YLAA Installation
YLAA Installation
72-ICOM6 (1015)
ISSUE DATE: 10/30/2015
SECTION 4 – INSTALLATION
To ensure warranty coverage, this equip- In installations where winter operation is intended and
ment must be commissioned and serviced snow accumulations are expected, additional height
by an authorized Johnson Controls must be provided to ensure normal condenser air flow.
service mechanic or a qualified service
person experienced in chiller installation. Clearances are listed in Figure 23 on page 85.
Installation must comply with all appli-
Foundation
cable codes, particularly in regard to elec-
trical wiring and other safety elements The unit should be mounted on a flat and level founda-
such as relief valves, HP cutout settings, tion, floor, or rooftop capable of supporting the entire
design working pressures, and ventilation operating weight of the equipment. See Physical Data
requirements consistent with the amount YLAA0058 – YLAA0175 60Hz on page 46 for oper-
and type of refrigerant charge. ating weight. If the unit is elevated beyond the normal
JOHNSON CONTROLS 35
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
COMPRESSOR MOUNTING 1. The chilled liquid piping system should be laid out
so that the circulating pump discharges directly into
The compressors are mounted on four (4) rubber iso- the cooler. The suction for this pump should be tak-
lators. The mounting bolts should not be loosened or en from the piping system return line and not the
adjusted at installation of the chiller. cooler. This piping scheme is recommended, but is
not mandatory.
REMOTE COOLER OPTION
2. The inlet and outlet cooler connection sizes are pro-
Not available at this time.
vided in Table 5 on page 46 (Physical Data).
CHILLED LIQUID PIPING 3. A 1/16” mesh strainer is provided at the cooler inlet
General – When the unit(s) has been located in its fi- line just ahead of the cooler. This is important to
nal position, the unit water piping may be connected. protect the cooler from entrance of large particles
Normal installation precautions should be observed in which could cause damage to the evaporator.
order to receive maximum operating efficiencies. Pip- 4. All chilled liquid piping should be thoroughly
ing should be kept free of all foreign matter. All chilled flushed to free it from foreign material before the
water evaporator piping must comply in all respects system is placed into operation. Use care not to
with local plumbing codes and ordinances. flush any foreign material into or through the cooler.
Since elbows, tees and valves decrease pump capacity, 5. As an aid to servicing, thermometers and pressure
all piping should be kept as straight and as simple as gauges should be installed in the inlet and outlet wa-
possible. All piping must be supported independent ter lines.
of the chiller.
6. The chilled water lines that are exposed to outdoor
Consideration should be given to com- ambients should be wrapped with supplemental
pressor access when laying out water pip- heater cable and insulated to protect against freeze-
ing. Routing the water piping too close to up during low ambient periods, and to prevent for-
the unit could make compressor servicing/ mation of condensation on lines in warm humid
replacement difficult. locations. As an alternative, ethylene glycol should
be added to protect against freeze-up during low
Hand stop valves should be installed in all lines to fa- ambient periods.
cilitate servicing.
7. A chilled water flow switch, (either by YORK or
Piping to the inlet and outlet connections of the chiller others) MUST be installed in the leaving water pip-
should include high-pressure rubber hose or piping ing of the cooler. If the factory wired flow switch
loops to ensure against transmission of water pump vi- and extension pipe kit is not selected, the field in-
bration. The necessary components must be obtained stalled flow switch must be installed so that there
in the field. is a straight horizontal run of at least 5 diameters
on each side of the switch. Adjust the flow switch
Drain connections should be provided at all low points paddle to the size of the pipe in which it is to be
to permit complete drainage of the cooler and system installed (see manufacturer’s instructions furnished
water piping. with the switch). The switch is to be wired to Ter-
A small valve or valves should be installed at the high- minals 13 and 14 of XTBC1 located in the control
est point or points in the chilled water piping to allow panel, as shown on the unit wiring diagram.
any trapped air to be purged. Vent and drain connec- The Flow Switch MUST NOT be used
tions should be extended beyond the insulation to make to start and stop the chiller (i.e. starting
them accessible. and stopping the chilled water pump). It
is intended only as a safety switch.
36 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
JOHNSON CONTROLS 37
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
38 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
14
13 XTBC1 4
Terminal Block, MICROPANEL
NF Disconnect SW
or Circuit Breaker
Flow Switch
1L1 1L2 1L3
GRD
L 2
XTBC2
It is possible that multiple sources of The unit evaporator heater uses 120VAC.
power can be supplying the unit power Disconnecting 120VAC power from the
panel. To prevent serious injury or death, unit, at or below freezing temperatures,
the technician should verify that NO can result in damage to the evaporator
LETHAL VOLTAGES are present inside and unit as a result of the chilled liquid
the panel AFTER disconnecting power, freezing.
PRIOR to working on equipment.
JOHNSON CONTROLS 39
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
A-
INTERNAL
INTERNALWIRING
WIRINGTO
TOOPTIONAL
OPTIONALREMOTE
REMOTETEMP.
TEMP.RESET
RESETBOARD
BOARD
A+
14
FLOW SWITCH
13
50
13
21
REMOTE UNLOAD STEP 1
13
20
PWM REMOTE TEMP RESET
13
19 INTERNAL WIRING TO 2-KCR CONTROL RELAY
13
18 INTERNAL WIRING TO 1-KCR CONTROL RELAY
13
51
REMOTE START / STOP
13
XTBC1 LD13130
All externally supplied contacts must be The unit evaporator heater uses 120VAC.
capable of switching 24VDC / 115 VAC. Disconnecting 120VAC power from the
Gold contacts are recommended. If sup- unit, at or below freezing temperatures,
plied contacts are from a Relay / Contac- can result in damage to the evaporator
tor (Inductive Load), the coil of the Relay and unit as a result of the chilled liquid
/ Contactor must be suppressed. Typical freezing.
suppressor is P/N 031-00808-000.
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or death,
the technician should verify that NO
LETHAL VOLTAGES are present inside
the panel AFTER disconnecting power,
PRIOR to working on equipment.
40 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
XTBC2
LD13242
All chiller supplied contacts are rated at It is possible that multiple sources of
115VAC, 100VA, resistive load only, and power can be supplying the unit power
must be suppressed at the load by user panel. To prevent serious injury or death,
if powering an inductive load (Relay / the technician should verify that NO
Contactor Coil). Typical suppressor P/N LETHAL VOLTAGES are present inside
is 031-00808-000. the panel AFTER disconnecting power,
PRIOR to working on equipment.
The unit evaporator heater uses 120VAC.
Disconnecting 120VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.
JOHNSON CONTROLS 41
FORM 150.72-ICOM6 (1015)
SECTION 4 – INSTALLATION
ISSUE DATE: 10/30/2015
42 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
ISSUE DATE: 10/30/2015
STANDARD EFFICIENCY
HIGH EFFICIENCY
NOTES:
1. For leaving liquid temperature below 40°F (4°C) (to 10°F [-12°C]) optional low temperature glycol kit required. Contact your
nearest Johnson Controls Office for application requirements.
2. For leaving liquid temperature higher than 55°F (13°C), contact the nearest Johnson Controls Office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-29°C) with an electric heater as standard.
4. For operation at temperatures above 115°F (46°C), the optional High Ambient Kit will need to be installed on the system.
JOHNSON CONTROLS 43
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
100
WATER PRESSURE DROP (PSI)
C
E
A
10
F
B D
1
10 100 1000
LD17642
WATER FLOW RATE (GPM)
44 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
JOHNSON CONTROLS 45
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
46 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales Office.
JOHNSON CONTROLS 47
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
ELECTRICAL DATA
It is possible that multiple sources of The unit evaporator heater uses 120VAC.
power can be supplying the unit power Disconnecting 120VAC power from the
panel. To prevent serious injury or death, unit, at or below freezing temperatures,
the technician should verify that NO can result in damage to the evaporator
LETHAL VOLTAGES are present inside and unit as a result of the chilled liquid
the panel AFTER disconnecting power, freezing.
PRIOR to working on equipment.
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
COMPRESSOR HEATERS
Compressor heaters are standard. ZP180 compressors ers must be energized for 18 – 24 hours prior to restart-
utilize 70W heaters; ZP235, compressor use 120W ing a compressor. This will assure that liquid slugging
heaters and ZP285 and ZP385 utilize 150W heaters. If and oil dilution does not damage the compressors on
power is OFF more than two hours, the crankcase heat- start.
48 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
NOTE:
Reference PIN 59 for Pump Model.
Use this table along with Table 9 Electrical Data without Pumps to determine electrical data of the unit plus the pump.
JOHNSON CONTROLS 49
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
NOTE:
• Reference PIN 59 for Pump Model.
• Use this table along with Table 8 Pump Electrical Data to determine electrical data of the unit plus the pump.
• Does not include Control Transformer.
52 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
JOHNSON CONTROLS 53
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
54 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
JOHNSON CONTROLS 55
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
ELECTRICAL NOTES
NOTES the rated load amps for all other loads included in
1. Minimum Circuit Ampacity (MCA) is based on the circuit. Otherwise, HACR‑type circuit breakers
125% of the rated load amps for the largest mo- must be used. Maximum HACR circuit breaker rat-
tor plus 100% of the rated load amps for all other ing is based on 225% of the rated load amps for the
loads included in the circuit, per N.E.C. Article largest motor plus 100% of the rated load amps for
430‑24. If the optional Factory Mounted Con- all other loads included in the circuit.
trol Transformer is provided, add the following
6. The “INCOMING WIRE RANGE” is the mini-
MCA values to the electrical tables for the system
mum and maximum wire size that can be ac-
providing power to the transformer: ‑17, add 2.5
commodated by the unit wiring lugs. The (2)
amps; ‑28, add 2.3 amps; ‑40, add 1.5 amps, ‑46,
preceding the wire range indicates the number of
add 1.3 amps; ‑58, add 1 amps.
termination points available per phase of the wire
2. The minimum recommended disconnect switch is range specified. Actual wire size and number of
based on 115% of the rated load amps for all loads wires per phase must be determined based on the
included in the circuit, per N.E.C. Article 440. National Electrical Code, using copper connec-
tors only. Field wiring must also comply with lo-
3. Minimum fuse size is based upon 150% of the rat-
cal codes.
ed load amps for the largest motor plus 100% of the
rated load amps for all other loads included in the 7. A ground lug is provided for each compressor
circuit to avoid nuisance trips at start‑up due to lock system to accommodate a field grounding con-
rotor amps. It is not recommended in applications ductor per N.E.C. Table 250‑95. A control circuit
where brown outs, frequent starting and stopping grounding lug is also supplied.
of the unit, and/or operation at ambient tempera-
8. The supplied disconnect is a “Disconnecting
tures in excess of 95ºF (35ºC) is anticipated.
Means” as defined in the N.E.C. 100, and is in-
4. Maximum fuse size is based upon 225% of the tended for isolating the unit for the available pow-
rated load amps for the largest motor plus 100% er supply to perform maintenance and trouble-
of the rated load amps for all other loads included shooting. This disconnect is not intended to be a
in the circuit, per N.E.C. Article 440-22. Load Break Device.
5. Circuit breakers must be UL listed and CSA certi- 9. Field Wiring by others which complies to the Na-
fied and maximum size is based on 225% of the tional Electrical Code and Local Codes.
rated load amps for the largest motor plus 100% of
56 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
035-21966-101 REVG
JOHNSON CONTROLS 57
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
58 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
JOHNSON CONTROLS 59
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
WIRING DIAGRAMS
035-21583-101 REV I
ELEMENTARY WIRING DIAGRAMS
60 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
DWG. 1
JOHNSON CONTROLS 61
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
035-21583-102 REV J
DWG. 2
1/2.1 What these numbers mean. Example:
1 = follow wire no.1 /'D
2. = is the DWG number on the bottom center of each page.
.1 = is the locator number across the top of the page.
At the top of the pages the numbers 1 to 11 go from left to right. Find drawing number 2 and in
column number 1 across the top of the page, locate wire number 1.
62 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
DWG. 2 LD16751a
JOHNSON CONTROLS 63
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
FAN WIRING
035-21583-103 REV C
LD16765a
DWG. 3
Figure 14 - FAN WIRING, STANDARD LOW SOUND OR ULTRA QUIET, YLAA0070 - YLAA0516
64 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD16766a
DWG. 3
FIGURE 14 - F
AN WIRING, STANDARD LOW SOUND OR ULTRA QUIET, YLAA0070 - YLAA0516 (CONT’D)
JOHNSON CONTROLS 65
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
FAN WIRING
Only fitted on systems with 3 or 4 fans.
035-21583-118 REV C
DWG. 18 LD16769a
66 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
DWG. 18 LD16770a
JOHNSON CONTROLS 67
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
035-21583-116 REV A
DWG. 16
68 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
PUMP WIRING
035-21583-105 REV D
DWG. 5 /'
JOHNSON CONTROLS 69
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
COMPRESSOR WIRING
035-21589-106 REV L
/'
70 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
/'
JOHNSON CONTROLS 71
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
035-21589-103 REV B
035-21589-103 REVB
LD13234A
72 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD13901
JOHNSON CONTROLS 73
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
POWER PANEL
035-21589-101 REV E
/'
74 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
/'
JOHNSON CONTROLS 75
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
/'
76 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
/'
JOHNSON CONTROLS 77
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18072
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top – no
obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
78 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18073
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
JOHNSON CONTROLS 79
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18074
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
80 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18075
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
JOHNSON CONTROLS 81
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18076
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
82 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18077
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
JOHNSON CONTROLS 83
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
WEIGHT DISTRIBUTION AND ISOLATOR Whenever the isolator option is ordered, the isolators
MOUNTING POSITIONS will be shipped loose with the chiller. Packed with
the isolators and also in the control panel informa-
General tion packet is a drawing and table specifically for each
Weights of specific chiller models vary significantly as chiller, based on the option selection. The drawing and
options are added. As a result, total weights, weights at table will be similar to the two samples shown below
individual isolator positions, and actual isolator selec- and on the following page. The drawing will show the
tion at each position cannot be published due to the isolator locations along with the weight in pounds and
vast number of possible combinations. This informa- kilograms at the specific location, isolator position,
tion will be available when the specific chiller/ option and location measurements for each isolator.
selection is made from the local Johnson Controls sales
office. Be aware, weights will change with each op- Sample Isolator Location Drawings
tion along with possible isolator changes. Weights and See Figure 22 below for sample printouts supplied in
isolators may need to be recalculated when the option the isolator package and in the chiller panel literature
selections are changed. packets.
L1 L2
Control Panel
0
R1 R2
0 Y
Top View
X
X DISTANCE Y DISTANCE
OPERATING WEIGHT
LOCATION INCHES (MM) INCHES (MM) VENDOR NUMBER
LBS (KG)
Figure 22 - SAMPLE PRINTOUT SUPPLIED IN THE ISOLATOR PACKAGE AND IN THE CHILLER PANEL
LITERATURE PACKET
84 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
CLEARANCES
See Figure 23 below for minimum clearances for all
YLAA units.
(2 m)
5
(1.3 m) (2 m)
(2 m)
NOTES:
1. No obstructions allowed above the unit.
2. Only one adjacent wall may be higher than the unit.
3. Adjacent units should be 10 feet (3 Meters) apart.
JOHNSON CONTROLS 85
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
ISOLATOR LOCATIONS
LD18078
1.4
LD18079
86 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18080
JOHNSON CONTROLS 87
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD18081
LD18082
88 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
ISOLATOR INFORMATION
One Inch Deflection Spring Isolator Cross-reference
CP
5/8"
Ø1/2"
H"
C"
T"
B" L" 5
D"
W"
LD13759A
MODEL NUMBER RATED CAPACITY (LBS) DEFLECTION RATED (IN) COLOR CODE
CP1-1D-85 85 1.360 LT. PURPLE
CP1-1D-120 120 1.200 DK. YELLOW
CP1-1D-175 175 1.170 DK. BLUE
CP1-1D-250 250 1.400 YELLOW
CP1-1D-340 340 1.130 RED
CP1-1D-510 510 1.020 BLACK
CP1-1D-675 675 1.320 DK. PURPLE
CP1-1D-900 900 1.020 DK. GREEN
CP1-1D-1200 1200 0.900 GRAY
CP1-1D-1360 1360 0.770 WHITE
CP1-1D-1785N 1785 0.880 GRAY/RED
MODEL NUMBER RATED CAPACITY (LBS) DEFLECTION RATED (IN) COLOR CODE
CP2-1D-1020 1020 1.020 BLACK
CP2-1D-1350 1350 1.320 DK. PURPLE
CP2-1D-1800 1800 1.020 DK. GREEN
CP2-1D-2400 2400 0.900 GRAY
CP2-1D-2720 2720 0.770 WHITE
CP2-1D-3570N 3570 0.880 GRAY / RED
JOHNSON CONTROLS 89
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
LD13790
90 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
Y2RS
5" 1-1/8"
5/8" 2-3/4"
2-3/4"
12"
3/8" GAP
5/8-11UNC
Ø3/4" TYP. (4)
TYP.(4)
3/4"
7/8"
1/2" LIMIT
STOP &
NUT 8-3/8"
OPER.
HEIGHT
12-1/4"
14"
3-1/2" LD13761A
3/8"
5"
NOTES:
1. ALL DIMENSIONS ARE IN INCHES, INTERPRET PER ANSI Y14.
2. STANDARD FINISH: HOUSING-POWDER COATED (COLOR:BLACK), SPRING-POWDER COATED (COLOR: SEE T
HARDWARE ZINC-ELECTROPLATE.
1. All dimensions are in inches, interpret per ANSI 4. All springs are designed for 50% overload capac-
3. EQUIPMENT MUST BE BOLTED OR WELDED TO THE TOP PLATE TO MEET ALLOWABLE SEISMIC RATINGS.
4. ALL SPRINGS ARE DESIGNED FOR 50% OVERLOAD CAPACITY WITH EXCEPTION OF THE 2D-3280N & 2D-2870
5
Y14. 5. REFER TO PAGE FOR INSTALLATION INSTRUCTIONS.
6. CONSULT FACTORY FOR CONCRETE INSTALLATION. ity with exception of the 2D-3280N and 2D-2870.
2. Standard finish: housing-powder coated (color, 5. Refer to next page for installation instructions.
black), spring-powder coated (color, see table be-
6. Consult factory for concrete installation.
low) hardware - zinc-electroplate.
3. Equipment must be bolted or welded to the top
plate to meet allowable seismic ratings.
RATED ALLOWABLE
SEISMIC RATED LOAD SPRING RATE SOLID LOAD COLOR
DEFLECTION G RATING
MOUNT SIZE (LBS) (LBS/IN) (LBS) CODE
(IN) HORIZONTAL
Y2RSI-2D-150 150 2.4 62 234 WHITE 34.7
Y2RSI-2D-320 320 2.3 140 490 YELLOW 16.3
Y2RSI-2D-460 460 2.3 200 688 GREEN 11.3
Y2RSI-2D-710 710 2.2 330 1072 DK BROWN 7.3
Y2RSI-2D-870 870 1.9 460 1312 RED 6
Y2RSI-2D-1200N 1200 1.9 638 1818 RED/BLACK 4.3
Y2RSI-2D-1450 1450 1.8 900 2450 TAN 3.6
Y2RSI-2D-1690 1690 1.7 1140 2892 PINK 3.1
Y2RSI-2D-2000N 2000 1.7 1318 3342 PINK/BLACK 2.6
Y2RSI-2D-2640N 2640 1.5 1854 4283 PINK/GRAY 2
PINK/GRAY/
Y2RSI-2D-2870N 3080 1.5 2004 4629 1.7
ORANGE
PINK/GRAY/DK
Y2RSI-2D-3280N 3740 1.8 2134 4930 1.4
BROWN
JOHNSON CONTROLS 91
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
("F")
WASHER ("E")
("F")
("C")
("C")
("B")
LD13763B
92 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
RD-Style DW
Isolators
CD
MOLDED
DURULENE
HF ø AD THRU
TYP 2 PLACES
BT
AL
W
L
LD13760A
1. All dimensions are inches, interpreted per ANSI 4. AL = Mounting hole center to center spacing.
Y14. Notes:
1. All dimensions are inches, interpreted per ANSI Y14. 5. HF = Free height of mount, prior to loading. Op- 5
2. Refer to Page 98 for installation instructions.
2. Refer to next page for installation
3. Mount molded ininstructions. eratingAlsoheight
weather resistant duralene compound as standard. available incalculated
other materials by the free height less
such as natural rubber, extreme high temperature silicone, high-damped silicone, nitrile and EDPM.
4. AL = Mounting hole center to center spacing. the static deflection under load. All dimensions
3. Mount molded in weather 5. HFresistant
= Free height duralene
of mount, prior com-
to loading. Operating height calculated by the free height less the
static deflection under load. All dimensions for reference only. for reference only.
pound as standard. Also6.available in other materi-
Hardware zinc-electroplated.
JOHNSON CONTROLS 93
FORM 150.72-ICOM6 (1015)
SECTION 5 – TECHNICAL DATA
ISSUE DATE: 10/30/2015
1. Read instructions in their entirety before begin- 4. Bolt or anchor all isolators to supporting structure
ning installation. utilizing base thru holes (“B”).
2. Isolators are shipped fully assembled and are to be 5. Remove top bolt and top washer. Place equip-
positioned in accordance with the submittal draw- ment on top of isolators so that mounting holes
ings or as otherwise recommended. in equipment or base line up with threaded hole
(“C”).
3. Set isolators on floor, housekeeping pad, or sub-
base, ensuring that all isolator centerlines match 6. Reinstall top bolt and washer and tighten down.
the equipment mounting holes. The VMC group
7. Installation is complete.
recommends that the isolator base (“A”) be in-
stalled on a level surface. Shim or grout as re-
quired, leveling all isolator bases to the same
elevation (1/32-inch maximum difference can be
tolerated).
TOP BOLT
("B")
TOP WASHER
D D
("C")
("B")
CL CL ("A")
SECTION D-D
LD13762B
94 JOHNSON CONTROLS
FORM 150.72-ICOM6 (1015)
ISSUE DATE: 10/30/2015
SECTION 6 – COMMISSIONING
JOHNSON CONTROLS 95
FORM 150.72-ICOM6 (1015)
SECTION 6 – COMMISSIONING
ISSUE DATE: 10/30/2015
96 JOHNSON CONTROLS