Unit Iv: Fundamentals of Harmonics: Fig.1: Current Distortion Caused by Nonlinear Resistance
Unit Iv: Fundamentals of Harmonics: Fig.1: Current Distortion Caused by Nonlinear Resistance
CONCEPTS:
HARMONIC DISTORTION
2. Fluorescent lighting
Fig.4: Fluorescent lamp with (a) magnetic ballast current waveform and (b)
its harmonic spectrum.
Fluorescent lights are discharge lamps; thus they require a ballast to provide a high
initial voltage to initiate the discharge for the electric current to flow between two
electrodes in the fluorescent tube.
Once the discharge is established, the voltage decreases as the arc current increases.
It is essentially a short circuit between the two electrodes, and the ballast has to
quickly reduce the current to a level to maintain the specified lumen output.
Thus, a ballast is also a current-limiting device in lighting applications.
There are two types of ballasts, magnetic and electronic.
A standard magnetic ballast is simply made up of an iron-core transformer with a
capacitor encased in an insulating material.
The iron-core magnetic ballast contributes additional heat losses, which makes it
inefficient compared to an electronic ballast.
Fig .5: Fluorescent lamp with (a) electronic ballast current waveform and
(b) its harmonic spectrum.
Harmonic indices
The two most commonly used indices for measuring the harmonic content of a waveform
are the total harmonic distortion and the total demand distortion. Both are measures of the
effective value of a waveform and may be applied to either voltage or current.
Interharmonics
Voltages or currents having frequency components that are not integer multiples of the
frequency at which the supply system is designed to operate (e.g., 50 or 60 Hz) are called
interharmonics. They can appear as discrete frequencies or as a wideband spectrum.
Interharmonics can be found in networks of all voltage classes.
Causes: Static frequency converters, cycloconverters, induction furnaces, and arcing devices.
Power line carrier signals can also be considered as interharmonics.
Interharmonic currents can excite quite severe resonances on the power system as the
varying interharmonic frequency becomes coincident with natural frequencies of the system.
They have been shown to affect power-line-carrier signaling and induce visual flicker in
fluorescent and other arc lighting as well as in computer display devices.
Since interharmonics can assume any values between harmonic frequencies, the
interharmonic spectrum must have sufficient frequency resolution.
Thus, a single-cycle waveform sample is no longer adequate to compute the interharmonic
spectrum since it only provides a frequency resolution of 50 or 60 Hz.
Any frequency in between harmonic frequencies is lost. The one-cycle waveform though is
commonly used to compute the harmonic spectrum since there is no frequency
between harmonic frequencies.
They include devices that provide low impedance paths to divert harmonics to ground and
devices that create a high impedance path to discourage the flow of harmonics.
Both of these devices,by necessity, change the impedance characteristics of the circuits into
which they are inserted.
Another weakness of the passive harmonic technologies is that they cannot adapt to changes
in electrical systems in which they operate.
Notch filters can provide power factor correction in addition to harmonic suppression. In
fact, power factor correction capacitors may be used to make notch filters.
Advantages of Passive filters:
1. Simple in construction, less costly and efficient
2. Serves dual purpose: harmonic filtration and power factor correction of load.
Disadvantages of Passive filters:
1. Cannot function under saturated condition.
2. Number of passive filters installed must be equal to the number of harmonic levels
to be compensated.
3. Connection of passive filters necessities a specific analysis of each installation.
4. Non adaptability to system variations.
5. Bulky in size.
6. Tendency to resonate with the other load.
Active filters:
When the number of harmonics to be filtered, large no of branches of passive filters will
be required .
The large no of branches of passive filters will be required.
The actual number of branches will depend upon no of harmonic level of branches will
depend upon no of harmonic level to be compensated.
Hence, because of passive filter use for filtration of large no of harmonics results in large size
&more cost.
Introduction of self commutated devices e.g. MOSFETS, IGBT etc, accelerated the research in
design of active filter & resulted low cost, high performance active filter suitable to eliminate
the harmonics of different orders to overcome the drawbacks of passive filters.
Active filters compensate voltage of current harmonic signal measured.
The injected voltage or current harmonic signal measured.
The injected voltage or current harmonic signals in to the power system network is of
same magnitude and opposite in phase of the measured harmonic signal.
It comprises power converter and control loop which controls the harmonics injection of
the filter as the function of harmonic signal measure.
Advantages of Active filters:
1. Superior filtering performance
2. Smaller physical size
3. Flexibility
http://www.elnet.cc/thd-and-tdd/
Total Harmonic Distortion (THD) and Total Demand Distortion (TDD)
The total harmonic distortion, or THD, of a signal is a measurement of the harmonic distortion present and is defined as the ratio of the sum of
the powers of all harmonic components to the power of the Fundamental frequency.
TDD(I) = Total Current Demand Distortion is Calculated harmonic current distortion against the full load (demand) level of the electrical system. At the
full load TDD(I)=THD(I). So TDD gives us better insight about how big impact of harmonic distortion in our system. For example we could have very
high THD but the load of the system is low. In this case the impact on the system is also low