF
with metallic process isolating
diaphragms, high-pressure
side (continued)

H
h
g2

b
1.6 mm dM
0.06 in

L
g

k d3
D g

P01-FMD77xxx-06-09-xx-xx-000

Process connection FMD77, high-pressure side ANSI flange with and without extended diaphragm seal, material
AISI 316/316L
H Device height see  ä 41, section "Device height H"
h Height of the device without flange thickness b

Flange 1 Boltholes Diaphragm seal


Ver- No- Class Dia- Thick- Raised Exten- Exten- Quan- Dia- Hole max. TK TK Flange
sion minal meter ness face sion sion tity meter circle Dia- Am- Pro- weight 2
dia- length dia- phragm bient cess
meter meter dia-
meter

D b g L d3 g2 k dM

[lb./sq.in] [in] [in] [in] [in] [in] [in] [in] [in] [mbar/10 K] [kg]
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

N 2 150 6 0.75 3.62 – – 4 0.75 4.75 2.32 +3.02 +0.90 2.6


152.4 19.1 91.9 19.1 120.7 59
P 3 150 7.5 0.94 5 – – 4 0.75 6 3.50 +0.23 +0.18 5.1
190.5 23.9 127 19.1 152.4 89

Q 3 150 7.5 0.94 5 2 3 4 0.75 6 2.83 +0.23 +0.11 6


190.5 23.9 127 50.8 76.2 19.1 152.4 72

4 6.6
101.6

6 7.1
152.4

8 7.7
203.8

T 4 150 9 0.94 6.19 – – 8 0.75 7.5 3.50 +0.23 +0.11 7.2


228.6 23.9 157.2 19.1 190.5 89

W 4 300 10 1.25 6.19 – – 8 0.88 7.88 3.50 +0.23 +0.11 11.7


254 31.8 157.2 22.4 200.2 89

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.
2) Housing weight see  ä 51

40 Endress+Hauser
Deltabar S

Process connections FMD77 JIS flanges, connection dimensions as per JIS B 2220 BL , raised face RF
with metallic process isolating
diaphragms, high-pressure
side (continued)

H
h
0.0787"
g2

2 mm

b
dM
g

k
D
P01-FMD77xxx-06-09-xx-xx-001

Process connection FMD77, high-pressure side, JIS flange, material AISI 316L/1.4435
H Device height see the following section "Device height H"
h Height of the device without flange thickness b

Flange 1 Boltholes Diaphragm seal

Ver- Nominal Nominal Diameter Thick- Raised Quan- Diameter Hole max. Dia- TK TK Flange
sion diameter pressure ness face tity circle phragm Ambient Process weight 2
diameter

D b g g2 k dM

[mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]


[in] [in] [in] [in] [in] [in]

X 50 A 10 K 155 16 96 4 19 120 59 +3.02 +0.60 2.3


6.1 0.63 3.78 0.75 4.72 2.32
1 80 A 10 K 185 18 126 8 19 150 89 +0.23 +0.31 3.5
7.28 0.71 4.96 0.75 5.91 3.50

4 100 A 10 K 210 18 151 8 19 175 89 +0.23 +0.11 4.7


8.27 0.71 5.94 0.75 6.89 3.50

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.
2) Housing weight see  ä 51

Device height H

Description Device height H (h + b)

T14 housing, optional display on the side 325 mm + flange thickness b (see tables)

T15 housing without display, flat cover 331 mm + flange thickness b (see tables)

T15 housing with display, high cover 343.5 mm + flange thickness b (see tables)

T17 housing, optional display on the side 341 mm + flange thickness b (see tables)

Endress+Hauser 41
Deltabar S

FMD78 Basic unit

P01-FMD78xxx-06-xx-xx-xx-000

FMD78 Basic unit


H Device height the following section "Device height H"
1 Diaphragm seal attachment

Device height H

Description Device height

T14 housing, optional display on the side 217 mm


T15 housing without display, flat cover 223 mm

T15 housing with display, high cover 235.5 mm

T17 housing, optional display on the side 233 mm

42 Endress+Hauser
Deltabar S

Process connection FMD78 Note!


with metallic process isolating • Specifications for the "TK Process" are listed in the following tables. These are typically values. These
diaphragm temperature coefficients apply to silicone oil and the process isolating diaphragm material AISI 316L/
1.4435. For other filling oils, this temperature coefficient must be multiplied by the TK correction factor of
the corresponding filling oil. For the TK correction factors, see also  ä 59 ff, section "Diaphragm seal filling
oils".
• The temperature coefficient "TK Ambient" is listed in relation to the capillary length on  ä 60 in the
"Influence of the temperature on the zero point" section.
• The weights of the diaphragm seals are given in the tables. See  ä 33 for the weight of the transmitter
and  ä 51 for the weight of the housing.
• The following drawings are drawings that illustrate how the system works in principle. In other words, the
dimensions of a diaphragm seal supplied can deviate from the dimensions given in this document.

Diaphragm seal cell structure

b
dM

P01-FMD78xxx-06-09-xx-xx-000

Process connection FMD78, material AISI 316L

Flange Diaphragm seal

Version Nominal Nominal max. Diameter Thickness max. Diaphragm TK Weight of two
diameter pressure 1 diameter Process diaphragm seals

D b dM

[mm] [mm] [mm] [mbar/10K] [kg]

UF DN 50 PN 16-400 102 20 59 +2.00 2.6


UH DN 80 PN 16-400 138 20 89 +0.20 4.6

UJ DN 100 PN 16-400 162 20 89 +0.30 6.2

Flange Diaphragm seal

Version Nominal Nominal max. Diameter Thickness max. Diaphragm TK Weight of two
diameter pressure 1 diameter Process diaphragm seals

D b dM

[in] [lb/sq.in] [in] [in] [in] [mbar/10K] [kg]


[mm] [mm] [mm]

VF 2 150-2500 4.01 0.79 2.32 +1.25 2.6


102 20 59

VH 3 150-2500 5.35 0.79 3.50 +0.25 4.6


136 20 89

VJ 4 150-2500 6.22 0.79 3.50 +0.19 6.2


158 20 89

1) The specified nominal pressure applies to the diaphragm seal. The maximum pressure for the measuring device is dependent on the lowest-rated element,
with regard to pressure, of the selected components. See also  ä 29, section "Pressure specifications".

Endress+Hauser 43
Deltabar S

Process connection FMD78 Threaded ISO 228 G 1/2 B and ANSI 1/2 MNPT, separator with PTFE seal
with metallic process isolating
diaphragm (continued)
100 100

90

89
➀ ➀
SW22 SW22
22 AF 22 AF

6 1/2 NPT

P01-FMD78xxx-06-09-xx-xx-012

Process connection FMD78, left: with threaded connection ISO 228 G 1/2 B, right: with threaded connection
ANSI 1/2 MNPT
1 PTFE seal as standard max. 260 °C/500 °F (higher temperatures on request)

Version Material Nominal pressure TK Process Weight of two


diaphragm seals

[mbar/10 K] [kg]

GA AISI 316L PN 40 +0.75 2.9

RL AISI 316L PN 40 +0.55 2.9

Tri-Clamp ISO 2852


h

dM
C7

P01-FMD78xxx-06-09-xx-xx-005

Process connection FMD78, Material: AISI 316L, surface roughness of the wetted surfaces  0.8 m as standard. Lower
surface roughness on request.

Version Nominal Nominal Nominal Diameter max. Height TK Process Weight of two
diameter diameter diameter Diaphragm diaphragm
ISO 2852 DIN 32676 diameter seals

C7 dM h

[in] [mm] [mm] [mm] [mbar/10 K] [kg]

TB DN 25 DN 25 1 50.5 24 37 +10.45 0.64

TC DN 38 DN 40 1 1/2 50.5 36 30 +2.40 2.0

TD DN 51 DN 50 2 64 48 30 +1.00 2.2

TF DN 76.1 – 3 91 73 30 +0.20 2.4

44 Endress+Hauser
Deltabar S

Process connection FMD78 Tri-Clamp pipe diaphragm seal ISO 2852


with metallic measuring
diaphragms (continued)

D
d2
L

P01-FMD78xxx-06-09-xx-xx-001

Process connection FMD78, Material: AISI 316L, surface roughness of the wetted surfaces  0.8 m as standard. Lower
surface roughness on request.

Version Nominal Nominal Diameter Diameter Diameter Height Face-to-face TK Process Weight of two
diameter diameter length diaphragm
ISO 2852 seals

D d1 d2 h L
[in] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]

SB DN 25 1 22.5 43.5 50.5 67 126 +4.49 3.4


1
SC DN 38 1 1/2 35.5 43.5 50.5 67 126 +3.46 2
SD 1 DN 51 2 48.6 56.5 64 79 100 +2.69 3.4

1) Including 3.1 and pressure test as per Pressure Equipment Directive, category II

Varivent N for pipes DN 40 – DN 162


40

dM max. = 50
ø68
P01-FMD78xxx-06-09-xx-xx-006

Process connection FMD78, surface roughness of the wetted surfaces  0.8 m as standard. Lower surface roughness on
request.

Version Material Nominal pressure TK Process Weight of two


diaphragm seals

[mbar/10 K] [kg]

TR AISI 316L PN 40 +1.65 2.6

Endress+Hauser 45
Deltabar S

Process connection FMD78 DRD DN50 (65 mm)


with metallic measuring
diaphragms (continued)

41

23.6
dM max. =50 4 x ø11.5
ø65–1.2
ø84
ø105
P01-FM78xxx-06-09-xx-xx-002

Process connection FMD78, surface roughness of the wetted surfaces  0.8 m as standard. Lower surface roughness on
request.

Version Material Nominal pressure TK Process Weight of two


diaphragm seals

[mbar/10 K] [kg]

TK AISI 316L PN 25 +1.25 1.5

Hygienic connection, sanitary tank spud, extended diaphragm seal 2"

53.5

ø91.45

ø100

ø132.7

P01-FMD78xxx-06-09-xx-xx-011

Process connection FMD78, surface roughness of the wetted surfaces  0.8 m as standard. Lower surface roughness on
request.

Version Material TK Process Weight of two


diaphragm seals

[mbar/10 K] [kg]

WH AISI 316L +1.64 5

46 Endress+Hauser
Deltabar S

Process connection FMD78 Taper adapter with coupling nut, DIN 11851 (dairy fitting)
with metallic measuring
diaphragms (continued)

40
f
m
k
dM
D
G
P01-FMD78xxx-06-09-xx-xx-007

Process connection FMD78, material AISI 316L, surface roughness of the wetted surfaces  0.8 m as standard. Lower
surface roughness on request.

Taper adapter Slotted nut Diaphragm seal

Ver- Nominal Nominal Diameter Adapter Thread Height Height max. TK Process Weight of
sion diameter pressure height Diaphragm two
diameter diaphragm
seals

D f G k m dM

[mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]


MR DN 50 PN 25 68.5 11 Rd 78 x 1/6" 22 19 52 +0.90 2.2

MS DN 65 PN 25 86 12 Rd 95 x 1/6" 25 21 66 +0.29 4.0

MT DN 80 PN 25 100 12 Rd 110 x 1/4" 30 26 81 +0.30 5.1

Threaded adapter, DIN 11851 (dairy fitting)


h

dM
d1
G
P01-FMD78xxx-06-09-xx-xx-008

Process connection FMD78, material AISI 316L, surface roughness of the wetted surfaces  0.8 m as standard. Lower
surface roughness on request.

Threaded adapter Diaphragm seal

Version Nominal Nominal Diameter Height Thread max. TK Process Weight of two
diameter pressure Diaphragm diaphragm
diameter seals

d1 h G dM

[mm] [mm] [mm] [mbar/10 K] [kg]

M3 DN 50 PN 25 54 35 Rd 78 x 1/6" 52 +0.95 1.8

M4 DN 65 PN 25 71 40 Rd 95 x 1/6" 66 +0.29 3.4

M5 DN 80 PN 25 85 40 Rd 110 x 1/4" 81 +0.19 4.0

Endress+Hauser 47
Deltabar S

Process connection FMD78 EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527
with metallic measuring JIS flanges, connection dimensions as per JIS B 2220 BL
diaphragms (continued)

g2

b
dM

2
g

k
D

P01-FMD78xxx-06-09-xx-xx-009

Process connection FMD78, EN/DIN flange, Material AISI 316L

EN/DIN flange 1 Boltholes Diaphragm seal

Ver- Nominal Nominal Shape 2 Dia- Thick- Raised Quan- Dia- Hole max. TK Weight of
sion diameter pressure meter ness face tity meter circle Diaphragm Process two
diameter diaphragm
seals

D b g g2 k dM

[mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]


B3 DN 50 PN 10-40 B1 (D) 165 20 102 4 18 125 59 +1.50 6.0

B5 DN 80 PN 10-40 B1 (D) 200 24 138 8 18 160 89 +0.20 10.5

BT DN 100 PN 10-16 B1 (C) 220 20 – 8 18 180 89 +0.35 9.5


B6 DN 100 PN 25-40 B1 (D) 235 24 162 8 22 190 89 +0.19 13.3

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets

JIS flange 1 Boltholes Diaphragm seal

Ver- Nominal Nominal Diameter Thickness Raised Quantity Diameter Hole max. TK Weight of
sion diameter pressure face circle Diaphragm Process two
diameter diaphragm
seals

D b g g2 k dM

[mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]

KF 50 A 10 K 155 16 96 4 19 120 59 +0.81 4.6

KL 80 A 10 K 185 18 127 8 19 150 89 +0.19 7.0

KH 100 A 10 K 210 18 151 8 19 175 89 +0.25 9.4

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.

48 Endress+Hauser
Deltabar S

Process connection FMD78 ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF
with metallic measuring
diaphragms (continued)
g2

b
dM

1.6 mm
0.06 in

L
g

k d3

D g

P01-FMD78xxx-06-09-xx-xx-010

Process connection FMD78, ANSI flange with and without extended diaphragm seal, material AISI 316/AISI 316L

Flange 1 Boltholes Diaphragm seal

Ver- Nominal Class Dia- Thick- Raised Exten- Exten- Quan- Dia- Hole max. Dia- TK Weight of
sion dia- meter ness face sion sion tity meter circle phragm Process two dia-
meter length dia- diameter phragm
meter seals

D b g L d3 g2 k dM
[lb/sq.in] [in] [in] [in] [in] [in] [in] [in] [in] [mbar/ [kg]
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] 10 K]

AF 2 150 6 0.75 3.62 – – 4 0.75 4.75 2.32 +1.10 5.2


152.4 19.1 91.9 19.1 120.7 59

AR 2 300 6.5 0.88 3.62 – – 8 0.75 5 2.32 +0.75 6.8


165.1 22.5 91.9 19.1 127 59
AG 3 150 7.5 0.94 5 – – 4 0.75 6 3.50 +0.40 10.2
190.5 23.9 127 19.1 152.4 89

AS 3 300 8.25 1.12 5 – – 8 0.88 6.62 3.50 +0.35 14


209.5 28.4 127 22.4 168.1 89

J4 3 150 7.5 0.94 5 2 3 4 0.75 6 2.83 +0.29 12


190.5 23.9 127 50.8 76 19.1 152.4 72
4 13.2
101.6

6 14.2
152.4

8 15.4
203.6
AH 4 150 9 0.94 6.19 – – 8 0.75 7.5 3.50 +0.25 14.4
228.6 23.9 157.2 19.1 190.5 89

AT 4 300 10 1.25 6.19 – – 8 0.88 7.88 3.50 +0.19 23.4


254 31.8 157.2 22.4 200.1 89

J5 4 150 9 0.94 6.19 2 3.7 8 0.75 7.5 3.50 +0.19 17.3


228.6 23.9 157.2 50.8 94 19.1 190.5 89
4 19.8
101.6

6 22.3
152.4

8 24.8
203.6

1) The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), made of Hastelloy C, Monel or
Tantalum is Ra 0.8 μm. Lower surface roughness on request.

Endress+Hauser 49
Deltabar S

"Separate housing" version


101 84 118

131
45.5
ø51.7
P01-xxxxxxxx-06-xx-xx-xx-000

Dimensions T14 housing, optional display on the side. Housing weight see  ä 51.

101 76 118
147
45.5

ø51.7
P01-xxxxxxxx-06-xx-xx-xx-001

Dimensions T17 housing, optional display on the side. Housing weight see  ä 51.

r ³ 120 mm r ³ 120 mm r ³ 120 mm

T14 T17
45
45

ø54.1

➀ ➀ ➀
81

+– +– +– +– +–

P01-xxxxxxxx-06-xx-xx-xx-002

Reduction of the mounting height of the process connection, for application of the separate housing.
1 Process connection adapter.

If the separate housing is used, the mounting height of the process connection is reduced by approx. 45 mm
as compared to the dimensions of the standard version.
The minimum bending radius (r) for the cable is 120 mm (4.7").

50 Endress+Hauser
Deltabar S

Weight Housing

T14 T15 T17 Separate housing

Aluminium AISI 316L Aluminium AISI 316L

with electronic insert 1.2 kg 2.1 kg 1.8 kg 1.2 kg


and display Weight of housing T14, T15 or T17 + 0.5 kg.
with electronic insert 1.1 kg 2.0 kg 1.7 kg 1.1 kg Weight of sensor + 0.5 kg.
without display

Process connections
• Process connections PMD70 with ceramic process isolating diaphragms:  ä 31 ff
• Process connections PMD75 with metallic process isolating diaphragms:  ä 33 ff
• Process connection FMD76 with ceramic process isolating diaphragms:  ä 36 ff
• Process connections FMD77 with metallic process isolating diaphragms, low-pressure side:  ä 38 ff
• Process connection FMD78 with metallic process isolating diaphragm:  ä 43 ff

Material T14/T15 housing:


• T14 housing, selectable:
– Die-cast aluminium with protective powder-coating on polyester basis: RAL 5012 (blue),
cover: RAL 7035 (grey)
– Precision cast stainless steel AISI 316L (1.4435)
• T15 housing: Die-cast aluminium with protective powder-coating on polyester basis: RAL 5012 (blue),
cover: RAL 7035 (grey)
• External operation (keys and key covering): Polycarbonate PC-FR,
RAL 7035 (grey)
• Sight glass: Mineral glass
• Cable gland: Polyamid (PA)
• Pressure compensation filter: PA6 GF10
• Bind plug: PBT-GF30 FR, for Dust Ex, Ex d, FM XP and CSA XP: AISI 316L (1.4435)
• Seals:
– Cable and blind plug seal: Silicone (VMQ)
– Pressure compensation filter o-ring: Silicone (VMQ)
– Cover: EPDM
– Sight glass: Silicone (VMQ)
• Nameplates: AISI 304 (1.4301)
T17 housing:
• Housing: Stainless steel AISI 316L (1.4404)
• Sight glass:
– Version for non-hazardous area, ATEX Ex ia, NEPSI Zone 0/1 Ex ia, IECEx Zone 0/1 Ex ia, FM NI, FM
IS, CSA IS: Polycarbonate (PC)
– ATEX 1/2 D, ATEX 1/3 D, ATEX 1 GD, ATEX 1/2 GD, ATEX 3 G, FM DIP, CSA Dust Ex: Mineral glass
• Cable gland: Polyamid (PA), for Dust-Ex: CuZn nickel-plated
• Blind plug: PBT-GF30 FR, for Dust-Ex: AISI 316L (1.4435)
• Pressure compensation filter: PA6 GF10
• Seals:
– Cable and blind plug seal: Silicone (VMQ)
– Pressure compensation filter o-ring: Silicone (VMQ)
– Cover: EPDM
– Sight glass: EPDM
• Nameplates: lasered

Process connections
• "Clamp connections" and "Hygienic connections" (see also Chapter "Ordering information"): AISI 316L/
1.4435
• "Threaded connection" and "DIN/EN flanges" (see also Chapter "Ordering information"): stainless steel AISI
316L with the material number 1.4435 or 1.4404
• With regard to their stability-temperatur property, the materials 1.4435 and 1.4404 are grouped together
under 13E0 in EN 1092-1 Tab.18. The chemical composition of the two materials can be identical.

Endress+Hauser 51
Deltabar S

Cable for separate housing:


• PE cable:
Slip-resistant cable with strain-relief members made of Dynemo; shielded using aluminium-coated film;
insulated with polyethylene (PE-LD), black; copper wires, twisted, UV resistant
• FEP cable:
Slip-resistant cable; shielded using galvanized steel wire netting; insulated with fluorinated ethylene
propylene (FEP), black; copper wires, twisted, UV resistant

TSE Certificate of Suitability


The following applies to all process wetted device components:
• They do not contain any materials derived from animals.
• No auxiliaries or operating materials derived from animals are used in production or processing.

! Note!
Process wetted device components are listed in the "Mechanical construction" ( ä 30) and "Ordering
information" ( ä 67) sections.

Miscellaneous:
• Measuring cell PMD70/FMD76, filling oil
– 25 mbar and 100 mbar measuring cell: Silicone oil
– 500 mbar and 3000 mbar measuring cell: Mineral oil
– for oxygen and ultra pure gas applications: Inert oil (Voltalef 1A)
• Measuring cell PMD75/FMD77 and FMD78, filling oil (Silicone oil)
– for oxygen and ultra pure gas applications: Inert oil (Halocarbon 6.3)
• Process isolating diaphragm material:
– PMD70/FMD76: Al2O3 (Aluminium-oxide-ceramic)
– PMD75, FMD77, FMD78:
– AISI 316L (1.4435)
– Alloy C276 (2.4819)
– Monel 400 (2.4360)
– Tantal
– AISI 316L (1.4435) with Gold-Rhodium coating (FMD77/FMD78 only)
– AISI 316L (1.4435) with 0.09 mm PTFE foil (FMD77/FMD78 only)
• Process isolating diaphragm PMD70/FMD76: Al2O3 (Aluminium-oxide-ceramic)
• Mounting accessories: mounting bracket with screws AISI 304 (1.4301)
• Capillary: AISI 316 Ti (1.4571)
• Protective hose for capillary: AISI 304 (1.4301)
• External earth terminal: AISI 304 (1.4301)
• Screws and nuts for side flanges:
– PMD70: hex.-headed bolt DIN 931-M10x50-A2-70, hex.-headed nut: DIN 934-M10-A4-70
– PMD75 PN 160: hex.-headed bolt DIN 931-M12x90-A2-70, hex.-headed nut DIN 934-M12-A2-70
– PMD75 PN 420: hex.-headed bolt ISO 4014-M12x90-A4, hex.-headed nut ISO 4032-M12-A4-bs
For process connections, seals and filling oils see ordering information,  ä 67 ff.

52 Endress+Hauser
Deltabar S

Human interface
Operating elements On-site display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The on-site display shows measured
values, dialog text as well as fault and notice messages in plain text, thereby supporting the user in every stage
of operation. The liquid crystal display of the device can be turned in 90° steps.
Depending on the installation position of the device, this makes it easy to operate the device and read the
measured value.

Functions:
• 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as current
display or for PROFIBUS PA as graphical display of the scaled value of the AI Block
• Simple and complete menu guidance thanks to seperation of the parameters into three levels
• Ech parameter is given as 3-digit ID number for easy navigation
• Option for configuring the display according to individual requirements and desires, such as language,
alternating display, display of other measured values such as sensor temperature, contrast setting
• Comprehensive diagnostic functions (fault and warning message, peak-hold indicators, etc.)
• Rapid and safe commissioning with the Quick Setup menus

Measured value display Parameter


Identification
Function name Value number

Header line
Main line
Unit
Information
line
– + E Symbol
Bargraph
Editing modes

Operating keys
Selection
options

Value that
can be edited

Current measured value


P01-xxxxxxxx-07-xx-xx-en-011

Endress+Hauser 53
Deltabar S

Operating keys on the exterior of the device


The operating keys of the housing T14 (aluminium or stainless steel) are located either outside of the housing,
under the protection cap or upon the electronic insert. The operating keys of the housing T17 (ironing stainless
steel) are located inside the housing upon the electronic insert. In addition, devices with an on-site display and
a 4 to 20 mA HART- or PROFIBUS PA electronic insert have operating keys on the on-site display.

4...20 mA HART

PROFIBUS PA/
FOUNDATION Fieldbus

0%
Zero

P01-PMx7xxxx-19-xx-xx-xx-038

The operating keys located externally on the device work on the Hall sensor principle. As a result, no additional
openings are required in the device. This guarantees:
• Complete protection against environmental influences such as moisture and contamination
• Simple operation without any tools
• No wear.

Operating keys and elements located internally on the electronic insert

➃➄ ➅➆ ➄➅
t ➅ t
Sim.

on
➀ on
➀ ➁ ➂ on
➀ ➁
➁ ➃ ➂
off off 0% off 1 2

0%

Sensor
Zero
Display ➄ Sensor
Zero
Display
Simulation

➂ on on ON CK S D A 0 8

on
HW

1 2 1 2 off off 1 2 3 4 5 6 7 8
PC

1 2 off
PC

PC
1 2 3 4 5 6 7 8
Address
Histo ROM

Histo ROM

SW
HW
HART
R
250002271-–

TM
250002272-–

250002273-–

FIELD COMMUNICATION PROTOCOL

HW-Version: 1 FOUNDATION
SW-Version: 2 HW-Version: 1 HW-Version: 1
SW-Version: 2 SW-Version: 2

P01-xxxxxxxx-19-xx-xx-xx-104 P01-xxxxxxxx-19-xx-xx-xx-105 P01-xxxxxxxx-19-xx-xx-xx-106

Electronic insert HART Elektronikeinsatz PROFIBUS PA Elektronikeinsatz FOUNDATION Fieldbus


1 Operating keys 1 Green LED to indicate value being accepted 1 Green LED to indicate value being accepted
2 Slot for optional display 2 Key for position calibration and device reset 2 Key for position calibration and device reset
3 Slot for optional HistoROM®/M-DAT 3 DIP-switch for bus address 3 Slot for optional display
4 DIP-switch for locking/unlocking 4 Slot for optional display 4 Slot for optional HistoROM®/M-DAT
measured-value-relevant parameters 5 Slot for optional HistoROM®/M-DAT 5 DIP-switch for locking/unlocking
5 DIP-switch for damping on/off 6 DIP-switch for locking/unlocking measured-value-relevant parameters
6 Green LED to indicate value being accepted measured-value-relevant parameters 6 DIP-switch for simulation mode on/off
7 DIP-switch for damping on/off

54 Endress+Hauser
Deltabar S

Local operation Function External operation Internal operation Display (optional)


(operation keys, optio- (electronic insert)
nal, not T17 housing)
Position calibration
X X X
(zero point correction)
Setting lower-range value
and upper-range value - X X
X
reference pressure present (HART only) (HART only)
at the device
Device Reset X X X
Locking and unlocking
measured-value-relevant  X X
parameters
Value acceptance indica-
X X X
ted by green LED
Switching damping on and X
 X
off (HART and PA only)
Setting bus address (PA)  X X
Switching simulation
mode on and off (FOUN-  X X
DATION Fieldbus)

Remote operation Depending on the position of the write protection switch at the device, all software parameters are accessible.

HART
Remote operation via:
• Handheld terminal Field Communicator 375 (see Chapter "Hard- und Software for on-site and remote
operation"  ä 56)
• FieldCare (see Chapter "Hard- und Software for on-site and remote operation"  ä 56 ff) mit
– Commubox FXA191 (see Chapter "Hard- und Software for on-site and remote operation"  ä 56 ff)
– Commubox FXA195 (see Chapter "Hard- und Software for on-site and remote operation"  ä 56 ff)
• Field Xpert:
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on Windows
Mobile. It communicates via wireless with the optional VIATOR Bluetooth modem connected to a HART
device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520. Field Xpert also works
as a stand-alone device for asset management applications. For details refer to BA060S/00/en.

PROFIBUS PA
Remote operation via:
• FieldCare (see Chapter "Hard- und Software for on-site and remote operation"  ä 56 ff)
– Profiboard: For the Connection of a Personal Computer to PROFIBUS
– Proficard: For the Connection of a Laptop to PROFIBUS

FOUNDATION Fieldbus
Remote operation via:
• Handheld terminal Field Communicator 375 (see Chapter "Hard- und Software for on-site and remote
operation"  ä 56 ff)
• Use an FF-configuration program for e.g. NI-FBUS configurator, to
– connect devices with "FOUNDATION Fieldbus signal" into an FF-network
– set FF-specific parameter
Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops and a
schedule based on the fieldbus concept.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
– Set block and device tags
– Set device addresses
– Create and edit function block control strategies (function block applications)
– Configure vendor -defined function and transducer blocks
– Create and edit schedules
– Read and write to function block control strategies (function block applications)
– Invoke Device Description (DD) methods

Endress+Hauser 55
Deltabar S

– Display DD menus
– Download a configuration
– Verify a configuration and compare it to a saved configuration
– Monitor a downloaded configuration

– Replace a virtual device by a real device


– Save and print a configuration
Note!
For further information please contact your local Endress+Hauser Sales Center.

Hard- und Software for on-site Commubox FXA191


and remote operation
For intrinsically safe communication with FieldCare via the RS232C interface. For details refer to
TI237F700/en.

Commubox FXA195
For intrinsically safe communication with FieldCare via the USB interface. For details refer to TI404F/00/en.

Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field instruent with CDI interface (=Endress+Hauser
Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to
TI405C/07/en.

Note!
For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory:
• Cerabar S PMC71, PMP7x
• Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70

ToF Adapter FXA291


The ToF Adapter FXA291 connects the Commubox FXA291 with instruments of the ToF platform, pressure
instruments and Gammapilot via the USB interface of a personal computer or a notebook. For details refer to
KA271F.

Field Communicator 375


With a handheld terminal, all the parameters can be configured anywhere along the 4 to 20 mA line via menu
operation.

56 Endress+Hauser
Deltabar S

HistoROM®/M-DAT (optional)
HistoROM®/M-DAT is a memory module, which is attached to the electronic insert. The HistoROM®/M-DAT
can be retrofitted at any stage (Order number: 52027785).

Your benefits
• Quick and safe commissioning of the same measuring points by copying the configuration data of one
transmitter to another transmitter
• Reliable process monitoring thanks to cyclical recording of pressure and sensor temperature measured values
• Simple dagnosis by recording diverse events such as alarms, configuration changes, counters for measuring
range undershoot and overshoot for pressure and temperature as well as user limit overshoot and undershoot
for pressure and temperature etc.
• Analysis and graphic evaluation of the events and process parameters via software (contained in scope of
supply).
HistoROM®/M-DAT can be ordered via feature 100 "Additional options 1" or feature 110 "Additional options
2" or as spare parts.  ä 70 ff. A CD with Endress+Hauser operating program is also included in the scope of
delivery.
You can copy data from one transmitter to another transmitter when operating a FOUNDATION Fieldbus
device via an FF configuration program. You need the Endress+Hauser FieldCare operating program and the
Commubox FXA291 service interface and the ToF Adapter FXA291 to be able to access the data and events
saved in the HistoROM®/M-DAT.

FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can
configure all Endress+Hauser devices as wella s devices from other manufacturers that support the FDT
standard.
FieldCare supports the following functions:
• Configuration of transmitter in offline and online operation
• Loading and saving device data (upload/download)
• HistoROM®/M-DAT analysis
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA191 and the RS232C serial interface of a computer
• HART via Commubox FXA195 and the USB port on a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
• FOUNDATION Fieldbus via Commubox FXA193 and the RS232C serial interface of a computer
• Service interface with adapter Commubox FXA291 and ToF Adapter FXA291 (USB).
For further information see È www.endress.com

Endress+Hauser 57
Deltabar S

Planning instructions, diaphragm seal systems


With the Endress Hauser selection tool "Applicator" you will find the optimum diaphragm seal for your
application. Online on "www.endress.com/applicator" or offline (on CD)
For further information please contact your local Endress+Hauser Sales Center.

Applications Diaphragm seal systems should be used if the process media and the device should be separated. Diaphragm
seal systems offer clear advantages in the following instances:
• In the case of high process temperatures ( ä 28, section "Process temperature limits".)
• In the case of process media that crystallise
• In the case of corrosive or highly various process media or process media with solids content
• In the case of heterogeneous and fibrous process media
• If good and rapid measuring point cleaning is necessary
• If the measuring point is exposed to vibrations
• For mounting locations that are difficult to access

Design and operation mode Diaphragm seals are separating equipment between the measuring system and the process medium.
A diaphragm seal system consists of:
• A diaphragm seal in a one-sided system, e.g. FMD77 or two diaphragm seals, in a two-sided system, e.g.
FMD78
• One capillary tube or two capillary tubes
• Fill fluid and
• A differential pressure transmitter.
The process pressure acts via the process isolating diaphragm of the diaphragm seal on the liquid-filled system,
which transfers the process pressure via the capillary tube onto the sensor of the differential pressure
transmitter.
Endress+Hauser delivers all diaphragm seal systems as welded versions. The system is hermetically sealed,
which ensures the highest reliability.
Note!
The correlations between the individual diaphragm seal components are presented in the following section.
For further information and comprehensive diaphragm seal system designs, please contact your local
Endress+Hauser Sales Center.

Diaphragm seal
The diaphragm seal determines the application range of the system by
• the process isolating diaphragm diameter
• the process isolating diaphragm stiffness and material
• the design (oil volume).

Diaphragm diameter
The larger the diaphragm diameter (less stiffness), the smaller the temperature effect on the measurement
result.
Note: To keep the temperature effect in practice-oriented limits, you should select diaphragm seals with a
nominal diameter of DN 80, in as far as the process connection allows for it.

Diaphragm stiffness
The stiffness is dependent on the process isolating diaphragm diameter, the material, any available coating and
on the diaphragm thickness and shape. The diaphragm thickness and the shape are defined constructively. The
stiffness of a process isolating diaphragm of the diaphragm seal influences the temperature operating range and
the measuring error caused by temperature effects.

Capillary
Diaphragm seals are used with the following capillary internal diameters as standard:
• DN 50: 1 mm
• > DN 50: 2 mm
The capillary tube influences the TK zero point, the ambient temperature operating range and the response time
of a diaphragm seal system as a result of its length and internal diameter.
 ä 60 ff, sections "Influence of the temperature on the zero point", "Ambient temperature range" and
"Response time".

58 Endress+Hauser
Deltabar S

Observe the installation instructions regarding capillary tubes. See  ä 64 ff, section "Installation
instructions".

Filling oil
When selecting the filling oil, fluid and ambient temperature as well as the operating pressure are of crucial
importance. Observe the temperatures and pressures during commissioning and cleaning. A further selection
criterion is the compatibility of the filling oil with the requirements of the process medium. For this reason,
only filling oils that are harmless to health are used in the food industry, such as vegetable oil or silicone oil. 
See also the following section "Diaphragm seal filling oils".
The filling oil used influences the TK zero point and the temperature operating range of a diaphragm seal system
and the response time.  ä 60 ff, sections "Influence of the temperature on the zero point" and "Response
time".

Differential pressure transmitter


The differential pressure transmitter influences the temperature operating range, the TK zero point and the
response time as a result of the volume of its side flange and as a result of its volume change. The volume
change is the volume that has to be shifted to pass through the complete measuring range.
Differential pressure transmitters from Endress+Hauser are optimised with regard to minimum volume change
and side flange.

Diaphragm seal filling oils

Version 1 Filling oil Permissible Permissible Density Viscosity Coefficient TK Notes


temperature range at temperature range of thermal correction
0.05 bar pabs  1 bar at pabs  1 bar expansion factor
[g/cm3] [cSt at [1/K]
25°C
(77°F)]
FMD77: A Silicone oil –40...+180°C –40...+250°C 0.96 100 0.00096 1 suitable for foods
FMD78: A, 1 (–40...+356°F) (–40...+482°F) FDA 21 CFR 175.105

FMD77: V High- –10...+200°C –10...+400°C 1.07 37 0.0007 0.72 high temperatures


FMD78: C, 3 temperature oil (+14...+392°F) (+14...+752°F)

FMD77: F Inert oil –40...+80°C –40...+175°C 1.87 27 0.000876 0.91 Oil for ultra pure gas
FMD78: D, 4 (–40...+176°F) (–40...+347°F) and oxygen
applications

FMD77: D Vegetable oil –10...+120°C –10...+200°C 0.94 9.5 0.00101 1.05 suitable for foods
FMD78: B, 2 (+14...+248°F) (+14...+392°F) FDA 21 CFR 172.856

FMD77: L Low –70...+80°C2 –70...+180°C2 0.92 4.4 0.00108 1.12 low temperatures
FMD78: E, 5 temperature oil (–94...176°F) (–94...+356°F)

1) Version for feature 90 in the order code


2) Observe temperature limits of the device ( ä 27 and  ä 28)

Endress+Hauser 59
Deltabar S

Influence of the temperature A temperature change results in a volume change of the filling oil. The volume change is dependent on the
on the zero point coefficient of thermal expansion of the filling oil and on the volume of the filling oil at calibration temperature
(constant in the range: +21 to +33°C (+69.8 to 91.4°F)).  ä 59, section "Diaphragm seal filling oils".
For example, the filling oil expands in the event of a temperature increase. The additional volume presses
against the process isolating diaphragm of the diaphragm seal. The stiffer a diaphragm is, the greater its return
force, which counteracts a volume change and acts on the measuring cell together with the operating pressure,
thus shifting the zero point. For the "TK Process", see  ä 43 ff, section "Process connections FMD78".
The following diagrams display the temperature coefficient "TK Ambient" dependent on the capillary length.
The following application is displayed: capillary temperature and transmitter temperature (ambient
temperature) change, the process temperature corresponds to the calibration temperature.
The temperature coefficients obtained from the diagrams apply to silicone oil and the process isolating
diaphragm material AISI 316L/1.4435. For other filling oils, these temperature coefficients must be multiplied
by the TK correction factor of the corresponding filling oil. For the TK correction factors, see  ä 59, section
"Diaphragm seal filling oils".

TK Ambient 12
[mbar/10 K] 7
6
10

5
6
4
3
4

2
2
mbar
1.4 1
10 K

0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-FMD78xxx-05-xx-xx-en-004

Example for:
– Diaphragm seal versions "B5, EN/DIN Flange DN 80 PN 10-40 B1, AISI 316L"
– Capillary length: 5 m
– Ambient temperature, capillary/transmitter: 45°C
– Filling oil: silicone oil
1. Select characteristic curve type for the diaphragm seal versions "B5" in accordance with the following
table.
Result: characteristic curve type 2
2. Obtain value for TK Ambient from the diagram.
Result: 1.4 mbar/10 K
3. TAmbient – TCalibration = 45°C – 25°C = 20°C 1.4 mbar/10 K x 20 K = 2.8 mbar
Result: In this application, the zero point is shifted by 2.8 mbar.
Note!
• The influence of temperature on the zero point can be corrected with position calibration.
• The temperature influence can be minimised by using a filling oil with a smaller coefficient of thermal
expansion, shorter capillaries, diaphragm seals with larger diaphragm diameter or by using a smaller capillary
internal diameter.

60 Endress+Hauser
Deltabar S

Characteristic Version Diaphragm seal


type
1 TF Tri-Clamp, ISO 2852 DN 76.1 (3"), AISI 316L/1.4435
2 GA Thread ISO 228 G 1/2 B, PN 40, AISI 316L, Separator, PTFE seal
RL Thread ANSI 1/2 FNPT, PN 40, AISI 316L, Separator, PTFE seal
UH Cell DN 80 PN 16-400, AISI 316L
UJ Cell DN 100 PN 16-400, AISI 316L
VH Cell 3" 150-2500 lbs, AISI 316L
VJ Cell 4" 150-2500 lbs, AISI 316L
B5 EN/DIN flange DN 80 PN 10-40 B1, AISI 316L
BT EN/DIN flange DN 100 PN 10-16 B1, AISI 316L
B6 EN/DIN flange DN 100 PN 25-40 B1, AISI 316L
AG ANSI flange 3" 150 lbs RF, AISI 316/316L
AS ANSI flange 3" 300 lbs RF, AISI 316/316L
AH ANSI flange 4" 150 lbs RF, AISI 316/316L
J5 ANSI flange 4" 150 lbs RF, AISI 316/316L, Extensions: 2"/4"/6"/8"
AT ANSI flange 4" 300 lbs RF, AISI 316/316L
KL JIS flange 80 A 10 K RF, AISI 316L
KH JIS flange 100 A 10 K RF, AISI 316L
MT DIN 11851 DN 80 PN 25, AISI 316L
M5 DIN 11851 DN 80 PN 25 socket, AISI 316L
3 MS DIN 11851 DN 65 PN 25, AISI 316L
M4 DIN 11851 DN 65 PN 25 socket, AISI 316L
J4 ANSI flange 3" 150 lbs RF, AISI 316/316L, Extensions: 2"/4"/6"/8"
4 SC Pipe seal diaphragm Tri Clamp, ISO 2852 DN 38 (1 1/2"), AISI 316L/1.4435
SD Pipe seal diaphragm Tri Clamp, ISO 2852 DN 51 (2"), AISI 316L/1.4435
5 UF Cell DN 50 PN 16-400, AISI 316L
VF Cell 2" 150-2500 lbs, AISI 316L
B3 EN/DIN flange DN 50 PN 10-40 B1, AISI 316L
AF ANSI flange 2" 150 lbs RF, AISI 316/316L
AR ANSI flange 2" 300 lbs RF, AISI 316/316L
KF JIS flange 50 A 10 K RF, AISI 316L
MR DIN 11851 DN 50 PN 25, AISI 316L
M3 DIN 11851 DN 50 PN 25 socket, AISI 316L
6 TD Tri-Clamp, ISO 2852 DN 51 (2"), DIN 32676 DN 50, AISI 316L/1.4435
7 TK DRD DN50 (65 mm), PN 25, AISI 316L/1.4435
TR Varivent Type N for tubes DN 40 – DN 162, PN 40, AISI 316L/1.4435

TK Ambient 90
[mbar/10 K]
80

70
11
60

50

40
10
30
9
20
8
10

0
0 1 2 3 4 5 6 7 8 9 10

Capillary length
[m]
P01-FMD78xxx-05-xx-xx-en-005

Endress+Hauser 61
Deltabar S

Characteristic Version Diaphragm seal


type
8 SB Pipe seal diaphragm Tri-Clamp, ISO 2852 DN 25 (1"), AISI 316L/1.4435
9 WH Sanitary tank spud, AISI 316L/1.4435, Extensions 2"
10 TC Tri-Clamp, ISO 2852 DN 38 (1 – 1 1/2"), DIN 32676 DN 40, AISI 316L/1.4435
11 TB Tri-Clamp, ISO 2852 DN 25 (1"). DIN 32676 DN 25, AISI 316L/1.4435

Ambient temperature range The operating temperature range of a diaphragm seal system depends on Fill fluid, "Capillary length and
internal diameter, Process temperature and Diaphragm seal oil volume.
The range of application can be extended by using a fill fluid with a smaller expansion coefficient and a shorter
capillary. The permitted operating temperature ranges in relation to the capillary length can be calculated
online at "Applicator Sizing Diaphragm Seal":
http://www.endress.com/applicator -> Applicator Sizing Diaphragm Seal -> Horncurve

P01-xxxxxxxx-20-xx-xx-en-001

Note!
• Endress+Hauser recommends you use a low temperature oil for applications that require short response
times or are close to the lower temperature limit (see "diaphragm seal fill fluid").
• Please contact your Endress+Hauser sales office for further information, comprehensive diaphragm seal
system designs and measuring technology solutions that are close to the application limits.

Response time The viscosity of the filling oil, the capillary length and the capillary internal diameter influence the frictional
resistance. The greater the frictional resistance, the longer the response time.
Furthermore, the volume change of the measuring cell influences the response time. The lower the
volume change of the measuring cell is, the less filling oil has to be shifted in the diaphragm seal system.
The following diagram shows typical response times (T90) for the various filling oils dependent on the
measuring cell and the capillary internal diameter. The values given are in seconds per metre of capillary length
and must be multiplied by the actual length of the capillary. The response time of the transmitter must also be
taken into consideration.

62 Endress+Hauser
Deltabar S

Ambient temperature range = 20°C


8

Response time (T90) [sec/m]


6
Silicone oil
4 High temperature oil
Vegetable oil
Inert oil
2

0
DN 50 DN 80 DN 50 DN 80 Nominal diameter
(1 mm) (2 mm) (1 mm) (2 mm) Capillary internal diameter
500 mbar 3 bar Measuring cell
P01-FMD78xxx-05-xx-xx-en-000

100 %

90 %

T90 t

P01-xxxxxxxx-05-xx-xx-xx-006

Presentation of the response time (T90%)


1 Pressure step
2 Output signal

Minimise response time by Comments

Larger capillary internal diameter The temperature effect increases with increasing diameter.

Shorter capillaries –

Filling oil with lower viscosity – Observe compatibility of the filling oil with the process
fluid.
– Observe the filling oil operating limits.

Endress+Hauser 63
Deltabar S

Installation instructions Instructions for diaphragm seal systems


• Endress+Hauser offer flushing rings as accessory to clean process isolating diaphragms without taking the
transmitters out of process.
For further information please contact your local Endress+Hauser Sales Center.
• The diaphragm seal together with the transmitter form a closed, calibrated system, which is filled through
ports in the diaphragm seal and in the measuring system of the transmitter. These ports are sealed and must
not be opened.
• In the case of devices with diaphragm seals and capillaries, the zero point shift caused by the hydrostatic
pressure of the filling liquid column in the capillaries must be taken into account when selecting the
measuring cell. If a measuring cell with a small measuring range is selected, the sensor nominal range can
be overdriven as a result of position adjustment.  See the following diagram and the following example.
• For devices with capillary a suitable fastening device (mounting bracket) is recommended.
• When using a mounting bracket, sufficient strain relief must be allowed for in order to prevent the capillary
bending down (bending radius 100 mm).
• The temperature and length of both capillaries should be the same when using two-sided diaphragm seal
systems.

Selecting the measuring cell (observe the hydrostatic pressure of the filling fluid column in the capillaries!)

pi

Capillaries with silicone oil


max. ρFl = 0.96 kg/dm3

ΔH = 1 m Hv = 1.8 m

min. +
Hu = 0.2 m

H1 = 0.3 m
+ –

Tank with water


ρM = 1.0 kg/dm3
P01-FMD78xxx-11-xx-xx-en-004

Pressure on the negative side of the differential pressure transmitter (p–) when the tank is empty (min. level)

p–= pHv+ pH1 = Hv • ρ Fl • g + H1 • ρFl • g + p i

kg kg
= 1.8 m • 0.96 • 9.81 m m
s + 0.3 m • 0.96 dm3 • 9.81 s + pi
dm3
= 197.77 mbar + p i

Pressure on the positive side of the differential pressure transmitter (p+) when the tank is empty (min. level)

p+= pHu+ pH1 = Hu • ρM • g + H1 • ρFl • g + pi

kg kg
= 0.2 m • 1 • 9.81 m m
s + 0.3 m • 0.96 dm3 • 9.81 s + pi
dm3
= 47.87 mbar + pi

Differential pressure at the transmitter (pTransmitter) when the tank is empty

64 Endress+Hauser
Deltabar S

Result:
If the tank were full, a differential pressure of –51.80 mbar would be present at the differential pressure transmitter. When
the tank is empty, a differential pressure of –149.90 mbar is present. Therefore, a 500 mbar measuring cell is required for
this application.

Installation instructions
In order to obtain more precise measurement results and to avoid a defect in the device, mount the capillaries
as follows:
• vibration-free (in order to avoid additional pressure fluctuations)
• not in the vicinity of heating or cooling lines
• insulate if the ambient temperature is below ore above the reference temperature
• with a bending radius of 100 mm.

Vacuum applications
For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter underneath
the lower diaphragm seal. A vacuum load of the diaphragm seal caused by the presence of filling oil in the
capillaries is hereby prevented.
When the pressure transmitter is mounted above the lower diaphragm seal, the maximum height difference
H1 in accordance with the following illustration on the left must not be exceeded. The maximum height
difference is dependent on the density of the filling oil and the smallest ever pressure that is permitted to occur
at the diaphragm seal on the positive side (empty tank), see the following illustration, on the right.

12.0
Low temperature oil
10.0
Height difference H1 [m]
Vegetable oil

8.0
– Silicone oil
6.0
High temperature
– + oil
+ –
4.0

H1 Inert oil
2.0
+
0.0
50 100 200 300 400 500 600 700 800 900 1000
Pressure, diaphragm seal positive side [mbarabs]

P01-FMD7xxxx-11-xx-xx-xx-001 P01-FMD7xxxx-05-xx-xx-en-002

Installation above the lower diaphragm seal Diagram of maximum installation height above the lower diaphragm
seal for vacuum applications dependent on the pressure at the
diaphragm seal on the positive side

Endress+Hauser 65
Deltabar S

Certificates and approvals


CE mark The device meets the legal requirements of the relevant EC directives. Endress+Hauser confirms that the
device has been successfully tested by applying the CE mark.

Ex approvals • ATEX
• FM
• CSA
• NEPSI
• IECEx
• GOST on request
• also combinations of different approvals
All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
 ä 82 ff, sections "Safety Instructions" and "Installation/Control Drawings".

Marine certificate • GL: FMD76, FMD78, PMD70, PMD75


• ABS: FMD76, FMD78, PMD70, PMD75

Functional Safety SIL / IEC The Deltabar S with 4 to 20 mA output signal have been developed to IEC 61508 standard. These devices can
61508 Declaration of confor- be used for flow, level and differential pressure monitoring up to SIL 3.
mity (optional) È For a detailed description of the safety functions with Deltabar S, settings and characteristic quantities for
functional safety, please refer tot the "Manual for Functional Safety- Deltabar S" SD189.
È For devices with SIL / IEC 61508 declaration of conformity see  ä 67 ff, Feature 100 "Additional option
1" and Feature 110 "Additional option 2" version E "SIL / IEC 61508, declaration of Conformity".

Overspill protection WHG (German Water Resources Act). See "Ordering information"  ä 67 (see also ZE259P/00/de).

CRN approvals Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
( ä 68, feature 70 "Process connection") has to be ordered with a CSA approval ( ä 67, feature 10
"Approval"). These devices are fitted with a separate plate bearing the registration number 0F10524.5C.

Pressure Equipment Directive The devices PMD70, PMD75, FMD76, FMD77 und FMD78 corresponds to Article 3 (3) of the EC directive
(PED) 97/23/EC (Pressure Equipment Directive) and has been designed and manufactured according to good
engineering practice.
Additionally applies:
– FMD78 with pipe diaphragm seal 1.5"/PN40:
Suitable for stable gases in group 1, category II
– PMD75, PN 420
Suitable for stable gases in group 1, category I

Standards and guidelines DIN EN 60770 (IEC 60770):


Transmitters for use in industrial-process control systems
Part 1: Methods for inspection and routine testing
DIN 16086:
Electrical pressure measuring instruments, pressure sensors, pressure transmitters, pressure measuring
instruments, concepts, specifications in data sheets
EN 61326-X:
EMC product family standard for electrical equipment for measurement, control and laboratory use.

66 Endress+Hauser
Deltabar S

Ordering information
PMD70 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
m 8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
– + E Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
W CSA Class II, III Division 1, Groups E – G (Dust-Ex)
E Combi-certification
ATEX II Ex ia + FM IS + CSA IS
ATEX II 1/2G Ex ia IIC T6 +
FM/CSA IS Class I, II, III Division 1 Group A - G
H NEPSI Ex ia IIC T6
I IECEx Zone 0/1 Ex ia IIC T6

20 Output; Operation:
n A 4...20 mA HART, SIL operation outside, LCD (see Fig. ➀, n)
4...20 mA HART, SIL operation inside, LCD (see Fig. ➀, o)
➂ B
C 4...20 mA HART, SIL operation inside (see Fig. o)
M PROFIBUS PA, operation outside, LCD (see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (see Fig. ➀, n)
Q FOUNDATION Fieldbus, operation inside, LCD (see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (see Fig. o)

30 Housing; Cable entry; Protection:


T14 A Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
T15 C Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M12x1 PA plug
E Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
F Aluminium T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
J Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
K Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
L Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
T17 M Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, M12x1 PA plug
N Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
P Aluminium T15 housing, optional display on the top, IP 65/NEMA 4X, Han7D plug, 90°
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover
Z Housing: see additional specifications

40 Nominal range; PN:


Nominal value PN
7B 25 mbar/2500 Pa/0.375 psi 10 bar/1 MPa/150 psi
7D 100 mbar/10 kPa/1.5 psi 16 bar/1,6 MPa/240 psi
7F 500 mbar/50 kPa/7.5 psi 100 bar/10 MPa/1500 psi
7H 3 bar/300 kPa/45 psi 100 bar/10 MPa/1500 psi
78 Prepared mounting Deltatop

Endress+Hauser 67
Deltabar S

PMD70 (continued) 50 Calibration; Unit:


1 Nominal range; mbar/bar
2 Nominal range; kPa/MPa
3 Nominal range; mmH2O/mH2O
4 Nominal range; inH2O/ftH2O
6 Nominal range; psi
8 Adjusted for Deltatop; see additional specification
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate; see additional specification

70 Process connection; Material:


B 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, C22.8 (CRN)
D 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, AISI 316L (CRN)
F 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, Alloy C (CRN)
G 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, PVDF
U RC 1/4 mounting: 7/16 – 20 UNF, AISI 316L (CRN)
1 1/4 – 18 NPT, mounting: PN 160: M10, C22.8 (CRN)
2 1/4 – 18 NPT, mounting: PN 160: M10, AISI 316L (CRN)
3 1/4 – 18 NPT, mounting: PN 160: M10, Alloy C (CRN)

80 Seal:
A FKM Viton
B EPDM
D Kalrez
E Chemraz
1 FKM Viton, cleaned from oil and greace
2 FKM Viton, cleaned for oxygen service
Note application limits pressure/temp.

100 Additional option 1:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted components, inspection certificate as per
EN 10204 3.1 acc. to specification 52005759
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL/ABS marine certificate
U Mounting bracket, wall/pipe, 304
V Mounting on shut-off valve from above
W Mounting on shut-off valve from below
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

110 Additional option 2:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted components, inspection certificate as per
EN10204 3.1 acc. to specification 52005759
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
(FM /CSA IS: nur für Div.1 Installation)
K Vent valves (2 pieces), Alloy C
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
R Screws 7/16 UNF, length 1 1/2" (4 pieces) for oval flange adapter PZO
S GL/ABS marine certificate
U Mounting bracket for wall/pipe, AISI 304
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1
5 Helium leak test EN 1518 with test certificate,
inspection certificate as per EN 10204 3.1

68 Endress+Hauser
Deltabar S

PMD70 (continued) 995 Identification:


Z1 Measuring point (TAG)
Z2 Bus address

PMD70 order code

Endress+Hauser 69
Deltabar S

PMD75 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d IIC T6
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
m V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust-Ex)
G NEPSI Exd IIC T6
H NEPSI Ex ia IIC T6
– + E
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates: ATEX II Ex ia / Ex d + FM/CSA IS + XP; ATEX II 1/2G Ex ia IIC T6+; ATEX II 2G Ex d IIC T6+;
FM/CSA IS + XP Cl.I Div.1 Gr.A-D

20 Output; Operation:
n A 4...20 mA HART, SIL operation outside, LCD (see Fig. ➀, n)
4...20 mA HART, SIL operation inside, LCD (see Fig. ➀, o)
➂ B
C 4...20 mA HART, SIL operation inside (see Fig. o)
M PROFIBUS PA, operation outside, LCD (see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (see Fig. ➀, n)
Q FOUNDATION Fieldbus, operation inside, LCD (see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (see Fig. o)

30 Housing; Cable entry, Protection:


A Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
T14
B Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M12x1 PA plug
T15 E Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
F Aluminium T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
J Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
K Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
L Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
M Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
+ –

T17 N Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
P Aluminium T15 housing, optional display on the top, IP 65/NEMA 4X, Han7D plug, 90°
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover
Z Housing: see additional specifications

70 Endress+Hauser
Deltabar S

PMD75 (continued) 40 Nominal range; PN:


Nominal value PN
7B 10 mbar/1 kPa/0.15 psi 160 bar/16 MPa/2400 psi
7C 30 mbar/3 kPa/0.45 psi 160 bar/16 MPa/2400 psi
7D 100 mbar/10 kPa/1.5 psi 160 bar/16 MPa/2400 psi
7F 500 mbar/50 kPa/7.5 psi 160 bar/16 MPa/2400 psi
7H 3 bar/300 kPa/45 psi 160 bar/16 MPa/2400 psi
7L 16 bar/1,6 MPa/240 psi 160 bar/16 MPa/2400 psi
7M 40 bar/4 MPa/600 psi 160 bar/16 MPa/2400 psi
8F 500 mbar/50 kPa/7.5 psi 420 bar/42 MPa/6300 psi
8H 3 bar/300 kPa/45 psi 420 bar/42 MPa/6300 psi
8L 16 bar/1.6 MPa/240 psi 420 bar/42 MPa/6300 psi
8M 40 bar/4 MPa/600 psi 420 bar/42 MPa/6300 psi
78 Prepared for Deltatop; PN = 160 bar
88 Prepared for Deltatop; PN = 420 bar

50 Calibration; Unit:
1 Nominal range; mbar/bar
2 Nominal range; kPa/MPa
3 Nominal range; mmH2O/mH2O
4 Nominal range; inH2O/ftH2O
6 Nominal range; psi
8 Adjusted for Deltatop; see additional specification
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate; see additional specification

60 Process isolating diaphragm material:


1 AISI 316L
2 Alloy C
3 Monel
5 Tantal
6 Alloy C with Gold-Rhodium coating

70 Process connection; Material:


B 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, C22.8 (CRN),
including 2 vent valves (AISI 316L)
C 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, C22.8, side vent,
including 4 fastening bolt connections and 2 vent valves (AISI 316L)
D 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, AISI 316L (CRN),
including 2 vent valves (AISI 316L)
E 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, AISI 316L, side vent,
including 4 fastening bolt connections and 2 vent valves (AISI 316L)
F 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, Alloy C (CRN),
without screws/vents
H 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, Alloy C,
side vent, without screws/vents
U RC 1/4 mounting: 7/16 – 20 UNF, AISI 316L (CRN),
including 2 vent valves (AISI 316L)
V RC 1/4 mounting: 7/16 – 20 UNF, AISI 316L, side vent,
including 4 fastening bolt connections and 2 vent valves (AISI 316L)
W Prepared for diaphragm seal mount
1 1/4 – 18 NPT, mounting: PN 160: M10, PN 420: M12, C22.8 (CRN),
including 2 vent valves (AISI 316L)
2 1/4 – 18 NPT, mounting: PN 160: M10, PN 420: M12, AISI 316L (CRN),
including 2 vent valves (AISI 316L)
3 1/4 – 18 NPT, mounting: PN 160: M10, PN 420: M12, Alloy C (CRN)

80 Seal:
A FKM Viton
C PTFE
F NBR
K Copper seal ring, cleaned for oxygen service
1 FKM Viton, cleaned from oil and greace
2 FKM Viton, cleaned for oxygen service
Note application limits pressure/temp.
3 PTFE, cleaned for oxygen service
H Copper seal ring

Endress+Hauser 71
Deltabar S

PMD75 (continued) 100 Additional option 1:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted components, inspection certificate as per EN
10204 3.1 acc. to specification 52005759
C NACE MR0175 (wetted parts)
D Material test certificate for wetted components as per EN 10204 3.1 and NACE
MR0175 material, inspection certificate as per EN 10204 acc. to specification
52010806
➃ M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL/ABS marine certificate
U Mounting bracket, wall/pipe, 304
V Mounting on shut-off valve from above (see Fig. ➃)
W Mounting on shut-off valve from below (see Fig. ➄)
➄ 2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1

110 Additional option 2:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted components, inspection certificate as per
EN 10204 3.1 acc. to specification 52005759
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
(FM/CSA IS: nur für Div.1 Installation)
K Vent valves (2 pieces), Alloy C
L Vent valves (4 pieces), Alloy C
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
R Screws 7/16 UNF, length 1 1/2" (4 pieces) for oval flange adapter PZO
S GL/ABS marine certificate
U Mounting bracket for wall/pipe, AISI 304
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1
5 Helium leak test EN 1518 with test certificate inspection certificate as per
EN 10204 3.1

995 Identification:
Z1 Measuring point (TAG)
Z2 Bus address

PMD75 complete order code

72 Endress+Hauser
Deltabar S

FMD76 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
m 2 ATEX II 1/2 D Ex ia IIC T6
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
7 ATEX II 3 G Ex nA II T6
– + E S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
E Combi-certification
ATEX II Ex ia + FM IS + CSA IS
ATEX II 1/2G Ex ia IIC T6 +
FM/CSA IS Class I, II, III Division 1 Group A - G
H NEPSI Ex ia IIC T6
I IECEx Zone 0/1 Ex ia IIC T6

20 Output; Operation:
n A 4...20 mA HART, SIL operation outside, LCD (see Fig. ➀, n)
4...20 mA HART, SIL operation inside, LCD (see Fig. ➀, o)
➂ B
C 4...20 mA HART, SIL operation inside (see Fig. o)
M PROFIBUS PA, operation outside, LCD (see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (see Fig. ➀, n)
Q FOUNDATION Fieldbus, operation inside, LCD (see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (see Fig. o)

30 Housing; Cable entry, Protection:


A Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
T15 D Aluminium T14 housing, optional display on the side, IP66/67/NEMA 4X/ 6P, M12x1 PA plug
E Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
T14 F Aluminium T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
J Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
K Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
L Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
M Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
N Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
P Aluminium T15 housing, optional display on the top, IP 65/NEMA 4X, Han7D plug, 90°
T17
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P,M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover
Z Housing: see additional specifications

40 Nominal range; PN:


Nominal value PN
7D 100 mbar/10 kPa/1.5 psi 16 bar/1,6 MPa/240 psi
7F 500 mbar/50 kPa/7.5 psi 100 bar/10 MPa/1500 psi
7H 3 bar/300 kPa/45 psi 100 bar/10 MPa/1500 psi

Endress+Hauser 73
Deltabar S

FMD76 (continued) 50 Calibration; Unit:


1 Nominal range; mbar/bar
2 Nominal range; kPa/MPa
3 Nominal range; mmH2O/mH2O
4 Nominal range; inH2O/ftH2O
6 Nominal range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate: see additional specification

70 Process connection low-pressure side; Material; Seal:


Mounting: 7/16 – 20 UNF
B 1/4 – 18 NPT IEC 61518, C22.8, FKM Viton (CRN)
D 1/4 – 18 NPT IEC 61518, AISI 316L, FKM Viton (CRN)
F 1/4 – 18 NPT IEC 61518, Alloy C, FKM Viton (CRN)
G 1/4 – 18 NPT IEC 61518, PVDF, FKM Viton,
Safety instructions, observe electrostatic charge.
K 1/4 – 18 NPT IEC 61518, AISI 316L, EPDM (CRN)
L 1/4 – 18 NPT IEC 61518, Alloy C, EPDM (CRN)
M 1/4 – 18 NPT IEC 61518, AISI 316L, Kalrez (CRN)
N 1/4 – 18 NPT IEC 61518, Alloy C, Kalrez (CRN)
P 1/4 – 18 NPT IEC 61518, AISI 316L, Chemraz (CRN)
Q 1/4 – 18 NPT IEC 61518, Alloy C, Chemraz (CRN)
S 1/4 – 18 NPT IEC 61518, AISI 316L, FKM Viton, cleaned from oil and greace (CRN)
T 1/4 – 18 NPT IEC 61518, AISI 316L, FKM Viton, cleaned for oxygen service (CRN)
U RC 1/4, AISI 316L, FKM Viton (CRN)

80 Process connection high-pressure side; Material:


EN/DIN flanges
B DN 80 PN 10-40 B1, AISI 316L
D DN 80 PN 10-40, AISI 316L with ECTFE coating
Safety instructions, observe electrostatic charge!
E DN 80 PN 10-40 B1, Alloy C276
F DN 100 PN 10-16 B1, AISI 316L
G DN 100 PN 25-40 B1, AISI 316L
H DN 100 PN 25-40, AISI 316L with ECTFE coating
Safety instructions, observe electrostatic charge!
J DN 100 PN 25-40 B1, Alloy C276
L DN 100 PN 10-16, AISI 316L with ECTFE coating
Safety instructions, observe electrostatic charge!
M DN 100 PN 10-16 B1, Alloy C276
ANSI flanges
P 3" 150 lbs RF, AISI 316/316L (CRN)
R 3" 150 lbs, AISI 316/316L with ECTFE coating
Safety instructions, observe electrostatic charge!
S 3" 150 lbs RF, Alloy C276 (CRN)
T 4" 150 lbs RF, AISI 316/316L (CRN)
U 4" 150 lbs, AISI 316/316L with ECTFE coating
Safety instructions, observe electrostatic charge!
V 4" 150 lbs RF, Alloy C276 (CRN)
W 4" 300 lbs RF, AISI 316/316L (CRN)
JIS flanges
1 10K 80A RF, AISI 316L
3 10K 80A RF, Alloy C276
4 10K 100A RF, AISI 316L

74 Endress+Hauser
Deltabar S

FMD76 (continued) 100 Additional option 1:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted components, inspection certificate as per
EN 10204 3.1 acc. to specification 52005759
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL/ABS marine certificate
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1

110 Additional option 2:


A not selected
E SIL/IEC 61508 Declaration of conformity
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
(FM/CSA IS: nur für Div.1 Installation)
K Vent valves (2 pieces), Alloy C
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
R Screws 7/16 UNF, length 1 1/2" (4 pieces) for oval flange adapter PZO
S GL/ABS marine certificate
U Mounting bracket for wall/pipe, AISI 304
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1
5 Helium leak test EN 1518 with test certificate, inspection certificate as per
EN 10204 3.1

995 Identification:
Z1 Measuring point (TAG)
Z2 Bus address

FMD76 order code

Endress+Hauser 75
Deltabar S

FMD77 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
m 2 ATEX II 1/2 D
4 ATEX II 1/3 D
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6

5 ATEX II 2 G Ex d IIC T6
+ E

7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx ia
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust-Ex)
G NEPSI Ex d IIC T6
H NEPSI Ex ia IIC T6
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates: ATEX II Ex ia / Ex d + FM/CSA IS + XP; ATEX II 1/2G Ex ia IIC T6+; ATEX II 2G Ex d IIC T6+;
FM/CSA IS + XP Cl.I Div.1 Gr.A-D

20 Output; Operation:
n A 4...20 mA HART, SIL operation outside, LCD (see Fig. ➀, n)
4...20 mA HART, SIL operation inside, LCD (see Fig. ➀, o)
➂ B
C 4...20 mA HART, SIL operation inside (see Fig. o)
M PROFIBUS PA, operation outside, LCD (see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (see Fig. ➀, n)
Q FOUNDATION Fieldbus, operation inside, LCD (see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (see Fig. o)

30 Housing; Cable entry, Protection:


T14 A Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M12x1 PA plug
T15 E Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
F Aluminium T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
J Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
K Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
L Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
M Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
+ – N Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
T17 P Aluminium T15 housing, optional display on the top, IP 65/NEMA 4X, Han7D plug, 90°
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover
Z Housing: see additional specifications

76 Endress+Hauser
Deltabar S

FMD77 (continued) 40 Nominal range; PN:


Nominal value PN
7D 100 mbar/10 kPa/1.5 psi 160 bar/16 MPa/2400 psi
7F 500 mbar/50 kPa/7.5 psi 160 bar/16 MPa/2400 psi
7H 3 bar/300 kPa/45 psi 160 bar/16 MPa/2400 psi
7L 16 bar/1.6 MPa/240 psi 160 bar/16 MPa/2400 psi

50 Calibration, Units:
1 Calibration: nominal range, mbar/bar
2 Calibration: nominal range, kPa/MPa
3 Calibration: nominal range, mmH2O/mH2O
4 Calibration: nominal range, inH2O/ftH2O
6 Calibration: nominal range, psi
B Custom calibration: see additional specification
C Factory calibration: see additional specification, Factory calibration certificate, 5-point
D DKD calibration: see additional specification

60 Process isolating diaphragm material (high-pressure side):


1 AISI 316L
2 Alloy C
3 Monel
5 Tantalum
6 AISI 316L with Gold-Rhodium coating
7 AISI 316L with 0.09 mm PTFE foil (not for vacuum applications)

70 Process connection low-pressure side; Material; Seal:


Mounting: 7/16 – 20 UNF
B 1/4 – 18 NPT IEC 61518, C22.8, FKM Viton (CRN)
D 1/4 – 18 NPT IEC 61518, AISI 316L, FKM Viton (CRN)
F 1/4 – 18 NPT IEC 61518, Alloy C276, FKM Viton (CRN)
H 1/4 – 18 NPT IEC 61518, AISI 316L, PTFE+C4-ring (CRN)
J 1/4 – 18 NPT IEC 61518, Alloy C, PTFE+C4-ring (CRN)
K 1/4 – 18 NPT IEC 61518, AISI 316L, EPDM (CRN)
L 1/4 – 18 NPT IEC 61518, Alloy C, EPDM (CRN)
M 1/4 – 18 NPT IEC 61518, AISI 316L, Kalrez (CRN)
N 1/4 – 18 NPT IEC 61518, Alloy C, Kalrez (CRN)
P 1/4 – 18 NPT IEC 61518, AISI 316L, Chemraz (CRN)
Q 1/4 – 18 NPT IEC 61518, Alloy C, Chemraz (CRN)
S 1/4 – 18 NPT IEC 61518, AISI 316L, cleaned from oil and greace (CRN)
T 1/4 – 18 NPT IEC 61518, AISI 316L, cleaned for oxygen service (CRN)
U RC 1/4, AISI 316L, FKM Viton (CRN)

80 Process connection high-pressure side; Material:


EN/DIN flanges
A DN 50 PN 10-40 B1, AISI 316L
B DN 80 PN 10-40 B1, AISI 316L
C DN 80 PN 10-40 B1, extended diaphragm seal: 50 mm/100 mm/200 mm,
extended diaphragm seal: see additional specification
F DN 100 PN 10-16 B1, AISI 316L
G DN 100 PN 25-40 B1, AISI 316L
ANSI flanges
N 2" 150 lbs, RF, AISI 316/316L (CRN)
P 3" 150 lbs, RF, AISI316/ 316L (CRN)
Q 3" 150 lbs RF, AISI 316/316L, extended diaphragm seal: 2"/4"/6"/8", extended
diaphragm seal: see additional specification
T 4" 150 lbs, RF, AISI 316L (CRN)
5 3" 150 lbs, RF, compact, 316/316L, flange ANSI B16.5
7 3" 150 lbs, RF, compact, 316/316L, 2"/4"/6"/8" barrel, flange ANSI B16.5
see additional specification
6 3" 300 lbs, RF, compact, 316/316L, flange ANSI B16.5
8 4" 150 lbs, RF, compact, 316/316L, flange ANSI B16.5
W 4" 300 lbs, RF, AISI 316L (CRN)
JIS flanges
X 10K 50A RF, AISI 316L
1 10K 80A RF, AISI 316L
4 10K 100 A RF, AISI 316L

Endress+Hauser 77
Deltabar S

FMD77 (continued) 90 Fill fluid:


A Silicone oil
D Vegetable oil
L Low temperature oil
V High-temperature oil
F Inert oil

100 Additional options 1:


A Additional options 1 not selected
B Material test certificate for wetted components, inspection certificate as per
EN 10204 3.1 acc. to specification 52005759
C NACE MR0175 material
D Material test certificate for wetted components as per EN 10204 3.1 and
NACE MR0175 material, inspection certificate as per EN 10204 acc. to
specification 52010806
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM module
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

110 Additional options 2:


A Additional options 2 not selected
E SIL/IEC 61508 declaration of conformity
G Separate housing, cable length see additional spec. + mounting
bracket, wall/pipe, 316L
(FM/CSA IS: nur für Div.1 Installation)
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM module
R Screws 7/16 UNF, length 1 1/2" (4 pieces) for oval flange adapter
PZO
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate,
inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

995 Identification:
Z1 Measuring point (TAG)
Z2 Bus address

FMD77 order code

78 Endress+Hauser
Deltabar S

FMD78 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
m 4 ATEX II 1/3 D
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d IIC T6
– + E
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx ia
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust-Ex)
G NEPSI Ex d IIC T6
H NEPSI Ex ia IIC T6
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates: ATEX II Ex ia / Ex d + FM/CSA IS + XP; ATEX II 1/2G Ex ia IIC T6+; ATEX II 2G Ex d IIC T6+;
FM/CSA IS + XP Cl.I Div.1 Gr.A-D

20 Output; Operation:
n A 4...20 mA HART, SIL operation outside, LCD (see Fig. ➀, n)
B 4...20 mA HART, SIL operation inside, LCD (see Fig. ➀, o)
➂ C 4...20 mA HART, SIL operation inside (see Fig. o)
M PROFIBUS PA, operation outside, LCD (see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (see Fig. ➀, n)
Q FOUNDATION Fieldbus, operation inside, LCD (see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (see Fig. p)

30 Housing; Cable entry, Protection:


T14 A Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M12x1 PA plug
E Aluminium T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
+ – F Aluminium T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
T15 J Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
K Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
L Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
M Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
N Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
P Aluminium T15 housing, optional display on the top, IP 65/NEMA 4X, Han7D plug, 90°
T17 1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Han7D plug, 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover
Z Housing: see additional specifications

Endress+Hauser 79
Deltabar S

FMD78 (continued) 40 Nominal range; PN:


Nominal value PN
7D 100 mbar/10 kPa/1.5 psi 160 bar/16 MPa/2400 psi
7F 500 mbar/50 kPa/7.5 psi 160 bar/16 MPa/2400 psi
7H 3 bar/300 kPa/45 psi 160 bar/16 MPa/2400 psi
7L 16 bar/1,6 MPa/240 psi 160 bar/16 MPa/2400 psi
7M 40 bar/4 MPa/600 psi 160 bar/16 MPa/2400 psi

50 Calibration, Units:
1 Calibration: nominal range, mbar/bar
2 Calibration: nominal range, kPa/MPa
3 Calibration: nominal range, mmH2O/mH2O
4 Calibration: nominal range, inH2O/ftH2O
6 Calibration: nominal range, psi
B Custom calibration: see additional specification
C Factory calibration: see additional specification, Factory calibration certificate, 5-point
D DKD calibration: see additional specification, DKD-Certificate

60 Process isolating diaphragm material:


1 AISI 316L
2 Alloy C
3 Monel
5 Tantalum
6 AISI 316L with Gold-Rhodium coating
7 AISI 316L with 0.09 mm PTFE foil (not for vacuum applications)

80 Process connection, Material:


Diaphragm seal cell structure
UF Cell DN 50 PN 16-400, AISI 316L
UH Cell DN 80 PN 16-400, AISI 316L
UJ Cell DN 100 PN 16-400, AISI 316L
VF Cell 2" 150-2500 lbs, AISI 316L (CRN)
VH Cell 3" 150-2500 lbs, AISI 316L (CRN)
VJ Cell 4" 150-2500 lbs, AISI 316L (CRN)
Threaded connections
GA Thread ISO 228 G 1/2 B, PN 40, AISI 316L, separator, PTFE seal
RL Thread ANSI 1/2 MNPT, PN 40, AISI 316L, separator, PTFE seal
Clamp connections
TB Tri-Clamp, ISO 2852 DN 25 (1"), DIN 32676 DN 25, EHEDG, 3A, AISI 316L
TC Tri-Clamp, ISO 2852 DN 25 – DN 38 (1 – 1 1/2"), EHEDG, 3A, AISI 316L
TD Tri-Clamp, ISO 2852 DN 40 – DN 51 (2")/DN 50, EHEDG, 3A, AISI 316L
TF Tri-Clamp, ISO 2852 DN 70 – DN 76.1 (3"), EHEDG, 3A, AISI 316L
Pipe diaphragm seal Clamp
SB Tri-Clamp, ISO 2852 DN 25 (1"), 3A, AISI 316L
SC Tri-Clamp, ISO 2852 DN 38 (1 1/2"), 3A, AISI 316L, 3.1 + P
ressure test acc. to PED Cat. II
SD Tri-Clamp, ISO 2852 DN 51 (2"), 3A, AISI 316L, 3.1 + Pressure test acc. to PED Cat. II
Hygienic connections
TR Varivent model N for pipes DN 40 – DN 162, PN 40, EHEDG, 3A, AISI 316L
TK DRD DN50 (65 mm), PN 25, 3A, AISI 316L
WH Sanitary tank spud, 3A, AISI 316L, extended diaphragm seal 2"
MR DIN 11851 DN 50 PN 25, EHEDG, 3A, AISI 316L
MS DIN 11851 DN 65 PN 25, EHEDG, 3A, AISI 316L
MT DIN 11851 DN 80 PN 25, EHEDG, 3A, AISI 316L
M3 DIN 11851 DN 50 PN 25 socket, EHEDG, 3A, AISI 316L
M4 DIN 11851 DN 65 PN 25 socket, EHEDG, 3A, AISI 316L
M5 DIN 11851 DN 80 PN 25 socket, EHEDG, 3A, AISI 316L
EN/DIN flanges
B3 DN 50 PN 10-40 B1, AISI 316L
B5 DN 80 PN 10-40 B1, AISI 316L
BT DN 100 PN 10-16 B1, AISI 316L
B6 DN 100 PN 25-40 B1, AISI 316L

80 Endress+Hauser
Deltabar S

FMD78 (continued) 80 Process connection, Material:


ANSI flanges
AF 2" 150 lbs RF, AISI 316/316L (CRN)
AR 2" 300 lbs RF, AISI 316/316L (CRN)
AG 3" 150 lbs RF, AISI 316/16L (CRN)
AS 3" 300 lbs RF, AISI 316/316L (CRN)
J4 3" 150 lbs RF, AISI 316/316L, extended diaphragm seal: 2"/4"/6"/8" (CRN),
extended diaphragm seal: see additional specification
AH 4" 150 lbs RF, AISI 316/316L (CRN)
AT 4" 300 lbs RF, AISI 316/316L (CRN)
J5 4" 150 lbs RF, AISI 316/316L, extended diaphragm seal: 2"/4"/6"/8" (CRN),
extended diaphragm seal: see additional specification
JIS flanges
KF 10K 50A RF, AISI 316L
KL 10K 80A RF, AISI 316L
KH 10K 100A RF, AISI 316L

90 Capillary, Fill fluid:


1 ...m capillary, silicone oil
2 ...m capillary, vegetable oil
3 ...m capillary, high temperature oil
4 ...m capillary, oil for oxygen service
5 ...m capillary, low temperature oil
A ...ft capillary, silicone oil
B ...ft capillary, vegetable oil
C ...ft capillary, high temperature oil
D ...ft capillary, oil for oxygen service
E ...ft capillary, low temperature oil

100 Additional options 1:


A Additional options 1 not selected
B Material test certificate for wetted components, inspection certificate as per
EN 10204 acc. to specification 52005759
C NACE MR0175 material
D Material test certificate for wetted components as per EN 10204 3.1 and
NACE MR0175 material, inspection certificate as per EN 10204 acc. to
specification 52010806
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM module
S GL/ABS marine certificate
U Mounting bracket, wall/pipe, 304
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

110 Additional options 2:


A Additional options 2 not selected
E SIL/IEC61508 Declaration of conformity
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
(FM/CSA IS: nur für Div.1 Installation)
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM module
R 4x srew UNF7/16, length 1-1/2"
S GL/ABS marine certificate
U Mounting bracket for wall and pipe, AISI 304
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

995 Identification:
Z1 Measuring point (TAG)
Z2 Bus address

FMD78 order code

Endress+Hauser 81
Deltabar S

Additional documentation
Field of Activities • Pressure measurement: Powerful instruments for process pressure, differential pressure, level and flow:
FA004P/00/en

Technical Information • Cerabar S: TI383P/00/en


• Deltapilot S: TI416P/00/en
• Deltatop:
– orifice plate (TI422P/00/en)
– pitot tube (TI425P/00/en)
• EMC test basic principles: TI241F/00/en

Operating Instructions 4...20 mA HART:


• Deltabar S: BA270P/00/en
• Description of device functions Cerabar S/Deltabar S/Deltapilot S: BA274P/00/en
PROFIBUS PA:
• Deltabar S: BA294P/00/en
• Description of device functions Cerabar S/Deltabar S/Deltapilot S: BA296P/00/en
FOUNDATION Fieldbus:
• Deltabar S: BA301P/00/en
• Description of device functions Cerabar S/Deltabar S: BA303P/00/en

Brief operating instructions • 4...20 mA HART, Deltabar S: KA1018P/00/en


• PROFIBUS PA, Deltabar S: KA1021P/00/en
• FOUNDATION Fieldbus, Deltabar S: KA1024P/00/en

Manual for Functional Safety • Deltabar S (4...20 mA): SD189P/00/en


(SIL)

Safety Instructions Certificate/Type of Device Electronic insert Documentation Version in the


Protection order code

ATEX II 1/2 G Ex ia IIC T6 PMD70, PMD75, – 4...20 mA HART, – XA235P 1 (6)


(WHG) FMD76, FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus

ATEX II 1/2 D PMD70, PMD75, – 4...20 mA HART – XA237P 2


FMD77, FMD78 – PROFIBUS PA, – XA280P
FOUNDATION Fieldbus
ATEX II 1/2 D Ex ia IIC T6 FMD76 – 4...20 mA HART – XA238P 2
– PROFIBUS PA, – XA281P
FOUNDATION Fieldbus
ATEX II 1/3 D PMD70, PMD75, – 4...20 mA HART – XA239P 4
FMD77, FMD78 – PROFIBUS PA, – XA282P
FOUNDATION Fieldbus

ATEX II 2 G Ex d IIC T6 PMD75, FMD77, – 4...20 mA HART, – XA240P 5


FMD78 PROFIBUS PA,
FOUNDATION Fieldbus
ATEX II 3 G Ex nA II T6 PMD70, PMD75, – 4...20 mA HART, – XA241P 7
FMD76, FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus

ATEX II 1/2 GD PMD70, PMD75, – 4...20 mA HART, – XA243P 3


Ex ia IIC T6 FMD76, FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus

ATEX II 1 GD Ex ia IIC T6 PMD70, PMD75, – 4...20 mA HART, – XA275P 8


FMD76, FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus

ATEX II 1/2 G Ex ia IIC T6 + PMD75, FMD77, – 4...20 mA HART, – XA242P B


ATEX II 2 G Ex d IIC T6 FMD78 PROFIBUS PA,
FOUNDATION Fieldbus

82 Endress+Hauser
Deltabar S

Certificate/Type of Device Electronic insert Documentation Version in the


Protection order code

ATEX II Ex ia + FM IS + CSA IS PMD70, FMD76 – 4...20 mA HART – XA235P, E


ATEX II 1/2 G Ex ia IIC T6 + ZD141P,
FM/CSA IS Cl.I,II,III Div.1 ZD142P
Gr.A-G FM: Zone 0,1,2/CSA: – PROFIBUS PA, – XA235P,
Zone 0,1,2 FOUNDATION Fieldbus ZD188P,
ZD189P

ATEX II Ex ia / Ex d + FM/ PMD75, FMD77, – 4...20 mA HART – XA242P, F


CSA IS + XP FMD78 ZD153P,
ATEX II 1/2G Ex ia IIC T6+ ZD186P
ATEX II 2G Ex d IIC T6+ – PROFIBUS PA, – XA242P,
FM/CSA IS + XP Cl.I Div.1 FOUNDATION Fieldbus ZD190P,
Gr.A-D ZD191P

Certificate/Type of Device Electronic insert Documentation Version in the


Protection order code

IECEx Zone 0/1 Ex ia IIC T6 PMD70, PMD75, – 4...20 mA HART, – XB004P I


FMD76, FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus

Certificate/Type of Device Electronic insert Documentation Version in the


Protection order code
NEPSI Ex ia IIC T6 PMD70, PMD75, – 4...20 mA HART, – XC004P H
FMD76, FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus
NEPSI Ex d IIC T6 PMD75, FMD77, – 4...20 mA HART, – XC006P G
FMD78 PROFIBUS PA,
FOUNDATION Fieldbus

Installation/Control Drawings Certificate/Type of Device Electronic insert Documentation Version in the


Protection order code

FM IS Class I, II, III, PMD70, PMD75, – 4...20 mA HART – ZD141P S


Division 1, Groups A – G; FMD76, FMD77, – PROFIBUS PA, – ZD188P
NI, Class I Division 2, FMD78 FOUNDATION Fieldbus
Groups A – D; AEx ia
CSA IS Class I, II, III, PMD70, PMD75, – 4...20 mA HART – ZD142P U
Division 1, Groups A – G; Class FMD76, FMD77, – PROFIBUS PA, – ZD189P
I Division 2, FMD78 FOUNDATION Fieldbus
Groups A – G

FM IS + XP Class I, PMD75, FMD77, – 4...20 mA HART – ZD186P C


Division 1, Groups A – D FMD78 – PROFIBUS PA, – ZD190P
FOUNDATION Fieldbus

CSA IS + XP Class I, PMD75, FMD77, – 4...20 mA HART – ZD153P D


Division 1, Groups A – D FMD78 – PROFIBUS PA, – ZD191P
FOUNDATION Fieldbus

ATEX II Ex ia + FM IS + CSA IS PMD70, FMD76 – 4...20 mA HART – XA235P, E


ATEX II 1/2 G Ex ia IIC T6 + ZD141P,
FM/CSA IS Cl.I,II,III Div.1 ZD142P
Gr.A-G FM: Zone 0,1,2/CSA: – PROFIBUS PA, – XA235P,
Zone 0,1,2 FOUNDATION Fieldbus ZD188P,
ZD189P

Endress+Hauser 83
Deltabar S

Certificate/Type of Device Electronic insert Documentation Version in the


Protection order code

ATEX II Ex ia / Ex d + FM/ PMD75, – 4...20 mA HART – XA242P, F


CSA IS + XP FMD77, ZD153P,
ATEX II 1/2G Ex ia IIC T6+ FMD78 ZD186P
ATEX II 2G Ex d IIC T6+ – PROFIBUS PA, – XA242P,
FM/CSA IS + XP Cl.I Div.1 FOUNDATION Fieldbus ZD190P,
Gr.A-D ZD191P

CSA XP Cl.I Div.1 Gr.B-D, PMD75, – 4...20 mA HART, – ZD229P V


Ex d, Zone 1,2 FMD77, PROFIBUS PA,
FMD78 FOUNDATION Fieldbus

Overspill protection • WHG: ZE260P/00/de

Instruments International

Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland

Tel. +41 61 715 81 00


Fax +41 61 715 25 00
www.endress.com
[email protected]

TI382P/00/EN/06.09
No. 71095431
CSS/FM+SGML 6.0 71095431